You are on page 1of 1

A Geometrical Dimensions of Stack

1 Diameter of Chimney D = 750 mm


2 Total Height of Chimney H = 35000
Height of Flared Portion of Chimney Hf = 1/5 H 1/3H if stack height is more than 40m ( as Per IS 6533-part 2)
3
Hf = 7000 mm
Diameter of Flared Portion of Stack Df = 1.8 D
4
Df = 1350 mm
5 Height of Cylindrical Portion of Hc = 28000 mm
7 No. of Segments for cylindrical portion Ns = 7 Nos
8 Length of Each segment Ls = 4000 mm

B Wind Load Calculation


Wind zone and basic wind speed as
per IS 875 in Vb in m/s.
1 I = 55 IV =44
II = 50 V =39
III = 47 VI =33
Project Wind Zone = IV
Basic wind velocity in m/s/ Earthquake = 44 m/s
coefficient
K1 = Risk coefficient = 1
(From IS 875, Table 1)
Take K1 as 1.0 for chemical plants To be
K2 = Terrain height and structure size = K2 determi
factor ned at
(From IS 875 From Table 2) repecti
Take the terrain as category 2 and
ve
class A for most chemical plants
heights
K3 = Topography factor = 1
(From IS 875)
Whether the location is within 200 Km = 1.00
from sea coast
If yes, K4 is 1.15. If No, K4 is 1.0
Design wind speed Vz in m/s =
Vz = K1K2K3K4 Vb 44 k2.m/s
h. Design wind pressure Pw in N/mm2 =
pw = 0.6 Vz2 / 106 0.0011616 k2.N/mm2

At Section 1 30 1.12
Height for K2 = 35 50 1.17
K2 = 1.1325 35 1.1325
Pw at Section 1 = 0.001315512 N/mm2
1 4735.843
Shape Factor at Section 1 (Ct) = 1.2
Force At Section 1 ( Ct x A x Pw) = 4735.8432 N
Bending Moment at Section 1 = 9471686.4 N.mm

At Section 2 30 1.12
Height for K2 = 31 50 1.17
K2 = 1.1225 31 1.1225
Pw at Section 2 = 0.001303896 N/mm2 2 4694.026 N
Shape Factor at Section 2 (Ct) = 1.2
Force At Section 2 ( Ct x A x Pw) = 4694.0256 N
Bending Moment at Section 2 = 37803110.4 N.mm

At Section 3 20 1.07
Height for K2 = 27 30 1.12
K2 = 1.105 27 1.105
Pw at Section 3 = 0.001283568 N/mm2 3 4620.845 N
Shape Factor at Section 3 (Ct) = 1.2
Force At Section 3 ( Ct x A x Pw) = 4620.8448 N
Bending Moment at Section 3 = 84764275.2 N.mm

At Section 4 20 1.07
Height for K2 = 23 30 1.12
K2 = 1.085 23 1.085 4537.21 N
Pw at Section 4 = 0.001260336 N/mm2 4
Shape Factor at Section 4 (Ct) = 1.2
Force At Section 4 ( Ct x A x Pw) = 4537.2096 N
Bending Moment at Section 4 = 150041548.8 N.mm

At Section 5 15 1.05
Height for K2 = 19 20 1.07
K2 = 1.066 19 1.066 4457.756 N
Pw at Section 5 = 0.001238266 N/mm2 5
Shape Factor at Section 5 (Ct) = 1.2
Force At Section 5 ( Ct x A x Pw) = 4457.75616 N
Bending Moment at Section 5 = 233308753.9 N.mm

At Section 6 10 1
Height for K2 = 15 15 1.05
K2 = 1.05 15 1.05 4390.848 N
Pw at Section 6 = 0.00121968 N/mm2 6
Shape Factor at Section 6 (Ct) = 1.2
Force At Section 6 ( Ct x A x Pw) = 4390.848 N
Bending Moment at Section 6 = 316446142.7 N.mm

At Section 7 0 1
Height for K2 = 11 10 1
K2 = 1 11 1 4181.76 N
7
Pw at Section 7 = 0.0011616 N/mm2
Shape Factor at Section 7 (Ct) = 1.2
Force At Section 7 ( Ct x A x Pw) = 4181.76 N
Bending Moment at Section 7 = 399169355.5 N.mm

At Section 8 ( Flare Section) 0 1


Height for K2 = 7 10 1
K2 = 1 7 1 10254.72 N
Pw at Section 7 = 0.0011616 N/mm2 8
Shape Factor at Section 7 (Ct) = Average ø
Dia of
1.2 Flare 1050.964
Force At Section 7 ( Ct x A x Pw) = 10254.71664 N
Bending Moment at Section 7 = 709602316.6 N.mm ø 2.454032