IHITC- ANOMALIES IN ENGINEERING WORKS

Sr. No. Items/location Observations


Laundry
1 Ro plant Water tank Float Valve issue
2 Steamers Pipes leakages
3 Electric Sheet Flooring Not present
4 Laundry washer Buzzer not installed
5 Hydro Extractor Limit switch is not installed
6 Hydro Extractor Digital hour meter is not installed
7 Utility Ironer Pressure Switch controller not installed
8 Flatwork Ironer Emergency Button not installed
9 Steam Generator Steam Filter not installed
Control Room
10 Control Panel Keys are not handed over
11 2 X Eight Ton ACs is required for the control room for cooling purpose
Control Room
of electrical equipment.
12 Partition wall sandwich panel between HT and LT Section with Glass
Control Room
panes to minimize the heat loss of ACs
13 Exhaust Fans Making Mechanical Noises
14
15 Exhaust Fans No Louvers
16 Ground Surface During Rainfall Water Penetrate
17 Wall Partition No partition between transformers and panels, high inside temperature
Genset
18 Oil storage Labelling missing
19 Fuel testing Testing Kit/ Lab Required
20 Generator Generators are not properly synchronized. Generator runs on no load /under
synchronization load in summer
21 Diesel Contractor Details Required

22 Cabin for Operators Missing


23 Software Calibration Missing
Application/Program
(Module Controlling)
24 Generator Tools Kits Missing
25 Services Details of last service performed
Water Pump Room
26 Cabin For Operator not finished
Sewerage Treatment Plant
27 Not Functional
28 Main Control Panel Fitting Required

1
IHITC- ANOMALIES IN ENGINEERING WORKS

29 No Ventilation, No Exhaust Fans


30 Hour Meters in AC’s Missing
Incinerator Room
31 Incinerator Incinerators can’t handle more than 50 patients.
Plumbing
Items Observations
Radiology
32 Wash Basin Not OK
Laboratory
33 Washbasin (Hematology) Not Installed (12 in Nos.)
Unit-4
34 Muslim Shower Missing
35 Muslim Shower Head Missing
Sewerage
36 Sewerage Line No proper Connections
37 Main Sewerage Line No proper connection and slopes
38 Doctors Room 4 Due to the design issues of sewerage system of the hospital, a
blockage has occurred in the Sewerage manhole behind of doctor’s
room 4. Due to this issue washroom of room 4 has been choked.

39 Sewerage line Sewerage line slope issues.


40 Sewerage Manholes Sewerage manholes are full of foams and wooden plies which is
causing blockage.
Water Plant Room
41 Floor No Flooring, Required Cleaning, Mechanical Equipment Present
(Elbows, Pipes)
42 Water Supply pipe line No bypass valve is given for fresh water pipeline in case of
maintenance
43 Water Supply pipe line Gate valve are leaking in plant room.

44 Handing over and Vacating of Quarters inside STP Premises from residents is needed
Complete Locking Down to avoid theft risks
of STP Premises
45 Wash Rooms/Toilets At several places Muslim showers, cocks are missing. Unit 4, ward B
Missing Items
46 Fire Hydrants: Hose are Hose is missing in Ward A
Missing
47 Fire Hydrants: No Hose No Hose Pipe Cabinet outside of Building
Pipe Cabinet outside of
Building
48 Leakages in patients Leakages in patients kitchen causes not only nuisance but increase
Kitchen efforts of House Keeping Staff for drying the leaked water.
49 Door Closers and Door It is mere 2month old building and Door Closers and Door Locks are

2
IHITC- ANOMALIES IN ENGINEERING WORKS

Locks not working at some places.


Door Closers also missing at vital doors like Admin Block Side Door of
Changing Room
50 Doctors Room 4 Due to the design issues of sewerage system of the hospital, a
blockage has occurred in the Sewerage manhole behind of doctor’s
room 4. Due to this issue washroom of room 4 has been choked.

51 Sewerage line Sewerage line slope issue

52 Doctors Room Central Laboratory wastage pipe is passing through sewerage manhole which
Space causes blocking
53 Behind Admin building Sewerage line is leaking

54 There is no way to disassemble Water Suction motors inside plant


room as it is welded with pipe
55 Underground Tank and The underground water tank is 12 feet deep and there are foot valves
Plant Room. installed with 4 and 5 inch MS Pipe. In case of changing foot valve
there Is no flange attached with pipe and the pipe has to be cut for
maintenance
56 Overhead water tank Rain water stays in the surroundings of Overhead Water tank which is
outside the fence. It can damage the walls of tank
57 All wards Floor sheet is damaged at several places.

58 UPS Room Door alignment is out.

59 Laundry Room MS pipe of steam generator needs thermal coating

Sewerage Treatment Unit (Not Functioning)


60 STP Chemical dosing is not done.

Safety Issues at Roof and Rainwater Drainage and Stagnation of Water in Alleys
Items Observations
61 All Ward Alleys No slope, gradient, pitch is maintained in alleys, it can cause growth of
flies, mosquitoes, fungus or other vectors. Very dangerous for hospital
environment. It can cause Dengue growth.
62 Rain water is not drained by natural gravity flow and stored on roof
Roof Drainage
which can cause generation of vectors and dengue.
66 Insects Screens for windows Insect screens are not provided for the open able windows.
67 Toilets in Doctors cafeteria are not provided with natural and
Ventilation Issues
mechanical ventilation
68 Pump room, Oxygen room and incinerator room floor is not leveled.
Floor Leveling Issues Rain water stands inside these rooms which can cause short
circuiting.

3
IHITC- ANOMALIES IN ENGINEERING WORKS

Security
Observations

Main Gate Fence at the back of the security guard room is missing.

69 Metal Detector Gate is missing

70 Bio Security Gate is missing

71 Boundary Fence is broken at several locations

72 CC TV Camera Surveillance There are many blind spots are present in the building. 32 CCTV
Blind Spots cameras are required.

Janitorial Services
Observations

73 Ward Entrances Commercial Foot Mud Catcher required at both entrances

74 Hospital Building Separate Bins are required in different colors for Metals, Glass,
Plastics and Paper

Landscaping
Observations

75 Area behind Dr Room Grass in several areas could not grow

Electrical
  Items Observations
76 Earth leakage Breaker Earth leakage Breaker missing in all DPs.
77 Earth Arresting Module Earth Arresting Module missing
78 Public Address System Not Functioning
79 Electric Distribution Panel of Electric Distribution Panel of Heaters are Hidden in Ceiling. Once on
Heaters Hidden in Ceiling in 13-14th August, its turning on by some FWO/NDMA Staff by mistake
minor OT caused fire/smoke which was suppressed by Service Square Staff.
Those panels should be installed in walls and clearly visible and
accessible to operation and maintenance staff.
80 Earthling & Grounding Earth Arrester Module is not installed

4
IHITC- ANOMALIES IN ENGINEERING WORKS

81 Fire Alarm System Fire Alarm System is not provided with Ring System Wiring.

82 Mosque Exposed Electric


Mosque Exposed Electric wire
wire

83   Majority of outside receptacles are missing weatherproof covers.

84 Electric Control Room No shade from rainwater protection


85  Electric Control Room Rain Water can enter from underneath the base of wall and top of
plinth. It can cause malfunctioning

86  Electric Control Room Holes at base of wall too big to prevent entry of rodents and reptiles.
They can cause biting of cables and subsequent malfunctioning

87  Electric Control Room No Protection Shield on Bus Bars


88  Electric Control Room All Panels are not properly insulated and dressed

89  Electric Control Room Safety glass missing


90  Electric Control Room Not waterproof
91  Electric Control Room No spares which can be used in emergency breakdown

92  Electric Control Room Electric sheet on floor is missing


93  Electric Control Room Base cover plate is missing in majority of electrical panels

94  Electric Control Room No proper covering and plugging of ducting at base to protect entry of
rodents, reptiles and insects. All animals are conductor and Can cause
short circuiting

95  Electric Control Room Acoustically not insulated properly


96 Electric Manhole Rain Water There are no concrete fillings around electric wires pipes. Rain water

5
IHITC- ANOMALIES IN ENGINEERING WORKS

Flooding enters through pipes. Each rain costs us 10 Liter petrol and 4-8 hours
of 3 Staff resources. Even then risk of short circuiting cannot be
avoided.
97 Mortuary •  16 mm cable is openly laid without dressing

98 Oxygen room •  Safety glass is missing, fire alarm not activated

99 Water Pump Room •  Electric Cable duct not dressed


100   •  Safety glass missing
101 Patient Kitchen •  Cables are not dressed

102   •  Electric panel safety glass missing


103   •  No air exhaust system
104   •  Joints of earthling cable not connected
105 Rodent Entry and Catching •  Rodent rat, hamster, chinchilla etc. entry and catching specially in
Traps between roofing proper rodent in all hospital to prevent

106   •  No Baiting Stations


107   •  No Rodent traps in between Roof and Ceiling which can cause any
cable cutting and short circuiting

108 Tube Well •Electrical cable is not underground.

109 UPS •  All UPS -Not Functioning


110 Streetlights/ Outdoor Lights •  Half are not connected and energized

111 General Earthling Only 12 grounding/ earthling locations are connected while 36 are not
connected

112 DB at Mosque No dressing and safety glass. No Spare wire

113 DB at Minor OT •  No dressing and safety glass. No Spare wire

114 Minor OT (UPS) •  No dressing No Spare wire


115 Lab and Emergency •  No dressing and safety glass. No Spare wire

116 Main UPS panel •  No safety glass No Spare wire


117 OG-2 Panel Lock handle issue
118 ATS-1 Panel Extra 230V AC relays required in case of emergency

6
IHITC- ANOMALIES IN ENGINEERING WORKS

119 Unit # 1 •  No dressing, No safety glass, No thimble, no change indicator and no


mechanical interlocking in MCC Breaker button and no cover sheet.
No Spare wire

120 Unit # 2 •  No dressing, safety glass, thimble, no mechanical interlocking in


MCC Breaker No Spare wire

121 Unit # 3 •  No dressing, safety glass, no thimble, no mechanical interlocking in


MCC
122   •   
Breaker No Spare wire (Not resolved)
123 Unit # 4 •  No safety glass, No thimbles, No spare wire

124 Unit # 5 •  No dressing, No safety glass, No thimbles, No spare wire

125 Ward A •  No thimbles, no safety glass, No Spare wire

126 Ward B and Corridor •  No dressing, No safety glass, No thimbles, No Spare wire

127 Streetlights •  No Sensor or No Master Control


128 Main ACs All Controllers are required to be reset/ restart on each time electricity
goes off
129 Stabilizer/Converter From 220 Not Provided even for the single medical equipment
To 110
130 Sockets at Bed side Not Functional
131 HT/LT •  Tripping LT and HT tripping is too frequent on low voltage by
WAPDA
132 Roof Top Roof Top Heating Panels, Locks and Doors are out of order, not water
protected

133 Lighting System Street lights panel lock keys are missing and some panels are
damaged.

134 Lighting System 9 Street lights are not working.

135 Lighting System Flood lights not working.

7
IHITC- ANOMALIES IN ENGINEERING WORKS

136 Ward B DB Breaker contactor ( kanghi) of Electrical panel of ward B is burnt due
to sparking.

137 Ward B DB, Ward A DB, Unit Water Heater breakers are not working
5 Electrical room,

138 Lighting System 1 Search light near mosque is not working

139 Lighting System Unit 4 electric room ceiling light is not working

140 Fire Alarm System Unit 1 fire alarm glass of MCB is still broken.

141 Control Room UPS of control room display issue

142 Electric Manhole Electric manhole is missing near underground water tank as wires are
naked and short circuit can happen.

143 Ward A, Ward B Joint Electrical Connection of washrooms with room ceiling lights.
When room light is turned off, washroom light also turns off.

144 Ward A, Ward B, Light plug electrical supply issue.

145 Electrical Connection Light plug and light issues in Biomedical Electrical bed panels inside
wards, rooms, and ICUs.

146 Unit 1 Light plugs for geysers issues

Heating, Ventilation and Air conditioning


147 Split AC Drain Pipe Outlets of Admin Block Split AC drain pipes are left in toilet due to
which water spreads in rooms and corridors.

148 AC panel issues Variable Frequency Drive panels are manual drive. They should be
auto drive.

8
IHITC- ANOMALIES IN ENGINEERING WORKS

149 Refurbished/Used ACs We have doubt on 4 ACs are Refurbished/Used

150 Trane Unit Stairs for Packaged air conditioning units have blocked end

151 Building Stairs No safety railing for stairs and walking platform for PACUs.

152 Building Stairs Stairs are straight and dangerous for moving equipment.

153 PACU Unit 3 Unit 5 Automatic Modular of Unit 3 euro Aire and Unit 5 euro Aire not
functional
154 Unit 1 SKM PACU SKM PACU of unit 1 thermostat not working and

155 Unit 2 SKM PACU Compressor trips after heating(becomes out of service)

156 Control Room UPS room UPS room split ac refrigerant issue and remote missing

157 Mortuary Unit Coverlid/protection of semi sealed Copland unit is missing.

158 Service Square Residences No heating arrangement

159 Service Square Residences No cooling arrangement

General
S.No Item/Location Description

160 Hospital Building No sufficient toilets for visitors

161 Hospital Building No toilets for kitchen staff.

IHITC Network infrastructure


Radiology
S.No Description Location IP Feedback

9
IHITC- ANOMALIES IN ENGINEERING WORKS

net port not working, NO POWER


162 Computer MRI Room 192.168.100.101
OUTLET
net port not working, NO POWER
163 Computer Control Room 192.168.100.102
OUTLET
net port Not functional , NO
164 Computer CT Scan 192.168.100.103
POWER OUTLET
165 Computer Office 192.168.100.104 net port not working

net port not working, NO POWER


166 Computer X-Ray 1 192.168.100.105
OUTLET

Unit: 1
S.No Description Location IP Status
167 Computer ICU Ward 192.168.100.106 Net port Not functional

Unit: 5
 
S.No Description Location IP Feedback
170 Computer ICU Ward 192.168.100.120 Not functional
192.168.2.18 Ext No
171 IP Phone Reception Not functional
1052

Ward: A
S.No Description Location IP Feedback

172 IP Phone Nurses Room 192.168.2.19 Ext No 1053 Not functional

Minor-OT
S. No Description

173 Data Port 1 Minor-OT-1 not working

10
IHITC- ANOMALIES IN ENGINEERING WORKS

174 Data Port 10 Minor-OT not working cross configure


175 2X Empty Data Ports Minor-OT
176 Empty Voice Port Minor-OT

IT/NETWORK-General Issues
177 No proper setting of any switch in RACK
178 Switches are not mounted in the rack properly
179 CCTV cables at main door are exposed, not properly waterproofed. Security point Highly Risky As
shown in the figure No. 3
180 Cables inside building are required to be properly in runway/ducting inside Ceiling
181 All outsides cameras need proper water proofing setup
182 Wires are open in celling
183 Empty Voice Port Minor-OT
184 Nurse Call System setup is not properly tagged and installed
185 Terminals of Nursing Caller System are not properly mounted just hang behind LCD
186 NVR failure there is no alternative for access & backup of camera if one goes down
187 Require backup NVR in case of main NVR failure to recording
188 PTZ camera cables are not safely housed
189 IP telephone are only working on POE no Power adapters
190 HDMI Cables main reception is damaged
191 Routers, Firewall, Wireless Access points are not Available, no internet Access
192 PA system speakers are not located in admin block as per site drawings
193 Fiber Optical cables are exposed without any protection Figure 4
194 Door access systems are required at ICU Units & Wards
195 CCTV cameras should be increased
196 Manuals and software applications are required for the CCTV, Windows & Nursing system software
etc.
197 Nursing call button Cables on Ward B bed 119, 214, 231 & 241 are damaged. (not resolved)
198 Reception net Port no 2 is not working

199 ICU wards net port no 4 is not working on Unit 4