System : 3 Phase 4 Wire

Supply Frequency : 50Hz

Panel Name : Main PCC Panel

Panel Type : Motor Control Center

Incomer Amps : 400A

Power Line Voltage : 415V

Control Voltage : 240V

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 1
ELECTRICAL CABINET DRAWINGS 20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
S.No. Sheet Title Revision S.No. Sheet Title Revision S.No. Sheet Title Revision
1 Cabinet System Details 31 61
2 List of Drawings 32 62
3 Control Elements Detail 33 63
4 Single Line Diagram 34 64
5 Incomer #1 Metering 35 65
6 Feeder No. 1, 250A FDR. 36 66
7 Feeder No. 2, 5.5KW DOL 37 67
8 Feeder No. 3, 11.2KW RDOL 38 68
9 Feeder No. 4, 22KW S/D 39 69
10 Feeder No. 5, 0.01A FDR. 40 70
11 Feeder No. 6, 0.01A FDR. 41 71
12 Feeder No. 7, 0.01A FDR. 42 72
13 Feeder No. 8, 0.01A FDR. 43 73
14 Feeder No. 9, 0.01A FDR. 44 74
15 Feeder No. 10, 0.01A FDR. 45 75
16 Termination Dwg Part 1 46 76
17 Termination Dwg Part 2 47 77
18 General Arrangement - External 48 78
19 General Arrangement - Internal 49 79
20 Bill of Quantity 50 80
21 51 81
22 52 82
23 53 83
24 54 84
25 55 85
26 56 86
27 57 87
28 58 88
29 59 89
30 60 90

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 2
20
LIST OF ALL DRAWINGS B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
A

Contactor Push Button Timer On-Delay Neutral Link Meters Power Contactor
NO Contact NO Contact NO Contact

I>> I>> I>>

Contactor Push Button Timer On-Delay MCB/MCCB/ACB MCCB/ACB Overload Relay


NC Contact NC Contact NC Contact Single Line Dwg

1 2 3
X4

Contactor Indicating Light Timer Switch Fuse Unit


ON: Green, Trip: Red SFU
Coil Fwd: Green, Rev: Blue Coil Single Line Dwg Motor

0 1

I>> I>> I>>

Wire/Cable Current Selector Switch MPCB Capacitor


Termination Transformer NO Contact Single Line Dwg MPCB Single Line Dwg

Power/Control Control Thermostat Contactor MCB TP Heater


Earth Transformer NC Contact Single Line Dwg Single Line Dwg

Sheet Number Reference: XX/YY Ferrul Number Reference: XXYY


XX: Sheet No, YY: Column No. XX: Sheet No, YY: Ferrul Number

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 3
20
ELEMENTS SYMBOLS B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
Incoming Cable
(185sqmm Cu)

400A,3P
MCCB

KWH ASS A

R,Y,B
2A Fuse
VSS V

250A 3P 25A 63A 80A 3P 2A 2A 2A 2A 2A 2A


MCCB 3P MCB 3P MCB MCCB 3P MCB 3P MCB 3P MCB 3P MCB 3P MCB 3P MCB

Cont. Cont. Cont.


AC3,12A AC3,22A AC3,32A

OL OL OL
6.3-10A 12.5-20A 16-25A

120sqmm Cu 4sqmm Cu 10sqmm Cu 10sqmm Cu 1sqmm Cu 1sqmm Cu 1sqmm Cu 1sqmm Cu 1sqmm Cu 1sqmm Cu
Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable

M1 M2 M3
F1 5.5KW 11.2KW 22KW F2 F3 F4 F5 F6 F7

250A Feeder for 5.5KW DOL for 11.2KW RDOL for 22KW Star-Delta for 0.01A Feeder for 0.01A Feeder for 0.01A Feeder for 0.01A Feeder for 0.01A Feeder for 0.01A Feeder for
Feeder No. 1 Feeder No. 2 Feeder No. 3 Feeder No. 4 Feeder No. 5 Feeder No. 6 Feeder No. 7 Feeder No. 8 Feeder No. 9 Feeder No. 10

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 4
20
SINGLE LINE DIAGRAM B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

Incoming Cable R1 06/02


(185sqmm Cu)
R Y B N Y1 06/02

Q5.1 B1 06/02
400A,3P
I>> I>> I>> MCCB N1 06/02

R1 Y1 B1 N1

B
0503 Y1 R1

0502 Y
Q5.2
0501 R 2A MCB
2A Fuse 0514 0515
ASS
0506
VSS A1 R
0504
R V1 Y CT
A TX5.1
Y V B 400/5A
0505 0507 0 415V/240V
B V2 A2 GND

0508
R 1S1
0509
1S2 0516 0517
Y 0510
KWH 2S1
0511 Q5.3
B 2S2
0512 4A MCB
3S1
N 3S2
0513

1 2

2 06/14

1 06/14

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 5
20
Incomer #1 Metering B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

05/39 R1 07/02 05/39 2 07/13

05/39 Y1 07/02

05/39 B1 07/02

05/39 N1 07/02

Q6.1
250A,3P
MCCB I>> I>> I>>

1A04
1A03
1A02
1A01

X6 1 2 3 4

To Feeder No. 1
250A

05/39 1 07/13

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 6
20
Feeder No. 1 B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

06/09 R1 08/02 06/25 2 08/13

06/09 Y1 08/02 Q7.2


2A SP MCB
06/09 B1 08/02
1B10

06/09 N1 08/02
OL7.1 OL7.1
Trip Ind. Trip Intlk

Q7.1 1B12 4
25A S7.1
3P MCB I>> I>> I>> Stop
Remote
1B13 5
1B03
1B02
S7.2
C7.1 1B01 Stop
3TF3110 Local
AC3 12A 1B14
1B06
1B05 1B11 6
S7.3 S7.4
1B04 Run Run
Local Rem. C7.1
OL7.1
3UA50 7
6.3-10A 1B09
1B08
1B07 1B15
1 2 3
X7
U1 V1 W1

M7.1
5.5KW H7.1 C7.1 H7.2
Trip Ind. Run Run

Feeder No. 2 06/25 1 08/13

07/25

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 7
5.5KW DOL for Feeder No. 2 20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

07/09 R1 09/02 07/25 2 09/13

07/09 Y1 09/02 Q8.2


2A SP MCB
07/09 B1 09/02
1C10

07/09 N1 09/02
OL8.1 OL8.1
Trip Ind. Trip Intlk

Q8.1 1C12 4
63A S8.1
3P MCB I>> I>> I>> Stop
Remote
1C13 5
1C03
1C02
S8.2
C8.1 1C01 Stop
3TF3300 Local
C8.2
AC3 22A 1C14
1C06
1C05 1C11 6 8
S8.3 S8.4 S8.4 S8.5
1C04 Fwd Rev Rev
Local Rem. C8.1 Local Rem. C8.2
OL8.1
3UA52 7 9
12.5-20A 1C09
1C15 1C17

1C08
C8.2 C8.1
1C07

1 2 3
X8
U1 V1 W1 1C16 1C18

M8.1
11.2KW H8.1 C8.1 H8.2 C8.2 H8.3
Trip Ind. Fwd Fwd Rev Rev

Feeder No. 3 07/25 1 09/13

08/28 08/25 08/20 08/33

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 8
11.2KW RDOL for Feeder No. 3 20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

08/09 R1 10/02 08/25 2 10/13

08/09 Y1 10/02 Q9.2


2A SP MCB
08/09 B1 10/02
1D14

08/09 N1 10/02
OL9.1 OL9.1
Trip Ind. Trip Intlk

1D16 7
Q9.1 S9.1
80A,3P Stop
MCCB I>> I>> I>> Remote
8
1D17
1D13
S9.2
1D03 Stop
1D02 Local
C9.1 1D01
1D18
3TF3400 C9.2 C9.3 9
AC3 32A S9.3 S9.4
1D06 1D12 Run Run
1D05 1D11 1D15 Local Rem. C9.1
1D04 1D10 10
1D19
OL9.1 1D19
3UA55
16-25A 1D09 T9.1 T9.1
C9.2 C9.3 C9.1 C9.2
1D08 Star Delta
1D07 1D21 1D24
1 2 3 4 5 6
X9 C9.2 C9.3
U1 V1 W1 1D20 1D23

1D22 1D25
M9.1
22KW H9.1 T9.1 C9.3 C9.1 H9.2 C9.2
Trip Ind. Star Main Run Delta
U2 V2 W2
08/25 1 10/13

09/23S 09/30 09/25 09/25 09/20 09/33


09/30D 09/28 09/23

Feeder No. 4

TITLE D DRG NO. SHEET


ABC Consultants & Engineers DWG/2014/05/01 9
22KW S/D for Feeder No. 4 C
20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

09/09 R1 11/02 09/25 2 11/13

09/09 Y1 11/02

09/09 B1 11/02

09/09 N1 11/02

Q10.1
2A
3P MCB I>> I>> I>>

1E04
1E03
1E02
1E01

X10 1 2 3 4

To Feeder No. 5
2A

09/25 1 11/13

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 10
20
Feeder No. 5 B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

10/09 R1 12/02 10/25 2 12/13

10/09 Y1 12/02

10/09 B1 12/02

10/09 N1 12/02

Q11.1
2A
3P MCB I>> I>> I>>

1F04
1F03
1F02
1F01

X11 1 2 3 4

To Feeder No. 6
2A

10/25 1 12/13

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 11
20
Feeder No. 6 B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

11/09 R1 13/02 11/25 2 13/13

11/09 Y1 13/02

11/09 B1 13/02

11/09 N1 13/02

Q12.1
2A
3P MCB I>> I>> I>>

1G04
1G03
1G02
1G01

X12 1 2 3 4

To Feeder No. 7
2A

11/25 1 13/13

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 12
20
Feeder No. 7 B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

12/09 R1 14/02 12/25 2 14/13

12/09 Y1 14/02

12/09 B1 14/02

12/09 N1 14/02

Q13.1
2A
3P MCB I>> I>> I>>

1H04
1H03
1H02
1H01

X13 1 2 3 4

To Feeder No. 8
2A

12/25 1 14/13

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 13
20
Feeder No. 8 B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

13/09 R1 15/02 13/25 2 15/13

13/09 Y1 15/02

13/09 B1 15/02

13/09 N1 15/02

Q14.1
2A
3P MCB I>> I>> I>>

1I04
1I03
1I02
1I01

X14 1 2 3 4

To Feeder No. 9
2A

13/25 1 15/13

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 14
20
Feeder No. 9 B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

14/09 R1 14/25 2

14/09 Y1

14/09 B1

14/09 N1

Q15.1
2A
3P MCB I>> I>> I>>

1J04
1J03
1J02
1J01

X15 1 2 3 4

To Feeder No. 10
2A

14/25 1

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 15
20
Feeder No. 10 B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
X6 1 2 3 4 X7 1 2 3 4 5 6 7 X8 1 2 3 4 5 6 7 8 9 X9 1 2 3 4 5 6 7 8 9 10 X10 1 2 3 4 X11 1 2 3 4

1D07
1D08
1D09
1D10
1D11
1D12
1D16
1D17
1D18
1D19
1A01
1A02
1A03
1A04

1B07
1B08
1B09
1B12
1B13
1B14
1B15

1C07
1C08
1C09
1C12
1C13
1C14
1C15
1C14
1C17

1E01
1E02
1E03
1E04

1F01
1F02
1F03
1F04
TITLE D DRG NO. SHEET
ABC Consultants & Engineers C
DWG/2014/05/01 16
TERMINATION DIAGRAM PART 1/2 20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
X12 1 2 3 4 X13 1 2 3 4 X14 1 2 3 4 X15 1 2 3 4
1H01
1H02
1H03
1H04
1G01
1G02
1G03
1G04

1J01
1J02
1J03
1J04
1I01
1I02
1I03
1I04

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 17
TERMINATION DIAGRAM PART 2/2 20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
ON OFF TRIP

1F5(1B) 2F7(1J)
225
Feeder No. 10, 0.01A FDR.
325
with 2A 3P MCB
Feeder No. 2, 5.5KW DOL

with 25A 3P MCB


2F6(1I)
225
Feeder No. 9, 0.01A FDR.
1F4(1A)
with 2A 3P MCB

300

Feeder No. 1, 250A FDR. 2F5(1H)


225
with 250A 3P MCCB Feeder No. 8, 0.01A FDR.

with 2A 3P MCB
ON OFF TRIP

1F3(1D)

2F4(1G)
Cable 325 Bus Bar 225 Cable
1625
Alley Chamber Feeder No. 7, 0.01A FDR.
Alley
Feeder No. 4, 22KW S/D with 2A 3P MCB
1700

with 80A 3P MCCB

2F3(1F)
225
1F2 R Y B Feeder No. 6, 0.01A FDR.

with 2A 3P MCB
350 A KWH V

2F2(1E)
225
Feeder No. 5, 0.01A FDR.

with 2A 3P MCB

1F1 FWD OFF REV

2F1(1C) TRIP

325
275

Incomer No. 1 Feeder No. 3, 11.2KW RDOL


400A 3P MCCB with 63A 3P MCB E
75

300 500 300 400 300


1800 400

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 18
GENERAL ARRANGEMENT - EXTERNAL 20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
Q15.1
225
C7.1
325 Q7.1

OL7.1

Q14.1
225

300 Q6.1

Q13.1
225

Panel Depth
400mm
C9.3 C9.2 C9.1 Q12.1 All Dim. in mm
Cable 325 Q9.1 Bus Bar 225 Cable
1625
Alley OL9.1
Chamber Alley

Q11.1
225

350

Q10.1
225

325 Q5.1
C8.2 C8.1
275 Q8.1

OL8.1

75

300 500 300 400 300


1800

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 19
GENERAL ARRANGEMENT - INTERNAL 20
B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED
S.No. Item Description Make Qty S.No. Item Description Make Qty S.No. Item Description Make Qty
1 MCCB , 400A 3P Siemens 1 No 31 Stand. P.B. (Red) with 1NC Teknik 3Nos 61
2 MCCB , 250A 3P Siemens 1 No 32 62
3 MCCB , 80A 3P Siemens 1 No 33 63
4 MCB , 63A 3P Siemens 1 No 34 64
5 MCB , 25A 3P Siemens 1 No 35 65
6 MCB , 2A 3P Siemens 6Nos 36 66
7 MCB, 2A DP Siemens 1 No 37 67
8 MCB, 4A DP Siemens 1 No 38 68
9 MCB, 2A SP Siemens 3Nos 39 69
10 Contactor 32A, 3TF3400 Siemens 3Nos 40 70
11 Contactor 22A, 3TF3300 Siemens 2Nos 41 71
12 Contactor 12A, 3TF3110 Siemens 1 No 42 72
13 Star Delta Timer Siemens 1 No 43 73
14 Neutral Link Reputed 8Nos 44 74
15 O/L 3UA55, 16-25A Siemens 1 No 45 75
16 O/L 3UA52, 12.5-20A Siemens 1 No 46 76
17 O/L 3UA50, 6.3-10A Siemens 1 No 47 77
18 CT 400/5A AE 3Nos 48 78
19 Ammeter AE 1 No 49 79
20 Ammeter Sel Switch Salzer 1 No 50 80
21 Voltmeter AE 1 No 51 81
22 Voltmeter Sel Switch Salzer 1 No 52 82
23 KWH Meter AE 1 No 53 83
24 Fuse with Fuse Base 2A Siemens 3Nos 54 84
25 Control TX 415/240V Reputed 1 No 55 85
26 Ind Light Red, 240VAC Teknik 4Nos 56 86
27 Ind Light Yellow, 240VAC Teknik 1 No 57 87
28 Ind Light Blue, 240VAC Teknik 1 No 58 88
29 Lum. P.B. (Green) with 1NO Teknik 3Nos 59 89
30 Lum. P.B. (Blue) with 1NO Teknik 1 No 60 90

TITLE D DRG NO. SHEET


ABC Consultants & Engineers C
DWG/2014/05/01 20
20
BILL OF QUANTITY B
CUSTOMER REV
A 18.04.17 DRAWINGS BUILT Mukesh Jha USER M/S Tek Smithe
This drawing is submitted only for confidential use. It may not be copied, printed A
or submitted to third parties without prior permission of ABC Consultants & Engineers REV DATE MODIFICATION DRAWN CHECKED

You might also like