DESIGNATION: PP-BARRACKS MOUNTING: SURFACE

SYSTEM: 400/230 VOLTS 3F, 3 WIRE + N + GROUND, 60Hz ENCLOSURE: NEMA - 1


MIN. I.C 25 kA FEED: EXISTING SPARE CIRCUIT BREAKER
LOCATION: B3 FROM BUILDING EXISTING PANELBOARD

CONNECTED LOAD
CKT. OVERCURRENT CONDUCTOR RACEWAY
LOAD DESCRIPTION AMPERE REMARKS
NO. VA D.F.
3F FAN FBN FCN AT AF P CODE TYPE CODE TYPE
1 ECB-TCEF-01 3,750 0.80 5.41 20 100 3 X3.5 THHN X3.5 IMC
2 ECB-TCEF-02 1,875 0.80 2.71 20 100 3 X3.5 THHN X3.5 IMC
3 ECB-TCEF-03 9,375 0.80 13.53 40 100 3 X8 THHN X8 IMC
4 ECB-TCEF-04 9,375 0.80 13.53 40 100 3 X8 THHN X8 IMC
5 ECB-CCSF-02 6,875 0.80 9.92 30 100 3 X5.5 THHN X5.5 IMC
6 ECB-CCSF-03 6,875 0.80 9.92 30 100 3 X5.5 THHN X5.5 IMC
7 ECB-CCSF-04 2,750 0.80 3.97 20 100 3 X3.5 THHN X3.5 IMC
8 SPARE 0.80 20 100 3
9 ECB-CCSF-01 688 0.80 2.99 20 100 1 S3.5 THHN S3.5 IMC
10 OSC-FANS 888 0.80 3.86 20 100 1 S3.5 THHN S3.5 IMC
11 OSC-FANS 888 0.80 3.86 20 100 1 S3.5 THHN S3.5 IMC
12 OSC-FANS 888 0.80 3.86 20 100 1 S3.5 THHN S3.5 IMC
13 OSC-FANS 888 0.80 3.86 20 100 1 S3.5 THHN S3.5 IMC
14 OSC-FANS 888 0.80 3.86 20 100 1 S3.5 THHN S3.5 IMC
15 OSC-FANS 888 0.80 3.86 20 100 1 S3.5 THHN S3.5 IMC
16 OSC-FANS 888 0.80 3.86 20 100 1 S3.5 THHN S3.5 IMC
17 ECB-ACCU OFFICE 1 1,865 0.80 8.11 20 100 1 S3.5 THHN S3.5 IMC
18 ECB-ACCU OFFICE 2 1,865 0.80 8.11 20 100 1 S3.5 THHN S3.5 IMC
19 ECB-ACCU OFFICE 3 1,865 0.80 8.11 20 100 1 S3.5 THHN S3.5 IMC
20 ECB-ACCU OFFICE 4 1,865 0.80 8.11 20 100 1 S3.5 THHN S3.5 IMC
21 ECB-ACCU OFFICE 5 1,865 0.80 8.11 20 100 1 S3.5 THHN S3.5 IMC
22 ECB-ACCU OFFICE 6 1,865 0.80 8.11 20 100 1 S3.5 THHN S3.5 IMC
23 Lighting 1,000 0.80 4.35 20 100 1 S3.5 THHN S3.5 IMC
24 Power 1,800 0.60 7.83 20 100 1 S3.5 THHN S3.5 IMC
25 Power 1,800 0.60 7.83 20 100 1 S3.5 THHN S3.5 IMC
26 SPARE - 20 100 1
TOTAL 63,565 0.79 59.00 30.78 36.11 31.76 42

DEMAND FACTOR : 0.79 MAIN CB : 100 AT 100 AF 3 P 400 V


DEMAND VA: 50,132 FEEDER:
. CODE: X30 TYPE: THNN RACEWAY: IMC
IT = 75.01 AMPS

NOTE: 1. PROVIDE 100% NEUTRAL COPPER BUSBAR.


2. PROVIDE GROUNDING COPPER BUSBAR COMPLYING WITH THE LOCAL CODE REQUIREMENT.
3. WIRE BENDING CLEARANCE(S) SHALL COMPLY WITH THE LOCAL CODE REQUIREMENT.
4. PROVIDE DIGITAL POWER METER FOR BILLING PURPOSES