Plug-in surge arrester, in accordance with Type 2/Class II, for 3-phase power supply networks with separate N
and PE (5-conductor system: L1, L2, L3, N, PE), with remote indication contact.
GTIN
GTIN 4046356948173
Weight per Piece (excluding packing) 390.000 g
Custom tariff number 85363030
Country of origin Germany
Technical data
Dimensions
Height 97.9 mm
Width 49.2 mm
Depth 74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch 2.7 Div.
06/12/2018 Page 1 / 10
https://www.phoenixcontact.com/sg/products/2905340
General
IEC test classification II
T2
EN type T2
IEC power supply system TN-S
TT
Mode of protection L-N
L-PE
N-PE
Mounting type DIN rail: 35 mm
Color light grey RAL 7035
traffic grey A RAL 7042
Housing material PA 6.6-FR 20% GF
PBT-FR
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, two-section, divisible
Number of positions 4
Surge protection fault message Optical, remote indicator contact
Protective circuit
Nominal voltage UN 240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N) 350 V AC
Maximum continuous operating voltage UC (L-PE) 350 V AC
Maximum continuous voltage UC (N-PE) 264 V AC
Rated load current IL 40 A (Biconnect M4 fork-type cable lug 6 mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs 20 kA
Maximum discharge current Imax (8/20) µs 40 kA
Follow current interrupt rating Ifi (N-PE) 100 A (264 V AC)
06/12/2018 Page 2 / 10
https://www.phoenixcontact.com/sg/products/2905340
Indicator/remote signaling
Switching function PDT contact
Operating voltage 5 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current 5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection method Plug-in/screw connection via COMBICON
Screw thread M2
Tightening torque 0.25 Nm
Stripping length 7 mm
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
Conductor cross section solid 0.14 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Connection data
Connection method Screw connection
06/12/2018 Page 3 / 10
https://www.phoenixcontact.com/sg/products/2905340
UL specifications
SPD Type 4CA
Maximum continuous operating voltage MCOV (L-L) 700 V AC
Maximum continuous operating voltage MCOV (L-N) 350 V AC
Maximum continuous operating voltage MCOV (L-G) 350 V AC
Maximum continuous operating voltage MCOV (N-G) 264 V AC
Nom. voltage 240/415 V AC
Mode of protection L-L
L-N
L-G
N-G
Power distribution system 3Y
Nominal frequency 50/60 Hz
Measured limiting voltage MLV (L-L) 3280 V
Measured limiting voltage MLV (L-N) 2000 V
Measured limiting voltage MLV (L-G) 2080 V
Measured limiting voltage MLV (N-G) 950 V
Nominal discharge current In (L-L) 20 kA
Nominal discharge current In (L-N) 20 kA
Nominal discharge current In (L-G) 20 kA
Nominal discharge current In (N-G) 20 kA
UL indicator/remote signaling
Operating voltage 125 V AC
Operating current 1 A AC
Tightening torque 2 lbf-in. ... 4 lbf-in.
Conductor cross section AWG 30 ... 14
UL connection data
Conductor cross section AWG 14 ... 2 (solid)
14 ... 4 (flexible)
Tightening torque 40 lbf-in. ... 50 lbf-in.
Drawings
97,9 49,2
F2
F1
L1 L1
L2 L2
L3 L3
N N
PE PE
06/12/2018 Page 5 / 10
https://www.phoenixcontact.com/sg/products/2905340
11 FM
PE L1 L2 L3
VALVETRAB VALVETRAB VALVETRAB VALVETRAB
N/PE T2 T2 T2
VAL-SEC-T2 VAL-SEC VAL-SEC VAL-SEC
N/PE-350-P T2-350-P T2-350-P T2-350-P
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / CCA / IECEE CB Scheme / EAC / DNV GL / cULus Recognized
Ex Approvals
06/12/2018 Page 6 / 10
https://www.phoenixcontact.com/sg/products/2905340
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
KEMA-KEUR
http://www.dekra-certification.com 2196453.01
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
IECEE CB Scheme
http://www.iecee.org/ NL-34356
RU C-
EAC
DE.A*30.B01561
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
Device marking
Label - EML (20XE)R - 0803452
Label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1,
THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK S1.1, mounting type: adhesive,
lettering field size: continuous x 20 mm
06/12/2018 Page 7 / 10
https://www.phoenixcontact.com/sg/products/2905340
Label, Roll, yellow, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1,
THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK S1.1, mounting type: adhesive,
lettering field size: continuous x 20 mm
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type:
snap into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type:
snap into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
End block
Quick mounting end clamp for NS 35/7,5 DIN rail or NS 35/15 DIN rail, with marking option, width: 9.5 mm, color:
gray
Marker for terminal blocks, Strip, white, labeled, Horizontal: L1, L2, L3, N, GND, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
06/12/2018 Page 8 / 10
https://www.phoenixcontact.com/sg/products/2905340
Marker for terminal blocks, Strip, white, labeled, Horizontal: Grounding symbol, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
Marker pen
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35
mm
Terminal marking
Flat zack marker sheet, Sheet, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting
type: snap into flat marker groove, for terminal block width: 5.2 mm, lettering field size: 5 x 4.5 mm
Spare parts
Replacement plug for surge arresters from the VALVETRAB SEC product range for L-N and L-PEN paths.
Replacement plug for surge arresters from the VALVETRAB SEC product range for the N-PE path.
06/12/2018 Page 9 / 10
https://www.phoenixcontact.com/sg/products/2905340