An extensive range of 48, 72, 96 and 144mm DIN style panel meters offering
measurement of all electrical and electronic parameters. Meters are shock resistant
and vibration proof and supplied with terminal covers. A selection of slide in dials
and customised options are available.
Movements
In Crompton Instruments’ world-patented ‘Hi-Q’ taut band suspension, all the
delicate parts of the traditional instruments are eliminated. There are no pivots, no
jewel bearings, no hair-springs and no air damping vane. Instead, a tough platinum
ribbon suspends the moving element between front and rear tension springs.
Specially contoured pads are fitted to the ends of the spindle, and the working gap at
each end is filled with a high quality silicon fluid. The pads, together with the fluid
reservoir, form a system which acts as a resilient built-in shock absorber. This
provides both rotational and longitudinal damping as the moving element floats on
oil with no bearing friction and is effectively cushioned against shock and vibration.
360° Synchroscopes and power factor meters have robust pivot and jewel bearings
Features with oil damping.
An extensive range of specialist
measuring meters in 4 case sizes Dials, Scales and Pointers
Standard dials are matt white with black printed scales and bar knife-edge pointers.
Shock resistant taut band suspension
Black dials with white or yellow scales and pointers are also available.
Vibration-proof Hi-Q damping Interchangeable slide in dials are used on models 242, 243 and 244 90° moving iron,
Slide in dials for 90°current, voltage and moving coil and frequency meters.
frequency on models 242, 243 and 244 General options include red supplementary pointers, red indexes (quadrant scales),
red, green or blue lines, bands or segments, finely spaced divisions, multi-scales,
Terminal covers supplied as standard special scales and captions to customer' requirements.
Benefits Illumination
Low cost Internal illumination is available in the following models:
Local indication • 244 and 246 shortscale moving coil and moving iron vane.
• 243, 244 and 246 longscale moving coil and moving iron vane.
Ease of installation
Through dial (Translucent) illumination on 244 and 246 models.
Minimal training Edge illumination on 243, 244 and 246 models.
Low maintenance Replaceable 6, 12 or 24V lamps are used on all models except 243 longscale meters,
Customised options and features where the lamps are internal.
Applications Specification
Performance BSEN60051
Switchgear
Measuring Ranges DIN 43701
Distribution systems Accuracy Overload BSEN60051
Generator sets Dimensions DIN 43700
Scale Marking Generally DIN43802
Control panels
Magnetic Influence BSEN60051
Energy management Safety IEC414
Building management Terminals Clamp strap M4 up to 25A. Clamp strap M8 over 25A
Humidity Range Up to 95% RH (non condensing)
Utility power monitoring
Test Voltage @50Hz 2kV RMS for 1 minute
Process control Overload AC Current x 1.2 continuous x 10 for 5 seconds
Motor control Overload AC Voltage x 1.2 continuous x 2 for 5 seconds
Frequency See main pages for other instruments
Approvals Damping Time Less than 3 seconds is standard. More heavily damped
movements are available on request.
LRS and BV Approvals.
Standard Calibration 23°C
Operating Temperature -20°C to +60°C
Enclosure Code IP54 as standard (to BSEN60529). IP55 consult factory
Terminals IP20B with terminal cover or terminal
boots fitted
Case Grade UL94V0
Base Grade UL94V1
8
240 Series DIN Panel Meters
Dimensions
Model 242 243 244 246
Bezel ‘A’ 48 x 48 72 x 72 96 x 96 144 x 144
Panel cut-out ‘B’ 45 x 45 68 x 68 92 x 92 138 x 138
Scale Length: 90° 42 65 94 145
Scale Length: 240° 72 112 150 230
Maximum overall depth ‘C’:
Ammeters and Voltmeters A.C. & D.C.* 64 64 64 60
Ammeters and Voltmeters with switch* – – 64 –
Dual Meters* – – 64 –
C Elapsed Time Meter/Hours Run* 64 64 64 –
Maximum Demand Indicator* – 64 64 60
Combined MDI & MI Indicator* – – 64 60
Maximum Demand Indicator with relay* – – 90 –
Frequency Meter 90°* 64 64 64 60
A Frequency Meter 240°* § § 120 125
Phase Angle, Power Factor Meter 90°* § § 107 §
240°* § § 107 §
M.C. Indicator with separate transducer* 64 64 64 60
Dynamometer 360° Synchroscope* – – 120 125
Dynamometer 360° Power Factor Meter* – – 120 –
A Phase Sequence Indicator* – 64 64 –
Position Indicator* § § 120 125
Speed Indicator* 64 64 64 60
Temperature Indicators* – – 120 125
Quadra Meters* – – 64 –
Panel cut-out Impulse Counters* 64 64 64 –
Wattmeter, Varmeter 90° § § 107 125
Maximum Panel B
Wattmeter, Varmeter 240° § § 107 125
thickness 10mm Model 244-21Y & 244-21Z – – 142 –
LED Synchroscope & Synchro Check Relay – – 80 –
LED 360° Synchroscope – – 80 –
§ Indicator Only
B * If separate terminal cover is used add 20 mm to dimension C
– Not available
9
240 Series DIN Panel Meters
Specification
Accuracy: 1.5% ES
Ratings: Ammeter: 250µA to 10A A.C.
Voltmeter: 15 to 600V direct connected
Frequency: 50/60Hz (single frequencies 25Hz to 3kHz on request)
Product Codes
Bezel Size mm 96
Scale length mm 65
Product Codes
Ammeters 244-80F
Voltmeters 244-80L
Dual A.C. Ammeter Dual A.C. Voltmeter
Direct Connected
13
240 Series DIN Panel Meters
Specification
Accuracy: Class 1.5
Ratings: Ammeters: 100µA to 25A, (200µA for 05 model)
4/20mA suppressed zero
40A for model 243/244-01A
Voltmeters: 50mV to 600V
1/5V suppressed zero
50, 60, 75, 100, 150mV for use with shunts
Impedance: Ammeters: 75mV internal shunt above 60mA
Connections Voltmeters: 1000Ω/V above 1V
D.C. Ammeter
Further details on our T-Sheet T118 available on request.
Specification
Accuracy: Class 1.5
Ratings: D.C. Current: 100µA to 25A direct connected
Connections 4/20mA suppressed zero.
Dual D.C. Ammeter D.C. Volts: 50mV to 600V
1/5 volt suppressed zero
50, 60, 75, 150mV for use with shunts.
Product Codes
Bezel Size mm 96
Scale length mm 94
Product Code
Dual D.C. Voltmeter
Ammeters 244-80M
Voltmeters 244-80E
18
240 Series DIN Panel Meters
Specification
Ratings Voltage: 63.5, 110, 120, 220, 230, 240, 380, 400, 415, 440, 480V
110/120V (115V Nominal)
220/240V (230V nominal)
Connections 380/480V (430V nominal)
360° LED Synchroscope Volts A.C. or via V.T.
Frequency: 40/65Hz
Burden at 50Hz: 4VA maximum
Suitable for single or three phase systems
Safety: IEC1010-1 (300V A.C. rms installation degree 2)
Dielectric: 4kV rms for 1 minute
Isolation: BUS/GEN/RELAY
Vibration: To Lloyds shipping specification
*Phase difference: +0 to 20°. +/-1°
*Voltage difference: +0 to 20% +/-2%
0 to 10% for models G & H
*Time Delay: 0 to 2.5 seconds +10%
*Accuracy: Synchronisation at T.D.C. is +1˚
*360° LED Synchroscope and Synchro Check Relay Only.
24
®
dseGenset
dse8610 MKII
ENVIRONMENTAL TESTING STANDARDS
ELECTRICAL SAFETY
The DSE8610 MKII is an easy to Designed to offer increased built in KEY LOAD SHARE FEATURES: BS EN 60950
use Synchronising Auto Start support for active sensors for 0 V • Peak lopping/sharing (with Safety of Information Technology Equipment,
Control Module suitable for use in a to 10 V & 4 mA to 20 mA. appropriate DSE mains including Electrical Business Equipment
multi-generator loadshare system, Comprehensive communication controller) TEMPERATURE
designed to synchronise up to 32 and system expansion options are • Sequential set start BS EN 60068-2-1
generators including electronic and available. • Manual voltage/frequency Ab/Ae Cold Test -30 oC
BS EN 60068-2-2
non-electronic engines. adjustment Bb/Be Dry Heat +70 oC
Using the DSE PC Configuration • R.O.C.O.F. and vector shift
VIBRATION
The DSE8610 MKII monitors the Suite Software allows easy protection BS EN 60068-2-6
generator and indicates operational alteration of the operational • Generator load demand Ten sweeps in each of three major axes
status and fault conditions, sequences, timers and alarms. With • Automatic hours run balancing 5 Hz to 8 Hz at +/-7.5 mm, 8 Hz to 500 Hz at 2 gn
automatically starting or stopping all communication ports capable of • Mains (Utility) decoupling HUMIDITY
the engine on load demand or fault being active at the same time, the • Mains (Utility) decoupling BS EN 60068-2-30
condition. DSE8610 MKII is ideal for a wide test mode Db Damp Heat Cyclic 20/55 oC at 95% RH
48 Hours
variety of demanding load share • Dead bus sensing BS EN 60068-2-78
System alarms are annunciated on applications. • Bus failure detection Cab Damp Heat Static 40 oC at 93% RH
the LCD screen (multiple language • Direct governor and AVR control 48 Hours
options available), illuminated LED • Volts and frequency matching SHOCK
and audible sounder. • kW and kvar load sharing BS EN 60068-2-27
• Dead bus synchronising Three shocks in each of three major axes
15 gn in 11 mS
The event log will record 250 events
to facilitate easy maintenance, and DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
an extensive number of fixed and BS EN 60529
flexible monitoring, metering and IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
protection features are included.
DSENET ®
RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 5-35V
+
ETHERNET
MSC
DEUTZ DETROIT
ISUZU IVECO
DSE8610 MKII MSC PERKINS JOHN DEERE
CATERPILLAR LOMBARDINI
MTU SISU
8xxxMKII
7 VOLVO JCB DIESELMAX
55xx 75xx 8xxx CUMMINS YANMAR
OTHER SCANIA AND OTHERS
BUS VOLT FREE GENERATOR SENSING FUEL & START CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
CURRENT VOLTS
D+
+ W/L
ISSUE 3
®
dseGenset
dse8610
SPECIFICATION
MKII DC SUPPLY
CONTINUOUS VOLTAGE RATING
• Built in governor and AVR control inputs DSE8000 and DSE8600 MKII MAGNETIC PICKUP
• Base load (kW export) control • Built in sensors to support 0 V to series. Contact DSE for further VOLTAGE RANGE
• Positive & negative kVAr export 10 V & 4 mA to 20 mA details +/- 0.5 V to 70 V
control • 12 configurable digital inputs • 132 x 64 pixel ratio display for FREQUENCY RANGE
• Mains (Utility) decoupling • Configurable 5 stage dummy load clarity 10,000 Hz (max)
protection and load shedding outputs • Real-time clock provides accurate
INPUTS
• 4-Line back-lit LCD text display • CAN, MPU and alternator event logging DIGITAL INPUTS A TO L
• Multiple Display Languages frequency speed sensing in one • Ethernet communication, provides Negative switching
• Five key menu navigation variant builit in advanced remote ANALOGUE INPUTS A TO D
• LCD alarm indication • Real time clock monitoring. Configurable as:
• Heated display option available • Manual and automatic fuel pump • Can be integrated into building Negative switching digital input
0 V to 10 V sensor
• Customisable power-up text and control management systems (BMS) and
0 Ω to 480 Ω sensor
4 mA to 20 mA sensor
images • Engine run-time scheduler programmable logic control (PLC)
• DSENet expansion compatibility • Fuel usage monitor and low fuel • Increased input and output ® OUTPUTS
• Data logging & trending facility level alarms expansion capability via DSENet OUTPUT A & B (FUEL & START)
• Internal PLC editor • Simultaneous use of all • Licence-free PC software 15 A DC at supply voltage
• Protections disable feature communication ports • IP65 rating (with supplied gasket)
OUTPUTS C & D
• Fully configurable via PC using • Remote SCADA monitoring via offers increased resistance to water 8 A AC at 250 V AC (Volt-free)
USB, RS232, RS485 & Ethernet various DSE software applications ingress
communication • MODBUS RTU & TCP support • Advanced Internal PLC editor allows AUXILIARY OUTPUTS E TO L
2 A DC at supply voltage
• Front panel configuration with PIN with configurable MODBUS user configurable functions to meet
protection pages for integration into building specific application requirements. BUILT IN AVR GOVERNOR CONTROL
500 Ω
• Power save mode management systems (BMS) MINIMUM LOAD IMPEDANCE
• 3 phase generator sensing and • Advanced SMS messaging EXPANSION DEVICES Fully isolated
protection (additional external modem • DSE124 CAN/MSC Extender
• Generator current and power required) • DSE2130 Input Expansion Module GAIN VOLTAGE
0 V to 10 V DC
monitoring (kW, kvar, kVA, pf) • Start & stop capability via SMS • DSE2131 Ratio-metric Input Fully isolated
• kW and kvar overload alarms messaging Expansion Module
• Reverse power alarms • 3 configurable maintenance • DSE2133 RTD & Thermo-couple OFFSET VOLTAGE
0 V to 10 V DC
• Over current protection alarms Expansion Module Fully isolated
• Unbalanced load protection • Compatible with a wide range of • DSE2152 Ratio-metric Output
• Independent earth fault protection CAN engines, including tier 4 Expansion Module DIMENSIONS
OVERALL
• Breaker control via fascia buttons engine support • DSE2157 Output Expansion 245 mm x 184 mm x 51 mm
• Fuel and start outputs • Uses DSE Configuration Suite PC Module 9.6” x 7.2” x 2.0”
configurable when using CAN Software for simplified • DSE2548 LED Expansion Module
PANEL CUT-OUT
• 8 configurable DC outputs configuration 220 mm x 160 mm
8.7” x 6.3”
-40 °C to +85 °C
RELATED MATERIALS STORAGE TEMPERATURE RANGE
-40 °F to +185 °F
TITLE PART NO’S
DSE8610 MKII Installation Instructions 053-182
DSE8610 MKII Operator Manual 057-254
-30 °C to +70 °C
OPERATING TEMPERATURE RANGE
DSE8610 MKII PC Configuration Suite Manual 057-238
-40 °F to +185 °F
Press (right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.
Repeat this process for the other digits of the PIN number. You can press (left) if you need
to move back to adjust one of the previous digits.
When (Tick) is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
EDITING A PARAMETER
Press the (Right) or (Left) to cycle to the section you wish to view/change. Then
press (Up) or (Down) to cycle to the parameter within the section you have chosen.
DIMENSIONS AND MOUNTING To edit the parameter, press (Tick) to enter edit mode. The parameter begins to flash to indicate
For flat surface mounting in a Type 1 enclosure to meet UL requirements that you are editing the value.
Press the up or down buttons to change the parameter to the required value.
DIMENSIONS PANEL CUTOUT:
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”) 220mm x 160mm (8.7” x 6.3”) Press (Tick) to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor at any time, press and hold the (Stop/ Reset) or (Tick) button.
Deep Sea Electronics Plc. Deep Sea Electronics inc.
Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708 NOTE: When the editor is visible, it is exited after 5 minutes of inactivity to ensure security.
Email: support@deepseaplc.com TOLL FREE (USA only) : Tel: 1 866 636 9703
Web: www.deepseaplc.com Email: dsesales@deepseausa.com NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
Web: www.deepseausa.com
NOTE: Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSE publication
057-239 DSE8610 MKII & DSE8610 MKII Configuraiton Suite PC Software Manual.
ADJUSTABLE PARAMETERS Front Panel Configuration Editor (continued)
Front Panel Configuration Editor (Factory default settings are shown in bold italicised text) Section Parameter as shown on display Values
Timers LCD Page Timer 0h 0m 0s
Section Parameter as shown on display Values Scroll Delay 0h 0m 0s
Display Contrast 0% Engine Pre Heat Timer 0h 0m 0s
Language English, Other. Engine Crank Duration 0h 0m 0s
Current Date and Time hh:mm Engine Crank Rest Time 0h 0m 0s
Engine Oil Pressure Low Shutdown 0.00 bar Engine Safety On Delay 0h 0m 0s
Oil Pressure Low Pre Alarm 0.00 bar Engine Smoke Limiting 0h 0m 0s
Coolant Temp high Pre Alarm 0 ºC Engine Smoke Limiting Off 0h 0m 0s
Coolant Temp High Shutdown 0 ºC Engine Warm Up Time 0h 0m 0s
Start Delay Off Load 0h 0m 0s Engine Cool Down Time 0h 0m 0s
Start Delay Telemetry 0h 0m 0s Engine Speed Overshoot Delay 0h 0m 0s
Engine Pre Heat Timer 0h 0m 0s Engine Failed To Stop Delay 0h 0m 0s
Engine Crank Duration 0h 0m 0s Battery Under Voltage Warning Delay 0h 0m 0s
Engine Crank Rest Time 0h 0m 0s Battery Over Voltage Warning Delay 0h 0m 0s
Engine Safety On Delay 0h 0m 0s Return Delay 0h 0m 0s
Engine Smoke Limiting 0h 0m 0s Generator Transient Delay 0h 0m 0s
Engine Smoke Limiting Off 0h 0m 0s Scheduler Scheduler Active / Inactive
Engine Warm Up Time 0h 0m 0s Schedule On Load Active / Inactive
Engine Cool Down Time 0h 0m 0s Schedule Period Weekly, Monthly
Engine Speed Overshoot Delay 0h 0m 0s
Engine Speed Overshoot 0h 0m 0s Schedule Time & Date Selection (1-16) Press to begin editing then or when selecting the
Engine Failed To Stop Delay 0h 0m 0s different parameters in the scheduler.
Battery Under Voltage Warning Active / Inactive
Battery Under Voltage Warning Delay 0h 0m 0s
Battery Under Voltage Warning 0V ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
Battery Over Voltage Warning Active / Inactive
Battery Over Voltage Warning Delay 0h 0m 0s The ‘running’ editor can be entered while the engine is running. All protections remain active if the
Battery Over Voltage Warning 0V engine is running while the running editor is entered.
Charge Alternator Failure Warning Active / Inactive
Charge Alternator Failure Warning 0V
Charge Alternator Warning Delay 0h 0m 0s
Press and hold the (Tick) button to enter the running editor.
Charge Alternator Failure Shutdown Active / Inactive
Generator Under Voltage Shutdown 0V ADJUSTABLE PARAMETERS (Running editor)
Under Voltage Pre-Alarm 0V
Loading Voltage 0V Enter the editor as described above.
Nominal Voltage 0V
Over Voltage Pre-Alarm 0V
Over Voltage Shutdown 0V
Under Frequency Shutdown 0 Hz
Under Frequency Pre-Alarm 0 Hz Press the (Up) or (Down) buttons to cycle to the section you wish to view/change.
Loading Frequency 0 Hz
Nominal frequency 0 Hz
Over Frequency Pre-Alarm 0 Hz
Over Frequency Shutdown 0 Hz To Edit the parameter press the (Tick) button to enter edit mode. The parameter begins to flash to
Full Load Rating 00 A indicate that you are editing the value.
kW Overload Trip 0%
Delayed Over current Active / Inactive
Gen Over Current Trip 0%
AC System 3 Phase 4 Wire
CT Primary 0A Power Cycle After Exit Press the (Up)or (Down) buttons to change the parameter to the required value.
CT Secondary 0A Power Cycle After Exit
Short Circuit Trip 0%
Earth CT Primary
Earth Fault Trip
0A
Active / Inactive
Press the (Tick) button to save the value. The parameter ceases flashing to indicate that it has
Earth Fault Trip 0% been saved.
Transient Delay 0h 0m 0s
Gen Reverse Power Delay 0h 0m 0s To exit the editor at any time , press and hold the (Tick) button.
Full kW Rating 0 kW
Full kVAr Rating 0 kvar
Load Ramp Rate 0%
Running Editor
Load Level For More Sets 0%
Load Level For Less Sets 0% Section Parameter as shown on display Values
Load Demand Priority 1 Display Contrast 0%
Gen Reverse Power 0 kW Language English, Other
Insufficient Capacity Delay 0h 0m 0s Load Demand Priority 1
Insufficient Capacity Action None / Indication / Warning / Shutdown / Electrical Trip Load Power Factor 0%
Reactive Load CTL Mode None / VAr Share Load Parallel Power 0%
Load Parallel Power 0 kW When In Mains Parallel Mode ) Commissioning Screens Active / Inactive
Load Power Factor 0% When In Mains Parallel Mode Override Starting Alarms Active / Inactive
Enable MSC Compatibility Active / Inactive Voltage Adjust (manual mode only engine running breaker open) 0%
Continued Overleaf Frequency Adjust (manual mode only engine running breaker open) 0%
Lembar data produk NSYCVF85M230PF
Karakteristik ClimaSys forced vent. IP54, 85m3/h, 230V, with
outlet grille and filter G2
Disklaimer: Dokumentasi ini tidak ditujukan sebagai pengganti dan tidak untuk digunakan untuk menentukan kesesuaian atau keandalan produk ini untuk aplikasi pengguna
Main
Range ClimaSys
Product name ClimaSys CV
Product or component type Fan
Type of filter Standard
Flow rate Free flow rate with standard filter: 85 m3/h at 50 Hz
Free flow rate with standard filter: 98 m3/h at 60 Hz
[Us] rated supply voltage 175...253 V
Input voltage 230 V 50/60 Hz
Complementary
Absorbed power 15 W 60 Hz
17 W 50 Hz
[In] rated current 0.121 A 50 Hz
0.097 A 60 Hz
Noise level < at 46…49 dB
Bearing type Ball
Height 170 mm external:
Width 150 mm external:
Depth 62 mm external:
Cut-out dimensions 125 x 125 mm
Net weight 0.78 kg
Material Outlet grille: injected thermoplastic (ASA PC)
Colour Outlet grille: grey (RAL 7035)
Ambient air temperature for operation -20…60 °C
Ambient air temperature for storage -40…70 °C
Maximum pressure 50 Pa flow rate 0 m³/h
Connections - terminals Faston connector
IP degree of protection IP54
Device composition 1 axial motor
2 protective grille: on the front and rear surfaces
1 filter: front of axial motor
1 outlet grille: front
1 cut-out template
13 Feb 20
1
1 power cord
Condition of use Flow rates depends on the work point, see ProClima software
Surrounding environment must be relatively clean
Filter must be cleaned and replaced regularly
Overfrequent filter replacement should be avoided
Outside temperature must be 5 °C lower than inside temperature
Offer Sustainability
REACh free of SVHC Yes
EU RoHS Directive Compliant
EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
Contractual warranty
Warranty 12 months
2
Product datasheet NSYCR150WU2C
Characteristics ClimaSys PTC heating resistance
150W,110-250V insulate
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range ClimaSys
Product name ClimaSys CR
Product or component type Resistance heater
Power range 150 W
Input voltage 110...250 V AC 50/60 Hz
Electrical connection 4 screw terminals 2.5 mm²
Complementary
Operating position Vertical
Ambient air temperature for operation -40…70 °C
IP degree of protection IP20
Electrical insulation class Class II
Product certifications VDE
UL
Material Body: extruded aluminium
Cover: plastic
Height 150 mm external:
Width 60 mm external:
Depth 90 mm external:
Condition of use Electrical protection is needed
Heaters must be installed with a thermal controller
Air sealed enclosure
Fixing mode By clips
Mounting support 35 mm DIN rail
Offer Sustainability
REACh free of SVHC Yes
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
13 Feb, 2020
1
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Contractual warranty
Warranty 18 months
2
Product data sheet REL91283
Characteristics
Main
Range of product RelayAux
Product or component type Fast trip and lockout relay
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Coil type Low consumption
[Uc] control circuit voltage 110 V DC (- 20 % + 10 % Un)
Product compatibility REL91351 (front connection socket)
REL91360 (flush mounting socket)
Status LED Without
Control type Manual reset
Automatic reset
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Local signalling Mechanical indicator (red)contact position:
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Complementary
Contacts type and composition 8 C/O
Insulation resistance > 100 MOhm at 500 V DC conforming to IEC 60255-5
[Uimp] rated impulse withstand voltage 5 KV during 1.2/50 µs conforming to IEC 60255-5
Contacts material AgNi
[Ie] rated operational current 10 A
Inrush current 80 A during 200 ms
200 A during 10 ms
Making capacity 40 A during 0.5 s at 110 V DC
Mechanical durability 10000000 Cycles
Power consumption in W High consumption: 500 W - peak (< 2 ms)
Low consumption: 1.4 W - permanent
High consumption: 45 W
Maximum pick up duration 10 Ms
Contact resistance 30 MOhm
Inter contact distance 1.8 Mm
Mechanical robustness Shocks 11 ms (5 gn) conforming to IEC 60068-2-27
Bumps 16 ms (10 Gn) conforming to IEC 60068-2-29
Height 50 Mm
Width 90 Mm
Depth 100.5 Mm
Net weight 0.6 Kg
Offer Sustainability
EU RoHS Directive Not applicable, out of EU RoHS legal scope
2
5 The efficiency
Acti 9
generations Acti 9 Exclusive new features give you the safest,
Unmatched, aesthetically attractive design ‘You can tell it’s a
simplest, and most efficient installations
high-quality product
you deserve
Unparalleled high-quality fit and finish
when you hold it’
of industry experience and 21 new patents The most flexible and innovative low-voltage modular system
make Acti 9 the new reference in low-voltage
Acti 9TM gives you unmatched efficiency, reduces design and installation time, eliminates
modular systems down time, and makes your business even more competitive. It simplifies you final distribution
operations with the right solution for every application. It even adds control and communication
capabilities, integrating easily with any facility management system and adapting to the dynamic
requirements of tertiary and industrial lighting applications.
VisiTrip TM
Acti 9 Smartlink
VisiSafe TM
Enter key code Enter key code Enter key code Enter key code
78176T 78176T 78176T 78176T
Residual current devices Vigi iC60 iDPN Vigi Control iCT iTL iPB iSSW iIL iEN, iME
Function Contactors Impulse Relays Push-buttons Switches Indicator Lights Kilowatt hour meters
RCD Type AC, A, SI AC, A, SI
single single single phase
Type 2P, 3P, 4P 1P + N 1P, 2P double double three phases
Type 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P
3P, 4P single + flashing light three phases
Rating (A) 25, 40, 63 4 to 40 indicator light voltage presence neutral
Standards IEC/EN 61009-1 IEC/EN 61009-1 Rating (A) 16, 25, 40, 63,100 16 & 32 20 20 to 125 40 to 6000
Sensitivity (mA) 10, 30, 100, 300, 300 S , 10, 30, 100, 300
500, 500 S , 1000 S
Type 2 or 3
1 pole Residual current circuit breakers iID iIDK
1 pole + neutral
RCD Type Asi, A, AC, B AC
2 poles Lighting, time and energy management
3 poles Type 2P, 4P 2P, 4P
MIN IH, IHP, ITM IC TH, THP CDS STD, SCU
3 poles + neutral Rating (A) 16 to 125 25, 40, 63
Silent electronic Programmable and Standard and Standard and Single and Dimmers
4 poles Standards IEC/EN 61008-1 IEC/EN 61008-1 and electromechanical mechanical time programmable twilight weekly programmable three-phase
timers switches switches thermostats load-shedders
Automatic Surge arresters Sensitivity (mA) 10, 30, 100, 300, 300 S , 500, 500 S 30, 300
recloser
auxiliaries Electrical auxiliaries and mounting accessories
2 poles 2 poles
2 poles 3 poles 3 poles
4 poles 4 poles 4 poles
Residual current Vigi residual current Integrated remote
circuit breaker device module control circuit breaker Installation and wiring Multiclip™ splitter block Acti 9 Smartlink Distribloc™ splitter block
Rating (A) 80 -- 63
safe for installers and coordination preventative time saved on down time best choice for
users in the most between MCB maintenance design and industrial and
severe environments and actuator installation tertiary buildings Combined iOF, iSD, iMN, iMX, and iMSU electrical auxiliaries between iC60 circuit breakers and iID
Terminal shields, interpole barrier, screw shields, plug-in
base, padlocking device, clip-on terminal markers, and
residual current circuit breakers, automatic recloser (ARA), and remote control auxiliaries (RCA)
rotary handle
Product data sheet LV429289
Characteristics
Main
Product or component type Plug-in kit
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Accessory / separate part category Mounting accessory
Range compatibility Compact NSX circuit breaker
Compact NSX DC circuit breaker
Circuit breaker name Compact NSX160
Compact NSX250
Compact NSX100
Poles description 3P
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Complementary
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Mounting mode Plug-in
[In] rated current 250 A
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
Main
Device short name Motor mechanism module with SDE adaptor
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Product or component type Motor mechanism
Device application Automatic spring charging
Range compatibility Compact NSX circuit breaker
Compact NSX DC circuit breaker
circuit breaker
Product compatibility PowerPact H-Frame
PowerPact J-Frame
[In] rated current 160 A
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
100 A
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
[Uc] control circuit voltage 208...277 V AC 60 Hz
220...240 V AC 50/60 Hz
Complementary
Control type Standard
Control signal type Impulse
Maintained
Mounting mode Fixed
Response time < 600 ms (opening)
< 80 ms (closing)
Maximum operating frequency 4 per minute
Maximum power consumption in VA 500 VA closing
500 VA opening
Provided equipment SDE adaptor
Locking options description Padlocking in OFF position
1 to 3 padlocks Ø 5 to Ø 8
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
2
May 21, 2020
Characteristics
Product data sheet
LV430841
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Range Compact
Product name Compact NSX
Device short name Compact NSX160N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3t
[In] rated current 125 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Utilisation category Category A
Breaking capacity 10 KA at 600 V AC 50/60 Hz conforming to UL 508
85 KA at 240 V AC 50/60 Hz conforming to UL 508
10 KA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 KA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 480 V AC 50/60 Hz conforming to UL 508
36 KA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 KA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 KA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N 50 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 KV
[Ics] rated service breaking capacity 10 KA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 KA at 525 V AC 50/60 Hz conforming to IEC 60947-2
36 KA at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 KA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 40000 Cycles
Electrical durability 10000 Cycles 440 V In/2 conforming to IEC 60947-2
15000 Cycles 690 V In/2 conforming to IEC 60947-2
20000 Cycles 440 V In conforming to IEC 60947-2
7500 Cycles 690 V In conforming to IEC 60947-2
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 35 Mm
Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating 125 A at 40 °C
Long time pick-up adjustment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
[tr] long-time delay adjustment range 120…400 S at 1.5 x In
15 S at 6 x Ir
Short-time pick-up adjustment type Isd Fixed
[Isd] short-time pick-up adjustment range 1250 A
Short-time delay adjustment type Fixed
2
Auxiliary contact composition Without
Local signalling Positive contact indication
Width 105 Mm
Height 161 Mm
Depth 86 Mm
Net weight 2.2 Kg
Environment
Standards EN/IEC 60947
UL 508
Product certifications EAC
CCC
Marine
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -55…85 °C
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
3
May 21, 2020
Characteristics
Product data sheet
LV431831
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Range Compact
Product name Compact NSX
Device short name Compact NSX250N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3t
[In] rated current 200 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Utilisation category Category A
Breaking capacity 85 KA at 240 V AC 50/60 Hz conforming to UL 508
10 KA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 KA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 480 V AC 50/60 Hz conforming to UL 508
36 KA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 KA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 KA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
15 KA at 600 V AC 50/60 Hz conforming to UL 508
Breaking capacity code N 50 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 KV
[Ics] rated service breaking capacity 10 KA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 KA at 525 V AC 50/60 Hz conforming to IEC 60947-2
36 KA at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 KA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 Cycles
Electrical durability 10000 Cycles 440 V In conforming to IEC 60947-2
10000 Cycles 690 V In/2 conforming to IEC 60947-2
20000 Cycles 440 V In/2 conforming to IEC 60947-2
5000 Cycles 690 V In conforming to IEC 60947-2
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 35 Mm
Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating 200 A at 40 °C
Long time pick-up adjustment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
[tr] long-time delay adjustment range 120…400 S at 1.5 x In
15 S at 6 x Ir
Short-time pick-up adjustment type Isd Adjustable
[Isd] short-time pick-up adjustment range 5...10 x In
Short-time delay adjustment type Fixed
2
Auxiliary contact composition Without
Local signalling Positive contact indication
Width 105 Mm
Height 161 Mm
Depth 86 Mm
Net weight 2.4 Kg
Environment
Standards EN/IEC 60947
UL 508
Product certifications CCC
EAC
Marine
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -55…85 °C
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
3
Product data sheet LV432538
Characteristics
Main
Product or component type Plug-in kit
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Accessory / separate part category Mounting accessory
Range compatibility Compact NSX circuit breaker
Compact NSX DC circuit breaker
Circuit breaker name Compact NSX630
Compact NSX400
Poles description 3P
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Complementary
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Mounting mode Plug-in
[In] rated current 630 A
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
Main
Device short name Motor mechanism module
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Product or component type Motor mechanism
Device application Automatic spring charging
Range compatibility Compact NSX circuit breaker
Compact NSX DC circuit breaker
circuit breaker
Product compatibility PowerPact L-Frame
[In] rated current 400 A
630 A
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
[Uc] control circuit voltage 208...277 V AC 60 Hz
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
220...240 V AC 50/60 Hz
Complementary
Control type Standard
Control signal type Impulse
Maintained
Mounting mode Fixed
Response time < 600 ms (opening)
< 80 ms (closing)
Maximum operating frequency 4 per minute
Maximum power consumption in VA 500 VA closing
500 VA opening
Locking options description Padlocking in OFF position
1 to 3 padlocks Ø 5 to Ø 8
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
Contractual warranty
Warranty 18 months
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Range Compact
Product name Compact NSX
Device short name Compact NSX400N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3t
[In] rated current 400 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Utilisation category Category A
Breaking capacity 85 KA at 240 V AC 50/60 Hz conforming to UL 508
22 KA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 KA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 KA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
30 KA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 KA at 600 V AC 50/60 Hz conforming to UL 508
50 KA at 480 V AC 50/60 Hz conforming to UL 508
50 KA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
42 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N 50 kA 415 V AC
Trip unit name Micrologic 2.3
Trip unit technology Electronic
Trip unit protection functions LSoI
Control type Toggle
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 KV
[Ics] rated service breaking capacity 11 KA at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 KA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 KA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 KA at 500 V AC 50/60 Hz conforming to IEC 60947-2
42 KA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 15000 Cycles
Electrical durability 12000 Cycles 440 V In/2 conforming to IEC 60947-2
3000 Cycles 690 V In conforming to IEC 60947-2
6000 Cycles 440 V In conforming to IEC 60947-2
6000 Cycles 690 V In/2 conforming to IEC 60947-2
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 45 Mm
Protection type L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
Trip unit rating 400 A at 40 °C
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.9...1 x Io
Long time delay adjustment type Fixed
[tr] long-time delay adjustment range 16 S at 6 x Ir
Thermal memory 20 minutes before and after tripping
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5...10 x Ir
2
Short-time delay adjustment type Fixed
Instantaneous pick-up adjustment type Ii Fixed
Instantaneous pick-up adjustment range 4800 A
Auxiliary contact composition Without
Local signalling LED 90 % Ir
LED 105 % Ir
LED ready
Width 140 Mm
Height 255 Mm
Depth 110 Mm
Net weight 6.05 Kg
Environment
Standards EN/IEC 60947
UL 508
Product certifications EAC
CCC
Marine
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -55…85 °C
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
Contractual warranty
Warranty 18 months
3
May 21, 2020
Characteristics
Product data sheet
LV432893
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Range Compact
Product name Compact NSX
Device short name Compact NSX630N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3t
[In] rated current 630 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Utilisation category Category A
Breaking capacity 85 KA at 240 V AC 50/60 Hz conforming to UL 508
22 KA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 KA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 KA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
30 KA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 KA at 600 V AC 50/60 Hz conforming to UL 508
50 KA at 480 V AC 50/60 Hz conforming to UL 508
50 KA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
42 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N 50 kA 415 V AC
Trip unit name Micrologic 2.3
Trip unit technology Electronic
Trip unit protection functions LSoI
Control type Toggle
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 KV
[Ics] rated service breaking capacity 11 KA at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 KA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 KA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 KA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 KA at 500 V AC 50/60 Hz conforming to IEC 60947-2
42 KA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 15000 Cycles
Electrical durability 6000 Cycles 690 V In/2 conforming to IEC 60947-2
2000 Cycles 690 V In conforming to IEC 60947-2
4000 Cycles 440 V In conforming to IEC 60947-2
8000 Cycles 440 V In/2 conforming to IEC 60947-2
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 45 Mm
Protection type L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
Trip unit rating 630 A at 40 °C
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.9...1 x Io
Long time delay adjustment type Fixed
[tr] long-time delay adjustment range 16 S at 6 x Ir
Thermal memory 20 minutes before and after tripping
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5...10 x Ir
2
Short-time delay adjustment type Fixed
Instantaneous pick-up adjustment type Ii Fixed
Instantaneous pick-up adjustment range 6900 A
Auxiliary contact composition Without
Local signalling LED ready
LED 90 % Ir
LED 105 % Ir
Width 140 Mm
Height 255 Mm
Depth 110 Mm
Net weight 6.2 Kg
Environment
Standards EN/IEC 60947
UL 508
Product certifications CCC
EAC
Marine
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -55…85 °C
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
3
Product data sheet XB5AA35
Characteristics black flush complete pushbutton Ø22 spring
return 1NO+1NC unmarked
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony XB5
Product or component type Push-button
Device short name XB5
Bezel material Plastic
Dark grey plastic
Head type Standard
Fixing collar material Plastic
Mounting diameter 22 mm
Sale per indivisible quantity 1
Shape of signaling unit head Round
Type of operator spring return
Operator profile Green flush, unmarked
Contacts type and composition 1 NO + 1 NC
Contact operation Slow-break
Connections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1
Complementary
Height 42 mm
Width 30 mm
Depth 52 mm
Terminals description ISO n°1 (13-14)NO
(21-22)NC
Resistance to high pressure washer 7000000 Pa at 55 °C, distance : 0.1 m
Contacts usage Standard contacts
Positive opening With conforming to EN/IEC 60947-5-1 appendix K
Operating travel 1.5 mm (NC changing electrical state)
2.6 mm (NO changing electrical state)
4.3 mm (total travel)
Apr 5, 2020
1
Operating force 3.5 N NC changing electrical state
3.8 N NO changing electrical state
Mechanical durability 10000000 cycles
Tightening torque 0.8…1.2 N.m conforming to EN 60947-1
Shape of screw head Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Contacts material Silver alloy (Ag/Ni)
Short-circuit protection 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal 10 A conforming to EN/IEC 60947-5-1
current
[Ui] rated insulation voltage 600 V (pollution degree 3) conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage EN/IEC 60947-1 6 kV
[Ie] rated operational current 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Electrical durability 1000000 cycles AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1: appendix C
1000000 cycles AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1: appendix C
1000000 cycles AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1: appendix C
1000000 cycles DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to
EN/IEC 60947-5-1: appendix C
1000000 cycles DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/
IEC 60947-5-1: appendix C
Electrical reliability Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to EN/IEC 60947-5-4
Device presentation Complete product
Device presentation Yes
GCR BRIDGE XB5AACUST04
Compatibility code XB5
Environment
Protective treatment TH
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -40…70 °C
Overvoltage category Class II conforming to IEC 60536
IP degree of protection IP66 conforming to IEC 60529
IP67
IP69
IP69K
NEMA degree of protection NEMA 13
NEMA 4X
IK degree of protection IK03 conforming to IEC 50102
Standards EN/IEC 60947-1
EN/IEC 60947-5-1
CSA C22.2 No 14
EN/IEC 60947-5-4
UL 508
JIS C8201-5-1
JIS C8201-1
Product certifications RINA
UL listed
BV
CSA
GL
DNV
LROS (Lloyds register of shipping)
2
Vibration resistance 5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
Shock resistance 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Contractual warranty
Warranty 18 months
3
Product data sheet XB5AA41
Characteristics red projecting complete push-button Diam22
spring return 1NO unmarked
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony XB5
Product or component type Push-button
Device short name XB5
Bezel material Plastic
Dark grey plastic
Head type Standard
Fixing collar material Plastic
Mounting diameter 22 mm
Sale per indivisible quantity 1
Complementary
Mechanical durability 10000000 cycles
Device presentation Complete product
Device presentation Yes
GCR BRIDGE XB5AACUST03
Compatibility code XB5
Environment
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -40…70 °C
IP degree of protection IP67
IP69
IP69K
IP66
IK degree of protection IK03
Offer Sustainability
Sustainable offer status Green Premium product
Apr 5, 2020
1
REACh Regulation REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
2
Data sheet 6AV2124-0MC01-0AX0
SIMATIC HMI TP1200 Comfort, Comfort Panel, Touch operation, 12"
widescreen TFT display, 16 million colors, PROFINET interface,
MPI/PROFIBUS DP interface, 12 MB configuration memory,
Windows CE 6.0 (Microsoft Support included Security updates
discontinued) configurable from WinCC Comfort V11
General information
Product type designation TP1200 Comfort
Display
Design of display TFT
Screen diagonal 12.1 in
Display width 261.1 mm
Display height 163.2 mm
Number of colors 16 777 216
Resolution (pixels)
● Horizontal image resolution 1 280 Pixel
● Vertical image resolution 800 Pixel
Backlighting
● MTBF backlighting (at 25 °C) 80 000 h
● Backlight dimmable Yes; 0-100 %
Control elements
Keyboard fonts
● Function keys
— Number of function keys 0
Installation type/mounting
Mounting position vertical
Mounting in portrait format possible Yes
Mounting in landscape format possible Yes
maximum permissible angle of inclination without 35°
external ventilation
Supply voltage
Type of supply voltage DC
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 0.85 A
Starting current inrush I²t 0.5 A²·s
Power
Active power input, typ. 20 W
Processor
Processor type X86
Memory
Flash Yes
RAM Yes
Memory available for user data 12 Mbyte
Type of output
Info LED No
Power LED No
Error LED No
Acoustics
Time of day
Clock
● Hardware clock (real-time) Yes
● Software clock Yes
● retentive Yes; Back-up duration typically 6 weeks
● synchronizable Yes
Interfaces
Number of industrial Ethernet interfaces 1; 2 ports (switch)
Number of RS 485 interfaces 1; RS 422 / 485 combined
Number of RS 422 interfaces 0; together with RS 485
Number of RS 232 interfaces 0
Number of USB interfaces 2; USB 2.0
● USB Mini B 1; 5-pole
Number of 20 mA interfaces (TTY) 0
Number of parallel interfaces 0
Number of other interfaces 0
Number of SD card slots 2
With software interfaces No
Industrial Ethernet
● Industrial Ethernet status LED 2
● Number of ports of the integrated switch 2
Protocols
PROFINET Yes
Supports protocol for PROFINET IO Yes
IRT Yes; As of WinCC V12
PROFIBUS Yes
MPI Yes
Protocols (Ethernet)
● TCP/IP Yes
● DHCP Yes
● SNMP Yes
● DCP Yes
● LLDP Yes
WEB characteristics
● HTTP Yes
● HTTPS Yes
● HTML Yes
● XML Yes
● CSS Yes
EMC
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes
● Limit class B, for use in residential areas No
Operating systems
proprietary No
pre-installed operating system
● Windows CE Yes
Configuration
Message indicator Yes
Alarm system (incl. buffer and acknowledgment) Yes
Process value display (output) Yes
Process value default (input) possible Yes
Recipe management Yes
Configuration software
● STEP 7 Basic (TIA Portal) No
● STEP 7 Professional (TIA Portal) No
● WinCC flexible Compact No
● WinCC flexible Standard No
● WinCC flexible Advanced No
● WinCC Basic (TIA Portal) No
● WinCC Comfort (TIA Portal) Yes; from V11
● WinCC Advanced (TIA Portal) Yes; from V11
● WinCC Professional (TIA Portal) Yes; from V11
Languages
Peripherals/Options
Printer Yes
SIMATIC HMI MM memory card: Multi Media Card Yes; Up to 128 MB
SIMATIC HMI SD memory card: Secure Digital Yes; Up to 2 GB
memory card
SIMATIC HMI CF memory card Compact Flash Card No
USB memory Yes
SIMATIC IPC USB Flashdrive (USB stick) Yes; Up to 16 GB
SIMATIC HMI USB stick Yes; Up to 8 GB
Network camera Yes
Dimensions
Width of the housing front 330 mm
Height of housing front 241 mm
Mounting cutout, width 310 mm
Mounting cutout, height 221 mm
Overall depth 65 mm
Weights
Weight without packaging 2.8 kg
Weight incl. packaging 3.5 kg
General information
Product type designation DI 16x24VDC ST
Firmware version V1.1
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color identification CC00
plate
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V13 SP1
version
● STEP 7 configurable/integrated as of version V5.5 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● DI Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 90 mA
Encoder supply
Short-circuit protection No
24 V encoder supply
● 24 V No
● Short-circuit protection No
Power loss
Power loss, typ. 1.7 W
Address area
Address space per module
● Address space per module, max. 2 byte; + 2 bytes for QI information
Hardware configuration
Automatic encoding
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0 + external terminals
● 3-wire connection BU type A0 + external terminals
● 4-wire connection BU type A0 + external terminals
Digital inputs
Number of digital inputs 16
Source/sink input P-reading
Input characteristic curve in accordance with IEC Yes
61131, type 1
Input characteristic curve in accordance with IEC No
61131, type 2
Input characteristic curve in accordance with IEC Yes
61131, type 3
Pulse extension No
Input voltage
● Rated value (DC) 24 V
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire 1.5 mA
sensor), max.
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Diagnostic information readable Yes
● Monitoring the supply voltage Yes
— parameterizable Yes
● Monitoring of encoder power supply No
● Wire-break Yes; Module-by-module, optional protective circuit for preventing
wire-break diagnostics in the case of simple encoder contacts: 25
kOhm to 45 kOhm
● Short-circuit No
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics No
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of No
the electronics
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 28 g
General information
Product type designation DQ 16x24 VDC/0.5 A ST
Firmware version V1.0
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color identification CC00
plate
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V11 SP2 / V13
version
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● DQ Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 60 mA; without load
Output voltage
Rated value (DC) 24 V
Power loss
Power loss, typ. 1 W
Address area
Address space per module
● Address space per module, max. 2 byte
Hardware configuration
Automatic encoding
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0 + Potential isolation module
● 3-wire connection BU type A0 + Potential isolation module
● 4-wire connection BU type A0 + Potential isolation module
Digital outputs
Type of digital output Source output (PNP, current-sourcing)
Number of digital outputs 16
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection Yes
● Response threshold, typ. 0.7 to 1.3 A
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of No
the electronics
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C
● vertical installation, min. 0 °C; in all other mounting positions
● vertical installation, max. 50 °C; in all other mounting positions
Altitude during operation relating to sea level
● Ambient air temperature-barometric pressure- On request: Negative ambient temperature down to -30 °C
altitude (without condensation), installation altitudes between 2 000 m and
5 000 m
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 28 g
General information
Product type designation AI 4xI 2-/4-wire ST
Firmware version V1.1
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification CC03
plate
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Measuring range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V11 SP2 / V13
version
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 37 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ. 0.85 W; Without encoder supply voltage
Address area
Address space per module
● Address space per module, max. 8 byte; + 1 byte for QI information
Analog inputs
Number of analog inputs 4; Differential inputs
● For current measurement 4
permissible input current for current input (destruction 50 mA
limit), max.
Cycle time (all channels), min. Sum of the basic conversion times and additional processing
times (depending on the parameterization of the active channels)
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage in 2-wire operation
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 100 Ω
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage in 2-wire operation
Cable length
● shielded, max. 1 000 m
Encoder
Connection of signal encoders
● for voltage measurement No
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 50 dB; Applies to up to ±5 V overvoltage in other channels
Repeat accuracy in steady state at 25 °C (relative to 0.05 %
input range), (+/-)
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of 70 dB
interference < rated value of input range), min.
● Common mode voltage, max. 10 V
● Common mode interference, min. 90 dB
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm No
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; at 4 to 20 mA
● Short-circuit Yes; 2-wire mode: Short-circuit of the encoder supply to ground or
of an input to the encoder supply
Potential separation
Potential separation channels
● between the channels Yes; channel group-specific between 2-wire current input group
and 4-wire voltage input group
● between the channels and backplane bus Yes
● between the channels and the power supply of Yes; only for 4-wire transducer
the electronics
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 31 g
General information
Product type designation CPU 1214C DC/DC/relay
Firmware version V4.2
Engineering with
● Programming package STEP 7 V14 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 500 mA; CPU only
Current consumption, max. 1 500 mA; CPU with all expansion modules
Output current
for backplane bus (5 V DC), max. 1 600 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V L+ minus 4 V DC min.
Power loss
Power loss, typ. 12 W
Memory
Work memory
● integrated 100 kbyte
● expandable No
Load memory
● integrated 4 Mbyte
● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● without battery Yes
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Address area
Process image
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. ±60 s/month at 25 °C
Digital inputs
Number of digital inputs 14; Integrated
● of which inputs usable for technological 6; HSC (High Speed Counting)
functions
Source/sink input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 14
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80
kHz & 3 @ 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; for technological functions: No
Digital outputs
Number of digital outputs 10; Relays
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
— Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Encoder
Connectable encoders
● 2-wire sensor Yes
1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Interface types
● Number of ports 1
● integrated switch No
Protocols
● PROFINET IO Controller Yes
Protocols
Supports protocol for PROFINET IO Yes
Communication functions
S7 communication
● supported Yes
● as server Yes
● as client Yes
● User data per job, max. See online help (S7 communication, user data size)
Number of connections
● overall 16; dynamically
Interrupts/diagnostics/status information
Integrated Functions
Number of counters 6
Counting frequency (counter) max. 100 kHz
Frequency measurement Yes
controlled positioning Yes
Number of position-controlled positioning axes, max. 8
Number of positioning axes via pulse-direction Up to 4 with SB 1222
interface
PID controller Yes
Number of alarm inputs 4
Potential separation
Potential separation digital inputs
● Potential separation digital inputs 500V AC for 1 minute
● between the channels, in groups of 1
Potential separation digital outputs
● Potential separation digital outputs Relays
● between the channels No
● between the channels, in groups of 2
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes
static electricity acc. to IEC 61000-4-2
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-4
● Interference immunity on signal cables acc. to Yes
IEC 61000-4-4
Interference immunity against voltage surge
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-5
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C; Number of simultaneously activated inputs or outputs 7 or
5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or
10 at 55 °C horizontal or 45 °C vertical
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Altitude during operation relating to sea level
● Installation altitude, min. -1 000 m
● Installation altitude, max. 2 000 m
Relative humidity
● Operation, max. 95 %; no condensation
Vibrations
● Vibration resistance during operation acc. to 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
IEC 60068-2-6
● Operation, tested according to IEC 60068-2-6 Yes
Shock testing
Configuration
Programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Know-how protection
● User program protection/password protection Yes
● Copy protection Yes
● Block protection Yes
Access protection
● Protection level: Write protection Yes
● Protection level: Read/write protection Yes
● Protection level: Complete protection Yes
Cycle time monitoring
● adjustable Yes
Dimensions
Width 110 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 435 g
Main
Range PowerLogic
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Product name PowerLogic PM5000
Device short name PM5330
Product or component type Power meter
Complementary
Power quality analysis Up to the 31st harmonic
Device application Power monitoring
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Multi-tariff
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Type of measurement Current
Voltage
Frequency
Power factor
Energy
Active and reactive power
[Us] rated supply voltage 100...415 V AC 45...65 Hz
125...250 V DC
Network frequency 50 Hz
60 Hz
[In] rated current 1 A
5 A
Poles description 3P + N
3P
1P + N
Maximum power consumption in VA 10 VA at 415 V
Ride-through time 80 Ms 120 V AC typical
100 Ms 230 V AC typical
100 Ms 415 V AC typical
Display type Backlit LCD
Display resolution 128 x 128 pixels
Sampling rate 64 samples/cycle
Measurement current 10…9000 MA
Analogue input type Voltage (impedance 5 MOhm)
Current (impedance 0.3 MOhm)
Measurement voltage 35…690 V AC 45...65 Hz between phases
20…400 V AC 45...65 Hz between phase and neutral
Frequency measurement range 45…65 Hz
Number of inputs 2 digital
Environment
Electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
IP degree of protection IP52 front: conforming to IEC 60529
IP30 body: conforming to IEC 60529
Relative humidity 5…95 % at 50 °C
Pollution degree 2
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -40…85 °C
Operating altitude 2000 m
Offer Sustainability
Sustainable offer status Green Premium product
REACh free of SVHC Yes
EU RoHS Directive
Compliant EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
2
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
3
Product data sheet RXM4AB1BD
Characteristics
Main
Range of product Zelio Relay
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Series name Miniature
Product or component type Plug-in relay
Device short name RXM
Contacts type and composition 4 C/O
[Uc] control circuit voltage 24 V DC
[Ithe] conventional enclosed thermal current 6 A at -40…55 °C
Status LED Without
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Control type Lockable test button
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Utilisation coefficient 20 %
Complementary
Shape of pin Flat
[Ui] rated insulation voltage 250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
[Uimp] rated impulse withstand voltage 2.5 KV during 1.2/50 µs
Contacts material AgNi
[Ie] rated operational current 3 A at 28 V (DC) NC conforming to IEC
3 A at 250 V (AC) NC conforming to IEC
6 A at 28 V (DC) NO conforming to IEC
6 A at 250 V (AC) NO conforming to IEC
6 A at 277 V (AC) conforming to UL
8 A at 30 V (DC) conforming to UL
Maximum switching voltage 250 V conforming to IEC
Load current 6 A at 250 V AC
6 A at 28 V DC
Maximum switching capacity 1500 VA/168 W
Minimum switching capacity 170 mW at 10 mA, 17 V
Operating rate <= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Mechanical durability 10000000 Cycles
Electrical durability 100000 Cycles for resistive load
Average coil consumption 0.9 W
Drop-out voltage threshold >= 0.1 Uc
Operating time 20 ms
Reset time 20 Ms
Average resistance 650 Ohm at 20 °C +/- 10 %
Rated operational voltage limits 19.2...26.4 V DC
Safety reliability data B10d = 100000
Environment
Dielectric strength 1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with reinforced
2000 V AC between poles with basic
Product certifications UL
CE
GOST
REACH
CSA
RoHS
Lloyd's
Standards UL 508
EN/IEC 61810-1
CSA C22.2 No 14
Ambient air temperature for storage -40…85 °C
Ambient air temperature for operation -40…55 °C
Vibration resistance 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
IP degree of protection IP40 conforming to EN/IEC 60529
Shock resistance 10 gn for in operation
30 gn for not operating
Pollution degree 2
Offer Sustainability
Sustainable offer status Green Premium product
REACh free of SVHC Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Decla-
ration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile No need of specific recycling operations
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
2
Product data sheet XB5AVG3
Characteristics
Main
Range of product Harmony XB5
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Product or component type Pilot light
Device short name XB5
Bezel material Dark grey plastic
Fixing collar material Plastic
Head type Standard
Mounting diameter 22 Mm
Sale per indivisible quantity 1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Shape of signaling unit head Round
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Cap/operator or lens colour Green
Operator additional information With plain lens
Light source Protected LED
Bulb base Integral LED
Light source colour Green
[Us] rated supply voltage 110...120 V AC at 50/60 Hz
Device presentation Complete product
Complementary
Height 42 Mm
Width 30 Mm
Depth 54 Mm
Terminals description ISO n°1 (X1-X2)PL
Net weight 0.038 Kg
Resistance to high pressure washer 7000000 Pa at 55 °C, distance : 0.1 m
Connections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming-
to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming-
to EN/IEC 60947-1
[Ui] rated insulation voltage 250 V (pollution degree 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage 4 KV EN 60947-1
Signalling type Steady
GCR BRIDGE XB5AVCUST04
Compatibility code XB5
Supply voltage limits 100…132 V AC
Current consumption 14 mA
Service life 100000 H at rated voltage and 25 °C
Surge withstand 1 KV conforming to IEC 61000-4-5
Apr 5, 2020
1
Environment
Protective treatment TH
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -40…70 °C
Overvoltage category Class II conforming to IEC 60536
IP degree of protection IP66 conforming to IEC 60529
IP67 conforming to IEC 60529
IP69 conforming to IEC 60529
IP69K conforming to ISO 20653
NEMA degree of protection NEMA 13
NEMA 4X
IK degree of protection IK05 conforming to IEC 50102
Standards UL 508
EN/IEC 60947-1
CSA C22.2 No 14
JIS C8201-5-1
EN/IEC 60947-5-1
EN/IEC 60947-5-4
JIS C8201-1
Product certifications CSA
UL listed
Vibration resistance 5 gn (f= 12…500 Hz) conforming to IEC 60068-2-6
Shock resistance 50 gn (duration = 18 ms) for half sine wave acceleration conforming-
to IEC 60068-2-27
30 gn (duration = 11 ms) for half sine wave acceleration conforming-
to IEC 60068-2-27
Resistance to fast transients 2 KV conforming to IEC 61000-4-4
Resistance to electromagnetic fields 10 V/M conforming to IEC 61000-4-3
Electromagnetic compatibility Electrostatic discharge - test level: 6 kV (on contact (on metal parts)) conforming-
to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV (in free air (in insulating parts)) conform-
ing to IEC 61000-4-2
Electromagnetic emission class B conforming to IEC 55011
Resistance to electrostatic discharge 6 KV on contact (on metal parts) conforming to IEC 61000-4-2
8 KV in free air (in insulating parts) conforming to IEC 61000-4-2
Electromagnetic emission Class B conforming to IEC 55011
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Decla-
ration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
2
Product data sheet XB5AVG4
Characteristics
Main
Range of product Harmony XB5
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Product or component type Pilot light
Device short name XB5
Bezel material Dark grey plastic
Fixing collar material Plastic
Head type Standard
Mounting diameter 22 Mm
Sale per indivisible quantity 1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Shape of signaling unit head Round
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Cap/operator or lens colour Red
Operator additional information With plain lens
Light source Protected LED
Bulb base Integral LED
Light source colour Red
[Us] rated supply voltage 110...120 V AC at 50/60 Hz
Device presentation Complete product
Complementary
Height 42 Mm
Width 30 Mm
Depth 54 Mm
Terminals description ISO n°1 (X1-X2)PL
Net weight 0.038 Kg
Resistance to high pressure washer 7000000 Pa at 55 °C, distance : 0.1 m
Connections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming-
to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming-
to EN/IEC 60947-1
[Ui] rated insulation voltage 250 V (pollution degree 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage EN 60947-1 4 kV
Signalling type Steady
GCR BRIDGE XB5AVCUST04
Compatibility code XB5
Supply voltage limits 100…132 V AC
Current consumption 14 mA
Service life 100000 H at rated voltage and 25 °C
Surge withstand 1 KV conforming to IEC 61000-4-5
Apr 5, 2020
1
Environment
Protective treatment TH
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -40…70 °C
Overvoltage category Class II conforming to IEC 60536
IP degree of protection IP66 conforming to IEC 60529
IP67 conforming to IEC 60529
IP69 conforming to IEC 60529
IP69K conforming to ISO 20653
NEMA degree of protection NEMA 13
NEMA 4X
IK degree of protection IK05 conforming to IEC 50102
Standards EN/IEC 60947-1
EN/IEC 60947-5-1
UL 508
EN/IEC 60947-5-4
JIS C8201-5-1
CSA C22.2 No 14
JIS C8201-1
Product certifications UL listed
CSA
Vibration resistance 5 gn (f= 12…500 Hz) conforming to IEC 60068-2-6
Shock resistance 50 gn (duration = 18 ms) for half sine wave acceleration conforming-
to IEC 60068-2-27
30 gn (duration = 11 ms) for half sine wave acceleration conforming-
to IEC 60068-2-27
Resistance to fast transients 2 KV conforming to IEC 61000-4-4
Resistance to electromagnetic fields 10 V/M conforming to IEC 61000-4-3
Electromagnetic compatibility Electrostatic discharge - test level: 6 kV (on contact (on metal parts)) conforming-
to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV (in free air (in insulating parts)) conform-
ing to IEC 61000-4-2
Electromagnetic emission class B conforming to IEC 55011
Resistance to electrostatic discharge 6 KV on contact (on metal parts) conforming to IEC 61000-4-2
8 KV in free air (in insulating parts) conforming to IEC 61000-4-2
Electromagnetic emission Class B conforming to IEC 55011
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Decla-
ration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
2
Product data sheet XB5AVG5
Characteristics
Main
Range of product Harmony XB5
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Product or component type Pilot light
Device short name XB5
Bezel material Dark grey plastic
Fixing collar material Plastic
Head type Standard
Mounting diameter 22 Mm
Sale per indivisible quantity 1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Shape of signaling unit head Round
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Cap/operator or lens colour Orange
Operator additional information With plain lens
Light source Protected LED
Bulb base Integral LED
Light source colour Orange
[Us] rated supply voltage 110...120 V AC at 50/60 Hz
Device presentation Complete product
Complementary
Height 42 Mm
Width 30 Mm
Depth 54 Mm
Terminals description ISO n°1 (X1-X2)PL
Net weight 0.038 Kg
Resistance to high pressure washer 7000000 Pa at 55 °C, distance : 0.1 m
Connections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming-
to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming-
to EN/IEC 60947-1
[Ui] rated insulation voltage 250 V (pollution degree 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage 4 KV EN 60947-1
Signalling type Steady
GCR BRIDGE XB5AVCUST04
Compatibility code XB5
Supply voltage limits 100…132 V AC
Current consumption 14 mA
Service life 100000 H at rated voltage and 25 °C
Surge withstand 1 KV conforming to IEC 61000-4-5
Apr 5, 2020
1
Environment
Protective treatment TH
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -40…70 °C
Overvoltage category Class II conforming to IEC 60536
IP degree of protection IP66 conforming to IEC 60529
IP67 conforming to IEC 60529
IP69 conforming to IEC 60529
IP69K conforming to ISO 20653
NEMA degree of protection NEMA 13
NEMA 4X
IK degree of protection IK05 conforming to IEC 50102
Standards CSA C22.2 No 14
UL 508
EN/IEC 60947-5-1
JIS C8201-5-1
EN/IEC 60947-1
EN/IEC 60947-5-4
JIS C8201-1
Product certifications CSA
UL listed
Vibration resistance 5 gn (f= 12…500 Hz) conforming to IEC 60068-2-6
Shock resistance 50 gn (duration = 18 ms) for half sine wave acceleration conforming-
to IEC 60068-2-27
30 gn (duration = 11 ms) for half sine wave acceleration conforming-
to IEC 60068-2-27
Resistance to fast transients 2 KV conforming to IEC 61000-4-4
Resistance to electromagnetic fields 10 V/M conforming to IEC 61000-4-3
Electromagnetic compatibility Electrostatic discharge - test level: 6 kV (on contact (on metal parts)) conforming-
to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV (in free air (in insulating parts)) conform-
ing to IEC 61000-4-2
Electromagnetic emission class B conforming to IEC 55011
Resistance to electrostatic discharge 6 KV on contact (on metal parts) conforming to IEC 61000-4-2
8 KV in free air (in insulating parts) conforming to IEC 61000-4-2
Electromagnetic emission Class B conforming to IEC 55011
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Decla-
ration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
2
PANEL ATS 1600A
No Description Qty Satuan Spesifikasi
BOX
1 BOX PANEL H1000 X W600 X D500 2 UNIT LOCAL
INCOMING
2 MCCB 3P 1600A 70kA NS1600H Microligic 2.0 1 PCS SCHNEIDER
3 CHANGE OVER SWITCH 1600A 1 PCS SOCOMEC
4 CURRENT TRANSFORMER 1600/5A 6 PCS HOWIG
5 RELAY CONTROL 1 LOT OMRON
6 TIMER 220VAC 2 PCS OMRON
7 DIGITAL POWER METSEPM2120 2 PCS SCHNEIDER
8 TOMBOL ON 2 PCS HOWIG
9 TOMBOL OFF 2 PCS HOWIG
10 SELECTOR M-O-A 2 PCS HOWIG
11 PILOT LAMP 11 PCS HOWIG
12 MCB CONTROL 10 PCS SCHNEIDER
13 LAMPU 2 PCS PHILLIPS
14 LIMIT SWITCH 2 PCS -
15 TERMINAL CABLE 1 LOT TAB
16 BUSBAR 1 LOT Ex-Japan
+ SUPPORT 1 LOT HOWIG
17 WIRING & ACC 1 LOT ASP
MCC FIX TYPE
No Description Qty Satuan Spesifikasi
BOX
1 BOX PANEL H800 X W600 X D500 3 Unit Local
BREAKER
2 MCCB 3P 160-400A 36kA NSX400F Micrologic 2.0 6 Pcs Schneider
3 MCCB 3P 100-250A 36kA NSX250F Micrologic 2.0 2 Pcs Schneider
ACCSESORIS BREAKER
4 Extend Rotari Handle (standart type) 8 pcs Schneider
5 OF/SDE/SDV 8 Pcs Schneider
6 DIGITAL POWER METSEPM2120 1 Pcs Schneider
7 CT 1600/5A 3 Pcs Howig
8 PILOT LAMP 19 Pcs Howig
9 TERMINAL CABLE 1 Lot TAB
10 CABLE POWER 1 Lot Jembo
11 BUSBAR 1 Lot Ex-Japan
+ SUPPORT BUSBAR 1 Lot Howig
12 WIRING & ACC 1 Lot SI
Project : Pembelian Material EDG Automation & Jasa Instalasi EDG Automation & Modifikasi Panel Distribusi