Professional Documents
Culture Documents
MPL-P142 - 6316345 - Vol.2 Sec. 11 General Specs-Electrical
MPL-P142 - 6316345 - Vol.2 Sec. 11 General Specs-Electrical
ELECTRICAL INSTALLATIONS
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
Section – 11
ELECTRICAL INSTALLATIONS
CONTENTS
S11 / 2
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
S11 / 3
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.1.1.1.1 The enclosed Specifications cover the Electrical Installation works for Villa.
11.1.1.1.2 The Contractor shall be responsible for coordinating with Dubai Electricity and
Water Authority (DEWA) for making all necessary arrangements for
connection of electricity supply to the sub-station and L.V. to the Main
Distribution Board MDB in the ground floor main electrical room, all in strict
compliance with current rules, regulations, requirements and
recommendations of D.E.W.A.
11.1.1.2.1 Main L.V.-Panel 2500A TPN ACB LV Panel, complete with Power Factor
Correction Panel PFCP, suitably rated kilo-watt-hour meters, CTs, ammeters,
voltmeter/selector switches, accessories etc. The PFCPs shall not be an
integral part of LV-Panel but shall be housed in a separate enclosure.
11.1.1.2.3 Final TPN MCB Distribution Boards DB-LV, DB-SS, DB-GF, DB-FF, DB/TEL-1,
DB/TEL-2, DB/FF, DB/AC-GF, DB/AC-MF.
11.1.1.2.4 The following heavy-duty IP65 weather-proof isolators for in compliance with
particulars in respective load schedules and drawings: 16-TPN 32A Isolator for
Lift, Pumps, S-A/C 97, SPN 25A Isolator-S-A/C Units, Pumps 1-160A TPN
Isolator – Fire Fighting Pump, 1-160A isolator for FAHU as attached 400 ATP
isolator for chiller.
11.1.1.2.6 All L.V. cabling, drawn in uPVC conduits/ducts, from boards DB-LV, DB-SS,
DB-GF, DB-MF and to isolators for fire fighting and water pumps in ground
floor pump room.
S11 / 4
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.1.1.2.8 All sub-circuit wiring in PVC conduits from respective final MCB boards to
outlet points associated with internal and external lighting, exhaust fans, water
heaters, general purpose ISA socket/s, isolators etc., all in compliance with
details in drawings and load schedules for respective MCB boards.
11.1.1.2.10 All lighting and other SP and DP switches; manually and timer activated
contactor operated multi-gang switch assembly units for control of lighting
circuits, all as indicated in the drawings.
11.1.1.2.15 Telephone and Cable TV systems complete with necessary external and
internal conduits with draw tapes/wires, wiring, line jack outlets, socket -
outlets, main and sub-main distribution frames, junction boxes etc. all in strict
compliance with the current rules, regulations, requirements and
recommendations of DU.
11.1.1.2.16 Conventional Fire Detection and Alarm System, and emergency and exit
lighting systems, all in compliance with the current rules, regulations,
requirements and recommendations of the local Civil Defense Authority.
11.1.1.2.17 SMATV system complete with all Dishes, Antennae, Head End Unit,
Amplifiers, Socket outlets, cabling, junction boxes etc.
11.1.1.2.18 Bell system complete with bell push buttons and Bells.
11.1.1.2.20 All necessary and suitably dimensioned manholes for electrical cables.
11.1.1.2.21 4 No. 100 mm diameter uPVC conduits complete with manholes for incoming
DU cables.
S11 / 5
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.2.1.1 All electrical installation works shall be carried out in strict compliance with
the current rules, regulations, requirements and recommendations of Dubai
Electricity and Water Authority (DEWA), and with reference to details in
drawings, respective distribution board load schedules and Specifications.
11.2.1.2 Wherever applicable, all works shall be carried out in full co -ordination
with Civil, A/C. plumbing, False ceiling and other sub-contractors.
11.2.1.3 The Contractor shall refer to the Schedules of Equipment and Materials to
ensure compliance with the quality of equipment and materials specified.
11.2.1.4 All items of equipment and materials shall comply with the
requirements of the relevant B.S. Specifications or equivalent I.E.G.
publications.
11.2.1.5 All works shall be carried out under the supervision of a qualified and
licensed Electrical Engineer.
11.2.1.6 The locations of electrical wiring accessories and other items indicated in the
drawings are notional and these may be relocated on site to suit revised
furniture layout or/and due to other architectural changes.
11.2.1.7 All lighting and water heater control switches for bathrooms, toilets etc. shall
be located outside these areas.
11.2.1.8 All final MCB distribution boards shall be of the sectionalized type with each
section protected by appropriate sensitivity 2-pole/4-pole RCCB / ELCB to
comply with the rules and regulations of DEWA. Other particulars shall be in
compliance with details indicated in respective load schedules. Cooker units
shall be individually protected by 30A MCB/30 mA sensitivity RCCB / ELCB.
11.2.1.9 In compliance with DEWA's directions, specified motoring circuits shall be
equipped appropriate 2-pole/ 4-pole RCCB / ELCB of 100 mA sensitivity in
conjunction with under voltage relays, ELSs, timers etc. at the respective
distribution boards.
11.2.1.10 Each domestic type exhaust fan shall be supplied via a flex outlet and
shall be controlled by a 5A/6A SP switch.
11.2.1.11 Each water heater shall be supplied via an unswitched fused connection unit
and shall be controlled by a 20A DP switch. The latter switches shall be
located outside toilets and bathrooms for controlling water heaters in these
areas.
11.2.1.12 Each window type AC. unit shall be supplied via a connecto r unit and
shall be controlled by a 20 A/30 A DP switch in compliance with details in load
schedules.
11.2.1.13 Each hand-dryer, water cooler, dish washing machine, clothes washing
machine, dryer, Jacuzzi or similar outlet shall be supplied via a switched
connection unit and controlled via a 20A DP switch with neon indicator.
Connection units shall be at safe distances from related water pipes and
the DP switches shall be installed at heights of 1.4 m AFFL.
11.2.1.14 Unless indicated otherwise in drawings, all electrical cables to respective
distribution boards shall be drawn in uPVC conduits of appropriate
S11 / 6
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.2.1.15 The main incoming telephone and CATV cables to the premises from DU shall
be drawn in uPVC conduit of appropriate diameter or as indicated in site
electrical drawing.
11.2.1.16 Unless indicated otherwise, the mounting heights above FFL of electrical
accessories and equipment shall generally be as follows :
11.2.1.17 Isolators for electrical supply to split AC condensing units shall be firmly
mounted on walls (generally on roof) or on robustly constructed angle irons/
sheet steel frames near the units. Prior to commencement of any works, the
Contractor shall submit samples of proposed electrical materials and
equipment, inclusive of all items of switchgear, wiring accessories, lighting
fixtures, cables and wires, conduits etc. for approval by the Engineer.
11.2.1.18 Lighting and small power circuits in any room or area, particularly in toilets,
bathrooms, washrooms and similar areas, shall be supplied from the same
phase. In the event if provision of two phases is considered necessary for
consideration of load balancing, the Contractor shall ensure that the minimum
spacing between points served from different phases shall be 2m.
11.2.1.19 13A switched socket outlets in kitchens and similar areas shall be connected in
their own dedicated circuits.
11.2.1.20 Wherever applicable, the Contractor shall supply and install uPVC conduits of
minimum diameter 50 mm concealed in building fabric from split A/C
condensing units on roof to respective indoor units in various areas of the
building.
11.2.1.21 All Earthling installation works shall strictly comply with the current rules and
regulations of DEWA Cross-sectional areas of circuit protective conductors
(CPC) shall be in compliance with DEWA's Wiring Regulations.
S11 / 7
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.3.1.1 GENERAL
11.3.1.1.2 The Drawings are for tender purposes only and are to be read in conjunction with
this Specification. Any discrepancy between the Drawings and the Specification
and any matter which requires clarification shall be referred to the Engineer
before tender.
Approval of such drawings by the Engineer does not relieve the Contractor of his
responsibility to provide an installation suitable in dimension, construction,
function and finish for the purpose intended.
This specification and the Contract Drawings are intended to indicate generally the
arrangement of apparatus required. But the Contractor will be deemed to
have included in his tender anything necessary to leave the installation complete
and in proper working order to the satisfaction of the Engineer whether or not
such items are Mentioned in the Specification or shown on the Drawings.
11.3.1.1.3 The General and Particular Specifications shall be read in conjunction with
the Contract Documents and Tender Drawings. In the event of any
discrepancy between the drawings and the Specifications, the drawings
shall be deemed correct for tendering purposes. The contractor,
however, shall be required to draw attention to such discrepancies at the
time of submitting his offer.
11.3.1.2.1 The Contractor shall confer and coordinate with the local Electricity
Supply Authority to obtain all relevant information, data and instructions
pertaining to his parts of the works.
S11 / 8
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.3.1.2.2 The Contractor shall confer and coordinate with the local Electricity Supply
Authority to make all necessary arrangements for connection of electricity
supply to the main distribution board/s designated MDB for the project.
11.3.1.2.3 The Contractor shall confer and coordinate with the local DU office to obtain
all relevant information, data and instructions pertaining to installation of
telephone and CATV systems.
11.3.1.3.1 The Contractor shall confer and coordinate with the plumbing works sub-
contractor to ascertain locations and routes of all water and drainage pipes
to ensure sufficient and safe clearances are maintained between these and
electrical services in all areas.
11.3.1.3.2 The Contractor shall confer and coordinate with the suppliers and installers of
all specialist equipment inclusive of Air Conditioning system, Fire Detection
and Alarm system, Telephone and CATV systems and any other systems as and
when specified in the project, to carry out installation of all electrical
wiring/cabling and conduits for points associated with these systems.
11.3.1.3.3 The Contractor shall include in his tender offer all necessary expenses, if
any, for providing services to other specialist sub-contractors.
11.3.1.4.1 Three sets of tender drawings for all electrical works shall be provided to
the Contractor. Any necessary design modifications shall be in the form of
design notes and /or sketches as directed by the Engineer.
11.3.1.4.2 The Contractor shall submit, within thirty days of Engineer's instructions
for commencement of works, two copies of drawings indicating dimensioned
details of holes, chases etc. required in the structure together with
dimensioned details of supports, bases etc. to be provided by others to
enable him to fulfill his part of the works.
11.3.1.4.3 During the course of the works the Contractor shall maintain a fully detailed
record of all changes to the tender drawings so as to ensure easy and accurate
preparation of all drawings as a true record of the actual installation.
The drawings shall show the complete electrical installation of all the works
within and external to the building/s, inclusive of the type, cross-sectional
areas and runs/lengths of all L.V. cables, the precise locations of all cables
which may be buried within the structure, and those sections of any external
cables which are buried directly in the ground.
The locations and depths of all underground cables at the various entry points
shall also be clearly indicated.
On completion of the project the Contractor shall submit three copies of these
"AS BUILT" Drawings
S11 / 9
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.3.1.5.1 Within one month of the completion of the installations, the Contractor
shall provide complete sets of record drawings and operating manual as
follows.
i) General arrangement of all electrical services "AS BUILT" to scale not less
than 1:100 metric.
ii) Details of all items of plant and equipment including name and address of
respective manufacturer, type and model, serial number, duty, rating and any
other pertinent information.
iii) Single line schematic drawings to scale not less than 1:100 metric, indicating
position of all distribution boards, isolators, switches etc. with relevant notes
describing their functions.
11.3.1.6.3 Any alternative offered shall be equivalent or better in quality than those
specified, and shall be approved in writing by the Engineer before being
installed in the project.
11.3.1.7.1 The Contractor shall provide necessary assistance and facilities to the
Engineer to inspect all materials and equipment at works on site during the
progress of the works.
11.3.1.7.2 The Contractor shall provide, free of charge, all necessary labor, materials,
testing equipment and measuring instruments which may be required to carry
out the various tests on the installations in compliance with the
recommendations and requirements of the relevant statutory authorities and
as directed by the Engineer.
11.3.1.8.1 On completion of the installation and prior to its being made "alive" for
service, the Contractor shall carry out the mandatory and other
S11 / 10
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.3.1.8.2 All test shall be carried out in strict compliance with the requirements and
recommendations of the 16th Edition of the I.E.E. Wiring Regulations of the
local Electricity Supply Authority.
11.3.1.8.3 The Electrical tests shall include but shall not be limited to the following:
The contractor shall supply, install, connect, and commission all items of electrical gear
in the approximate locations indicated in the drawings, all in compliance with in load
schedules and distribution schematic drawing.
11.4.1.1 The main MCCB L.V. Distribution board/s, designated SMDB/s, shall be of
600/1000V insulation grade and shall be designed and constructed to comply
with the requirements of BS EN 60439: 1: 1999. The busbars constructed
of highest quality and purity copper shall be used throughout shall be designed
and certified to withstand short circuit of 40 kA for 1 second.
11.4.1.2 Unless stated otherwise, the SMDB/s shall generally be of wall-mounted type,
and shall be air-insulated, totally enclosed, fully interlocked and of Form
2 construction.
11.4.1.3 The board shall be dust and damp proof to comply with the requirements of IP
43.
S11 / 11
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.4.1.5 All necessary cable boxes, lugs, clamps etc. appropriate to the cable sizes shall
be provided
11.4.1.6 All MCCBs shall be designed and constructed to provide short circuit breaking
capacity of 35 kA, and shall conform to the requirements of BS EN 60947 –
1:1999. All MCCBs shall be of thermal-magnetic, manually and automatically
operated type, and shall be design to provide positive trip-free operations on
abnormal loads with quick-break contacts for both manual and automatic
operations. Adequate protection for the stationary and movable contacts
shall be provided with rapid and effective arc interrupting devices. An inverse
time-delay thermal over-current trip element and a magnetic instantaneous
over current trip element shall be provided on each pole of the breaker for
common tripping of all poles.
11.4.1.7 In compliance with the requirements and directions of DEW A, the following
meters and accessories shall be supplied, tested and installed each board.
- 3 No. suitably scaled ammeters.
- 1 No. suitably scaled voltmeter with integral phase selector switch.
- 3. No. current transformers.
11.4.1.8 No. and locations of kilo-watt-hour meters suitable for three phase integrated
unbalanced loads shall be indicated in the single line distribution schematic.
11.4.1.2.1 The design of all final MCB distribution boards shall strictly conform to the
requirements of DEWA with respect to busbar sectionalization, and number and
respective sensitivities of RCCBs / ELCB for each board. Other details related to MCB
ratings, wiring sizes, phase load distribution etc. in respective load schedules shall
remain unaltered.
11.4.1.2.2 All boards shall be factory fabricated and constructed of corrosion-resistant
sheet steel of minimum thickness 1.2 mm. All boards shall comply with the
requirements of BS EN 60439: 1 : 1999. Busbars constructed of highest quality
and purity copper shall be used throughout.
11.4.1.2.3 Unless specifically stated or required otherwise, all boards shall be flush mounted,
totally enclosed, dust, damp and corrosion proof type. Each board shall be
equipped with a robust cover, lock and key.
11.4.1.2.4 All MCBs shall be of high performance, rapid interrupting, current-limiting type
designed and type tested to BS EN 60898 : 2003.
11.4.1.2.5 All MCBs shall be thermal-magnetic, manually and automatically operated type to
provide positive trip free operation on abnormal overloads with quick-break
contacts, the thermal element providing inverse time-delay tripping on abnormal
overloads, and the magnetic element providing instantaneous tripping on short-
circuits.
11.4.1.2.6 All MCBs shall be suitable for mounting on rails inside the enclosure to
facilitate removal of one without disturbing the others.
11.4.1.2.7 MCBs shall be of type 2 characteristic for general lighting and small power circuits,
and of type 3 characteristic for circuits supplying AC units, pumps or similar other
equipment using induction motors. Category of duty shall be M6 or M9 depending
on the fault level at the point of installation.
S11 / 12
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.4.1.2.8 All RCCBs / ELCBs shall be designed and constructed to comply with the
requirements of BS EN 61008: 1 : 1995.
The sensitivities in milli-amperes of respective RCCBs shall be indicated in he load
schedules.
11.4.1.3 ISOLATORS
11.5 SECTION E - 5
The contractor shall supply, install, test, connect and commission an automatic power
factor correction panel of kVAr rating as specified and indicated in the distribution
schematic drawing and load schedule for LV Panel Board..
Unless stated or required otherwise, the panel shall form an integral part of the LV Panel
Board. Where this is not possible, the panel shall be installed adjacent to the LV Panel.
The panel shall be constructed of highest quality corrosion-resistant sheet steel coated
with a compound to provide resistance against corrosion and scratches. The panel shall
be complete with main incoming isolator switch, an electronic power factor
regulator/controller, power factor improvement capacitors, power factor meter,
contactors, fuses and any other component and accessories deemed necessary for a high
quality power factor correction equipment.
The components of the panel shall be selected and designed to ensure that the power
factor of the system is maintained at a minimum value of 0.9 lag for all loads up to the
full load.
11.5.1.1.1 The panel shall be complete with incoming cable box, cable gland, lug,
clamps etc.
11.5.1.1.2 The panel door shall be mechanically interlocked to prevent opening
before the equipment is isolated.
11.5.1.1.3 ON/OFF/AUTO switches shall be provide mounted flush on the panel.
11.5.1.1.4 Each capacitor unit shall comprise requisite number of individual capacitor
elements manufactured from impregnated metallized paper and plastic
film.
S11 / 13
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.5.1.1.5 Each step shall be designed for kVAr rating as specified in the load
schedule for LV Panel Board and as indicated in the distribution schematic
drawings.
11.5.1.1.6 The Regulator/Control gear shall be designed to provide, but shall not be
limited to, the following features and facilities.
(ii) No-volt release which will instantly disconnect the capacitor bank in the
event of mains supply failure. With the return of mains voltage the
capacitor banks shall be switched ON after 90 seconds.
(iii) LED indication of capacitive and inductive load and the number of steps
energized.
(iv) The main incoming isolator / load break switch shall be of 600/1000 V
insulation grade and shall be designed and rated for the required
capacitive switching duty.
The contractor shall supply, install, test and connect all cables and wires, commencing from
the Main Distribution Board (MDB), thence to Final MCB distribution Boards, isolators
for A/C split condensing units, pumps, A/C F.C.U./A.H.U. etc. if specified or required, all in
compliance with details called for in the distribution schematic drawing, cable routes
drawing and the respective load schedules for the various boards.
S11 / 14
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.6.1.1.7 All final sub-circuit wiring shall be drawn in PVC conduits concealed within
the building fabric.
11.6.1.1.8 All XLPE insulated cables shall conform to the requirements of BS 5467: 1997.
11.6.1.1.9 All PVC insulated cables shall conform to the requirements of BS 6346: 1997.
11.6.1.1.10 All PVC insulated wiring for lighting and small power shall conform to
the requirements of BS 6004: 2000.
11.6.1.1.11 All rubber-insulated cables suitable for continuous temperature of 150 deg.
C for final connection to heating equipment, (and where otherwise subjected to
heat), shall conform to the requirements of BS 6007: 2000.
11.6.1.1.12 All insulated flexible cords and cables shall conform to the requirements of BS
6500 : 2000.
11.6.1.1.13 All low-loss co-axial cables for TV installation works shall conform to the
requirements of BS 5425:1986.
11.6.1.1.14 Prior to commencing installation works, the contractor shall submit, for
the Engineer's study and approval, the proposed method of installation of
cables and wiring in each area together with working drawings with all
necessary details.
The Contractor shall supply and install a complete network of conduits, trunking, trays and
duct works in accordance with the requirements of wiring and cabling of the project.
11.7.1.1 GENERAL
11.7.1.1.1 All conduits, trunking, trays etc. shall be arranged in a neat and inconspicuous
manner, and each system shall be completely assembled, inspected and tested
prior to cables/wiring being drawn in them.
11.7.1.1.2 All works shall be carried out in strict compliance with the recommendations of
the manufacturer and the Wiring Regulations in BS 7671 : 2001.
11.7.1.1.3 Prior to commencement of any part of the works, the Contractor shall submit,
for Engineer's study and approval, two sets of prints indicating conduit,
trunking, tray and duct sizes together with the proposed layout of respective
systems.
11.7.1.2.2 All conduits throughout the installations shall be sufficiently large cross-sections and
shall be arranged, with sufficient number of strategically located drawing
boxes, to allow easy drawing of any or all the cables. Care shall be exercised
to ensure that the number of wires drawn in a conduit, relative to its diameter,
does not exceed the number stipulated in the Wiring Regulations, BS 7671:2001.
Should these differ in any way with the Regulations of the local. Electricity Supply
Authority, the requirements of the latter shall be adhered to.
S11 / 15
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.7.1.2.3 All conduits shall be run in a manner to facilitate self-draining to outlet boxes.
Each length of the conduit shall be cleaned and dried with the help of a swab
drawn through its length, and all boxes shall be cleaned to remove moisture
prior to installing the cables.
11.7.1.2.4 Conduit bends shall be made with the bore of the tube remaining full and free
throughout and all conduits shall be perfectly smooth inside and out- side, and
free from any burrs and sharp comers. Bends shall be made without heating the
conduits and by using approved type of bending machine or bending block to
give results consistent with the best grade of craftsmanship.
11.7.1.2.5 No more than two right angle bends shall be permitted between draw- in boxes.
No diagonal runs of conduits shall be allowed on the walls of structure.
Conduits concealed in the ceiling slab shall run parallel to walls and beams, and
those concealed in walls shall be run vertical and / or horizontal.
11.7.1.2.6 All conduits cast in concrete or laid in floor screeds shall be effectively secured,
positioned and protected against mechanical damage, ingress of concrete etc.
Allowance shall be made for thermal expansion and contraction of straight runs of
conduits.
11.7.1.2 INSTRUCTIONS & GUIDELINES FOR CONDUIT INSTALLATION: [Cont'd.]
11.7.1.2.1 Where conduits run parallel to one another, the distance between adjacent
conduits shall not be less than 15 mm. At junction of multi-run of conduits,
rectangular adapter boxes having internal dimensions not less than 150 x 100
x 50 mm, shall be used. Maximum of Nos. 20 mm diameter and a maximum of
2 Nos. 20 mm diameter conduits shall enter the longer and shorter sides of
the boxes respectively. For more or larger sized conduits, larger boxes of
appropriate sizes shall be used.
11.7.1.3.1 All PVC conduits shall be high-impact, rigid and heavy gauge complying with
the requirements of BS 6099 : PART 2 : SECTION 2.2 :1982. Fittings and
accessories shall be of same manufacture as the conduits.
S11 / 16
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.7.1.3.2 All conduits shall be unthreaded, slip-fit and push-on type. Unless
otherwise specified only plain couplers shall be used. All joints shall be
made with weather-proof adhesive as recommended by the manufacturer.
11.7.1.3.4 At all expansion joints in the structure, expansion couplers shall be installed.
11.7.1.3.5 Draw-in boxes and switch mounting boxes shall be made of PVC and shall be
equipped with earth terminals.
11.7.1.3.6 Wherever necessary, approved type of flexible conduits and adapters may
be used.
11.7.1.3.7 Spacing of conduit runs from other services shall be the following
minimum values :
9.7.1.3.8 Minimum wall thickness of conduits used shall be 1.8 mm for conduit of inner
diameter 20 mm, the thickness increasing progressively with increase of
diameter of conduit
11.7.1.4.1 All metal conduits shall be heavy gauge welded screwed steel tubing
complying with the requirements of BS 4568: 1: 1970, and shall be heavily
galvanized both inside and outside throughout their entire lengths. All
conduit fittings and accessories shall be finished to the same classification of
protection as for the conduit.
11.7.1.4.2 All conduits shall be fixed in approved manner by means of crumpets,
saddles, spacer bar saddles, cast distance saddles, cadmium plated steel
screws, bolts, nuts etc. all complying with the requirements of BS 4568: 2:
1970.
11.7.1.4.3 All conduits shall be threaded so that the ends of the conduits butt
close together in conduit coupling. Lock nuts shall be provided at all running
joints. All exposed threads shall be thoroughly coated with red lead after
installation.
11.7.1.4.4 All conduits shall be mechanically and electrically continuous and shall
be effectively bonded and earthed. Earth connections and bonding to conduits
shall be by means of copper tape or copper earth wire and earthing clamps
complying with BS 951:1999. Where the conduit makes contact with
structural steel, an efficient and permanent bond shall be made between
the conduit and metal work.
S11 / 17
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.7.1.4.5 All conduit boxes shall be constructed of malleable iron or pressed steel and
shall have the same classification for protection as for the conduit. Where
they do not serve as outlets, they shall be fitted with lids secured with brass
screws. Earthing terminals shall be provided in all outlet boxes
11.7.1.4.6 All conduits shall be checked on completion and all imperfections shall be
made good. Rust, minor damage and the exposed threads in conduit runs
installed on the surfaces shall be painted with two coats of Zinc chromate
paint and finished with approved air drying metallic paint. Conduits
concealed in the building structure shall be painted with two coats of air
drying red lead paint. The paints shall be applied immediately after the
completion of conduit installation.
11.7.1.4.7 Wherever there is likely to be excessive condensation, boxes shall be filled
with a suitable plastic compound approved by the Engineer.
11.7.1.4.8 At all expansion joints in the structure an approved type of flexible sliding
connection shall be provided at every run of conduit to take up any
expansion or contraction of the conduit under service conditions. Bonding
across the joint shall be maintained by separate circuit protective conductor.
11.7.1.4.9 All conduit runs shall have adequate clearance between them and all other
service lines.
11.7.1.4.10 Flexible conduits complying with complying with the requirements
of BS 731: 1: 1952 shall be used wherever necessary to allow movement
between the conduit and equipment to be connected. For such connections
approved type of solid bronze adapters with standard thread for the flexible
shall be used.
11.7.1.5.1 Rigid heavy gauge PVC trunking of approved manufacturer may be used in lieu
of multiple runs and shall be rigidly supported along their entire lengths. All
fixings shall be carried out with cadmium plated steel screws.
11.7.1.5.2 All PVC trunking and their lids shall comply with the requirements of BS 4678: 4: 1982.
11.7.1.5.3 The installation of PVC trunking shall be carried out in strict compliance with
the recommendations of the manufacturer
11.7.1.5.4 Allowance shall be made for expansion of the trunking by using washers at all
fixing points.
11.7.1.5.5 Separate circuit protective conductors shall be used throughout the system for
earthing purposes.
11.7.1.5.6 All jointing shall be carried out using vinyl cement glue in compliance with
manufacture's recommendations.
S11 / 18
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.7.1.6.2 Cable trays shall be supplied in nominal 2.4 m lengths and shall be of the return
flange type.
11.7.1.6.3 Trays up to but not including 150mm width shall be of 20 SWG thickness. Trays of width
150mm to 375 mm shall be of thickness 16 mm SWG. Trays of width 375 mm to 600 mm
shall be of thickness 14 mm SWG.
11.7.1.6.4 Sections of trays shall be jointed using 6mm diameter mushroom-headed safelt bolts and
nuts complying with the requirements of BS 1449.
11.7.1.6.6 Holes cut in trays for passage of cables shall be suitably bushed.
11.7.1.7.1 All cable support ladders shall be manufactured from pre-galvanized sheet steel,
of minimum thickness 1 metric gauge, complying with the requirements of BS
449:21969.
11.7.1.7.2 Ladders shall be hot-dip galvanized to comply with the requirements of BS 729,
and shall be suitable for installation in humid conditions prevailing in the U.A.E.
11.7.1.7.3 The rungs of ladders shall be supported on either ends by hexagonal profiled
steel sheets channels.
11.7.1.7.4 In both horizontal and vertical runs the ladder shall firmly supported by
accessories and devices to ensure they are able to withstand the weight of
cables.
11.7.1.7.5 Where ladders are mounted on walls, a minimum distance of 25mm shall be
maintained between walls and cable services.
11.7.1.7.6 Where ladders are run horizontally supported by cantilevers or other devices, the
spacing of the latter shall be in compliance with manufacturer's
recommendations.
11.7.1.7.7 The width of ladders shall be adequate to ensure that the minimum spacing
between surfaces of adjacent cables shall be the diameter of the larger cable.
11.7.1.7.8 The ladders shall be connected to the EARTH and electrical continuity shall be
maintained throughout their entire run.
S11 / 19
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.7.1.7.9 The installation shall be complete with all accessories inclusive of necessary
joints, couplings, bends, clamps, support brackets, wall and ceiling plates,
mounting rails, take-off hooks etc., all manufactured by the manufacturer of
ladders.
The Contractor shall supply, install, test and connect complete lighting and small power
installations, inclusive of all luminaries, lamps/tubes, switches, contactor switches, socket
outlets and other wiring accessories, conduits, trunking, sub-circuit wiring etc., all in strict
compliance with these Specifications, drawings, Load Schedules and Schedules for
luminaires and wiring accessories.
11.8.1.1 GENERAL
11.8.1.1.1 All wiring shall be carried out in strict compliance with cable sizes and circuit
details given in respective load schedules and drawings.
11.8.1.1.2 All wiring of multi-point sub-circuits shall be carried out as a "loop-in" system.
No joints in any point in the wiring run shall be permitted.
11.8.1.1.3 Wiring for lighting and small power circuits shall be run in separate
conduits/trunking back to their respective final MCB distribution boards .
Circuits supplied from different phases shall not be housed in the same
conduit. Care shall be exercised to ensure both the live and the neutral
conductors of a circuit shall in all cases be contained in the same conduit.
11.8.1.1.4 Every single pole switch and MCB in a two-wire circuit shall be connected to
the phase conductor. Every single phase circuit shall have its own neutral
and earth connections taken from its respective final distribution board.
11.8.1.1.5 Wiring for each circuit run in trunking shall be taped and bound at
intervals throughout the entire length and shall be labelled at each junction
and terminal point for easy identification of circuits.
11.8.1.1.6 Prior to drawing wiring in conduits/trunking, the entire system inclusive
of outlet boxes, isolators, MCB distribution boards etc. shall be completed
and inspected. Any conduits/trunking not accepted by the Engineer
shall be replaced without additional charges.
The Contractor shall pay special attention to the segregation of L.V.
wiring system for fire detection and alarm system, Telephone, Intercom,
MATV and other E.L.V. systems, to ensure no adverse interaction shall occur
between the various systems. Segregation of wiring system shall strictly
comply with the requirements of BS7671:2001 (I.E.E. Wiring regulations).
11.8.1.1.7 Color code and identification of cable/wiring cores shall be in compliance
with the local Electricity Supply Authority's regulations.
S11 / 20
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.8.1.1.8 All luminaires and wiring accessories shall be as described and specified in
the respective schedules of equipment. Samples of each type of luminaire,
wiring accessory and other related equipment shall be submitted for
Engineer's final approval before placing orders for the same.
Specification for general requirements and tests for all luminaires shall conform to the
requirements of BS EN 60598:1: 2000.
11.8.1.2.2.1 Lighting fixtures with tungsten filament lamps shall comply with the
requirements of BS EN 60598.
11.8.1.2.2.2 All tungsten filament lamps shall comply with the requirements of BS
6179:1982.
11.8.1.2.2.3 Edison screw lamp holders shall comply with the requirements of BS
EN 60238: 1999.
S11 / 21
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.8.1.2.3.1 All low voltage halogen lamp luminaires shall comply with the
requirements of BS 4533:102 ; Section 102.6 : 1990, BS EN 60598.
These shall generally be used as recessed down lighters and shall be
complete with a separate or integral transformer and 50 W halogen
lamp.
11.8.1.2.3.2 The body of the fixture shall be made of high quality die -cast
aluminum with steel hook springs and shall be complete with a 50 mm
diameter dichroic reflector. A terminal block mounting rod and the
lamp's steel hook fixing system shall facilitate easy installation.
11.8.1.2.3.3 Tungsten halogen lamps shall generally comply with the requirements of
BS 1075: 1989, IEC 357: 1977.
11.8.1.3.1 SWITCHES
Domestic flush type and industrial metal clad surface type shall be
specified for different areas shown in the drawings and as indicated in
the schedule of Accessories and Materials.
11.8.1.3.1.2 All 20A DP switches for controlling water heaters and like equipment
shall conform to the requirements of BS 3676:1:1989.
S11 / 22
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.8.1.3.2.1 All general purpose socket outlets shall be of 13 A shuttered type with
neon indicators complying with the requirements of BS 1363: 2: 1995.
These shall generally be connected either in a radial or in a ring circuit
as indicated in the drawings and load schedules for final MCB
distribution boards.
Domestic flush type and industrial metal clad surface type shall be
specified for different areas as shown in the drawings and as indicated
in the schedules of wiring accessories and materials.
11.8.1.3.2.2 In all under floor installations, the wiring for 13A, 3 -pin, general
purpose socket outlets shall be drawn in a separate compartment of a
multi-compartment underfloor trunking and shall be appropriately
segregated from all extra-low voltage cabling in compliance with the
recommendations detailed in section 528 of BS 7671:2001.
All cooker control units shall comply with the requirements of BS 4177:1992 . Each
unit shall be flush type complete with 45 A DP main switch; 1 3A socket outlet with
neon indicator and cooker connection unit complying with the requirements of BS
5733:1995.
All switched and un-switched connection units indicated in the drawings shall
comply with the requirements of BS 5733:1995. These shall be flush type
complete with 20 A DP switches (where applicable), 13 A fuse -link to BS
1362: 1973 , flex outlets, neon indicators and mounting boxes.
All junction boxes shall comply with the requirements of BS 6220:1983. These shall
have either 4 or 3 terminal blocks. 10A/30A ratings, accepting 4/6 6.0sq. mm single
core cables.
S11 / 23
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
These shall be suitable for use in multi-outlet aerial system, providing necessary safety
isolation rated at 2000 VAC isolation to BS 415:1994. These outlets shall 6e designed for
UHF/VHF TV and VHF/FM radio signals reception.
All connector units indicated in the drawings for connection to split-type and window type A.C
units shall comply with the requirements of BS 5733 :1995.
11.9.1 EARTHING
The contractor shall supply, install, test and connect a complete earthing system
comprising necessary earthing electrodes, earth bars, earth electrode cables, earth
electrode inspection housing, protective conductors, connections and any other
components and accessories deemed necessary for a highly reliable, safe and satisfactory
earthing system to the approval of the local Electricity Supply Authority.
11.9.1.1 GENERAL
11.9.1.1.1 The installation of the earthing system shall comply with the requirements of
BS 7671:2001 (IEE Wiring Regulations) and with the Code of Practice
detailed in BS 7430:1998. Should the regulations and recommendations
detailed in the aforementioned standards differ in any way with those of
the local Electricity Supply Authority, the requirements &
recommendations of the latter shall be adhered to.
11.9.1.1.2 The main L.V. earthing system shall comprise earth electrode/s installed
at suitable locations near the main distribution board. Appropriate sized
copper earthing conductor shall connect the earthing electrode/s to main
copper earth bar in the main distribution board. Frames for all items of L.V.
switchgear, all earthing conductors etc. shall in turn be connected to the main
earth bar.
S11 / 24
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.9.1.2.1 The installation of the earthing system shall comply with the requirements of
BS 7671:2001 (IEE Wiring Regulations) and with the Code of Practice
detailed in BS 7430:1998. Should the regulations and recommendations
detailed in the aforementioned standards differ in any way with those of
the local Electricity Supply Authority, the requirements &
recommendations of the latter shall be adhered to.
11.9.1.2.2 In areas of high soil resistivity it may be necessary to install more than one
earth electrode. In such cases the electrodes shall be at least 6 m apart
with the necessary couplers between them.
11.9.1.2.3 The number of earth electrodes and their types, diameter, length, setting
depth and the method of installation shall be in complete conformity
with the aforementioned Standards and the requirements of the local
Electricity Supply Authority. The earth electrode/s resistance shall not exceed
1.0 ohm or the value recommended by the local Supply Authority.
11.9.1.2.4 In general, the earth electrodes shall be driven to a minimum depth o f 3 m or
0.3 m below permanent water level. The earth electrodes shall comprise
minimum 16 mm diameter hard drawn copper rods complete with hardened
steel tip, driving cap and phosphor bronze coupling suitable for the required
size of copper earth conductor.
11.9.1.2.5 The copper earth conductor shall connect the earth electrodes to the main
earth bar via a test clamp to be located 0.6 m above F.F.L.
The earth electrode cable shall be PVC sheathed stranded copper conductor of
appropriate cross-sectional area The cable shall connect the earth electrode/s to the
main earth bar. One end of the cable shall be sweated into a lug and connected to the
main earth bar with 16 mm (minimum) diameter brass washers and two brass lock nuts.
The other end shall be connected to the earthing electrode/s in compliance with the
recommendations of the manufacturer of earth electrodes.
A concrete inspection housing with a heavy duty hinged cast iron cover and frame made in
a pit 300 x 300 mm shall be provided for each earth electrode connection. A permanent
label marked with the words "SAFETY ELECTRICAL EARTH – DO NOT REMOVE" shall be
provided at each connection.
11.9.1.5.1 All metal parts of every electrical equipment shall be connected to the
earthing system. Metal parts of item of electrical equipment to be earthed
shall include but shall not be limited to, switchgear, metal armour of cables,
metal conduits trunking, trays, accessories, outlet boxes, motor and
S11 / 25
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.9.1.5.2 As described above, all items in the system shall be effectively earthed so that
these are continuously electrically conductive. The electrical resistance at any
point in the system to earth shall not exceed 1 ohm, or the value stipulated
by the local Electricity Supply Authority.
11.9.1.5.3 The neutral conductor shall not be earthed any where within the complex.
11.9.1.5.4 The earthing of water mains and other service lines shall be carried out in strict
compliance with the recommendations of BS 7671:2001.
11.10.1.1 GENERAL
This specification document describes the minimum requirements for the
design, engineering, supply, installation, pre-commissioning testing and
commissioning of a 12kWp on-grid solar photovoltaic (PV) system
S11 / 26
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
Once the detail design of the PV system has been finalized and approved
by all parties, the PV Contractor shall present projected system energy
generation calculations
11.10.1.2.3 Installation
S11 / 27
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
S11 / 29
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
S11 / 30
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
S11 / 31
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.10.1.4.12 AC Cables
11.10.1.4.12.1 All other AC cables including armored and unarmored
designs, single and multi-core constructions shall be according to DEWA
Wiring Regulations.
11.10.1.4.12.1.1 BS 5467 - for XLPE insulated armored cables
11.10.1.4.12.1.2 BS 7889 - for XLPE insulated single core un
armored cables
The PV Contractor shall design, supply and install LV, AC Collection Board
that combines the AC outputs from each inverter into a balanced 3-phase
output (400 V AC, 3-phase), which is then terminated at the SMDB circuit
breaker at the electrical room.
S11 / 35
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
galvanized, or when parts are located in high corrosive areas, stainless steel
A316 shall be used instead
11.10.1.4.19 Construction
All connection plates should be installed on the outside surface of the
supports. Accessories like bends, Tees, risers shall be made with
manufacturer’s fittings or equivalent. The effective radius must be not less
than that allowable bending radius of the cables involved
Sufficient space in the building electrical room or any separate room shall
be provided to the PV Contractor to wall mount the string inverters. The
SMDB shall be provided at the Electrical room
S11 / 36
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.10.1.4.25 Training
The PV Contractor shall be responsible for developing a training schedule
and presentation to the Client personnel regarding operation and
maintenance of equipment installed as specified in this specification. The
PV Contractor shall be responsible for completing a 2-day training on the
PV power system to the Client’s personnel.
Equipment Warranty
Minimum 10 years defect Liability period
Modules
Limited Peak Power of 90%
Inverters 10 years standard manufacturer’s warranty
Monitoring System 10 years standard manufacturer’s warranty
Full PV system 1 full year, Free Maintenance including all parts required
S11 / 37
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
The Contractor shall supply and install voice, data and CATV systems as described below and
in compliance with the requirements detailed in the drawings. All works shall be carried out in
strict compliance with the current rules, regulation and recommendations of the local DU
office.
11.10.1.1 GENERAL
11.10.1.1.1 The works shall comprise supply and installation of main and sub-main
distribution frames, conduits, trunking, voice, data and CATV outlet points
complete with voice, data and CATV socket outlets, wiring and any other
components and accessories deemed necessary for reliable and satisfactory
voice, data and CATV systems.
11.10.1.1.2 The Contractor shall lease with DU supplying and drawing wires
between the distribution frames and the various outlets.
11.10.1.1.3 All equipment used in the installation shall be approved by the local DU
office.
11.10.1.1.3 The Contractor shall submit, for Engineer's study and approval, equipment
schedule and comprehensive wiring diagram of the system prior to
commencing any installation works.
All distribution cabinets for telephone and CATV systems, structural cables Cabinets shall
be corrosion resistant, fully enclosed, dust and vermin proof and complete with hinged
doors with lock and key. These shall be constructed from high-quality sheet steel or fiber
glass and shall be approved by the local office of DU.
11.10.1.3.1 The fiber optic cables may be run in cable tray of appropriate size.
S11 / 38
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
11.10.1.3.2 Generally the Contractor shall be required to supply and install the following
high-impact uPVC conduits of approved manufacture :
11.10.1.3.3 Should the No. and diameter of above conduits be different from those
required by DU, the requirements of the latter shall be adhered to.
11.11.1.1 SCOPE
The Contractor shall supply, install, test, connect and commission a high-quality Fire
Detection and Alarm System comprising a Fire Alarm Panel, Smoke Detectors, Heat
Detectors, Manual Call Points, Sounders together with all necessary fire-resistant cables
and accessories deemed essential for a safe, reliable and satisfactory system, conforming
to the relevant and applicable requirements and recommendations of BS 5839:1:2002, BS
5445 and BS 5446, and complying with the rules, regulations and recommendations of the
local Civil Defense Authority.
11.11.1.2.1 The various components of the proposed Fire Detection and Alarm
System indicated in the drawings are notional and their numbers may be
altered to comply with the requirements and recommendations of the local
Civil Defense Authority.
11.11.1.2.2 Prior to submitting his proposal, the Contractor shall be required to
coordinate with the aforementioned Authority and the selected/approved
manufacturer of the proposed equipment to ensure all necessary
components, accessories, cabling etc. are included in the offer.
11.11.1.2.3 Prior to placing order for any equipment, the Contractor shall
submit comprehensive documents comprising working drawings,
catalogues and descriptive literature of components, maintenance manuals
etc. for Engineer's study and approval.
11.11.1.2.4 All installation works shall conform to the best principles of modern
practice and shall be carried out by competent tradesmen of appropriate
grades.
S11 / 39
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
These shall be of optical and addressable type designed to detect visible smoke
from slow smoldering fires. These shall comply with the requirements of
BS 5839:1:2002, BS 5446:1:2000.
S11 / 40
Vol.2 Section–11 MPL-P142_6316345_Dubai Hills Estate, Dubai - UAE
11. Electrical Installation
These shall be designed to detect high energy fires with little or no smoke, and
shall comply with the requirements of BS 5446:2.2003.
These shall comply with the requirements of BS 5839:2:1983, and shall be of the
color and type specified by the local Civil Defense Authority.
11.11.1.4.5 BELLS
These shall comply with the requirements of BS 5839:1:2002, and shall have an
output of 100 dB at a distance of 1 meter.
11.11.1.4.6 WIRING
All wiring and cabling shall be carried out using fire-resistant 2-core 1.5 sq.mm
screened type cables complying with the requirements of BS 7629:2:1997 and
BS 6387:1994 or as approved by the local Civil Defense Authority.
1. Ludwig, Germany
2. Bega, Germany
3. Siemens, Germany
4. Philips, Holland
5. Zumbotel, Austria
6. Trilux, Germany
7. National, Japan
8. Telemechanique, France
9. MK, UK
12. ABB
17. Egatube, UK
18. Davies, UK
19. Swift, UK
21. Burn, UK
S11 / 42