Calculation of Relay Settings For MiCOM P543
Calculation of Relay Settings For MiCOM P543
Distance Setup
Setting Mode :Simple
Phase Chars. :Quadrilateral
Quad Resistance :Common/Proportional
Fault Resistance : 0.450
Zone1 Ph Status : Enable on channel fail
Zone1 Ph Reach : 80%(ZL)
Trip Time : Inst.
Zone2 Ph Status : Enable on channel fail
Zone2 Ph Reach : 120%(ZL)
Trip Time : 0.400 Sec.
Zone4 Ph Status : Enable on channel fail
Zone4 Ph Reach : 10%(ZL) (Reverse
Direction)
Trip Time : 1.0 Sec.
Ground Chars. : Quadrilateral
Quad Resistance : Common/Proportional
Fault Resistance : 0.450
Zone1 Gnd Status : Enable on channel fail
Zone1 Gnd Reach : 80%(ZL)
Trip Time : Inst.
Zone2 Gnd Status : Enable on channel fail
Zone2 GndReach : 120%(ZL)
Trip Time : 0.400 Sec.
Zone4 Gnd Status : Enable on channel fail
Zone4 Gnd Reach : 10%(ZL) (Reverse
Direction)
Trip Time : 1.0 Sec.