 GENERAL
The RS4E5600 CENTUM VP Integration Package runs on a safety engineering station (SENG) to archieve system
integration on the ProSafe-RS or ProSafe-RS Lite with the CENTUM VP. (*1) This software is available for ProSafe-
RS and ProSafe-RS Lite (*2).
*1: In an RS Project, this package cannot be used together with “CI Server Integration Package” (RS4E5700).
*2: For ProSafe-RS Lite, it has been supported since ProSafe-RS R4.06.

 FUNCTION OVERVIEW
With this software, in the ProSafe-RS/ProSafe-RS Lite and the CENTUM VP integrated system, access can be made
from a human interface station (HIS) or a field control station (FCS) to a safety control station (SCS) to perform the
following:
• SCS data can be operated and monitored from the HIS. (*1)
• SCS data can be accessed from the FCS.
• Process Alarms, Annunciator Alarms and System Alarms by the SCS can be managed on the HIS.
• The HIS can show the SCS’s status.

With this software, users can configure a system that integrates ProSafe-RS/ProSafe-RS Lite and the CENTUM VP,
as illustrated below.

Automation Design Server

Ethernet

ProSafe-RS CENTUM VP CENTUM VP


SENG HIS HIS/ENG

Vnet/IP

SCS FCS FCS

F01E.ai

SENG: Safety Engineering Station


SCS: Safety Control Station
HIS: Human Interface Station
ENG: Engineering Station
FCS: Field Control Station

*1: None of SCS I/Os needs to add to the number of I/Os of “VP6H1100 basic operation and monitoring function.”
*2: If the SENG and HIS/ENG are installed in the same computer, refer to the GS “ProSafe-RS Safety Instrumented System
Overvew (for Vnet/IP)” (GS 32P01B10-01EN) or “ProSafe-RS Lite Safety Instrumented System Overview” (GS 32P51B10-
01EN).

Figure Example of Configuration of ProSafe-RS and VP Integration System

Yokogawa Electric Corporation GS 32P04D10-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Nov. 2015 (YK)
5th Edition Jan. 22, 2021 (YK)
<<Contents>> <<Index>> 2
 FUNCTIONS
The CENTUM VP integration package has the functions summarized in the following table.

Function Description
Tag name definition Using tag name builder, tag names are assigned to SCS's variable and function blocks. The
data of SCS can be accessed from FCS of CENTUM VP, operated and monitored with a
screen same as FCS from HIS.
Alarm priority definition Using the Alarm Priority builder, output format and action of process alarm are defined in the
HIS viewer when the alarm occurs or it is recovered normally.
Alarm processing definition The alarm processing table is a list that set importance of the alarm of SCS. User import the
alarm processing table which user defined in CENTUM VP in alarm processing table builder.
Annunciator message definition Using the Tag Name builder, the content of annunciator messages to be shown on the HIS on
an SCS-by-SCS basis is defined.
Common definitions for integration with In the Properties window of an SCS project, SCS parameters necessary for integration with
the CENTUM VP (*1) the CENTUM VP are defined.
*1: The SCS parameters must be defined on the CENTUM VP side separately and it’s necessary to start tag list generation
function.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04D10-01EN Nov. 27, 2015-00
<<Contents>> <<Index>> 3
l SCS Data Types and Function Block Name which are Assigned Tag Names
SCS’s variable data type and function blocks which can assign tag name are summarized in the following table.
The points of tag which are assigned tag name are included in the points of tag monitoring of the CENTUM VP.

Data type/Function
Function category Details
Blocks
BOOL BOOL type
Inter variable DINT Integer-type
REAL REAL number-type
IO_REAL Analog
I/O variable
IO_BOOL Discrete
ECW_B Data Setting (BOOL)
Data Setting from
ECW_I Data Setting (integer)
external device
ECW_R Data Setting (real number)
ANLG_S Analog Input Function Block with Data Status

Analog input ANLGI Analog Input


indication HSDTR Analog Input Function Block for Smoke and Heat Detector (with Reset Function)
GASDTR Analog Input Function Block for Gas and Flame Detector (with Reset Function)
Velocity limit VEL Velocity Limit Alarm
ANN Annunciator
Annunciator
ANN_FUP First-up Alarm Annunciator
GOV_B Grouping Override (BOOL)
GOV_IB Grouping Override (discrete)
OVR_B Override (BOOL)
Override from HIS OVR_I Override (integer)
OVR_R Override (real number)
OVR_IB Override (discrete)
OVR_IR Override (analog)
Password PASSWD Password entry
BOOL-Type Data Manual Operation Function Block with Two-Position
MOB_11
Answerback
BOOL-Type Data Manual Operation Function Block with Three-Position
Manual operation MOB_21
Answerback
MOB_RS Auto-Reset BOOL-Type Data Manual Operation
MOA Analog-Type Data Manual Operation
PSI_I Integer-type fire and gas communication input

Safety subsystem PSI_R Real-type fire and gas communication input


communication I/O PNI_I Integer-type PROFINET communication input
PNI_R Real-type PROFINET communication input
SCI_B Subsystem Communication Input (BOOL)
SCI_I Subsystem Communication Input (integer)
SCI_R Subsystem Communication Input (real number)
Subsystem
SCO_B Subsystem Communication Output (BOOL)
SCO_I Subsystem Communication Output (integer)
SCO_R Subsystem Communication Output (real number)

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04D10-01EN Nov. 14, 2017-00
<<Contents>> <<Index>> 4
The following table summarizes the capacity of function blocks that can be operated/monitored for each SCS in an
integrated CENTUM VP system configuration.

Maximum Number of Blocks

Name Function Block/Element Name SSC60,


S2SC70 L1SC70 SSC50
(*1)
ANLG_S/ANLGI/HSDTR/GASDTR Analog input block
Velocity (rate-of-change) alarm
VEL
block
OVR_B/OVR_I/OVR_R/OVR_IR/OVR_IB/GOV_B/ Total 2700 Total 2700 Total 1800
Override block
GOV_IB
PASSWD Password block
MOB_11/MOB_21/MOB_RS/MOA Manual loader block
BOOL/ECW_B BOOL-type variable 3200 3200 3200
IO_BOOL BOOL-type contact I/O variable 1500 1500 1000
DINT/REAL/ECW_I/ECW_R/IO_REAL DINT/REAL-type variable 900 900 900
Safety subsystem communication
PSI_I/PSI_R/PNI_I/PNI_R (*2) 2000 ― ―
I/O block
SCI_B/SCI_I/SCI_R/SCO_B/SCO_I/SCO_R Subsystem communication block 2000 (*3) 2000 (*3) 2000 (*3)
ANN/ANN_FUP Annunciator message 2000 2000 1000
*1: For L1SC70, supported by ProSafe-RS R4.06 or later.
*2: Supported by ProSafe-RS R4.03.10 or later.
*3: The maximum number of subsystem communication blocks per SCS earlier than ProSafe-RS R4.03.10 is up to 500.

 SYSTEM REQUIREMENTS
Refer to the GS “ProSafe-RS Safety Instrumented System Overview (for Vnet/IP)” (GS 32P01B10-01EN) or
“ProSafe-RS Lite Safety Instrumented System Overview” (GS 32P51B10-01EN).

 MODELS AND SUFFIX CODES


Description
Model RS4E5600 CENTUM VP Integration Package
-V Software license
Suffix
1 Always 1
Codes
1 English version

 ORDERING INFORMATION
Specify the model and suffix code(s).

 TRADEMARK ACKNOWLEDGMENT
The names of corporations, organizations, products and logos herein are either registered trademarks or trademarks
of Yokogawa Electric Corporation and their respective holders.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04D10-01EN Jan. 22, 2021-00
Subject to change without notice.

You might also like