Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Tech Tips

by Jeff Jowett, Megger

A Look at Fault Currents

A
n adequate grounding system is I = 3Io = 3E
t ————————————————
able to deal successfully with fault 3Rf + R1 + R2 + R0 + j(X1 + X2 + X0)
conditions. Put crudely, an electri-
where
cal fault is a breakdown in insulation that
I0 is total zero sequence fault current at the location, in rms amperes
sends current in an unwanted direction. The
(note that 3I0 is total ground fault current)
current must return from the fault point to
its source. For personnel safety, protection E is phase-neutral prefault voltage, in rms volts
of equipment, and continued functioning Rf is estimated minimum resistance, in ohms
of the electrical system, such current must (Rf = 0 may be assumed)
be quickly diverted and normal operation R1 + jX1 is positive sequence equivalent fault impedance, in ohms
restored. R2 + jX2 is negative sequence equivalent fault impedance, in ohms
Return to source may be accommodated (usually R1 + jX1 = R2 +jX2 is assumed)
through the earth, through metallic conduct- R0 + jX0 is the zero sequence equivalent fault impedance at the fault
ing paths, or both. When soil is the means location, in ohms
of return, a voltage gradient develops in the
vicinity of the grounding system. Magnitude For double-line faults, between two phases and ground, the equation
of this gradient is directly proportional to becomes:
soil resistivity and inversely to distance.
Safe and effective grid design depends on a I = 3I0 = 3E(R2 + jX2)
knowledge of current distribution and what t ————————————————————————————
(R1 + jX1) (3Rf + R2 + R0 + j(X2 + X0)) + (R2 + jX2) (3Rf + R0 + jX0)
the grid must accommodate under various
conditions. A so-called “ground” may occur Total symmetrical grid current (Ig), the current flowing from the grid
by a fallen conductor contacting earth, or the into surrounding soil, is therefore a component of It with its magnitude
grounding system may be directly involved, dependent upon specific conditions. The location of the fault has a major
as in a flash-over. Single-circuit transmis- impact on current distribution. Consider first a fault within a substation
sion lines and feeders tend to have faults on the secondary side of a typical delta/wye-grounded transformer. There
of low magnitude. These can be difficult to already exists a low impedance metallic path through the grid from the
clear and also make shock hazards of long point of the fault and the source, the transformer. Current need only travel
duration. On double or multicircuit lines, as far as the grid and back to the transformer. In this case, negligible current
fault currents are of greater magnitude but flows into surrounding soil, so overall grid current and ground potential
also clear more quickly. rise (GPR) are negligible (Ig = 0). However, suppose the fault were on the
For grid design, in order to mitigate primary side. The on-site transformer does not now contribute to the fault
ground potential rise, touch potentials, and current. It all originates from a remote source, beyond the substation. In
step potentials, it is necessary to begin with this case, there is no direct metallic path as previously described; all of the
the ability to calculate total symmetrical fault current must return through the soil. Symmetrical grid current, that
ground fault current, It: flowing from the grid in a radial pattern, comprises 100% of total current
(Ig = It). GPR may be high.

www.netaworld.org Spring 2010 NETA WORLD 1


These cases demonstrate the extremes of current distri- pole grounding electrodes. In this case, grid current is typi-
bution. What if ground fault current originated from both cally only a small fraction of total current, perhaps less than
local and remote sources? An example would be a substa- ten percent, and a feeder fault is rarely a worst case for the
tion grounded-wye/delta/grounded-wye transformer and substation grounding system.
a remote source with a grounded-wye secondary. If a fault Fault clearance, then, is not a simple case of current
occurred within the substation, fault current is contributed going to ground via the on-site grid. Current divides in
by both local and remote sources. This situation represents known and understood ways, but the details and calculation
a combination of the first two examples. Current from the of magnitude can be complex. A thorough knowledge of
local source circulates through the grid while that from the current distribution is critical in grid and grounding system
remote source must return through the soil. Symmetrical design. The mathematics of some typical examples will be
grid current is now a fraction of total current and is equal examined in a later edition.
to the percent of total ground fault current contributed by
the remote source. Finally, imagine that the fault occurs, not
within the substation, but at a distant point on a transmis- Source of information: Tennessee Valley Public Power
sion line. Now, current divides and returns through soil to Ass’n; Allen & Hoshall Architects Engineers, Nashville,
both the substation and the remote source which could be a TN; Alexander Publications, Newport Beach, CA.
main station or generating plant. The substation grounding
grid is not involved in the latter of these tow paths. Again,
the symmetrical grid current of the substation in question Jeffrey R. Jowett is Senior Applications Engineer
is some fraction of total current. In this case, it equals the for Megger in Valley Forge, Pennsylvania, serving
the manufacturing lines of Biddle, Megger, and
percent contributed by the local source. Multi-Amp for electrical test and measurement
The preceding examples represent clear-cut cases where instrumentation. He holds a BS in Biology and
no shield wires or feeder neutrals are present. However, this Chemistry from Ursinus College. He was employed
simplified condition often does not apply. Overhead shield for 22 years with James G. Biddle Co. which became
wires and feeder neutrals provide convenient parallel paths Biddle Instruments and is now Megger.
for fault current. Feeder neutrals in wye-grounded systems
are also grounded and connected to the transformer neutral
bushing. Shield wires are normally grounded at intervals
along the line’s length and at the substations at each end. In
addition, other alternate paths may exist through convenient,
continuous metal objects like fences, railroad tracks, and
grounded pipes. This phenomenon of parallel current paths
is known as current division, and the IEEE has dubbed this
“split factor.”.Therefore, in such a system there are two cur-
rent divisions to be computed: the one previously described
between local and remote sources, and the division between
the grounding system and the alternate current paths.
Consider a fault on the primary side of the substation
transformer: whereas in the simplified example grid current
equaled total current, the multiple grounds downstream
of the grounded wye now carry the major portion of fault
current. The grid current may now be reduced to something
like a third of total current. A fault on the secondary side,
however, will circulate current directly through the grid
between the fault point and the grounded wye. As in the
simplified situation, symmetrical grid current to remote
earth is negligible, but there will be a small amount due to
induction from live conductors onto the overhead static wire.
Because of the short path and low impedance, total fault
current will be greater than in the case of a primary fault, and
so this needs to be considered when sizing the conductor.
Lastly, there is the case of a fault occurring remotely
at some distance down the line. Most of the current will
return to the source through the feeder neutral. Because of
the lower impedance, total current will be greater than for a
fault on the primary side. The farther the fault occurs down
the line, the added impedance decreases total current and
increases the amount returning through the soil by parallel

2 NETA WORLD Spring 2010 www.netaworld.org

You might also like