8 PLANT OPERATION....................................................................................................39
8.1 Load Sharing........................................................................................................39
8.2 Start/Stop Sequence.............................................................................................40
8.3 Blackout Recovery Start......................................................................................41
8.4 Load Dependent Start (high load)........................................................................42
8.5 Load Dependent Stop (low load).........................................................................42
8.6 Bus Abnormal......................................................................................................43
8.7 Standby Start options...........................................................................................43
8.8 Heavy Consumer Blocks......................................................................................44
8.9 Non-preferential Groups......................................................................................45
9 AUTOMATIC BUS-TIE................................................................................................47
10 ALARMS.........................................................................................................................48
10.1 Alarm List............................................................................................................48
10.2 MODBUS-slave Alarms......................................................................................49
10.3 System Hard-wired Alarms..................................................................................49
11 MODBUS SLAVE INTERFACE..................................................................................50
11.1 MODBUS Functions............................................................................................50
11.2 MODBUS address list..........................................................................................51
11.3 Packed Digital Data..............................................................................................52
11.4 Force Digital Channel Format..............................................................................54
11.5 Exception Codes...................................................................................................55
11.6 Response Time.....................................................................................................55
11.7 RS485 Port Hardware..........................................................................................55
12 PMS HARDWARE.........................................................................................................56
12.1 PMS Operator panel.............................................................................................56
12.2 PMS I/O module..................................................................................................59
12.3 Connections - Redundant Ethernet.......................................................................61
12.4 Connections - DC Power Supply.........................................................................62
12.5 Connections - Alarms including RS485 (serial alarms).......................................63
12.6 Connections - AC Bus/Generator.........................................................................64
12.7 Connections - PMS I/O-Signals...........................................................................65
13 FLOWCHARTS..............................................................................................................66
13.1 Legend..................................................................................................................66
13.2 PMS Controller functions....................................................................................67
13.3 Operation modes..................................................................................................68
13.4 CB Trip.................................................................................................................69
13.5 Alarm Limits........................................................................................................71
13.6 Disconnect & Stop Generator..............................................................................72
13.7 Low Load Stop.....................................................................................................74
13.8 Offloading............................................................................................................74
13.9 Engine Cooldown.................................................................................................75
13.10 Start & Connect Generator...................................................................................76
13.11 Start Blocking.......................................................................................................77
13.12 Blackout Recovery...............................................................................................78
13.13 Standby Request...................................................................................................79
13.14 Engine Start..........................................................................................................80
13.15 Synchronizer........................................................................................................81
This manual describes the functionality of the standard off-the-shelf MEGA-GUARD E-series
Power Management System (PMS).
The MEGA-GUARD E-series PMS is an innovative automation system that takes minimum
engineering time and minimum different types of modules to design a complete power plant
for various bus and generation types.
The MEGA-GUARD E-series PMS allows for engineering a complete power plant with
identical off-the-shelf PMS-sets for each power/generation connection. It does so by
configuring the specific usage and function of each PMS-set via standard menu options that
fulfill most -if not all- commonly required functionality and grids. In instances where special
functionality and/or signals are required -beyond the off-the-shelf PMS design- the standard
PMS-sets can be easily expanded with minimal additional engineering.
The MEGA-GUARD E-series PMS can be used as a stand-alone system with a RS485 multi-
drop serial link to a 3rd party Alarm & Monitoring System. It can also be integrated with other
MEGA-GUARD systems such as MEGA-GUARD Operator Workstation(s) for graphic
mimic plant representation or e.g. with MEGA-GUARD Alarm and Monitoring System.
Abbreviations:
ABT Automatic Bus-Tie OWS Operator Work Station
AMS Alarm & Monitoring System PMS Power Management System
CB Circuit-Breaker PT Potential (voltage) Transformer
CT Current Transformer PTI Power Take-In
DEC Decrease PTO Power Take-Out
EU Engineering Unit STBY Standby
INC Increase SWBD Switch Board
Legend:
Warning/Important remark
2 PMS INTRODUCTION
The MEGA-GUARD Power Management System (PMS) is an advanced system that provides
the full automation of power plants with low or medium voltage switchboards.
The PMS is a modular system with one fully configurable PMS Controller for each
generation set or automatic bus-tie. With the standard pre-defined functionality -i.e. without
additional software engineering- there can be used maximum 9 PMS controllers to satisfy a
wide variety of grid configurations.
PMS functions include engine start/stop logic, sync check and auto synchronizing functions,
load sharing both active and re-active, frequency and voltage control, load block start
request/permissive handling and non preferential tripping.
One PMS Controller consists of a PMS Control Panel including a PMS I/O-module. The PMS
Controllers for each generation set are interconnected via a redundant Ethernet bus.
The PMS Controller can operate as a stand-alone independent generator controller as well as a
fully integrated part of a complex and fully automated power management system. This level
of autonomy ensures the highest level of reliability and availability of each generation set.
Each PMS controller measures and displays up to 15 system variables. The standard PMS
Controller can also be configured as controller for an Automatic Bus-Tie (ABT) or an
automatic Shore connection circuit-breaker.
The PMS Controller -also referred to as PMS-set- consists of the following electronic
modules that are interconnected with a special I/O-cable:
The main program for the generator control and power management is running in the PMS
Operator Panel executed by a powerful control processor. Two Ethernet ports maintain the
redundant communication with the other PMS Controllers e.g. for bus load calculations. The
control processor interfaces with the belonging PMS I/O board via a special I/O-cable with a
default length of 3 meter.
See paragraph 12.1 for the detailed hard-ware description of the PMS Operator Panel.
See paragraph 12.2 for the detailed hard-ware description of the PMS I/O module.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PMS INTRODUCTION
MEGA-GUARD Power Management Systems have been applied on vessels for more than 20
years with the approval of all major classification societies. Type Approval (TA) certificates
are typically available for LRS, GL, BV, ABS, DNV, BV and RINA. Certificates for other
classification societies can be arranged depending applicable procedures.
Germanischer Lloyd:
Be aware of requirement for SYNC-CHECK RELAY (see 7.7)
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
OPERATOR INTERFACE
3 OPERATOR INTERFACE
The PMS Operator Panel is a user-friendly interface for operating and monitoring of a
generation set or automatic bus-tie or automatic shore circuit-breaker.
Circuit-Breaker closed,
- Generator Power (kW)
No alarms, system healthy
- Generator Voltage (V)
- Generator Current (A)
- Generator Frequency (Hz)
- Cos. phi (φ)
- Bus Voltage
Circuit-Breaker opened,
- Bus Frequency
Last alarm shown
Right side
- Bus 1 Voltage (V)
Bus-Tie closed, - Bus 1 Frequency (Hz)
No alarms, system healthy Bus 1 (generator connection)
ABT: right/higher bus #B
SHORE: shore supply
Left side
- Bus 2 Voltage (V)
Bus-Tie opened, - Bus 2 Frequency (Hz)
No alarms, system healthy Bus 2 (bus connection)
ABT: left/lower bus #A
SHORE: switchboard
ALAR
3.2 Alarm Display M
The red ALARM lamp indicates an active alarm in this PMS Controller. The lamp is steady on
when there is a critical alarm that is blocking start and close commands. First the alarm(s)
must be accepted with the ACK button -and the ALARM lamp must go OFF -or change to
flashing- to enable these commands again. The lamp is flashing slowly when there is an active
alarm that is not blocking start and close commands (e.g. blackout) or flashing fast when
there is a system alarm.
Pushing the ALARM button shows the Alarm display. The Alarm Display returns to the
Operation Display by pushing the ALARM button again, or automatically when no scrolling
takes place for more then 30 seconds.
ALARM-PAGE
▲▼
OFFLOAD FAILURE ALARM ACK. STOP
VOLTAGE HIGH ALARM HORN
Alarms sorting priority: The small arrows are shown when applicable and
1. Unaccepted (flashing) alarms indicate that there un-shown newer alarms (▲) and/or
2. Accepted (steady) alarms ▲▼ older alarms (▼) which become visible when using
3. Occurrence (last to first) scroll up/down buttons.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
OPERATOR INTERFACE
PASSWORD
Password: *|
ACK. STOP
HORN
Value ▲ ▼ ◄ ► Accept ACK STOP
Cancel
Level 2
2. ALARM LIMITS
Value EU ACK. STOP
1. BUS ABNORMALS >> HORN
2. BUS ALARMS >>
3. GEN. PROTECTIONS/TRIP CB >>
4. GEN. ALARMS >>
Level 3
2. 2 BUS ALARMS
Value EU
1. HIGH VOLTAGE ALARM %
2. HIGH
103 VOLTAGE DELAY SEC
3. LOW 3 VOLTAGE ALARM %
4. LOW
97 VOLTAGE DELAY SEC
5. HIGH
3 FREQUENCY ALARM %
103 ▼
1 *
Example menus do not necessary reflect literal menu texts and/or actual values!
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
OPERATOR INTERFACE
2.2 CHANGE
VALUE EU
3. LOW VOLTAGE ALARM %
97
ACK. STOP
New value: 97 HORN
The changed settings are stored periodically in the flash memory, earliest when
the menus are exited. If there are changed values which are waiting to be stored
in flash memory, this is indicated by the flashing System On Led. Do not turn off
the power while System On Led is flashing otherwise changed settings can be
lost!
The PMS Operator Panel shows the following system statuses on the front.
2 *
Example menus do not necessary reflect literal menu texts and/or actual values!
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
OPERATOR INTERFACE
The PMS Operator Panel has 12 colored pushbuttons with integrated Led lamps for the
operation and monitoring of the generation set and/or Automatic Bus-Tie.
The button texts of these 12 buttons are printed on a regular transparent overhead sheet and
-after cutting- inserted from right-rear side of panel which has a slot to insert the sheet behind
the plastic front.
START 1st
AUTO CLOSE INC. MENU
RUN STBY
2nd
MANUA STOP OPEN DEC. ALARM
STBY
L
The PMS panels are delivered with the indicated standard text sheets. A text sheet template
(pdf file) can be requested to make and print special button texts, when needed.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
START-UP / INITIAL CONFIGURATION
This chapter describes the usage of the menus and the PMS controller basic settings. These
basic settings could theoretically fulfill the configuration of a basic PMS due to the use of
relative (%) default settings for the functional parameterization. Refer to the next chapters for
the more detailed configuration of functions and options.
Observe basic safety rules before first power-up of the PMS Operator Panel(s) with
commissioning and e.g. service replacement, such as:
- Select Switchboard Local mode to prohibit any undesired controls until the PMS
controller is fully configured!
- Do not connect the Ethernet cables until after the controller number is set in the
boot loader menu (see 4.1) to avoid addressing conflicts and possible loss of
settings.
The first action with the panel first power-up must be the setting of the PMS controller
number. This setting is done in the boot loader menu that is accessed by pressing the ACK
button while connecting the 24Vdc power supply to the
panel. The controller is re-booted when the controller ACK. while Power-up
number is accepted (ACK) and stored in flash memory.
Menu:
1. Controller no.
[1-9] 1 >>
2. Advanced menu [p/w] >>
Select ▲ ▼ Enter ►
New value: 1
ACK. STOP
HORN
Change ▲ ▼ Accept ACK Cancel
STOP
3 *
Example menus do not necessary reflect literal menu texts and/or actual values!
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
START-UP / INITIAL CONFIGURATION
A unique controller number from 1 to 9 must be set for each PMS-controller. This number is
used for the processor Ethernet IP address (192.168.1.[No+60]) and is the MODBUS slave
number on the PMS RS485 MODBUS SLAVE multi-drop link.
The PMS controller number -and PMS application version- can be checked in the menus.
Item Menu / Setting description EU
1.1. MAIN SETTINGS : CONTROLLER ID
read only
1. PMS CONTROLLER NO. [1-9]
read only
2. PMS APPLICATION VERSION
The PMS can be configured for any of the following grid configurations. For the sake of the
PMS configuration a bus is considered to be a Bus when there is connected:
● Generator -or other device as configured in 4.4- controlled by PMS controller, or
● Heavy consumer(s) configured in any PMS controller, or
● Non-preferential group(s) configured in any PMS controller
Type 1: Bus 1
Example:
2x ABT, both
connected
to Bus 3!
Bus 4 Bus 3 Bus 4 Bus 3
See 4.5
Select the applicable type of plant grid. Selecting one option (“yes”) automatically resets the
other options (“no”). Changing the grid selection on one controller synchronizes the grid
settings on the other controllers, when these are connected at this time.
Item Menu / Setting description EU
1.2 MAIN SETTINGS: GRID / BUS CONFIGURATION
1 OF 5
1. TYPE 1 - 1X BUS (1) Y/N
2. TYPE 2 - 2X BUS (1 / 2) Y/N
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
START-UP / INITIAL CONFIGURATION
WRONG *GRID* SETTINGS(503) is alarmed when Ethernet is connected and the grid is not
set the same on all controllers. AUTO-mode can now not be selected.
This setting selects the specific PMS-controller (PMS-set) functionality for the specific
generation types (1~3) as described in chapters 7 and 8 or that of the automatic bus-tie (5) as
described in chapter 9. Selecting one option (“yes”) automatically resets the other options
(“no”).
Item Menu / Setting description EU
1.3 MAIN SETUP: CONTROLLER FUNCTION
1 of 5
1. DIESEL / TURBINE GENERATOR Y/N
2. EMERGENCY GENERATOR Y/N
3. reserved
4. reserved
5. AUTOMATIC BUS-TIE Y/N
4.5 Ratings
All percentage (%) settings in the PMS controller relate to the nominal/rated
(100%) settings as set in this Ratings menu! “Power” and “Load” variables relate
to the ENGINE CAPACITY (kW).
The capacity of each gen-set is configured: how much power it can deliver to what bus.
Item Menu / Setting description EU
1.4 MAIN SETTINGS: RATINGS / BUS
1. CONNECTED TO BUS NO. #
GENERATOR CAPACITY
2. GENERATOR NOMINAL VOLTAGE V
3. GENERATOR ENGINE CAPACITY
kVArNOMINAL FREQUENCY HZ
4. GENERATOR CAPACITY kVA
5. GENERATOR POWER FACTOR -
6. GENERATOR RATED CURRENT kVA A
7. ENGINE CAPACITY kW
φ
Where:
kW
Gen. Nominal Voltage is specified as: V ; 100% of relative voltage
settings
Gen. Nominal Frequency is specified as: Hz ; 100% of relative frequency
settings
Generator capacity is specified as: kVA @ cosφ
4 *
These abbreviations/notations can be used to mark relevant functionality descriptions when specific for an application
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
START-UP / INITIAL CONFIGURATION
The Bus No. is specified in relationship to the configured Plant Grid (see 4.3). If the controller function is that of
an ABT, the Bus number is that of the lowest connected bus.
If two ABT are connected in series, the Bus number -for both- is that of the lowest bus!
See example at grid type 4, par. 4.3
The PMS-controller current measurement is configured with the ratio of the current
transformer (CT). For example, a current transformer with 1000A:1A step-down ratio is
configured with ratio setting of 1000.
For switchboards with rated voltages above 690VAC, external voltage transformers (VT)
must be used for measuring -and limiting- bus/generator voltages. For example, a VT that
reduces 6kV to 230V is configured with the ratio setting 26.1 (6000/230).
The PMS IO-board voltage measurement is optimized for measurement ranges [110~440Vac]
or [590~690Vac]. The IO-board input voltage -for example 230Vac- is set so that the IO-
board can automatically select the corresponding calibrated measurement range (in this
example: calibrated range [110~440Vac] is automatically selected).
Observe that the jumpers on the PMS IO-module are positioned according the
set voltage range (see 12.6)!
The PMS current measurement is optimized for measurements ranges up to [1A] or [5A]. The
IO-board input current -for example 2A- is set so that the IO-board can automatically select
the corresponding calibrated measurement range (in this example: calibrated range [5A] is
automatically selected).
Observe that the jumpers on the PMS IO-module are positioned according the
set current range (see 12.6)!
Each diesel generator with the standby start enabled is part of the standby start sequence and
can be automatically started by a standby start request. See 8.2.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
START-UP / INITIAL CONFIGURATION
The PMS IO-board detects and alarms incorrect connections of the generator and/or bus.
Following alarms are enabled when the diesel engine is running and delayed with a fixed time
of 10 seconds:
GEN PHASE ERROR(271) is alarmed when the generator voltage (connections) L1, L2, L3 are
falsely connected resulting in incorrect phase sequence.
GEN MISSING PHASE(272) is alarmed when the generator voltage (connections) L1 or L2 or
L3 are not connected or failed otherwise.
GEN FREQUENCY FAIL(273) is alarmed when the generator frequency drops below 70% of
nominal frequency.
Following alarms are enabled when a bus voltage (>20%) is measured and delayed with a
fixed time of 10 seconds:
BUS PHASE ERROR(274) is alarmed when the bus voltage (connections) L1, L2, L3 are
falsely connected resulting in incorrect phase sequence.
BUS MISSING PHASE(275) is alarmed when the bus voltage (connections) L1 or L2 or L3 are
not connected or failed otherwise.
BUS FREQUENCY FAIL(276) is alarmed when the bus frequency drops below 70% of
nominal frequency.
The IO-board Led indications VOLTAGE GENERATOR and VOLTAGE BUSBAR show the
above errors by fast flashing of the corresponding Led. Otherwise these Led’s show the
energized (on) -or not energized (off)- generator/bus status.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
ALARM / PROTECTION LIMITS
Each of the alarms in this chapter can be disabled by setting the detection level to 0%!
Each of the alarms in this chapter is alarmed in every mode, including local.
5.1 Bus Abnormal Alarms
Following limits are set on each gen-set for detecting bus abnormal alarm conditions. Any
bus abnormal alarm will start the next standby generator and trip its own circuit breaker when
the standby -or other- generator is ready to be connected to the bus (i.e. connected over
blackout). See also 8.6.
Item Menu / Setting description EU
2.1 ALARM LIMITS: BUS ABNORMAL ALARMS
1. HIGH VOLTAGE ALARM %
2. HIGH VOLTAGE DELAY SEC
3. LOW VOLTAGE ALARM %
4. LOW VOLTAGE DELAY SEC
5. HIGH FREQUENCY ALARM %
6. HIGH FREQUENCY DELAY SEC
7. LOW FREQUENCY DELAY %
8. LOW FREQUENCY ALARM SEC
Following limits are set on each gen-set for detecting bus alarm conditions. If the standby
start with bus alarm option is enabled (see 8.7) any bus alarm will start the next standby
generator and disconnect itself after substitution.
Item Menu / Setting description EU
2.2 ALARM LIMITS: BUS ALARMS
1. HIGH VOLTAGE ALARM %
2. HIGH VOLTAGE DELAY SEC
3. LOW VOLTAGE ALARM %
4. LOW VOLTAGE DELAY SEC
5. HIGH FREQUENCY ALARM %
6. HIGH FREQUENCY DELAY SEC
7. LOW FREQUENCY ALARM %
8. LOW FREQUENCY DELAY SEC
Following limits are set on each gen-set for tripping of the circuit-breaker (CB) to protect the
generation set. The generator protections alarms -including circuit-breaker (CB) trip output-
are active in every mode, including local.
Item Menu / Setting description EU
2.3 ALARM LIMITS: GEN. PROTECTIONS / TRIP CB
1. OVER-CURRENT TRIP CB %
2. OVER-CURRENT TRIP DELAY SEC
3. REVERSE POWER TRIP CB (- ) %
4. REVERSE POWER DELAY SEC
5. OVER-VOLTAGE TRIP CB %
6. OVER-VOLTAGE TRIP DELAY SEC
7. UNDER-VOLTAGE TRIP CB %
8. UNDER-VOLTAGE TRIP DELAY SEC
9. OVER-FREQUENCY TRIP CB %
10. OVER-FREQUENCY TRIP DELAY SEC
11. UNDER-FREQUENCY TRIP CB %
12. UNDER-FREQUENCY TRIP DELAY SEC
OVER-VOLTAGE TRIP(221),
UNDER-VOLTAGE TRIP(222),
OVER-FREQUENCY TRIP(223),
UNDER-FREQUENCY TRIP(224),
OVER-CURRENT TRIP(225),
REVERSE POWER TRIP(226) are alarmed -and the circuit-breaker is tripped- when the
relevant above limits and delays are exceeded.
Following limits are set on each gen-set for detecting generator alarm conditions.
Item Menu / Setting description EU
2.4 ALARM LIMITS: GEN. ALARMS
1. OVER-LOAD ALARM %
2. OVER-LOAD ALARM DELAY SEC
GEN. OVER-LOAD (ALARM)(231) is alarmed when the relevant limits and delays are
exceeded.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
CONFIGURABLE I/O SIGNALS
Each PMS IO-module has 14 digital contact inputs (channels 1…14) and 14 digital relay
outputs (channels 15…28).
8 digital contact inputs (channels 1…8) and 8 digital relay outputs (channels 15…22) can be
free configured to suit application and customer requirements. The front texts of these 16
channel windows can be printed on a regular (white) paper sheet and inserted -from the
module top- behind the transparent plastic front. Relevant configuration menus will appear
when belonging I/O-signals are configured.
The other 6 digital contact inputs (channels 9…14) and 6 digital relay outputs (channels 23…
28) have fixed functionality and fixed printed text windows.
For each configurable input channel (1…8) there can be set a single code for selecting its
input condition/function. Below list shows the supported input codes.
1 Engine safety shutdown N.O. Closed by engine protection device when shut down 7.4
2 Engine pre-alarm N.O. Closed by pre-alarm; start next standby generator 7.5
3 Engine load shift N.O. Closed by operator, start next standby DG, stop this DG
11 CB close request N.O. Close to synchronize & close CB (alike front command) 7.6
12 CB open request N.O. Close to offload & open CB (alike front command) 7.8
13 CB tripped by ACB device N.O. Closed by ACB when abnormal tripped 7.9
14 CB trip command N.O. Close to trip CB
15 CB trip manual cmnd N.O. Close to trip CB when in MANUAL
16 CB trip all command N.O. Close to trip all CB on own -and connected- busses
17 CB trip all auto cmnd N.O. Close to trip all CB -in AUTO- on own/connected bus
18 CB tripped by short-circuit device N.O. Closed by short-circuit device when tripped
19 Sync-check device failed N.C. Opened by Sync-check device for report alarm
31 PTI operation N.O. Close for PTI function; open for PTO function (shaft)
32 Harbour mode N.O. Close for Harbour mode (emergency generator) 7.11
33 Inhibit low load stop N.O. Close to prevent any low load auto stop 8.5
35 Trip non-preferential groups N.O. Close to trip all non-preferential groups on board
36 Trip non-preferential groups N.O. Close to trip all non-preferential groups on board; start
next standby DG
41** Consumer block Request 1 N.O. Close to request heavy consumer block 1 8.8
42** Consumer block Request 2 N.O. Close to request heavy consumer block 2
43** Consumer block Request 3 N.O. Close to request heavy consumer block 3
44** Consumer block Request 4 N.O. Close to request heavy consumer block 4
45** Consumer block Request 5 N.O. Close to request heavy consumer block 5
46** Consumer block Request 1 N.O. Close to request heavy consumer block 1 8.9
47** Consumer block Request 2 N.O. Close to request heavy consumer block 2
48** Consumer block Request 3 N.O. Close to request heavy consumer block 3
49** Consumer block Request 4 N.O. Close to request heavy consumer block 4
50** Consumer block Request 5 N.O. Close to request heavy consumer block 5
91** Stop buzzer N.O. Close to silence the buzzers on all panels
Note that it is possible to use the same code for multiple channels! For example, if code #16 is
used to configure channels 7 and 8 then the “CB trip all” command is activated when input 7
is closed OR when input 8 is closed.
Item Menu / Setting description EU
3.1 CONFIGURABLE IO: INPUT CHANNELS
* *
Heavy consumer blocks can not be configured on controllers used for ABT
* *
Heavy consumer blocks can not be configured on controllers used for ABT
* *
Heavy consumer blocks can not be configured on controllers used for ABT
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
CONFIGURABLE I/O SIGNALS
For each configurable output channel (15…22) there can be selected a single code for its
activation condition/function. Below list shows the supported output codes.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
CONFIGURABLE I/O SIGNALS
FUNCTION OUTPUTS
301** CONSUMER BLOCK ACCEPT 1 Activated to allow consumer 1 8.8
302** CONSUMER BLOCK ACCEPT 2 Activated to allow consumer 2
303** CONSUMER BLOCK ACCEPT 3 Activated to allow consumer 3
304** CONSUMER BLOCK ACCEPT 4 Activated to allow consumer 4
311** NON-PREFERENTIAL TRIP 1 (OUTP) Activated to trip group 1 8.9
312** NON-PREFERENTIAL TRIP 2 (OUTP) Activated to trip group 2
313** NON-PREFERENTIAL TRIP 3 (OUTP) Activated to trip group 3
314** NON-PREFERENTIAL TRIP 4 (OUTP) Activated to trip group 4
321 RAISE VOLTAGE Activate/pulse to raise voltage (AVR) 8.1
322 LOWER VOLTAGE Activate/pulse to lower voltage (AVR)
331 PRE-LUBRICATION Activate to pre-lubricate the engine 7.10
333 CB STATUS Activated when CB closed
If channel 22 is used as SYNC-CHECK RELAY (see 7.7) the setting 3.2.8. will not be
functional.
* *
Heavy consumer blocks and Non-preferential groups can not be configured on controllers used for ABT
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
CONFIGURABLE I/O SIGNALS
The PMS IO-module front texts of the 16 configurable channel windows can be printed on a
regular (white) paper sheet and inserted -from the module top- behind the transparent plastic
front.
Example
5cm 10cm
CONSUMER CONSUMER
BLOCK BLOCK
REQUEST 1 PERMISSION 1
CONSUMER CONSUMER
BLOCK BLOCK
5cm REQUEST 2 PERMISSION 2
CONSUMER CONSUMER
BLOCK BLOCK
REQUEST 3 PERMISSION 3
BUS-TIE #A NON-
CLOSED PREFERENTIAL
TRIP 1
BUS-TIE #B NON-
CLOSED PREFERENTIAL
TRIP 2
ENGINE NON-
PRE-ALARM PREFERENTIAL
TRIP 3
ENGINE -
SAFETY -
10cm SHUTDOWN
CB -
TRIPPED -
A text sheet template (pdf file) can be requested to make and print special channel texts, when
needed.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
GENERATOR OPERATION
7 GENERATOR OPERATION
LOC REM
ENGINE SELECTOR SWITCH = REMOTE *2 ENGINE SELECTOR SWITCH = REMOTE
MANUAL AUTO
*1
LOCAL, or
*2
Lamp ON when PUSH to select Lamp ON when
REMOTE + PUSH; MANU AUTO
MANUAL mode AL AUTO AUTO mode
to select MANUAL
START
Start extra engine; will
Flash while pre-lub and/or Flash while pre-lub and/or
RUN Start engine auto-stop after cool-
starting, On when running starting, On when running
down if CB not closed *4
*3
Load sharing
*4
Load dependent start/stop
*5
Blackout prevention / offload check
Pushbuttons START/STOP, INC/DEC, 1st STBY/2nd STBY and Engine Selector Switch have no function when PMS-set used for Shaft
Generator or Shore Connection or ABT
The PMS-set is switched off from the front of the SWBD section with an on/off-switch
connected to the PMS-module. When the on/off-switch is set in OFF (LOCAL) all PMS-set
outputs are de-activated and in neutral condition.
When the on/off-switch is set in ON the PMS is default set in MANUAL mode and next -if
allowed- AUTO mode can be selected.
Relevant PMS I/O-module signals (this signal is relevant to all PMS functions):
I/O Channel text Condition/signal Signal description for indicated condition Configurabl
e
DIN SWBD/PMS select Open potential free PMS-set = OFF No FIXED
Closed potential free PMS-set = ON (Manual or Auto)
MANUAL
MANU or AUTO mode can be selected by the corresponding pushbuttons on the PMS
AL
Operator Panel. In case of a diesel generator [D/G] or [E/G] the AUTO mode can only be selected
when
AUTO
the (engine) remote control is selected.
Relevant PMS I/O-module signals (this signal is relevant to all AUTO functions):
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
GENERATOR OPERATION
I/O Channel text Condition/signal Signal description for indicated condition Configurabl
e
DIN Engine Remote Ctrl Closed potential free Remote Control on No FIXED
The engine *5 [D/G] or [E/G] can be started with a manual or automatic start engine command.
The manual start engine command is given with the PMS Operator Panel
START pushbutton when in AUTO or MANUAL mode or -optional- from PMS mimic. The
RUN
pushbutton lamp is flashing while starting/energizing; on when energized.
The start command is accepted -and the pre-lubrication output activated- when the engine is
ready to start and set in remote control and there is no external safety shutdown or pre-alarm.
The start output is activated when the pre-lubricating finished. The start output is de-activated
-and the start is successful- when the engine achieves the running status. The start attempt
failed when the engine does not achieve the running status within the re-start delay that is
started at the end of the start pulse. In AUTO the start output will then be activated again and
this will be repeated until the number of start attempts is completed or until the engine
achieves the running status. In MANUAL there will only be performed one start attempt.
Described functionality and settings allow the PMS-set to directly operate an engine start
solenoid valve. If the engine is equipped with its own local control system the number of start
attempts must be set to “1”.
Item Menu / Setting description EU
4.1 START/STOP: ENGINE START
1. MAXIMUM START PULSE SEC
2. NUMBER OF START ATTEMPTS #
3. RE-START DELAY SEC
4. PRE-LUBRICATING TIME SEC
ENGINE NOT READY TO START (205) is alarmed if the ready to start input is not activated.
ENGINE START FAILURE(201) is alarmed if the engine does not achieve the running status
within the applicable number of start attempts or sooner when the start fail input is activated.
The gen-set can be used again after this alarm has been reset.
5 *
engine: also referred to as ‘prime mover’
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
GENERATOR OPERATION
ENERGIZE FAILURE(211) is alarmed if -after the engine achieved running status- the
generator voltage does not reach the voltage level within the energized delay. In this case also
the engine stop is activated. The gen-set can be used again after this alarm has been reset.
The engine [D/G] or [E/G] can be stopped with a manual or automatic stop engine command.
STOP
The manual stop engine command is given with the PMS Operator Panel pushbutton
when in AUTO or MANUAL mode or -optional- from PMS mimic.
The pushbutton lamp is flashing while stopping (e.g. during cool down); on when
engine is stopped.
Causes -except external- that can give an automatic stop engine command:
Generator energizing failure alarm
Engine idle run time (cool down) finished
The stop command is accepted -and the stop output activated- when the engine is set in
remote control and when the generator circuit-breaker is open. A stop command during
normal operation can either be an operator command e.g. from the stop pushbutton or -in
AUTO- an automatic stop command after engine cooling down. The stop output is activated
for the duration of the stop pulse time.
Item Menu / Setting description EU
4.2 START/STOP: ENGINE START / STOP
1. STOP PULSE TIME SEC
2. ENGINE COOLDOWN TIME SEC
3. COOLDOWN WITH PRE-ALARM Y/N
ENGINE STOP FAILURE(202) is alarmed if the engine still has the running status after the
stop pulse is de-activated. The gen-set can be used again after this alarm has been reset.
ENGINE EXT. SHUTDOWN(203) is alarmed when the engine safety shutdown input is
activated from the engine local safety system. This engine can not be started again until this
signal returns to normal and the alarm is reset.
I/O Channel text Condition/signal Signal description for indicated condition Configurabl
e
DIN CB status Open potential free CB is opened No FIXED
DIN Engine running Closed potential free Engine running No FIXED
DIN Engine safety shutdown Closed potential free Engine shutdown by safety Yes (1)
DIN Engine pre-alarm Open potential free Not pre-alarm condition Yes (2)
DOUT Engine stop Closed potential free Stop signal to engine No FIXED
The manual close breaker command is given with the PMS Operator Panel
CLOSE
pushbutton when in AUTO or MANUAL mode or -optional- from PMS mimic or
external CB close request input signal.
The lamp is flashing while synchronizing; on when the circuit-breaker is closed.
The close command (pushbutton or automatic) is accepted when the gen-set is running and
energized. If the bus is dead, the circuit-breaker will be directly closed. If the bus is energized,
this gen-set [D/G] or [E/G] will first be synchronized with the energized bus before closing the
circuit-breaker.
Each PMS-set has a dedicated SYNCHRONIZER that is integrated on the PMS I/O module.
The synchronizer controls the frequency of the gen-set to the frequency of the energized bus
before allowing the circuit-breaker to be closed when the bus/generator phase angle and the
voltage/frequency deviation is within the specified dead band. The synchronizer controls the
gen-set with raise/lower speed signals.
The synchronizer can be put in a test mode that allows visual verification of the synchronizer
conditions on the board LEDs without actually closing the circuit-circuit breaker (see 13.15).
Item Menu / Setting description EU
5.1 CB OPEN/CLOSE: SYNCHRONIZER / CB CLOSE
1. ∆ VOLTAGE %
2. ∆ FREQUENCY NEGATIVE %
3. ∆ FREQUENCY POSITIVE %
4. ∆ PHASE ANGLE NEGATIVE degree
5. ∆ PHASE ANGLE POSITIVE degree
6. MIN. PULSE TIME SEC
7. MAXIMUM SYNC TIME SEC
8. I/O-BOARD SYNC. TEST MODE 0~2
SYNCHRONIZE FAILURE (213) is alarmed when the gen-set is not synchronized within the
maximum sync time (and the circuit-breaker can not be closed). The gen-set will be idle
running and the close command can be attempted again after this alarm is reset.
CB CLOSE FAILURE (214) is alarmed when the circuit-breaker fails to close after the close
command has been given. The gen-set will be idle running and the close command can be
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
GENERATOR OPERATION
attempted again after this alarm is reset. Note that this failure will also be alarmed if the
backup sync-check relay is applied (see 7.7) and this prevents activation of the circuit-breaker
while the synchronizer allows closure!
If required by class society (see 2.4) an additional SYNC-CHECK RELAY is to be applied that
continuously monitors if the bus/generator phase angle and frequency variation are within a
second set of synchronizing settings *6 and that closes the output contact if these conditions are
fulfilled. This contact is to be connected in series with the synchronizer contact CB close
(channel 23) and therewith adds the backup sync-check protection of the circuit-breaker (see
12.7). The sync-check relay can only be configured on relay output channel 22!
Item Menu / Setting description EU
5.4 CB OPEN/CLOSE: SYNC-CHECK BACKUP RELAY
1. CH.22 USE AS SYNC-CHECK BACKUP Y/N
2. CH.22 ∆ PHASE ANGLE degree
3. CH.22 ∆ FREQUENCY Hz
The manual open breaker command is given with the PMS Operator Panel
OPEN
pushbutton when in AUTO or MANUAL mode or -optional- from PMS mimic or
external CB open request input signal. In AUTO the open breaker command is
blocked if disconnection would cause a blackout. The lamp is flashing while
offloading (AUTO only); on when the circuit-breaker is opened.
Causes that can give an automatic open breaker command:
Generator is being offloaded (see 8.5)
Generator protections (see 5.3)
External trip signals
Offload failure (optional)
6
Note that the Sync-check settings are to be set "less sensitive" then the synchronizer settings!
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
GENERATOR OPERATION
In MANUAL mode the command will open the circuit-breaker regardless of the generator or
bus load therewith potentially causing a plant blackout when not operated with care. In
AUTO mode the generator is disconnected in controlled manner i.e. the circuit-breaker will
only be opened after first the generator is offloaded below the low load limit.
Item Menu / Setting description EU
5.2 CB OPEN/CLOSE: OFFLOAD / CB OPEN
1. CB OPEN PULSE TIME SEC
2. LOW LOAD LIMIT TO OPEN CB %
3. MAX. OFFLOAD (PARALLEL) TIME SEC
OFFLOAD FAILURE(212) is alarmed when the gen-set is not offloaded within the maximum
offload time. Depending of the chosen disconnect option, the circuit-breaker will be opened
anyway or will remain closed for the operator to take the appropriate actions. This alarm must
first be reset before this gen-set can be started or loaded again.
CB OPEN FAILURE(215) is alarmed when the breaker is not actually opened after the open
command. In AUTO mode the gen-set is now controlled back to the average plant load to
avoid a reverse power situation. This alarm must first be reset before this gen-set can be
offloaded again (and open the circuit-breaker again).
The circuit-breaker can be tripped -i.e. opened without offloading- by the generator
protections (see 5.3) and by the following optional CB trip command input channels (only
active when the relevant input channel has been configured):
The circuit-breaker can also be tripped by external devices outside the PMS such as automatic
circuit breaker (ACB) or short-circuit protection device (S/C).
ACB ABNORMAL TRIPPED(227) is alarmed when CB was tripped by external ACB device
or when CB was opened by unknown cause.
CB TRIP EXT. COMMAND(228) is alarmed when any of the command inputs (14~17)
is
activated and meets the relevant conditions.
Any CB trip(ped) command results in the automatic tripping of all non-preferential groups
and -if option enabled (see 8.7)- results in the start of the next standby generator.
The gen-set [D/G] or [E/G] frequency is adjusted with the PMS operator panel INC/DEC
pushbuttons.
The increase/decrease frequency command is given with the PMS Operator Panel
INC. pushbuttons when in MANUAL mode, or automatically in AUTO mode.
The lamps are on while the corresponding button is pushed or while the
DEC.
corresponding engine increase/decrease speed signals are automatically operated.
In MANUAL mode the pushbuttons will increase/decrease the gen-set speed and therewith
correspondingly increase/decrease the frequency and consequently increase/decrease the
(active) load.
In AUTO mode the pushbuttons can be used to adjust taking or shedding extra load on this
gen-set from the otherwise balanced shared load (see 8.1).
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
GENERATOR OPERATION
The emergency generator can be switched to harbour mode with an external key-switch. The
harbour mode is a semi-automatic mode. In this semi-automatic mode the generator must be
started/stopped/connected/disconnected by manual command while performing automatic
frequency and load control. The harbour mode allows the emergency generator to be
manually started and connected to fulfill the relative low load conditions when docked and
achieve higher fuel economy. The emergency generator harbour mode is indicated by the
slow flashing MANUAL indication.
7.12 Bus-Ties
Each PMS-set has the possibility for connecting the feedback closed status of the 2 adjacent
bus-ties. Only the bus-ties to adjacent buses can be configured, where input for BUS-TIE #A
connects to the lower/left adjacent bus and input for BUS-TIE #B connects to the higher/right
adjacent bus.
For example with type 5 grid configuration (see picture below); a PMS-set that e.g. belongs to
bus 1 can configure the feedback of the bus-tie connecting to bus 5 (designated: #A) and/or
the bus-tie connecting to bus 2 (designated: #B).
#A #B
Bus 5 Bus 4
#B #A
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
GENERATOR OPERATION
BUS-TIE #A TRIPPED(261) is alarmed when the bus-tie is being opened while generators are
still connected to the gen-set bus (in above example: while generators are still connected to
bus 1).
8 PLANT OPERATION
Plant automatic functions described in this chapter are only applicable for the PMS-sets that
are set in AUTO mode and which do not have unaccepted alarms blocking automatic
functions.
In AUTO mode the PMS-sets perform balanced load sharing by default. In this mode all
interconnected*7 gen-sets will be equally loaded as percentage of their capacity. Each PMS-set
load setpoint is calculated as the average load of all gen-set that are connected to the grid and
that are set in AUTO. Standard the PMS-set performs speed (frequency) control of the gen-
set [D/G] or [E/G] to perform active load sharing (i.e. percentage of capacity in kW).
Item Menu / Setting description EU
6.1 LOAD SHARING: CONTROLLER - SPEED
1. FREQUENCY - PROP. BAND *8 %
2. FREQUENCY - DEAD BAND %
3. ACTIVE LOAD - PROP. BAND *2 %
4. ACTIVE LOAD - DEAD BAND %
5. MIN. PULSE TIME SEC
6. MAX. PULSE TIME/CYCLE TIME SEC
LOAD TOO HIGH DEVIATION (216) is alarmed -only in balanced load sharing mode- when
the load deviates more then (+/-) the maximum load deviation for longer then the delay time.
In AUTO mode the operator can set/adjust a base load setpoint on a specific gen-set by using
the INC/DEC pushbuttons. This results in unbalanced load sharing mode until the base load
setpoint is reset. The base load setpoint -when set- is shown on the main operation display.
The base load is automatically reset when the bus load drops below the reset unbalanced
mode load level or after the preset time or when the gen-set is disconnected, stopped or put in
MANUAL. The operator can manually reset the unbalanced load setpoint by pushing the
INC+DEC pushbuttons simultaneous. Gen-sets will not be automatically stopped by low load
condition (see 8.5) during unbalanced load sharing mode.
Item Menu / Setting description EU
6.3 LOAD SHARING: UNBALANCED MODE
1. ENABLE UNBALANCED MODE Y/N
2 LOW BUS LOAD TO RESET %
3 TIME TO RESET MIN
INC.
INC
to set/increase the base load setpoint
DEC.
DEC
to set/decrease the base load setpoint
Each gen-set -with the standby start enabled (see 4.7)- is part of the standby start sequence
which means that the gen-set can be automatically started by a standby start request.
Each gen-set is assigned a sequence number that represents the order in which the gen-sets are
automatically connected by standby start requests. In a split bus operation the standby start
sequence is determined for each bus section.
1st. The gen-set that is ready to connect*9 with the lowest sequence number on the bus or
STBY on the split bus section will be first connected and is indicated with the 1ST STBY
pushbutton lamp on the operator panel.
2nd.
STBY Next gen-set that will be connected is indicated with the 2ND STBY pushbutton lamp.
The start sequence of each gen-set can be set by operating the 1ST STBY or 2ND STBY
pushbuttons. The gen-set where the 1ST STBY pushbutton is pressed becomes the next (first: if
no gen-sets are running) in the standby sequence. It does so by exchanging his sequence
number with the gen-set that otherwise would have been started next. The same functionality
-for altering the second gen-set in the start sequence- applies when operating the 2ND STBY
pushbutton. In split bus operation these buttons only affect the start sequence of the own bus
section. The start sequence can not be changed while any generator is starting/synchronizing
on the own bus.
The stop sequence is the reversed start sequence: the connected gen-set with the highest
sequence number will be first offloaded and disconnected when allowed by the low load
demand. The stop sequence of the connected gen-sets can be changed by pressing the button
1ST STBY which -in this connected case- makes this the first-to-stop. Note that this also alters
the start sequence of the other connected gen-sets.
9
* Ready to connect: gen-set healthy/without alarms and set in AUTO (and not yet connected)
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PLANT OPERATION
DG1 DG2 DG3 DG4 DG5 DG6 DG1 DG2 DG3 DG4 DG5 DG6
auto auto auto auto auto auto auto auto auto man auto auto
1 2 3 4 5 6 4 3 2 1 5 6
1st
2nd 1st 1st 1st 1st
4 2 3 1 5 6 4 3 2 1 6 5
2nd
1st 2nd
4 3 2 1 5 6 3 4 2 1 5 6
When the bus section of the 1ST standby gen-set has a blackout, this generator will be started
and connected. A blackout recovery delay can be set e.g. to start the emergency generator
with little delay therewith first allowing recovery via the main gen-sets and prevent isolation
of the emergency bus.
Item Menu / Setting description EU
7.1 AUTO START/STOP: BLACKOUT START
1. BLACKOUT RECOVERY DELAY SEC
BLACKOUT (291) is alarmed at blackout condition after the blackout recovery delay.
When the load of any connected gen-set exceeds the set limits -during the preset time- it will
request for a standby generator. This causes the first standby gen-set to be started and
connected. The delay timers are restarted when a new generator is connected.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PLANT OPERATION
A blackout prevention check is calculated for every generator to determine if its power is still
required to satisfy the actual bus load. When a generator has the lowest priority (highest
standby number) and if the blackout prevention check is okay for a sustained period this
generator will be offloaded and disconnected (and stopped).
max. 1400kW
G1 G2 G3
800kW 600kW 300kW
75%
600 450 225
When a bus abnormal condition is alarmed (see 5.1), the next standby gen-set will be started
and when it is ready to be connected to the bus, the gen-set(s) with bus abnormal alarm will
be tripped and the standby generator will be directly connected over blackout. The engine of
the abnormal gen-set will be stopped directly or after cooling down, depending the specific
cooldown setting (see 7.5).
The following conditions can optionally start the next standby generator:
These conditions are enabled/ disabled with the indicated settings. The pre-alarm option is
enabled/disabled by the configuration of the relevant hardware input channel. After the next
standby generator is started and connected due to an engine pre-alarm or a bus alarm, the
substituted generator can be left running or offloaded and disconnected, depending the set
disconnect options (see 7.8).
Item Menu / Setting description EU
7.4 AUTO START/STOP: OPTIONS
1. WITH CB TRIP Y/N
2. WITH NON-PREF. LOAD TRIP Y/N
3. WITH BUS ALARM Y/N
ENGINE PRE-ALARM (204) is alarmed to attend the operator of the eminent engine failure. If
the gen-set was disconnected by the pre-alarm (see 7.8), this alarm must first be reset
-possible when the input is deactivated- before this gen-set can be started or connected again.
When there is not sufficient load available or generators running and preconfigured heavy
consumers are planned to be switched on the bus, the next standby gen-set(s) will be started
and connected before the specific heavy consumer is allowed to be connected to the bus.
The consumer activates the request input after which the spinning reserve and the number of
connected generators are checked against the configured requirements of the consumer. When
more generation is required, next standby generator(s) are started. The consumer block accept
output is activated when the requirements of the consumer block are fulfilled and the request
input is still active and after a set delay. The requests are processed in sequence from lowest
number to highest number if more then one heavy consumer is requested at the same time.
The accept output is reset when the number of connected gen-sets becomes too low or when
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PLANT OPERATION
the request input is deactivated. The low load auto stop function is disabled while there is a
heavy consumer request active.
Each PMS-set -except when used as ABT- has the possibility for configuring up to 4 heavy
consumers on any bus (see 4.3) with each their power requirements and requirement for
number of connected generators. The consumer blocks furthermore require that the
appropriate request input signals (see 6.2) and accept output signals (see 6.3) are configured.
Item Menu / Setting description EU
8.0 HEAVY CONSUMERS: COMMON
1. CONNECTED TO BUS #
2. CONSUMER ACCEPT DELAY SEC
3. REQUIRED GENERATORS #
When the bus is close to overloading, groups of non-preferential consumers can be tripped to
prevent an actual bus overload.
The high load limit and delay can be configured at which condition each non-preferential
group will be tripped. This allows groups to be tripped in predefined order. The non-
preferential group(s) will be tripped without any delay when there is a circuit-breaker tripped
on the corresponding bus. The non-preferential group(s) on the board will be tripped without
any delay when the programmable group trip input is activated. The trip output remains active
as long as the trip condition remains active with a minimum time of 5 seconds.
Each PMS-set -except when used as ABT- has the possibility for configuring up to 4 non-
preferential groups on any bus (see 4.3) with each their high load trip condition and delay.
The non-preferential groups furthermore require that the appropriate trip output signals (see
6.3) are configured. As a response to any non-preferential trip the next standby generator can
be started, if this option is enabled (see 8.7).
Item Menu / Setting description EU
9.0 NON-PREF. GROUPS: COMMON
1. CONNECTED TO BUS #
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PLANT OPERATION
NON-PREFERENTIAL TRIP x (281~284) is alarmed -on the PMS-set where configured- when
a non-preferential group 1~4 is tripped.
9 AUTOMATIC BUS-TIE
The PMS Controller can also be used as controller for an Automatic Bus-Tie (ABT) circuit-
breaker.
The ABT can synchronize and connect 2 live buses/switchboards when the
MANU controller is enabled by the PMS select signal. This is indicated by the MANUAL
AL
indication lamp.
The close ABT circuit breaker command is issued with the PMS Operator Panel
CLOSE
pushbutton or -optionally- from a PMS mimic or external CB close request
input signal. This command initiates that first both live buses are automatically
synchronized before the circuit-breaker is closed by the controller. The
lamp is flashing while synchronizing; on when the circuit-breaker is closed.
The open ABT circuit breaker command is issued with the PMS Operator Panel
OPEN pushbutton or -optional- from PMS mimic or external CB open request input signal.
This command opens the ABT unconditionally. The lamp is on when the circuit-
breaker is opened.
10 ALARMS
A RS485 multi-drop serial port is provided on each PMS Operator Panel that outputs the
alarms of each gen-set via a MODBUS-slave protocol (see 11).
Hard-wired common system alarms are required by most classification societies. These
signals are realized by connecting the Fail and Horn contact outputs of each PMS panel (see
12.5).
I/O Description Condition/signal Signal description for indicated condition
All FAIL PMS Power/System fail Closed potential free All PMS-CONTROLLERS:
contacts NO Power and/or System Fail
In series alarm
All HORN External Horn (new alarm) Opened potential free All GEN-SETS:
contacts NO horn (/new alarm)
In parallel
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
MODBUS SLAVE INTERFACE
A RS485 multi-drop serial port is provided on each PMS Operator Panel that outputs the
alarms and monitoring values of each gen-set via a MODBUS slave protocol and accepts
basic PMS commands.
The RS485 ports of all PMS Operator panels are connected parallel (see 12.5) as a RS485
multi-drop link to a host computer that operates as the MODBUS MASTER. The PMS
controllers are accessible by their MODBUS slave number (see 4.2). The host computer must
provide a galvanic isolation of its RS485 serial input port.
The Mega-Guard PMS system uses the Cyclic Redundancy Check (CRC) as the error check
for each message.
Detailed explanation of the MODBUS protocol can be found in the Gould Modicon Modbus
Protocol Reference Guide, Nov.'83, Gould Inc., Andover. Praxis Automation Technology can
supply you with a copy of the relevant pages.
● Function 03/04
Analog channels described in this chapter can be requested by MODBUS function
‘03’ or '04' (READ HOLDING/INPUT REGISTERS) to obtain the value of the analog
channel.
● Function 05
Specific Digital input channels (commands) described in this chapter can be forced
on/off by MODBUS function '05'.
Structures are sent according Motorola (MSB LSB or Big Endian) processor set.
The MSB and LSB are (two's complement) signed integers (PMS maximum range = -9999 till
9999).
Examples:
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
MODBUS SLAVE INTERFACE
The maximum allowed amount of data request by means of function”3”,”4” is 125 analog
values (2 bytes data).
Each PMS controller is addressed with its slave number (see 4.2).
The controller alarms and relevant statuses are requested with function 03 and send as
packed digital data. The digital data is packed in 5 words as described in 11.3.
The controller analog values are requested with function 04*1. The values are multiplied by a
scale factor for a better resolution since decimal points are not available in the used integer
range. To get the original decimal formatting the Modbus-master must scale the received data
with the scaling factor as is given in the Modbus list.
The alarms and other digital data are packed as indicated in below tables. The address and
function to request the specific packed words are indicated in the Modbus address list (see
11.2).
The PMS controller makes no difference between function requests 03 or 04.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
MODBUS SLAVE INTERFACE
X Running
X Energized
X CB closed
X 1st standby
X 2nd standby
X 1st to stop
X spare
It is possible to give basic PMS operator commands to each (slave) PMS controller through
the Modbus interface with function 05 and slave number (see 4.2).
According to the MODBUS protocol the requested ON/OFF state is specified by a constant in
the query data field: a value of FF 00 hex forces the ‘coil’ (i.e. command) to be ON; a value
of 00 00 forces the ‘coil’ to be OFF. All other values are illegal and will not affect the ‘coil’!
The commands must be pulsed -minimal for duration of 1 Modbus request- and are processed
with the same functions and conditions as the front pushbuttons.
Standard MODBUS error messages (exception responses) are returned on any illegal request.
Note: MODBUS points within the PMS range which refer to undefined -or spare- addresses
are still valid addresses and will return an undefined value.
The MODBUS query is processed at the end of each I/O scan cycle. The worst case delay is
one cycle time plus overhead of in total 95 milliseconds. The typical delay is half the cycle
time (ca. 50 milliseconds).
The RS485 ports of all PMS Operator panels are connected in multi-drop configuration (see
12.5) to a host computer that operates as the Modbus-master. The host computer must provide
a galvanic isolation of its RS485 serial input port.
Specification
Interface port RS485
Connection A, B screw terminals
Cable 2-wire twisted communication cable
Port settings Baudrate 19200, 8 bits, 1 start bit, 1 stop bit, No parity
Protocol MODBUS RTU Slave
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PMS HARDWARE
12 PMS HARDWARE
Properties:
General
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PMS HARDWARE
Operating Environment
Ambient temperature 0 to +70 degrees Celsius
Test specification EN60945
Display
Display LCD monochrome graphic display
Resolution 192 x 64 pixels;
6 lines (approx. 35 characters) in text mode
Application pushbuttons
Number of application buttons incl. lamp 12
Pushbutton/lamp available colors Red, green, yellow, blue, white
Text window each button 14x14 mm
Dimming Yes where applicable
Text background illumination Yes
Button/lamp configuration of texts Printed on transparent “overhead” sheet,
cut in 2 strips -for top/bottom row- of
15x130mm, inserted from the panel side
I/O-module interface
Connector 9-pole Sub-D, female
Cable Special, including DC supply of I/O-module
Relay outputs
Relay 1 - Horn - Open contact (horn = off / Power off)
- Closed contact (horn = on)
Relay 2 - System Fail - Open contact (system fail / Power fail)
- Closed contact (system healthy)
Relay 1 & 2 contact rating 30VDC, 2A
250V, 500mA
Ethernet cable
Cable type SFTP shielded cable 24AWG / 4 pairs
Wiring standard TIA / EIA T568A
Connectors RJ45
Cable part number / length 76.0.900, 0.5m
76.0.901, 2m
76.0.902, 5m
76.0.903, 10m
RS485
Compliance EIA RS-485, half-duplex
Usage MODBUS multi-drop slave
Serial port
Compliance Special (RS232 / TTL levels)
Usage Maintenance
USB
Number of USB ports 1
USB compliance 2.0
Function - USB-stick for firmware update
- USB-stick for loading and saving panel
configurations.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PMS HARDWARE
Properties:
General
Part number 98.6.034.802
Model size H=200, W=127, D=34mm
Mounting TS35 DIN-rail
Locking Special included end-bracket
Power supply via special 9-pole Sub-D
Weight 950 grams
Operating Environment
Ambient temperature 0 to +70 degrees Celsius
Test specification EN60945
Digital inputs
Number of digital inputs Total 14:
- 6 x fixed functionality
- 8 x configurable functionality
Input signal type Potential free contact (N.O. or N.C.)
Open voltage: 5VDC,
contact current: 10mA
Terminals (28) Detachable screw terminals
for wires up to Ø 2.5mm2,
B-terminals are common for all inputs
Relay outputs
Number of relay outputs Total 14:
- 6 x fixed functionality
- 8 x configurable functionality
Output signal type Potential free contact (N.O. or N.C.)
Contact ratings 30VDC, 2A
250VAC, 500mA
Terminals (28) Detachable screw terminals
for wires up to Ø 2.5mm2
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
PMS HARDWARE
13 FLOWCHARTS
13.1 Legend
TERMINATOR:
DATA (IO):
X Begin point & name of pre-defined X
DIN channel, pre-defined (fixed)
DIN
process
DIN
DISPLAY:
DOUT
DATA (IO):
X (YYY) Alarm shown on display (also result X
DOUT channel, pre-defined (fixed)
of pre-defined process
DOUT
DISPLAY: DATA (IO):
X X (YYY)
Variable / status shown on display DOUT channel, configurable
DATA (IO):
MANUAL ACTION:
X X inputs and outputs (variables)
Operation of pushbutton (or switch)
between process
DECISION:
PROCESS:
X X A branch in the process depending
An operation or action step
parameter setting
DELAY or PULSE:
Off-page reference X
A fixed waiting/pulse period
DELAY or PULSE:
BRANCH:
X A waiting/pulse period depending
Unconditional branch in process
parameter setting
OR:
Logical OR (joining of branches)
OR:
Logical OR NOTE:
(ZZ) = reference of input channel (see 6.2)
(YYY) = reference of output channel (see 6.3)
AND: Px.x.x = reference of parameter/setting (see 14)
Logical AND
NEGATION:
Logical NOT
CALLOUT:
COMMENT
Add comments
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
BUSBAR
G G G
M M M
AUTOMATIC
GENERATOR GENERATOR GENERATOR
BUS-TIE
GENERATOR
D/Gor E/G
ALARMLIMITS
END
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
SWBDSWITCH:
LOCAL/ AUTO
DIN
NO
INPUT = CLOSED
YES
ENGINE SWITCH:
LOCAL/ REMOTE
ENGINE REMOTE
CTRL
DIN
NO
INPUT = CLOSED
YES
PUSHBUTTON: PUSHBUTTON:
MANUAL AUTO
MANUAL AUTO
REMOTE LOCAL
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
13.4 CB Trip
CB TRIP
DIN
DIN
CB TRIPPED TRIP CB TRIP CB TRIP CB
DIN
DIN
TO/ FROM
CB TRIPPED TRIP CB TRIP CB CONNECTED
BUS
NO NO
MODE: MANUAL MODE: AUTO
YES YES
CB TRIPPED
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
GENERATION
PROTECTION
NO NO NO
Ugen > P2.3.5 Fgen > P2.3.9 Igen > P2.3.1
NO NO NO
Ugen < P2.3.7 Fgen < P2.3.11 Pgen < -P2.3.3
D/G,
HARBOUR MODE SHA
(32)
DIN
HARBOUR
TRIP CB
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
ALARMLIMITS
PMS CONTR.
FUNCTION
ON
NO NO NO NO NO
Ubus > P2.2.1 Ubus < P2.2.3 Fbus > P2.2.5 Fbus < P2.2.7 Pgen > P2.4.1
BUS HIGHVOLTAGE BUS LOWVOLTAGE BUS HIGHFREQUENCY BUS LOWFREQUENCY GENERATOR OVER-
ALARM(251) ALARM(252) ALARM(253) ALARM(254) LOAD(231)
BUS GENERATOR
ALARM ALARM
NO NO NO NO
Ubus > P2.1.1 Ubus < P2.1.3 Fbus > P2.1.5 Fbus < P2.1.7
BUS ABNORMAL
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
CB STATUS
DIN
NO
CB CLOSED CB TRIP
YES TRIP CB
OPERATIONMODES
REMOTE
AUTO
STANDBYREQUEST
SUBSTITUE REQ.
OPERATIONMODES
AUTO
MANUAL SUBSTITU
SU TED
BSTITUTION LOWLOADSTOP
ON BUS
YES AUTOSTOP
OPTION:
P1.6.2
BLACKOUT PREVENT
NO
IN MANUAL
LOWLOADSTOP OFFLOAD
B/OPREVENT OK OPEN CB
DOUT
PULSE:
CB OPEN
T = P5.2.1
EXPIRED
NO
DISCONNECTED
Cont’d on next
page
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
Cont’d from
previous page
GENERATOR DISCONNECTED
ENGINE RUNNING
DIN
NO
RUNNING?
YES
PUSHBUTTON:
OPERATIONMODES
STOP
AUTO
STANDBYSTART
REQUEST (NOT)
COOLDOWN
STOP ENGINE
DOUT
PULSE:
ENGINE STOP
T = P4.2.1
EXPIRED
NO
STOPPED
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
LOWLOADSTOP
DIN
D/GON-LINE = Gon
NO Pres – LOADgen
> P7.3.1
INHIBIT YES
YES
AUTOSTOP
NO
NO
Gon > = 2
STANDBY
SEQUENCE
YES
LAST
NO
FIRST TOSTOP
YES
DELAY:
T > P7.3.2
BLACKOUT
AUTOSTOP
PREVENT OK
13.8 Offloading
OFFLOAD
NO
CB CLOSED
YES
OFFLOAD
NO Pgen<
DELAY:
T> 5.2.3 P5.2.2
YES
OFFLOADFAILURE
(212) YES
OPTION:
P5.3.1
NO
OPENCB
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
COOLDOWN
ENGINE PRE-ALARM
(2)
DIN
NO
PRE-ALARM
YES
YES OPTION:
P4.2.3
NO
DELAY:
P4.2.2
STOP ENGINE
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
OPERATION MODES
REMOTE
PMS CONTR.
FUNCTION
D/Gor E/G
START BLOCK
READYTOSTART
OPERATIONMODES
AUTO
STANDBY
SEQUENCE
FIRST
NON-PREFERENT
STANDBYREQUEST GROUPS
B/ORECOVER STBYSTART
ENGINESTART
RUNNING
DELAY:
T > P2.1.4
NO
Ugen > P4.3.1
YES
ENERGIZE FAILURE NO
(211)
Fgen > P4.3.1
YES
GENERATOR
ENERGIZED
STANDBY
CONNECT
DIN
CB STATUS
DIN
YES
CB CLOSED
NO
F bus
SP ON
TEST MODE = 1
DOUT
ENGINE SYNC-CHECK
INC. SPEED
SYNCHRONIZED
SYNCHRONIZE CONTROL
DOUT
ENGINE
DEC. SPEED
SET RESET
DOUT
SYNCHRONIZE DELAY: PULSE:
CLOSE CB
FAILURE (213) T > P5.1.7 T = P5.1.6
YES
CONNECTED SUBSTITUTION
START BLOCK
ANYCRITICALALARM
READYTOSTART ENGINE RUNNING OPERATION MODES
(LAMXP STEADY)
DIN
DIN
BLACKOUT
RECOVERY
NO
Ubus < 20%
YES
NO
Fbus < 20%
YES
CHECKALLCB STATUS
CB STATUS
X ON BUS
DIN
DIN
NO
ALLCB OPEN?
YES
BLACKOUT (291)
DEADBUS LIVEBUS
S/C DEVICE
S/CCB
TRIPPED DEV ICE
(229) CHECKALLS/C TRIPS
TRIPPEDCB (229) ON BUS
NO
S/C TRIPS< 2
YES
DELAY:
T > P7.1.1
B/ORECOVER
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
NO
CB CLOSED
YES
NON-PREFERENTIAL ENGINEPRE-ALARM
CONSUMER BLOCKS
GROUPS (2)
DIN
NO OPTION NO OPTION
P7.4.1 P7.4.3
YES YES
NO OPTION ENGINEPRE-ALARM
P7.4.2 (204)
YES
SUBSTITUTE REQ
NO NO NO NO
Pgen> P7.2.1 Pgen> P7.2.3 Pgen> P7.2.5 Igen> P7.2.7
STANDBY
REQUEST
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
ENGINESTART
ENGINE RUNNING
DIN
ENGINE YES
RUNNING
NO
ENGINESTART FAIL
DIN
YES
EXT. START FAIL
NO
NO DOUT 331
CONFIGURED
DOUT
PULSE / DELAY: PULSE PRE-LUBRICATION
P4.1.4 (331)
DELAY
DELAY
DOUT
NO
ENGINE START
ENGINE YES
RUNNING
NO
RE-START DELAY
DELAY:
P4.1.3
MANUAL
OPERATION MODES
AUTO
START ATTEMPT + 1
NO START ATTEMPT
> = P4.1.1
YES
ENGINESTART
FAILURE (201) RUNNING
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
13.15 Synchronizer
SYNC. CHECK
IO-BOARDSYNCHRONIZER TEST MODE
L24 L24
DEAD-BUS
BLACKOUT
LIVE-BUS
L19
PMS CONTR. Other
FUNCTION
ABT
NO Fgen> NO
Fbus < 10Hz
(Fbus–P5.1.2)
YES YES LED indications with
L15
synchronize test-mode
NO Fgen< NO
(Fbus+P5.1.3) Fgen < 10Hz
Note: the test-mode does
YES YES not influence the actual
L20 L17
output relay statuses only
provides alternative LED
functions!
NO Ugen> NO
Ubus < 20V
(Ubus–P5.1.1)
Note for test-mode=1:
YES YES
L16
the CB close relay is not
being activated but the
NO Ugen<
(Ubus+ P5.1.1)
NO
Ugen < 20V LED is activated -at close
condition- for ~3s after
YES YES
L21 L18
which the test continues
BUS BLACKOUT -
FREQUENCY
BUS BLACKOUT -
NO Φgen> VOLTAGE
(Φbus-P5.1.4) GEN BLACKOUT -
FREQUENCY
YES GEN BLACKOUT -
VOLTAGE
SYNC START
NO Φgen<
(Φbus+ P5.1.5) FREQUENCY
SYNC OK
YES
VOLTAGE
SYNC OK
L22
ANGLE
SYNC OK
SYNCHRONIZED
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
LOADCONTROL
D/G, E/G
NO
CB CLOSED
YES
PUSHBUTTON: PUSHBUTTON:
OPERATION MODES
INC DEC
AUTO
NO SET /
OFFLOADING
RESET RESET
UNBALANCED
LOADSHARINGMODE
AUTO
YES ENABLE= P6.3.1 OPERATIONMODES
MANUAL
DELAY: AUTO OPERATIONMODES
T > P6.3.3
YES MANUAL
NO
UNBALANCEDLOAD
SHARING
YES BALANCED NO
LOADSHARING?
DOUT
ENGINE
INC. SPEED
LOADSETPOINT
DOUT
ENGINE
DEC. SPEED
ENABLE ACTIVELOADCONTROLLER
P.B. = P6.1.3
D.B. = P6.1.4
FREQUENCYCONTROLLER
END
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
BUS NO. #
(P8.0.1)
CALCULATE BUS X:
POWER RESERVE = Pres
D/GON-LINE = Gon
REQUEST
INHIBIT
AUTO-STOP
NO
Pres > P8.#.1
YES
Gon > NO
P8.#.2
WAIT
YES
DELAY:
T > P8.0.2
NOT
DOUT
CONSUMER BLOCK
ACCEPT #
(301~ 304)
CONSUMER #
ACCEPT
STANDBYREQ.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
BUS NO. #
(P9.0.1)
CALCULATE BUS X:
LOAD = Pbus
ANYCB TRIPPED
NO ANY NO
CB TRIPPED
Pbus > P9.#.1
YES YES
PULSE:
T = 5SEC
DOUT
NON-PREF. TRIP
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
FLOWCHARTS
Following main menu levels are provided for the configuration of each PMS controller:
1 - MAIN SETUP
2 - ALARM LIMITS
3 - CONFIGURABLE I/O
4 - START/STOP
5 - CB OPEN/CLOSE
6 - LOAD SHARING
7 - AUTO START/STOP
8 - HEAVY CONSUMERS
9 - NON-PREFERENTIAL GROUPS
See 3.3 for the description of the menu displays and menu operations.
MEGA-GUARD Ship Automation and Navigation System
Operator Guide Power Management System
MENUS / PARAMETER LIST
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
1 MAIN SETTINGS
1.1. CONTROLLER ID
1. PMS CONTROLLER NO. 1..9 1 READ ONLY
-
2. PMS APPLICATION VERSION - READ ONLY
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
2 ALARM LIMITS
14.3 Configurable IO
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
3 CONFIGURABLE IO
14.4 Start/Stop
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
4 START / STOP
14.5 CB open/close
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
5 CB OPEN / CLOSE
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
6 LOAD SHARING
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
8 HEAVY CONSUMERS
8.0. COMMON
1. CONNECTED TO BUS # 1
2. ACCEPT DELAY SEC 10
Engineering Unit
Commissioning
Menu Item
Sea Trail
Default
New
Description Note
9 NON-PREFERENTIAL GROUPS
9.0. COMMON
1. BUS NUMBER NON-PREF GROUPS # 1