MP SITE NAME ALARM START TIME AUTONOMY RCA TOTAL OUTAGE


We need to ensure GAC alarm is working so
that we are alarted for any issue happen on
DG. We`re having unnecesary /prolonged
outage due to our failure to do right job during
PM
NEWL ITASWI_UCSAF BTS BATTERY LOW@ 19-06-2021 22:37:21 02:00hrs per PM 08-06-2021 DG failed to start due to DG battery went fault,replaced-Affecting 1 tenant. 0:03
Atleast we need to be proactive and treat cases
as potential hazard and that could cause
outage any time. This outage was preventable
Two rectifier modules(Power ware) went fault,replaced.Failure to investigate the
if we installed new rectifier on time
reason for module failure as the rectifier controller .is fault,new rectifier to be
PIVOTECH VIKINDU OOS DIRECT 00:20hrs per PM 12-05-2021 installed on today-Affecting 2 tenants. 4:48
We normally have low coolant level sensor
which must have trigered incase of decreased
coolant level in adiator. Foe this case only
temperature switch triggered which was not
supposed to trigger under this circumstance.
DG shut down with engine high temperature due to low coolant level,coolant added (Need to be checked as I suspect something else
MBWEWE3 BATTERY LOW@ 20-06-2021 13:11:34 00:40hrs per PM 06-05-2021 temporary.Mechanical team will attend today for further investigation-Affecting 3 4:30 happened i.e. fan belt broke)
tenants.
Also why no GAC alarm. We could reduce
outage time if this was working

PIVOTECH
We need to ensure GAC alarm is working so
that we are alarted for any issue happen on
DG. We`re having unnecesary /prolonged
outage due to our failure to do right job during
PM
NEWL BOMANI DC Voltage@ 19-06-2021 18:39:23 06:00hrs per PM 23-03-2021 DG failed to start due to DG battery went fault,replaced-Affecting 1 tenant. 1:07