The manufacture shall mention the equivalent IEEE model or PSS/E model.

Parameters that
confirms to Salient Pole Generator Model (GENSAL) or Round Rotor Generator Model
(GENROU) model of PSS/E shall be provided.

S.No. Parameter of Generator and Turbine (GENSAL) Remarks


1 Rated terminal voltage (KV) Major
2 Rated MVA and MW (Major) Major
3 Inertia constant (MW sec / MVA) H Major
4 Minimum stable loading (MW) Major
5 Reactive power capability curve. (Major) Major
Additional capacity (MW) obtainable from
Generating Units in excess of Net Declared
6 Capability Major
Derated capacity (MW) on a monthly basis, if
7 applicable; Minor
8 Direct axis synchronous reactance (% on MVA) Xd. Major
9 Direct axis transient reactance (% on MVA) X’d. Major
10 Direct axis sub‐ transient reactance (% on MVA) X’’d. Major
Quadrature axis synchronous reactance (% on MVA)
11 Xq. Minor
Quadrature axis transient reactance (% on MVA)
12 x’q. Minor
Quadrature axis sub‐transient reactance (% on MVA)
13 X”q. Minor
Direct axis transient open circuit time constant (sec)
14 T’d0. Major
Direct axis sub‐transient open circuit time constant
15 (sec) T”do. Major
Quadrature axis transient open circuit time constant
16 (sec) T’q0. Minor
Quadrature axis transient open circuit time constant
17 (sec) T”q0. Minor
18 Stator Resistance (Ohm) Ra. Major
19 Stator Leakage reactance (Ohm) xq. Major
20 Stator time constant (Sec). Minor
Short circuit and Open circuit saturation
characteristics curve of the generator for various
21 terminal voltages. Major
22 Type of turbine. Major
23 Operating Head (Mtr) Major

1
Parameter of Excitation Control System
The manufacture shall mention the equivalent IEEE model or PSS/E model. Parameters that
confirms to Simplified Exciter Models (SEXS) model of PSS/E shall be provided.

S.No. Parameter of Excitation Control System (SEXS) Value Remarks


1 Type of excitation. Brushless Major
2 Maximum field voltage. 121.8 Major
3 Minimum field voltage. 3.7 Major
4 Rated field voltage. 45.3 Major

Details of excitation loop in block diagrams showing


5 transfer functions of individual elements using I.E.E.E Major
Synbols
6 DC gain of excitation loop. Major

7 Dynamic characteristics of over‐excitation limiter Minor

8 Dynamic characteristics of under‐excitation limiter. Minor

Block Diagram for Simplified Exciter Models (SEXS) model is as shown below:
Parameter of Governor
The manufacture shall mention the equivalent IEEE model or PSS/E model. Parameters that
confirms to Hydro Governor Model (HYGOV) model of PSS/E shall be provided.

S.No. Parameter of Governor (HYGOV) Value Remarks


1 Governor average gain (MW/HZ) or turbine gain (At) Major
2 Time constant of water governor valve. Tr Major
3 Governor valve opening limits. (Gmax & Gmin) Minor
4 Governor valve rate limits. (Velocity Limit ± Velm, Velocity Limit. Minor
5 Water time constant. (Major) Tw Major
Governor block diagram showing transfer functions of individual
6 elements using I.E.E.E symbols or PSS/E model.
Major
7 Permanent droop (R) Major
8 Temporary droop (r) Major
9 Filter time constant (Tf) Major
10 Servo time constant (Tg) Major
Parameter of Transmission Line

S.No. Parameters of Transmission Line Value Remarks


1. Name of conductor and length of transmission line
Thermal Limit (Ambient Temp. 40ºC (Terai) , 30ºC (Hill)),
2. Max Temp 80ºC
3. R, X, B Parameter of transmission line
Parameter of Transformer

S.No. Parameters of Transformer Remarks


1. Voltage Level
2 Continuous Rating (MVA)

3 Impedance ( X and R)
3 Vector group
4 Tap changing facility