Professional Documents
Culture Documents
40.0-1 Cat Generator Paralleling Switchgear: Sheet 001
40.0-1 Cat Generator Paralleling Switchgear: Sheet 001
0-1
September 2011
Sheet 40 001
Paralleling Switchgear
Cat Generator Contents
Cat® Generator Paralleling Switchgear
Introduction
22
23
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.0-2
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.0-4
24
Cat Switchgear Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.1-1
Standard and Custom Configurable Products . . . . . . . . . . . . . . . . . . . 40.1-2
Cat Switchgear Control Technology Features. . . . . . . . . . . . . . . . . . . . 40.1-3 25
XLM Switchgear
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.2-1 26
Standard Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.2-2
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.2-3
Technical Data—XLM One-Line Diagrams . . . . . . . . . . . . . . . . . . . . . . 40.2-4
27
Functional Sequences of Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . 40.2-10
EGP Switchgear 28
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.3-1
Standard Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.3-2 29
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.3-3
Technical Data—EGP One-Line Diagrams . . . . . . . . . . . . . . . . . . . . . . . 40.3-4
Functional Sequences of Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . 40.3-12
30
Medium Voltage Systems
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.4-1 31
XLM Medium Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.4-4
EGP Medium Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.4-8 32
Custom Systems
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.5-1
Technical Data—One-Line Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 40.5-2
33
Specifications
See Eaton’s Product Specification Guide, available on CD or on the Web. 34
CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010
Low Voltage XLM 35
UL 1558 Switchgear . . . . . . . . . . . . . . . . Section 16426E Section 26 23 13.11
Low Voltage XLM
UL 891 Switchboard . . . . . . . . . . . . . . . . Section 16429E Section 26 24 13.31 36
Medium Voltage XLM
Metal-Clad Switchgear . . . . . . . . . . . . . . Section 16346E Section 26 13 26.13 37
Low Voltage EGP
UL 1558 Switchgear . . . . . . . . . . . . . . . . Section 16426G Section 26 23 13.13
Low Voltage EGP 38
UL 891 Switchboard . . . . . . . . . . . . . . . . Section 16429G Section 26 24 13.33
Medium Voltage EGP
Metal-Clad Switchgear . . . . . . . . . . . . . . Section 16346G Section 26 13 26.16 39
40
41
42
43
22 Introduction Cat Switchgear combines the proven Reliable, flexible and powerful.
low voltage Magnum DS power circuit Cat Switchgear is designed with the
breaker and Magnum Switchgear with most critical power needs in mind:
General Description Cat Switchgear control technology.
23 Cat® Generator Paralleling Switchgear Cat controls technology is for optimal ■ Data center/data processing
is a product developed through a joint power generation and electrical ■ Healthcare
venture between Caterpillar and Eaton distribution system performance. ■ Critical industrial/chemical
24 Corporation. Caterpillar, an industry It provides advanced, industry- processes
leader in electric generator sets, and leading, microprocessor-based ■ Distributed generation/cogeneration
Eaton, an industry leader in Low and engine generator set control
25 Medium Voltage Switchgear have ■ Water/wastewater treatment
provided exclusively in Cat Switch-
combined forces to create Cat gear. Medium voltage systems ■ Government/military
Generator Paralleling Switchgear... combine VCP-W breakers and VacClad ■ Banking/credit card processing
26 the most reliable and feature rich Metal-Clad switchgear with the same ■ Landfill gas power
product available in the market today! proven generator control technology.
Cat Switchgear Features
27 Cat Switchgear has been designed
Applications
to integrate hand-in-glove with ■ Built-in redundancy
Caterpillar’s on-package, microproces- ■ Emergency/legally required ■ Reliability
28 sor-based engine control. Exclusively standby systems
■ Touchscreen interface
from your Caterpillar dealer, you can ■ Optional standby backup systems
now get the market’s best efficiency, ■ Simple, intuitive operation
■ Distributed generation
29 reliability and dependability all in ■ Advanced communications
■ Peak shaving capabilities
one package.
■ Prime power ■ Integrated digital technology
30 ■ Advanced generator control and
protection
■ Detailed engine and electrical reports
31 ■ Best-in-class footprint
32
33
34
35
36
37
38
39
40
XLM Medium Voltage
41
42
43
Standards
Low Voltage Cat Switchgear conforms
22
to the following applicable standards:
■ NEMA® Standard SG-5 23
■ CSA®
■ ANSI C37.20.1 24
■ ANSI C37.51
■ UL® Standard 1558
■ NFPA 110, NFPA 99 and NFPA 70 25
The switchgear uses Magnum DS
Breakers that are designed to NEMA 26
Standard SG-3; ANSI Standards
C37.13, C37.16, C37.17 and UL 1066.
Optional switchboard construction 27
is available that is built to UL Standard
891. These switchboards use Magnum
SB Breakers for generator mains, 28
utility mains and electrically operated
feeders, and molded-case breakers for Overview
non-switched feeders. 29
Medium Voltage Cat Switchgear
conforms to the following applicable 30
standards:
■ NEMA SG-5
■ ANSI/IEEE C37.20.2
31
■ CSA-C22.2 No. 31-M89
■ EEMAC G8-3.2. 32
■ NFPA 70, 99, 110
42
43
40
41
42
43
Paralleling: The procedure of connect- Station Battery: A power supply Utility Protection: A collection of
ing two or more generators, or other used for control of switchgear. protective relays or a multifunction 22
power sources, of the same phase, relay required by the utility to detect
Synchronizer: A device that will
voltage and frequency characteristics abnormal conditions and open the
synchronize an on-coming electric
supplying the same load.
generator set with the bus or another
utility breaker. 23
Peak Shaving: Process by which electric generator set, and allows XLM Switchgear (Emergency
utility customers minimize peak multiple power sources to be Transfer [Xfer] and Load Management
demand utility charges or exports connected in parallel. Switchgear): Parallels multiple
24
power to the utility grid. engine/gensets and the utility to serve
Synchroscope: An instrument that
downstream loads. Typically does
Prime Power Application: Prime provides a visual indication of proper
not include downstream ATS units. 25
Power is when the genset is the only time for closing of the breaker when
power source. synchronizing generators to connect XLMT Switchgear: Same as XLM
Processor: A specially configured
them in parallel with another source. except with a controlled generator 26
bus tie breaker between the utility
logic controller with appropriate input- TFT (Thin Film Transistor): A type
bus and the engine genset bus.
output capability and programming. of touchscreen display technology
used in HMI devices that offers high 27
SAW (Surface Acoustic Wave):
levels of brightness and clarity.
A premium touchscreen sensing
technology that offers maximum 28
protection from wear or contaminants.
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
(Closed Transition)
Listings
Parallel Multiple
Peak Shaving
24
Parallel With
Load Shed/
Application
Emergency
(Standby)
Soft Load
Load Add
Switches
Standby
Gensets
Transfer
Export
Utility
25
Transfer and Load Management Paralleling Switchgear (XLM)
40.2 208–600V UL 1558 ■ ■ ■ ■ ■ ■ ■ ■ XLM product is used when genera- 26
G UL 891 tors will be paralleled with a utility
(even if utility breaker is not located
in the same line-up as generator
breakers). Allows closed transition 27
transfer to/from utility, continuous
paralleling with utility for peak
shaving or exporting. 28
XLM
Emergency Generator Paralleling Switchgear (EGP)
40.3 208–600V UL 1558 ■ ■ ■ ■ ■ EGP product is used to parallel 29
G G UL 891 multiple gensets to a common bus
where interconnect with the utility
is not necessary. EGP systems are
typically used where there are
30
downstream Transfer Switches.
31
EGP
Medium Voltage Paralleling Switchgear
40.4 2.4–27 kV ANSI C37.20.2 ■ ■ ■ ■ ■ ■ ■ ■ ■ Medium Voltage product is for 32
ANSI C37.20.3 applications in excess of 600 Vac.
Systems are available in any of
52 the configurations above (XLM or
EGP). Medium Voltage systems use
33
vacuum circuit breakers for genera-
MV tor and distribution switching.
34
Custom Paralleling Switchgear Products
40.5 208–27 kV UL 1558 ■ ■ ■ ■ ■ ■ ■ ■ ■ Custom Products are available to
UL 891 meet the most demanding or unique 35
ANSI C37.20.2 system requirements. (Ex., multiple
ANSI C37.20.3 utilities, multiple ties, special load
control, custom sequence of
operations, and so on) 36
37
38
39
40
41
42
43
36
37
38
39
40
41
42
43
Ethernet 24
ATS
25
Modbus
ATS Cat
ATS
26
ATS 27
to SCADA or BMS
43
Cat Switchgear System ■ Low cost redundancy the remote communications run
22 Advantages ■ Enhanced performance completely independent of the
■ UL, NFPA, CSA and IEEE compliant
paralleling switchgear automation.
Cat Switchgear performs generator This ensures remote communication
23 protective functions internal to the ■ Higher mean time between failure devices or systems will not affect
EMCP 3.S controller. With Cat ■ Lower mean time to repair the reliability of your Cat Switchgear.
technology, you can monitor, process, Figures 40.1-2 and 40.1-3 show
24 compare, display and transmit data Advanced Communications examples of remote communication
with a high degree of precision and Capabilities connections to the Cat Switchgear.
control—and that control translates
25 into high reliability and functionality. Cat Switchgear technology is Communications with Building
equipped with exceptional remote Management or SCADA Systems
EMCP 3.S technology provides Cat communications technologies, Cat Switchgear can also easily
26 Switchgear with enhanced features enabling you to control and monitor
your engine generator sets from
communicate data to third party
that set the standards for the industry. Building Management, SCADA or
anywhere at anytime. Whether other monitoring systems. For these
■ Unequaled fault tolerance
27 ■ World-leading operator interface
at home, in the office, or on the
road, you can access controls and
applications, a Data Table Interface
acts as a “firewall” between your Cat
■ Sophisticated communications abilities information on a real-time basis and Switchgear system and the Building
28 respond immediately...even control Management or SCADA System. The
■ Superior connectivity
multiple facilities from a single Data Table Interface serves up the
Additional Cat Switchgear centralized site. requested data to the third-party
29 advantages include:
Whether on-site or off-site, the “ monitoring system, but stays
available remote communications completely independent of all critical
■ Less installation wiring
package gives you the identical generator control automation. This
■ Smaller footprint provides better
30 utilization of available space interface and same capabilities as ensures remote communication
standing in front of the generator or devices or systems will not affect
■ Detailed engine and electrical reports the reliability of your Cat Switchgear.
Cat Switchgear. Although identical,
31
32 End User PC
- Full Control or View Only
(depending on password)
- Dedicated Static
33 I.P. Address
41
42
43
On-Site Off-Site 22
Provided with View Only Remote Client
Cat Switchgear - Web Browser
View Only
23
Your Company
Remote Client
Network
VPN Device
- Web Browser
24
Cat Switchgear VPN TUNNEL
25
Firewall Device
VP
- VPN Access
N
Ethernet Port
26
TU
N
N
Remote Client
EL
Switchgear PC Cat. 5 cable - Web Browser
- 1 Web Server (up to approx. 300')
Remote Client
27
- Ethernet Port
- Web Browser
Firewall Device 28
- VPN Access
29
Figure 40.1-3. Off-Site Remote—(TCP-IP) Web-Based Connection with Multiple Users (View Only)
30
31
32
33
34
35
36
37
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
32
33
34
35
36
37
38
39
40
41
42
Figure 40.2-1. XLM2 Low Voltage Switchgear
PR = Protective Relay.
43
43
23
24
25
26
27
28
29
30
31
32
Figure 40.2-2. Typical Electrical System with XLM1 Switchgear (One Generator Source, One Utility Source)—
(For Multiple Utility Sources, see Custom Configurable Switchgear Section 40.5)
33 PR = Protective Relay.
Breaker Size
Max. Feeder
Max. Utility
Bus Rating
Bkr. Size
Generator
R
kW (480V)
Lbs (kg)
Weight
Min. Max. Height Width Depth
35
Main
CELL A
52N1 DIST
800 0 532 800 1600 1600 99.00 44.00 72.00 3300
MDS-CXX
36 CONTROLS
52G1
CONTROLS
(2514.6) (1117.6) (1828.8) (1498)
1600 533 1064 1600 1600 1600 3400
HMI (1544)
37 CELL B 19”
TOUCHSCREEN
2000 1065 1330 2000 2000 2000 3600
MDS-CXX
96.06 TOUCHSCREEN
DISABLE ENABLE
HORN
SILENCE HORN
52D1
(1634)
(2440.0)
38 SYSTEM
SR750 CONTROLS
OPEN
G
CLOSED
R
3000 1331 2000 3000 3200 3200 78.00 3700
(1981.2) (1680)
CELL C 4000A, 5000A and 6000A breakers available in 44.00-inch wide struc-
ture. Contact your local Caterpillar Electric Power dealer for more details.
39 UCLOS 86
52G1
CONTROLS Low voltage switchgear for up to 3500 kW generator set ratings
at 480V is also available. Contact local Caterpillar Electric Power dealer
for more details.
40 CELL D
66.00 (1676.4) with D1 (optional as shown).
MDS-CXX
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures—
52N1 Top or Bottom Entry
41 Structure Rear Conduit Opening Recommended
22.00 22.00 22.00 Depth Width Depth Number of 3.50 or
(558.8) (558.8) (558.8) 4.00-Inch Conduits
42 66.00
(1676.4) 66.00 (1676.4) 16.00 (406.4) 19.30 (490.2) 9
72.00 (1828.8) 16.00 (406.4) 25.30 (642.6) 12
FRONT ELEVATION 78.00 (1981.2) 16.00 (406.4) 31.30 (795.0) 15
43 84.00 (2133.6) 16.00 (406.4) 37.30 (947.4) 18
22
23
24
25
26
27
28
29
30
31
Figure 40.2-4. Typical Electrical System with XLM2 Switchgear (Two Generator Sources, One Utility Source)— 32
(For Multiple Utility Sources, see Custom Configurable Switchgear Section 40.5)
PR = Protective Relay.
33
SECT 1 SECT 2 SECT 3 Generator Dimensions
Breaker Size
Breaker Size
Max. Feeder
34
Max. Utility
Bus Rating
Bkr. Size
Generator
R
kW (480V)
Lbs (kg)
Weight
Min. Max. Height Width Depth
Main
CELL A 35
52N1 DIST
CONTROLS MDS-CXX
CONTROLS 800 0 532 800 1600 1600 99.00 66.00 72.00 5000
52G1
(2514.6) (1676.4) (1828.8) (2270)
36
OPEN CLOSED
1600 533 1064 1600 1600 1600 5200
G R
CELL B
HMI (2361)
19”
TOUCHSCREEN
52G1
CONTROLS
MDS-CXX
2000 1065 1330 2000 2000 2000 5600
(2542)
37
96.06 TOUCHSCREEN
DISABLE ENABLE
HORN
SILENCE HORN
52D1
(2440.0) SYSTEM 3000 1331 2000 3000 3200 3200 84.00 5800
SR750 CONTROLS
CELL C
OPEN
G
CLOSED
(2133.6) (2633)
38
4000A, 5000A and 6000A breakers available in 44.00-inch wide structure.
52G2
MDS-CXX
Contact your local Caterpillar Electric Power dealer for more details.
CONTROLS
UCLOS 86
52D2 Low voltage switchgear for up to 3500 kW generator set ratings
at 480V is also available. Contact local Caterpillar Electric Power dealer
39
for more details.
CELL D
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures— 40
MDS-CXX MDS-CXX
22
23
24
25
26
27
28
29
30
31
32 Figure 40.2-6. Typical Electrical System with XLM3 Switchgear (Three Generator Sources,One Utility Source)—
(For Multiple Utility Sources, see Custom Configurable Switchgear Section 40.5)
PR = Protective Relay.
33
SECT 1 SECT 2 SECT 3 SECT 4 Generator Dimensions
Breaker Size
Breaker Size
Max. Feeder
Max. Utility
34
Bus Rating
Bkr. Size
Generator
R
kW (480V)
Lbs (kg)
Weight
Min. Max. Height Width Depth
Main
CELL A
35 52N1
CONTROLS
MDS-CXX MDS-CXX
DIST
CONTROLS
52G1 52G3
800 0 532 800 1600 1600 99.00 88.00 72.00 7100
(2514.6) (2235.2) (1828.8) (3223)
36 CELL B
HMI
OPEN
G
CLOSED
R
OPEN
G
CLOSED
(2440.0) SYSTEM
SR750 CONTROLS (3496)
OPEN CLOSED
G R
52D2 4000A, 5000A and 6000A breakers available in 44.00-inch wide struc-
86
ture. Contact your local Caterpillar Electric Power dealer for more details.
Low voltage switchgear for up to 3500 kW generator set ratings
39 CELL D
at 480V is also available. Contact local Caterpillar Electric Power dealer
MDS-CXX MDS-CXX MDS-CXX
22
23
24
25
26
27
28
29
30
31
Figure 40.2-8. Typical Electrical System with XLM4 Switchgear (Four Generator Sources, One Utility Source)—
32
(For Multiple Utility Sources, see Custom Configurable Switchgear Section 40.5)
PR = Protective Relay. 33
SECT 1 SECT 2 SECT 3 SECT 4 SECT 5 Generator Dimensions
34
Breaker Size
Breaker Size
Max. Feeder
Max. Utility
Bus Rating
Bkr. Size
Generator
kW (480V)
Lbs (kg)
Weight
Min. Max. Height Width Depth
Main
CELL A
52N1
CONTROLS
MDS-CXX
52G1
MDS-CXX
52G3
DIST
CONTROLS 35
OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
800 0 532 800 1600 1600 99.00 110.00 72.00 9100
36
HMI
CELL B 19”
TOUCHSCREEN 52G1 52G3
(2514.6) (2794.0) (1828.8) (4131)
96.06
MDS-CXX
MDS-CXX
CONTROLS CONTROLS
(2440.0)
TOUCHSCREEN
DISABLE ENABLE
HORN
SILE NCE HORN 52D1 52D3 1600 533 1064 1600 1600 1600 9300
SYSTEM
SR750 CONTROLS (4222)
37
OPEN CLOSED
OPEN CLOSED
G R G R
52D2
MDS-CXX
52D4
(4313)
UCLOS 86
66.00 (1676.4)
72.00 (1828.8)
16.00 (406.4)
16.00 (406.4)
19.30 (490.2)
25.30 (642.6)
9
12
42
78.00 (1981.2) 16.00 (406.4) 31.30 (795.0) 15
84.00 (2133.6) 16.00 (406.4) 37.30 (947.4) 18
43
Figure 40.2-9. XLM4 Low Voltage Switchgear Layout
22
23
24
25
26
27
28
29
30
31
32
Figure 40.2-10. Typical Electrical System with XLMT4 Switchgear (Four Generator Sources, One Utility Source, One Generator Bus Tie Breaker)
33 (For Multiple Utility Sources, see Custom Configurable Switchgear Section 40.5)
PR = Protective Relay.
Breaker Size
Max. Feeder
Max. Utility
Bus Rating
Bkr. Size
Generator
kW (480V)
Lbs (kg)
35
Weight
CELL A
Min. Max. Height Width Depth
Main
52N1 DIST MDS-CXX
DIST
CONTROLS CONTROLS MDS-CXX
CONTROLS
MDS-CXX
36 CELL B HMI
19”
OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
OPEN
G
CLOSED
52D1
52T1
CONTROLS
52G1
CONTROLS
MDS-CXX
52G3
CONTROLS (2514.6) (3352.8) (1828.8) (4131)
TOUCHSCREEN
DISABLE ENABLE
HORN
SILE NCE HORN
52D5
(2440.0) SYSTEM
1600 — 1064 1600 1600 1600 78.00 9300
37
SR750 CONTROLS
OPEN CLOSED
OPEN CLOSED
(1981.2) (4222)
G R G R
CELL C
52G2 52G4
MDS-CXX
52D2
MDS-CXX
52T1
CONTROLS
MDS-CXX
52D6
CONTROLS 2000 — 1330 2000 2000 2000 84.00 9500
UCLOS 86
(2133.6) (4313)
38 CELL D 3000 — 2000 3000 3200 3200 9800
MDS-CXX
52N1
MDS-CXX MDS-CXX MDS-CXX MDS-CXX
(4449)
52D3 52G2 52D7 52G4
22 XLM Functional Sequence of Operations 6. The system is now running in Emergency Mode.
b. Exit from Emergency Mode
A. The EPS Automation shall be provided with the
1. The operator removes the System Mode Selector
following Modes of Operation:
23 1. Automatic/Standby Mode
Switch from Transfer to Emergency position and
returns it to the Auto position.
a. The utility main breaker is closed serving utility 2. Following an adjustable time delay (which can be
24 power to the generator/load bus. abbreviated by the operator), the generator plant
b. The generator main breakers are open. is passively synchronized and paralleled to the
c. The automation is standing by to act in response to a utility source by closing the utility main breaker.
25 utility failure. 3. The generator plant is soft ramp unloaded until
2. Emergency Mode (Standby) the utility source is nominally serving the entire
system load.
26 a. Utility Failure
4. The generator breakers are opened
1. Utility protective relaying senses utility voltage
or frequency out of tolerance. OR
27
2. The utility main breaker is opened. 4. [With Generator Bus Tie Breaker] The generator
3. A run request is sent to the generator plant. bus tie breaker is opened and then all of generator
28 4. The first generator up to voltage and frequency
breakers are opened.
is closed to the bus. 5. The generators are allowed to run for their
programmed cool-down period.
29 5. [With Generator Bus Tie Breaker]
6. The system is now back in Automatic/Standby Mode.
The generator bus tie breaker is closed.
6. The remaining generators are synchronized and 4. Load Management Mode
30 paralleled to the bus as they come up to voltage a. Entry
and frequency. 1. Select one of the modes of operation:
7. The system is now in Emergency Mode.
31 i. Import Limit—The user places the Import/
b. Utility Restoration and Exit from Emergency Mode Export toggle switch in the Import position
1. Utility protective relaying senses utility voltage and places the Base Load/Utility Tracking
32 and frequency within tolerance. toggle switch in the Utility Tracking position.
The user sets the Utility Import set point to
2. Following an adjustable time delay (which can be the desired amount of kW that they want
abbreviated by the operator) to ensure that the
33 utility power source is stable, the generator plant
to import through the Utility Circuit Breaker
during Load Management Mode.
is passively synchronized and paralleled to the
utility source by closing the utility main breaker. ii. Export Limit—The user places the Import/Export
34 toggle switch in the Export position and places
3. The generator plant is soft ramp unloaded until the Base Load/Utility Tracking toggle switch in the
the utility source is nominally serving the entire Utility Tracking position. The user sets the Utility
35 system load. Export Set point to the desired amount of kW
4. The generator breakers are opened. that they want to export through the Utility
5. The generators are allowed to run for their Circuit Breaker during Load Management Mode.
36 programmed cool-down period. iii. Base Load Import—The user places the
6. The system is now back in Automatic/Standby Mode. Import/Export toggle switch in the Import
position and places the Base Load/Utility
37 3. Transfer to Emergency Mode Tracking toggle switch in the Base Load posi-
a. Entry tion. The user sets the Base Load set point to
the desired amount of kW that they want the
38 1. The operator places the System Mode Selector Switch
generator plant to assume during Load Man-
into the Closed Transfer to Emergency position.
agement Mode. The controls shall not allow
2. A run request is sent to the generator plant. the generator plant to export kW through
39 3. The first generator up to voltage and frequency the Utility Circuit Breaker and shall always
is closed to the bus at no load. maintain a nominal amount of Utility kW
40 4. The remaining generators are synchronized and imported through the Utility Circuit Breaker.
paralleled to the bus at no load as they come up iv. Base Load Export—The user places the
to voltage and frequency. Import/Export toggle switch in the Export
41 5. When all generators are on the bus they are soft position and places the Base Load/Utility
ramp loaded until the generator plant is nominally Tracking toggle switch in the Base Load
serving the entire load on the bus and the position. The user sets the Base Load set point
42 utility main breaker is opened. to the desired amount of kW that they want
the generator plant to assume during Load
OR Management Mode. The controls shall allow
43 5. [With Generator Bus Tie Breaker] When all generators the generator plant to export kW through the
are on the bus, they are paralleled across the genera- Utility Circuit Breaker.
tor bus tie breaker. They are then soft ramp loaded
until the generator plant is nominally serving all of
the load on the bus and the utility main is opened.
2. The user places the System Mode Selector 6. Utility Fail Test Mode
Switch in the Load Management position. 22
a. Entrance into Utility Fail Test Mode
3. A run request is sent to the generator plant. 1. The Utility Fail Test Switch is placed in the
4. The generators are allowed to run for a five- ON position. 23
minute warm-up time (which can be abbreviated 2. Voltage sensing at the utility protective relay is
by the operator). opened, which simulates a loss of utility. 24
5. The generators are synchronized and paralleled 3. The system enters into Emergency Mode
to the bus at no load after completion of the as described in the “Emergency Mode”
warm-up time. sequence above. 25
6. When all generators are on the bus they are soft b. Exit from Utility Fail Test Mode
ramp loaded until the generator plant is nominally
serving the required amount of the load on the 1. The Utility Fail Test Switch is placed in the 26
bus to meet the mode of operation selected. OFF position.
7. The generator output is dynamically adjusted to 2. Voltage sensing at the utility protective relay 27
maintain the set point to meet the mode of opera- is restored, which simulates the return of
tion selected. If at any time the system is unable utility power.
to maintain the set point then a “Set point 3. The system exits from Emergency Mode
28
Exceeded” alarm shall be sounded. as described in the “Emergency Mode”
8. Should the utility fail at any time during Load sequence above. 29
Management operation, the utility protective B. When the Generator Sets are carrying the facility load,
relays shall cause the utility main to open and be the EPS Automation shall support two (2) sub-modes:
locked out, thus placing the system in Emergency Load Shed/Load Add, and Generator Demand Priority. 30
Mode until the Utility is restored (as described in
Emergency Mode exit). 1. Load Shed Control
a. The System Controls shall include a Load Shed
31
b. Exit
1. The operator removes the System Mode Selector Control function to control the loads served by the
Switch from Load Management position and generator plant. 32
returns it to the Auto position. b. The Load Shed Control shall have one Essential Load
Shed Priority Level for each generator in the system
2. The generator plant is soft ramp unloaded until plus one Non-Essential Load Shed Priority Level 33
the utility source is nominally serving the entire (which is always shed in the Emergency Mode
system load and the generator main breakers of operation).
are opened.
c. The Load Shed Control shall control each of the 34
3. The generators are allowed to run for their distribution circuit breakers that are shown on
programmed cool-down period. the drawings. Distribution circuit breakers to be
controlled shall be electrically operated. Each 35
4. The system is now back in Automatic/Standby Mode. electrically operated distribution circuit breaker
shall be field selectable to be assigned to any of
5. No Load Test Mode
the available Load Shed Priority Levels. 36
a. Entrance into No Load Test Mode 1. Provide the following controls for each
1. The No Load Test Switch is placed in the Essential Load Shed Priority Level 37
ON position.
i. Shed Delay Timer, adjustable from
2. All available generators are started. 0 to 1024 seconds
38
3. All generators come up to voltage and frequency ii. Add Delay Timer, adjustable from
and remain running disconnected from the bus. 0 to 1024 seconds
4. The system is now in No Load Test Mode. iii. Load Shed Override Selector (shed/auto/add)
39
b. Exit from No Load Test Mode iv. Status indicators to show whether the
1. The No Load Test Switch is placed in the Priority Level is Added or Shed 40
OFF position. 2. Provide the following controls for each
2. The generators are allowed to run for their Non-Essential Load Shed Priority 41
programmed cool-down period. i. Load Shed Override Selector (shed/auto/add)
3. The system is now back in Automatic/Standby Mode. ii. Status indicators to show whether the 42
Priority Level is Added or Shed
43
3. Additionally, the Load Shed Controls shall have: NOTE: The following applies to systems with two or
22 more generators.
i. Load Shed Control Switch (On/Off)
2. Generator Demand Priority Control
ii. User-settable Load Shed % (as a function of
23 on-line generator capacity) a. The System Controls shall include a Generator
Demand Priority Control function to automatically
iii. User-settable Load Shed Time Delay match the on-line generator capacity to the loads to
24 iv. User-settable Load Add % (as a function of
avoid unnecessary operation of all the generators
when the loads are low.
on-line generator capacity)
b. The following controls shall be provided for each
25 v. User-settable Load Add Time Delay generator:
vi. User-settable Bus Underfrequency set point 1. User-settable Generator Priority Selector
26 vii. User-settable Bus Underfrequency time delay 2. Status indicator for the Generator Priority Selected
viii. Bus Underfrequency Reset Pushbutton 3. Status indicator for generator On-line or Off-line
27 c. The Generator Demand Priority Control shall have
ix. Bus Underfrequency indicator
the following controls:
4. Conditional Load Shed—Upon entrance into
28 Emergency Mode of operation, the Load Shed
1. Generator Demand Priority Control Switch (On/Off)
Control shall shed all Essential and Non-Essential 2. User-settable Generator Remove % (as a function
loads. As generators come to the bus, Essential
29 Priority Level loads shall be added conditionally
of a single generator capacity)
42
43
31
32
33
34
35
36
37
38
39
40
41
42
Figure 40.3-1. EGP3 Low Voltage Switchgear (Three Generator Sources) 43
Equipment ■ Automatic load shed control with ■ Distribution sections with group
22 on-screen operator adjustments mounted UL 489 molded case circuit
Standard Equipment—EGP for essential (Life/Safety), critical breakers (UL 891 construction only.)
■ Low voltage EGP systems use and non-essential loads. Manual ■ Also available in 150 kA or 200 kA
23 Magnum DS power circuit breaker load shed/load add control bus bracing configurations
switchgear and Magnum power ■ Automatic generator demand ■ Also available in 8000 and 10,000A
circuit breakers. For complete priority with on-screen operator continuous cross bus ratings at
24 technical details on Magnum DS adjustments for automatic addition 600 Vac
switchgear, see Tab 20 and removal of generator to the ■ Also available with 4000, 5000 and
■ Operator interface touchscreen load bus
25 (Choose one of the following): ■ System status and alarm annuncia-
6000A UL 1066 breakers
■ Trip unit metering and communica-
❑ High Redundancy Product, tion with color display and 85 dbA tions (Digitrip 520M, 520MC
26 19.00-inch surface acoustic wave alarm horn with silence button and 1150)
LCD TFT color touchscreen with ■ Password secured settings and ■ Also available in 5 kV, 15 kV and
key switch adjustments for generator and 27 kV class configurations
27 ❑ Standard product, 15-inch system setups and protective (See Section 40.4)
resistive LCD TFT color relaying
■ Remote monitoring and control
touchscreen ■ Alarm summary reports
28 ■ Settings reports
■ Building Automation System
or SCADA communications—
■ Direct data communication to Cat
microprocessor-based engine gen- ■ Engine and generator load charts Modbus or Ethernet
29 erator set control network (EMCP) ■ Engine trend data ■ Remote notification
■ System overview screen with ■ UL 891, UL 1558 or CSA listed ■ Historical data trending
one line mimic diagram that and labeled ■ Communication to Cat ATS units
30 depicts real-time metering, status ■ NEMA 1 or NEMA 3R, deadfront ■ Automated Joint Commission
and control freestanding construction report
■ Full function 0.5% accuracy analog ■ Copper bus, braced for 100 kA
31 and digital AC metering for genera- ■ Three-phase, four-wire, 100% Tie Breaker Application
tors: voltage 1-2, 2-3, 3-1; current neutral, 0.25-inch x 2.00-inch copper
1, 2, 3; frequency; power factor; Many systems require the use of tie
32 ground bus breakers to meet Code or system per-
kW; kVAR
■ Available in 600V, 480/277V or formance requirements. Tie breakers
■ Full function engine gauges: RPM, 208/120V, 60 Hz can be used anywhere throughout the
33 DC battery voltage, oil pressure,
■ UL 1066 listed power circuit breakers, line-up to segment or isolate desired
engine coolant temperature,
42–200 kAIC, two-step stored energy sources, loads or sections of bus.
engine hours, number of starts
drawout mounted electrically
34 ■ 3-D engine data operated with long time and Emergency Generator Bus Tie
■ Full function synchronizing and par- instantaneous trip, and circuit Certain NFPA Codes require all life
alleling controls with selection for breaker control switch with lights safety and critical loads (Priority 1
35 automatic or manual synchronizing ■ Continuous cross bus ratings up to loads) to be restored in a maximum
■ NFPA 110 engine/generator 10,000A at 600 Vac of 10 seconds. If the total Priority 1
status, pre-alarm, lamp test button, load that must be restored in ten
36 ■ Mechanical lugs for incoming and
shutdown fault annunciation and 85 seconds exceeds the capacity of
outgoing conductors
dBA alarm horn with silence button a single generator, an emergency
■ Top or bottom conduit entry generator bus tie breaker should be
■ Full function 0.5% accuracy analog
37 and digital AC metering for system:
■ Plug together control connections used. This allows one generator on
across shipping splits each side of the tie to restore power
voltage 1-2, 2-3, 3-1; current 1, 2, 3;
to Priority 1 loads in under 10 seconds.
38 frequency; power factor; kW; kVAR Optional Equipment—EGP The system can then parallel all
■ System control functions for ■ Distribution sections with generators across the emergency
auto (standby for emergency), test electrically operated drawout generator bus tie breaker so the full
39 without load and test with load UL 1066 circuit breakers generator plant capacity is available.
■ Circuit breaker trip functions—short
Note: Priority 1 loads must be split to either
time and/or ground fault
40 (in addition to long time and
side of the generator tie breaker. See Page
40.3-9 for an example of a system with an
instantaneous) emergency generator bus tie breaker.
■ Steel barriers between switchboard
41 or switchgear sections for compart-
mentalization
42 ■ Bus/cable barriers
43
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33 Figure 40.3-2. Typical Electrical System with EGP2 Assembly and ATS Units (Two Generator Sources)
Breaker Size
Max. Feeder
kW (480V)
Bus Rating
R
Generator
Lbs (kg)
Weight
35
Main
CELL A
52G1 MDS-CXX
DIST
CONTROLS CONTROLS
36 52G2
0 532 800 1600 1600 99.00 66.00 72.00 5000
(2514.6) (1676.4) (1828.8) (2270)
533 1064 1600 3200 3200 5100
CELL B
37 HMI
19”
TOUCHSCREEN
(2315)
1065 1330 2000 4000 3200 5300
MDS-CXX
96.06 52D1
(2440.0) TOUCHSCREEN
DISABLE ENABLE
HORN
SILE NCE HORN
(2406)
38 OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
1331 2000 3000 6000 3200 84.00 5500
CELL C
(2133.6) (2497)
SYSTEM
52G2
4000A, 5000A and 6000A breakers available in 44.00-inch wide struc-
CONTROLS
39
MDS-CXX
CONTROLS
52D2 ture. Contact your local Caterpillar Electric Power dealer for more details.
Low voltage switchgear for up to 4000 kW generator set ratings
at 480V is also available. Contact local Caterpillar Electric Power
dealer for more details.
40 CELL D
MDS-CXX
22
23
24
25
26
27
28
29
30
31
32
33
Figure 40.3-4. Typical Electrical System with EGP3 Assembly and ATS Units (Three Generator Sources)
34
35
36
37
38
39
40
42
43
Configuration
Generator Dimensions
Breaker Size
Max. Feeder
kW (480V)
Bus Rating
Bkr. Size
R
Generator
Number
Min. Max. Height Width Depth
Lbs (kg)
23
Weight
CELL A
Main
52G1 DIST
CONTROLS
MDS-CXX
CONTROLS
52G2
24 OPEN
G
CLOSED
R
0 532 800 3200 1600 99.00 66.00 84.00 7000 1
CELL B HMI
(2514.6) (1676.4) (2133.6) (3178)
19” 52G2
96.06 TOUCHSCREEN CONTROLS
MDS-CXX
G
CLOSED
R
OPEN
G
CLOSED
R
533 1064 1600 4000 3200 88.00 7500 2
CELL C (2235.2) (3405)
26
SYSTEM
CONTROLS 52G3
CONTROLS
MDS-CXX
G
CLOSED
R
4.00-Inch Conduits
CELL B HMI
19” 52G2
66.00 (1676.4) 16.00 (406.4) 19.30 (490.2) 9
TOUCHSCREEN CONTROLS
72.00 (1828.8) 16.00 (406.4) 25.30 (642.6) 12
MDS-CXX MDS-CXX
33 (2440.0) TOUCHSCREEN
DISABLE ENABLE
HO RN
SILENCE HO RN
G
CLOSED
R
OPEN
G
CLOSED
34 CONTROLS
CONTROLS
CELL D
35 MDS-CXX MDS-CXX MDS-CXX MDS-CXX
36 22.00
(558.8)
22.00
(558.8)
22.00
(558.8)
22.00
(558.8)
88.00
(2235.2)
37 FRONT ELEVATION
CONFIGURATION 2
39
40
41
42
43
22
23
G1 G2 G3 G4
Main D1 D2 D3 D4 26
Service
27
28
29
ATS1 N E
ATS2 N E ATS3 ATS4
N E N E
To Normal To Emergency
Distribution Circuits 30
Circuits
32
LP1 BP1 LP2 BP2 LP3 BP3 LP4 BP4
33
Figure 40.3-6. Typical Electrical System with EGP4 Assembly and ATS Units (Four Generator Sources)
34
35
36
37
38
39
Figure 40.3-7. Automated Joint Commission Report
40
42
43
Configuration
Generator Dimensions
Breaker Size
Max. Feeder
kW (480V)
R
Bus Rating
Bkr. Size
Generator
Number
Min. Max. Height Width Depth
Lbs (kg)
23
Weight
CELL A
Main
52G1 MDS-CXX
DIST
CONTROLS CONTROLS
52G2
24 CELL B HMI
OPEN
G
CLOSED
G
CLOSED
R
OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
(3609)
SYSTEM
CONTROLS 52G3
CONTROLS
52G4
CONTROLS
MDS-CXX
533 1064 1600 4000 3200 110.0 84.00 9500 2
52D3
(279.4) (2133.6) (4313)
26 1065 1330 2000 6000 2000 88.00 8000 1
CELL D (2235.2) (3632)
MDS-CXX MDS-CXX MDS-CXX MDS-CXX
(279.4) (4358)
22.00 22.00 22.00 22.00
(558.8) (558.8) (558.8) (558.8)
1331 2000 3000 6000 2000 88.00 8200 1
88.00
(2235.2) (3723)
28 (2235.2) 1331 2000 3000 6000 3200 110.0 9800 2
FRONT ELEVATION
CONFIGURATION 1
(279.4) (4449)
4000A, 5000A and 6000A breakers available in 44.00-inch wide struc-
29 SECT 1 SECT 2 SECT 3 SECT 4 SECT 5 ture. Contact your local Caterpillar Electric Power dealer for more details.
R
Low voltage switchgear for up to 4000 kW generator set ratings
at 480V is also available. Contact local Caterpillar Electric Power
30 CELL A
dealer for more details.
52G1 DIST
CONTROLS
MDS-CXX
52G2
MDS-CXX
52G4
CONTROLS
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures—
Top or Bottom Entry
31 CELL B
OPEN
G
CLOSED
R
OPEN
G
CLOSED
96.06 TOUCHSCREEN
52G2
CONTROLS
52G4
CONTROLS
MDS-CXX MDS-CXX
OPEN
G
HORN
SILENCE
CLOSED
R
HORN
OPEN
G
CLOSED
34
MDS-CXX MDS-CXX
52G1 52G3
38
39
40
41
42
43
Utility 22
Source
23
G1 G2 G3 G4
Revenue
Metering HMI 24
Touchscreen
D1 D2
Priority 1
Feeder
Priority 1
Feeder D3 D4 27
28
~ ~ ~
To Normal ~ ~ 29
Distribution ~
Circuits To Emergency
Circuits
ATS1 N E ATS2 N E ATS3 N E ATS4 N E 30
33
Figure 40.3-9. Typical Electrical System with EGPT4 Switchgear (Four Generator Sources, One Emergency Generator Bus Tie Breaker)
34
35
36
37
38
39
40
41
42
43
Configuration
Generator Dimensions
Breaker Size
Max. Feeder
kW (480V)
R
Bus Rating
Bkr. Size
Generator
Number
Min. Max. Height Width Depth
Lbs (kg)
23
Weight
CELL A
Main
52G1 DIST
CONTROLS CONTROLS
OPEN CLOSED
G R
24 CELL B HMI
19”
TOUCHSCREEN
MDS-CXX
52T1
CONTROLS
MDS-CXX MDS-CXX
0 532 800 3200 1600 99.00 110.00 78.00 7800 1
96.06 52D1 52D2 52D3
(2514.6) (2794.0) (1981.2) (3541)
(2440.0)
TOUCHSCREEN HORN
DISABLE ENABLE S ILENCE HORN
OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
OPEN
G
CLOSED
G
CLOSED
R
dealer for more details.
19” 52T1
TOUCHSCREEN
Conduit Space for 22.00-Inch (558.8 mm) Wide Structures—
MDS-CXX MDS-CXX MDS-CXX
CONTROLS
96.06 52D1 52D3 52D4
(2440.0)
Top or Bottom Entry
TOUCHSCREEN HORN
DISABLE ENABLE S ILENCE HORN
31 CELL C
OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
OPEN
G
CLOSED
R
OPEN
G
CLOSED
SYSTEM
CONTROLS 52G2 MDS-CXX
52G3 52G4
Structure Rear Conduit Opening Recommended
CONTROLS CONTROLS CONTROLS
52T1 Depth Width Depth Number of 3.50 or
4.00-Inch Conduits
32 CELL D
MDS-CXX MDS-CXX MDS-CXX MDS-CXX MDS-CXX
66.00 (1676.4) 16.00 (406.4) 19.30 (490.2) 9
52G1 52D2 52G2 52G3 52G4
72.00 (1828.8) 16.00 (406.4) 25.30 (642.6) 12
33 22.00
(558.8)
22.00
(558.8)
22.00
(558.8)
22.00
(558.8)
22.00
(558.8)
22.00
(558.8)
78.00 (1981.2)
84.00 (2133.6)
16.00 (406.4)
16.00 (406.4)
31.30 (795.0)
37.30 (947.4)
15
18
110.00
(2794.0)
34 FRONT ELEVATION
CONFIGURATION 2
36
37
38
39
40
41
42
43
4. The remaining generators are synchronized and iv. Status indicators to show whether the Priority
paralleled to the bus as they come up to voltage Level is added or Shed
43 and frequency.
5. The system is now in No Load Test Mode.
2. Provide the following controls for each NOTE: The following applies to systems with two or
Non-Essential Load Shed Priority more generators. 22
i. Load Shed Override Selector (shed/auto/add) 2. Generator Demand Priority Control
ii. Status indicators to show whether the a. The System Controls shall include a Generator 23
Priority Level is Added or Shed Demand Priority Control function to automatically
match the on-line generator capacity to the loads to
3. Additionally, the Load Shed Controls shall have: avoid unnecessary operation of all the generators 24
when the loads are low.
i. Load Shed Control Switch (On/Off)
b. The following controls shall be provided for each
ii. User-settable Load Shed % (as a function generator: 25
of on-line generator capacity) 1. User-settable Generator Priority Selector
iii. User-settable Load Shed Time Delay 2. Status indicator for the Generator Priority 26
iv. User-settable Load Add % (as a function of Selected
on-line generator capacity) 3. Status indicator for generator On-line or Off-line 27
v. User-settable Load Add Time Delay c. The Generator Demand Priority Control shall have
vi. User-settable Bus Under frequency Set point the following controls: 28
1. Generator Demand Priority Control Switch (On/Off)
vii. User-settable Bus Under frequency time delay
2. User-settable Generator Remove % (as a function 29
viii. Bus Under frequency Reset Pushbutton
of a single generator capacity)
ix. Bus Under frequency indicator
3. User-settable Generator Remove Delay
4. Conditional Load Shed—Upon entrance into
30
4. User-settable Generator Add % (as a function of a
Emergency Mode of operation, the Load Shed
single generator capacity)
Control shall shed all Essential and Non-Essential
loads. As generators come to the bus, Essential 5. User-settable Generator Add Delay
31
Priority Level loads shall be added conditionally
based on the number of generators on line. When d. Upon entrance into Emergency mode, all generators
the first generator comes to the bus, Priority Level shall be started and paralleled to the bus. After the 32
1 loads shall be added; Second generator, priority Remove Time Delay, generators shall be removed
2, etc. After a time delay that allows all opera- from the bus as a function of the generator percent-
tional generators to come to the bus, Load Shed age loading by the user selected Generator Remove 33
Mode shall shift to Load Sensitive Mode. time delay. Generators shall be removed from the
bus in descending priority. Should the generator
5. Load Sensitive Load Shed—After all generators percentage loading increase to the user selected 34
have been given sufficient time to come to the Generator Add limits for the user selected Add Delay,
bus, load shed shall shift to “Load Sensitive” the next generator will be started, synchronized and
mode. The system shall compare current paralleled to the bus. Generators shall be added 35
generator on-line capacity (in kW) to current to the bus in ascending priority order. Should the
load requirements. If surplus capacity is greater generator plant ever reach 95% loading, the next
than the calculated Load Add set point, after the priority generator shall be started and added to 36
Load Add Time Delay the next Load Shed Priority the bus with no time delay.
shall be added. This calculation will continue until
all Sheddable Loads are added, or until surplus 37
capacity is less than the calculated Load Add
setpoint. If surplus capacity is less than the
calculated Load Shed setpoint, after the Load 38
Shed Time Delay the next Load Shed Priority
shall be shed. This calculation shall continue until
all Sheddable Loads are shed, or until surplus 39
capacity is greater than the calculated Load Shed
setpoint. The Load Shed Control, in its automatic
shedding and adding of loads, shall not override 40
any manual load shed/add operation.
6. Should the load bus frequency fall below the user 41
selected bus underfrequency setpoint for a period
longer than the bus underfrequency time delay,
then all Priority Level loads shall be shed and load 42
addition shall not resume until the operator has
depressed the Bus Underfrequency Reset button.
The bus underfrequency protection shall override 43
any manual load add operation.
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
42
43
Other Available Protective Generator bus tie breakers can be See Page 40.4-7 for an example of
22 Functions and Options applied to serve several purposes: an XLM system with generator bus
tie breaker.
A. (87B) Switchgear Bus Differential 1. Starting of large loads—the
23 —Bus differential relays are high generator bus tie can be opened to Emergency Generator Bus Tie
speed protective devices that are allow multiple generators to be Certain NFPA codes require all life
used to limit damage from faults paralleled before being connected safety and critical loads (Priority 1
24 within the switchgear by quickly to large load(s). Once multiple loads) to be restored in a maximum of
isolating the faulted “zone.” generators are paralleled, the 10 seconds. If the total Priority 1 load
Differential relays measure the generator bus tie can be closed that must be restored in 10 seconds
25 difference between the current to power the large loads. exceeds the capacity of a single
flowing into and the current flow- 2. Load banks—the generator bus generator, an emergency generator
ing out of a given “zone.” Systems tie can allow the generators to be bus tie breaker should be used. This
26 with multiple utilities and/or tie isolated from the normal utility fed allows one generator on each side
breakers will typically have more bus. Having a distribution breaker of the tie to restore power to Priority 1
than one bus differential zone. In or set of load take-off lugs on the loads in under 10 seconds. The
27 this configuration, during a differ- generator side of the bus allows system can then parallel all generators
ential fault, only breakers feeding the generators to be load bank across the emergency generator bus
in and out of the faulted zone are tested without affecting any tie breaker so the full generator plant
28 tripped and locked out. The other normal utility fed loads. capacity is available.
zone(s) are unaffected and can
Note: Priority 1 loads must be split to
continue to operate. 3. Emergency Standby systems with
29 Automatic Transfer Switches—the
either side of the emergency generator
bus tie breaker.
B. Generator Neutral Grounding generator bus tie provides isola-
Resistors—provide added tion between the normal and See Page 40.4-12 for an example
30 protection for generator windings emergency buses. During a loss of an EGP emergency system with
by limiting the fault current during of utility power, the generator
line to ground faults. generator bus tie breaker.
bus tie can be opened to isolate all
31 normal loads and allow restora-
Tie Breaker Application tion of power to emergency
Many systems require the use of loads. Once emergency loads
32 tie breakers to meet code or system are restored, the emergency bus
performance requirements. Tie tie can be reclosed to restore
breakers can be used anywhere power to normal loads.
33 throughout the line-up to segment
or isolate desired sources, loads
or sections of bus.
34
Generator Bus Tie
Generator bus ties can be used to
35 separate the normal electric service
sources from the generator sources.
This can also allow separation of load
36 breakers to either side of the generator
bus tie breaker in order to allow isola-
tion of load banks, or dedicated emer-
37 gency loads. This separation also may
be required by NFPA or local Codes.
38
39
40
41
42
Air/Cool System Screen
43
Other Recommended Protective 4. Extensive information on Surge Surge capacitors are recommended
Functions and Options Protection, Arrestors and to protect the alternator on 5 kV or 22
Capacitors can be found in Tab 5 15 kV Gensets.
Generator Neutral Grounding “Metal-Clad Switchgear—
Resistors are recommended to VacClad-W—Medium Voltage.” 1. Surge capacitors should be used 23
protect generator windings. to protect AC alternators.
5. Recommended minimum protec-
2. Surge capacitors are used to
1. NGRs provide added protection tion: surge arrester for protection
prevent regular electric flow 24
for generator windings by limiting from high overvoltage peaks, or
the fault current during line to surge capacitor for protection from being grounded.
ground faults. from fast-rising transient. Please 3. Protective Surge Capacitor 25
note that the surge arresters or systems should be designed
2. Cat Switchgear recommends a surge capacitor alone may not
Low Resistance Grounding system to operate in conjunction with
with a Neutral Grounding Resistor
provide adequate surge protection lightning arresters to provide 26
from escalating voltages caused surge protection for generator
tied to the Generator Neutral rated by circuit resonance.
at10 seconds and the Line to alternators.
Neutral voltage. 6. Good protection: Surge arrester in
27
4. The capacitor should reduce the
parallel with surge capacitor for steepness of the wave front of the
a. NGRs protect the alternator protection from high overvoltage
windings on MV and HV peaks and fast rising transient.
voltage surge, thereby reducing 28
gensets with 87G schemes. the stress on the turn and line-to-
This option may not provide ground insulation.
b. On 4160V systems, 2400V adequate surge protection from
10 seconds, 200A NGRs are escalating voltages caused by 5. Surge capacitors function best 29
commonly specified. circuit resonance. When applying when located as close as possible
surge capacitors on both sides of to the generator alternator output
c. On 13.8 kV systems, 8000V
a circuit breaker, a surge capacitor leads. 30
10 seconds, 100A NGRs are
commonly specified. on one side of the breaker must be
6. Surge capacitors should be
RC Snubber or ZORC, to mitigate 31
Surge Arresters are recommended to connected line-to-ground, and
possible virtual current chopping.
protect Switchgear. be on the load side of the breaker
7. Better protection: RC snubber in to eliminate the chance of a bus
1. A surge arrester is used to prevent parallel with surge arrester for short-circuit in the event of 32
large surges from power inconsis- protection from high frequency capacitor failure.
tencies, lightning, switching, etc., transients and voltage peaks.
from reaching electronic instru- 7. Maximum effectiveness is 33
ments and ensure the safety of 8. Recommended best protection: achieved in limiting impulse
individuals nearby by limiting the ZORC, plus proper surge arrester voltages, if a low-resistance and
crest of impending voltage surges preceding ZORC where needed for low-inductance ground connec- 34
to safe values. protection against lightning. ZORC tion is established. All ground
provides protection from high connections need to be tied
2. Surge arrestors are connected frequency voltage transients together with a minimum 35
between each electrical conductor and limits peak magnitude of the #6 AWG copper conductor.
in a power system and the ground, transient to 1 to 2 PU (see ZORC
8. Although surge capacitors are
which provides a short-circuit to description in Tab 5 on Page 5.4-18
installed line-ground, they should
36
the ground. for more detail). Surge arrester
be rated for line-to-line voltage in
provides protection from higher
3. Surge arrestors are typically the event they are installed on an
installed on utility feeders, and
voltage peaks resulting from
ungrounded or poorly grounded
37
lightning surges.
feeders exiting the building to system.
other loads.
9. Cat Switchgear recommends 38
the following values based on
system voltage: 0.5 f on 5 and
7.5 kV, 0.25 f on 15 kV, and 39
0.13 f on systems operating
at 24 kV and higher.
40
10. Where applicable, the surge
capacitor shall conform to
NEMA CP-1 standards. 41
42
43
42
43
23
24
25
26
27
28
29
30
Figure 40.4-2. Medium Voltage XLM1 Switchgear (One Generator Source, One Utility Source)—
31 (For Multiple Utility Sources, see Custom Configurable Switchgear Section 40.5)
Note: 87B = Bus Differential Protection (if applicable).
33
VTN1 VTG1
35 HMI
19”
86 G R UCLOS TOUCHSCREEN 86 G R
CLOSE LOCKOUT
SWITCH
LOCKOUT AUTO
36 95.00
(2413.0)
37 VTB1
38 CELL B
39 52N1 52G1
40
36.00 36.00 36.00
(914.4) (914.4) (914.4)
41 108.00
(2743.2)
FRONT ELEVATIO N
42
Figure 40.4-3. 5/15 kV XLM1 Switchgear Layout
Note: All structures are 96.25 inches (2444.8 mm) deep.
43 Note: See Figures 40.4-11 and 40.4-12 for typical distribution structure layouts.
Note: See Tab 5 Medium Voltage Metal-Clad Switchgear for conduit space, weights, etc.
TO 87B1
22
TO 87B1
23
TO 87B2 24
25
26
TO TO TO 27
TO 87B1 TO 87B1 87B2 87B2 87B2
28
29
Figure 40.4-4. Medium Voltage XLMT3 Switchgear (Three Generator Sources, One Utility Source, One Generator Bus Tie Breaker) — 30
(For Multiple Utility Sources, see Custom Configurable Switchgear Section 40.5)
Note: 87B = Bus Differential Protection (if applicable); 87B1 = Zone 1; 87B2 = Zone 2.
31
SECT 1 SECT 2 SECT 3 SECT 4 SECT 5 SECT 6 SECT 7 SECT 8
R
32
VTN1 52D1 52ET1 VTB2 VTG1 VTG2 VTG3
CELL A
Utility Relay Dist. Relay Tie Relay Gen. Relay Gen. Relay Gen. Relay 33
HMI
19”
86 G R
UCLOS
CLOSE LOCKOUT
SWITCH
LOCKOUT AUTO
TOUCHSCREEN 86 G R
86 G R
86 G R
86 G R
86 G R
34
95.00
(2413.0) 86 G R
VTB1 35
CELL B
Dist. Relay
52N1 52D2 52G1 52G2 52G3 36
41
42
43
26 HMI
19”
TOUCHSCREEN 86 G R 86 G R 86 G R
27 95.00
(2413.0)
28
29 CELL B
31
36.00 36.00 36.00 36.00
(914.0) (914.0) (914.0) (914.0)
32 144.00
(3658.0)
FRONT ELEVATION
33
Figure 40.4-6. EGP3 5/15 kV Switchgear
34 General Description
Cat Emergency Generator Paralleling ■ For use with multiple downstream Cat Switchgear brings the power and
35 (EGP) Switchgear for multiple engine Automatic Transfer Switches reliability of microprocessor technol-
generator sets. ■ Cat switchgear is designed ogy to your generator switchgear
to integrate hand-in-glove with application. Through the use of the
36 ■ Automatic start, synchronize,
Cat Automatic Transfer Switches operator interface (HMI) touchscreen
parallel and load share on a display with easy-to-follow graphical
common bus (ATS), Generators, and Uninterrupt-
ible Power Systems (UPS). EGP representations, Cat Switchgear
37 ■ Main lugs output to feed down- Switchgear is optionally available merges the features of:
stream emergency distribution with direct communication to Cat
■ Optional emergency distribution ■ Power monitoring
ATSs to provide “fingertip” control
38 circuit breakers and monitoring of all your facility ■ Switchgear automation
■ Load shed/load add ATSs from one convenient ■ Generator set control
Generator demand priority central location ■ Optional remote communications
39 ■
40
41
42
43
43
31
32
33
34
35
36
37
38
39
40
41
42
43
22
23
24
25
26
27
28
29
30
33
VTG1 VTG2 VTG3
34
Gen. Relay Gen. Relay Gen. Relay
CELL A
35
HMI
19”
TOUCHSCREEN 86 86 86
36
G R G R G R
95.00
(2413.0)
37
38
CELL B
39
VTB1 52G1 52G2 52G3
40
22 TO 87B1 TO 87B2
TO 87B1
23
24 TO 87B2
25
26
27
TO TO TO TO TO TO TO
87B1 87B1 87B1 87B2 87B2 87B2 87B2
28
29
30
Figure 40.4-9. Medium Voltage EGPT4 Switchgear (Three Generator Sources, One Emergency Generator Bus Tie)
31 Note: 87B = Bus Differential Protection (if applicable); 87B1 = Zone 1; 87B2 = Zone 2.
32 R
SECT 1 SECT 2 SECT 3 SECT 4 SECT 5 SECT 6 SECT 7 SECT 8 SECT 9
34
19”
TOUCHSCREEN 86 G R
86 G R
86 G R
86 G R
86 G R
86 G R
86 G R
95.00
(2413.0) 86 G R
86 G R
86 G R
35
CELL B
Dist. Relay Tie Relay Dist. Relay
36 VTB1 52G1 52G2 52D2 52D3 52G3 52G4 52D5
23
24
25
26
27
28
29
30
31
Figure 40.4-11. Typical Medium Voltage Distribution Section
32
SECT 1
R
33
52D1
34
Dist. Relay
CELL A 35
86 G R
36
95.00
(2413.0) 37
86 G R
38
CELL B
Dist. Relay
39
52D2 40
41
36.00
(914.4) 42
FRONT ELEVATION
43
Figure 40.4-12. 5/15 kV Distribution Section Layout
Note: All structures are 96.25 inches (2444.8 mm) deep.
Note: See Tab 5 Medium Voltage Metal-Clad Switchgear for conduit space, weights, etc.
Control panel discrete control interface (16) x 1/c #14 AWG (includes spares) DC control ≤30 Vdc Discrete control (start/stop, emergency stop
and crank terminate, includes spares, etc.)
25 Best source 24 Vdc (4) x 1/c #10 AWG DC control ≤30 Vdc ±24 Vdc from generator battery system to
(2 x + 24 Vdc and 2 x–24 Vdc) supplement switchgear 24 Vdc control voltage
31
32
33
34
35
36
37
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Custom Systems 22
General Description
Cat Generator Paralleling Switchgear has the power and 23
flexibility to handle even the most unique or demanding
configurations and project requirements. If the standard
XLM (Emergency Transfer (Xfer) and Load Management), 24
and EGP (Emergency Generator) configurations do not fit
the needs of your specific project, Cat Switchgear offers
fully customized solutions. 25
In many cases, custom configurable systems are based
on standard XLM or EGP configurations with additional
requirements such as:
26
■ Multiple utility connections
■ Multiple tie breakers
27
■ Unique sequence of operations
■ Special switchgear layout requirements, and so forth 28
Example Custom Overview Screen
Regardless of what the project requires, Cat Switchgear
can meet your needs. Some examples of Custom System 29
one-line diagrams and layouts are on the following pages.
30
31
32
33
34
35
Example Custom Oil/Fuel System Screen
36
Example Custom Overview Screen
37
38
39
40
41
42
43
23
24
25
26
52N2
27
Bus #1 Bus #2
28
29
30
31
32
33
Figure 40.5-1. Low Voltage Main-Generator-Tie-Generator-Main Switchgear (Two Utility Sources, Four Generator Sources, Two Generator
Bus Tie Breakers)
34 PR = Protective Relay.
35 R
SECT 2 SECT 3 SECT 4 SECT 5 SECT 6 SECT 7
36 CELL A
52N1 DIST MDS-CXX
MDS-CXX MDS-CXX
52N2
CONTROLS CONTROLS CONTROLS
G R G R G R
HMI HMI
CELL B
38 19”
TOUCHSCREEN
MDS-CXX
52G1
CONTROLS
52BT1 MDS-CXX
52G3
19”
TOUCHSCREEN
CONTROLS CONTROLS
95.00 TOUCHSCREEN
DISABLE ENABLE
HORN
SILE NCE HORN
52D1 52D5 TOUCHSCREEN
DISABLE ENABLE
HORN
SILE NCE HORN
G
CLOSED
R
OPEN
G
CLOSED
R
CONTROLS
CELL C
52G2 52G4
40
MDS-CXX MDS-CXX MDS-CXX
CONTROLS CONTROLS
52D2 52BT1 52D6
41 CELL D
MDS-CXX MDS-CXX MDS-CXX MDS-CXX MDS-CXX MDS-CXX
42
22.00 22.00 22.00 22.00 22.00 22.00 22.00
(558.8) (558.8) (558.8) (558.8) (558.8) (558.8) (558.8)
43 154.00
(3911.6)
FRONT ELEVATION
22
23
24
25
26
27
28
Figure 40.5-3. Medium Voltage Main-Tie-Generator-Tie-Main Switchgear (Two Utility Sources, Two Generator Sources, Two Generator
Bus Tie Breakers)
Note: 87B = Bus Differential Protection (if applicable). 29
SECT 1 SECT 2 SECT 3 SECT 4 SECT 5 SECT 6 SECT 7 SECT 8 SECT 9 SECT 10 SECT 11 30
R
VTN1 52D1 52T1 VTB2 VTG1 VTG2 52T2 VTB3 52D3 VTN2
CELL A
Utility Relay Dist. Relay Tie Relay Gen. Relay Gen. Relay Tie Relay Dist. Relay Utility Relay 31
HMI
19”
86 G R UCLOS TOUCHSCREEN 86 G R
86 G R 86 G R
86 G R
86 G R 86 G R 86 G R UCLOS
32
CLOSE L OCKOUT CLOSE L OCKOUT
S WITCH S WITCH
L OC KOUT A UTO L OC KOUT A UTO
95.00
(2413.0) 86 G R
86 G R
36.00 36.00 36.00 36.00 36.00 36.00 36.00 36.00 36.00 36.00 36.00 34
(914.4) (914.4) (914.4) (914.4) (914.4) (914.4) (914.4) (914.4) (914.4) (914.4) (914.4)
396.00
(10,058.4) 35
FRONT ELEVATIO N
37
38
39
40
41
42
43
22
G1 G2 G3 G4
32
Figure 40.5-5. Large Critical Power System—Multiple Generators Closed Transition and Load Shed/Add LV Complex Utility
33 and Generator Paralleling System
G1 G2 Gx
35 Utility
Utility Utility Tie Protection
Utility Tie Protection Typical
Gen Closed Transition
Closed Transition Generator
36 Paralleling and Breaker
Synch Paralleling and
Soft Load/Unload Soft Load/Unload
MV Generator Bus
37 Load Shed/Load Add
MV Gen Gen MV
Main Main Main Main
38 MV Bus A MV Bus B
40 Typical
Secondary
Substations
No Load Shed/Load Add
41 Open Transition Main-Tie-Main
Transfer or Closed Transition
Secondary Momentary Overlap for
42 Main
LV Bus A
Main-Tie-Main
LV Bus B
Tie
43 Typical LV Breaker
Figure 40.5-6. Large Critical Power System—Multiple Generators Closed Transition (Active Sync) and Load Shed/Add MV Complex Utility
and Generator Paralleling System
22
MV Generators X = Number of Units
G1 G2 Gx 23
Utility
Utility Utility Tie Protection
Utility Tie Protection Typical
Closed Transition Generator
Gen Closed Transition 24
Synch Paralleling and
Paralleling and Breaker
Soft Load/Unload Soft Load/Unload
MV Generator Bus
25
Load Shed/Load Add
MV Gen Gen MV
Main Main
Tie
Main Main 26
MV Bus A MV Bus B
Typical
Tie 31
LV Breaker Load Shed/Load Add
32
Figure 40.5-7. Large Critical Power System—Multiple Generators MV/LV Closed Transition and MV/LV Load Shed/Add MV Complex Utility
and Generator Paralleling System
33
Gen
Load Shed/Load Add 37
MV Gen MV
Main Field Installed Main Main
Main
MV Bus A Cable by Contractor MV Bus B 38
Typical Synch & Paralleling
MV Vacuum Closed Transition
Breaker Soft Loading/Unloading 39
Load Shed/Load Add
Figure 40.5-8. Large Critical Power System—Multiple Generators MV Only Closed Transition and MV/LV Load Shed/Add MV Complex Utility
and Generator Paralleling System
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43