IHITC- ANOMALIES IN ENGINEERING WORKS
44 Handing over and Vacating of Quarters inside STP Premises from residents is needed
Complete Locking Down to avoid theft risks
of STP Premises
45 Wash Rooms/Toilets At several places Muslim showers, cocks are missing. Unit 4, ward B
Missing Items
46 Fire Hydrants: Hose are Hose is missing in Ward A
Missing
47 Fire Hydrants: No Hose No Hose Pipe Cabinet outside of Building
Pipe Cabinet outside of
Building
48 Leakages in patients Leakages in patients kitchen causes not only nuisance but increase
Kitchen efforts of House Keeping Staff for drying the leaked water.
49 Door Closers and Door It is mere 2month old building and Door Closers and Door Locks are
2
IHITC- ANOMALIES IN ENGINEERING WORKS
52 Doctors Room Central Laboratory wastage pipe is passing through sewerage manhole which
Space causes blocking
53 Behind Admin building Sewerage line is leaking
Safety Issues at Roof and Rainwater Drainage and Stagnation of Water in Alleys
Items Observations
61 All Ward Alleys No slope, gradient, pitch is maintained in alleys, it can cause growth of
flies, mosquitoes, fungus or other vectors. Very dangerous for hospital
environment. It can cause Dengue growth.
62 Rain water is not drained by natural gravity flow and stored on roof
Roof Drainage
which can cause generation of vectors and dengue.
66 Insects Screens for windows Insect screens are not provided for the open able windows.
67 Toilets in Doctors cafeteria are not provided with natural and
Ventilation Issues
mechanical ventilation
68 Pump room, Oxygen room and incinerator room floor is not leveled.
Floor Leveling Issues Rain water stands inside these rooms which can cause short
circuiting.
3
IHITC- ANOMALIES IN ENGINEERING WORKS
Security
Observations
Main Gate Fence at the back of the security guard room is missing.
72 CC TV Camera Surveillance There are many blind spots are present in the building. 32 CCTV
Blind Spots cameras are required.
Janitorial Services
Observations
74 Hospital Building Separate Bins are required in different colors for Metals, Glass,
Plastics and Paper
Landscaping
Observations
Electrical
Items Observations
76 Earth leakage Breaker Earth leakage Breaker missing in all DPs.
77 Earth Arresting Module Earth Arresting Module missing
78 Public Address System Not Functioning
79 Electric Distribution Panel of Electric Distribution Panel of Heaters are Hidden in Ceiling. Once on
Heaters Hidden in Ceiling in 13-14th August, its turning on by some FWO/NDMA Staff by mistake
minor OT caused fire/smoke which was suppressed by Service Square Staff.
Those panels should be installed in walls and clearly visible and
accessible to operation and maintenance staff.
80 Earthling & Grounding Earth Arrester Module is not installed
4
IHITC- ANOMALIES IN ENGINEERING WORKS
81 Fire Alarm System Fire Alarm System is not provided with Ring System Wiring.
86 Electric Control Room Holes at base of wall too big to prevent entry of rodents and reptiles.
They can cause biting of cables and subsequent malfunctioning
94 Electric Control Room No proper covering and plugging of ducting at base to protect entry of
rodents, reptiles and insects. All animals are conductor and Can cause
short circuiting
5
IHITC- ANOMALIES IN ENGINEERING WORKS
Flooding enters through pipes. Each rain costs us 10 Liter petrol and 4-8 hours
of 3 Staff resources. Even then risk of short circuiting cannot be
avoided.
97 Mortuary • 16 mm cable is openly laid without dressing
111 General Earthling Only 12 grounding/ earthling locations are connected while 36 are not
connected
6
IHITC- ANOMALIES IN ENGINEERING WORKS
126 Ward B and Corridor • No dressing, No safety glass, No thimbles, No Spare wire
133 Lighting System Street lights panel lock keys are missing and some panels are
damaged.
7
IHITC- ANOMALIES IN ENGINEERING WORKS
136 Ward B DB Breaker contactor ( kanghi) of Electrical panel of ward B is burnt due
to sparking.
137 Ward B DB, Ward A DB, Unit Water Heater breakers are not working
5 Electrical room,
139 Lighting System Unit 4 electric room ceiling light is not working
140 Fire Alarm System Unit 1 fire alarm glass of MCB is still broken.
142 Electric Manhole Electric manhole is missing near underground water tank as wires are
naked and short circuit can happen.
143 Ward A, Ward B Joint Electrical Connection of washrooms with room ceiling lights.
When room light is turned off, washroom light also turns off.
145 Electrical Connection Light plug and light issues in Biomedical Electrical bed panels inside
wards, rooms, and ICUs.
148 AC panel issues Variable Frequency Drive panels are manual drive. They should be
auto drive.
8
IHITC- ANOMALIES IN ENGINEERING WORKS
150 Trane Unit Stairs for Packaged air conditioning units have blocked end
151 Building Stairs No safety railing for stairs and walking platform for PACUs.
152 Building Stairs Stairs are straight and dangerous for moving equipment.
153 PACU Unit 3 Unit 5 Automatic Modular of Unit 3 euro Aire and Unit 5 euro Aire not
functional
154 Unit 1 SKM PACU SKM PACU of unit 1 thermostat not working and
155 Unit 2 SKM PACU Compressor trips after heating(becomes out of service)
156 Control Room UPS room UPS room split ac refrigerant issue and remote missing
General
S.No Item/Location Description
9
IHITC- ANOMALIES IN ENGINEERING WORKS
Unit: 1
S.No Description Location IP Status
167 Computer ICU Ward 192.168.100.106 Net port Not functional
Unit: 5
S.No Description Location IP Feedback
170 Computer ICU Ward 192.168.100.120 Not functional
192.168.2.18 Ext No
171 IP Phone Reception Not functional
1052
Ward: A
S.No Description Location IP Feedback
Minor-OT
S. No Description
10
IHITC- ANOMALIES IN ENGINEERING WORKS
IT/NETWORK-General Issues
177 No proper setting of any switch in RACK
178 Switches are not mounted in the rack properly
179 CCTV cables at main door are exposed, not properly waterproofed. Security point Highly Risky As
shown in the figure No. 3
180 Cables inside building are required to be properly in runway/ducting inside Ceiling
181 All outsides cameras need proper water proofing setup
182 Wires are open in celling
183 Empty Voice Port Minor-OT
184 Nurse Call System setup is not properly tagged and installed
185 Terminals of Nursing Caller System are not properly mounted just hang behind LCD
186 NVR failure there is no alternative for access & backup of camera if one goes down
187 Require backup NVR in case of main NVR failure to recording
188 PTZ camera cables are not safely housed
189 IP telephone are only working on POE no Power adapters
190 HDMI Cables main reception is damaged
191 Routers, Firewall, Wireless Access points are not Available, no internet Access
192 PA system speakers are not located in admin block as per site drawings
193 Fiber Optical cables are exposed without any protection Figure 4
194 Door access systems are required at ICU Units & Wards
195 CCTV cameras should be increased
196 Manuals and software applications are required for the CCTV, Windows & Nursing system software
etc.
197 Nursing call button Cables on Ward B bed 119, 214, 231 & 241 are damaged. (not resolved)
198 Reception net Port no 2 is not working
11
IHITC- ANOMALIES IN ENGINEERING WORKS
12