Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

Please return one copy with approved signature or stamps, after reviewing the contents

of this specification. The delayed approval would affect to products’ delivery.

APPROVAL SPECIFICATION
Cast coil dry-type Transformer

Project Name VNP Viettel 4000kVA Cu

Project No. 502852593

Customer Name VNTRA

1 2020.11.10 Position of secondary terminal revised YP SONG CY LIM KS LEE


0 2020.11.04 Issued for approval YP SONG CY LIM KS LEE

Prepared Checked Approved


Rev date contents
by by by
Transformer Specification

Rated
High Low Vector Conductor
power Qty Remark
Voltage (V) Voltage (V) group (HV/LV)
(kVA)

4000 22000 400 Dyn11 Cu/Cu 1 1LKR205643

2/3
Document list

Data sheet

No Data sheet Revision Remarks


TR-1 1LKR205643 0
TR-2
TR-3

Rating plate drawing

No Drawing No. Revision Remarks


TR-1 1LKR205643-71 0
TR-2
TR-3

Transformer outline drawing

No Drawing No. Revision Remarks


TR-1 1LKR205643-81 1 Position of secondary terminal revised

TR-2
TR-3

Accessories (catalog, manual, drawing)

No Description Revision Remarks


1 KN-805 0 Digital controller catalogue and user manual
2
3

3/3
Technical data sheet
Hitachi ABB Power Grids
Project No. Date Rev
Project: VNTRA-VNP Viettel 4000kVA Cu 502852593 2020-11-04 0

Design no.: 1LKR205643 Deg. YPS

General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11:2018
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated power [kVA] 4000
Rated high voltage [V] 22000
Rated low voltage [V] 400
Tapping on HV (De-energized tap changer) ± 2 steps X 2.5 %
Vector group Dyn11
Type of cooling AN
Insulation system thermal class (HV/LV) [°C] F/F (155/155)
Temperature rise at principal tapping (HV/LV) [K] 100/100
Winding conductor (HV/LV) Cu/Cu
Ambient temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1

Technical Characteristic at AN, 75°C


No load loss [W] 6500 +15% IEC tolerance
Load loss [W] 28000 +15% IEC tolerance
Efficiency at 50% Load, 1 PF [%] 99.18 (for reference)
Impedance [%] 7 ±10% IEC tolerance
Full wave lightning impulse (HV/LV) [kV] 125 / -
Applied voltage (HV/LV) [kV] 50 / 3
Sound pressure level at 1.0m (LpA) dB(A) 70

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805
- Temperature sensor: PT-100Ω (1 pc/phase, total 3 pc)
- Cooling fan
- Bi-directional roller

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Routine test: voltage ratio test for each tapping and other tests at principal tapping according to IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.
6. Harmonic effects are not considered if not specified in the data sheet.
ABB POWER GRIDS KOREA

THREE PHASE DRY TYPE TRANSFORMER

SERIAL NUMBER:

STANDARD: IEC 60076-11:2018 HIGH VOLTAGE


TAP RATED CURRENT
YEAR OF MANUFACTURE LINK
VOLTAGE (V) - AN (A)

RATED POWER - AN (kVA) 4000 3-4 23100

RATED POWER - AF (kVA) - 4-5 22550

RATED FREQUENCY (Hz) 50 5-6 R 22000 105.0

IMPEDANCE - AN (%) 6-7 21450

TEMPERATURE RISE HV/LV (K) 100/100 7-8 20900

AMBIENT TEMPERATURE (Max.) 40


INSULATION SYSTEM F/F
THERMAL CLASS HV/LV (℃) (155/155)
CONNECTION SYMBOL Dyn11 LOW VOLTAGE
RATED RATED CURRENT
CLIMATE/ENVIRON./FIRE CLASS C1/E2/F1
VOLTAGE (V) - AN (A)

WINDING CONDUCTOR (HV/LV) Cu/Cu 400 5773.5

DEGREE OF PROTECTION IP00

TYPE OF COOLING AN

INSULATION LEVEL HV/LV (kV) 24/1.1


C B A
LI 125 c b a n
HV WITHSTAND VOLTAGE (kV)
AV 50
LI -
LV WITHSTAND VOLTAGE (kV)
AV 3
TOTAL MASS (kg) 9500

Note: Impedance is left blank and measured value is engraved at the time of shipment. The
drawing is not subsequently revised to add the test value.
KN 805-p DIGITAL TEMPERATURE CONTROLLER
Free voltage
(AC100~270V 50/60Hz,DC 100~300V )
4 sensor input(Pt100Ω)
Operation setting function for each channel(run/stop)
caution:”stop” selected channel is not displayed KN805- P
Program type function
(Setting value)
Temp, max storage function for each channel
Data storage function
COM
Fan auto / manual function
Buzzer function (fault, alarm, trip)
Test function for each input channel
Channels scanning
SCAN : ch1-2-3-4 scanning( 2 sec)
AUTO :automatic hottest scanning www.neurontech.kr

MAN :manual scanning


Scan time setting function(2~10 sec)
Outputs delay time setting function
Fan ( 0.1~6.0 sec)
Alarm, Trip ( 0.5~10.0 sec)
SPECIFICATION

◆ INPUT ◆ ANALOG OUTPUT


4 INPUT Pt100 Ω- 3Wires (DIN IEC 751)
Pt100Ω-3Wires DC 4~20mA (RANGE:0~200
(RANGE:0~200℃)℃)
Load Resistance Max 600
600ΩΩ
◆ 4 INPUT (INPUT/OUTPUT ISOLATION)
EMI FILTER, OVERVOLTAGE PROTECTION
◆ SERIAL COMMUNICATION
◆ INPUT MEASURING CYCLE RS-485 MODBUS RTU (OPTION: RS-232)
60m /120m / 240m /480m SEC(setting function) (INPUT/OUTPUT ISOLATION)
◆ ACCURACY ◆ TEMPERATURE INDICATION
+/- 0.5℃(Full Scale) 1℃
◆ TEMPERATURE MEASURING RANGE ◆ DATA STORAGE
-
-50~250℃
50~250 ℃ 10YEARS
◆ TEMPERATURE INDICATION
◆ POWER SUPPLY
1℃ AC100 to 270V 50/60Hz,DC100~300V
◆ AMBIENT TEMPERATURE
◆ DIELECTRIC STRENGTH
OPERATION -20 to 60℃ AC2000V for 1min
◆ POWER CONSUMPTION
◆ AMBIENT HUMIDITY 7VA
OPERATION 10 to 90% RH
◆ INSULATION RESISTANCE
◆ OUTPUT CONTACTS CAPACITY 500V DC 100M ohm Minimum
TRIP,ALARM,FAULT,FAN AC 250V 10A (Resistance Load)
CONTACT DC 30V 10A (Resistance Load) ◆ WEIGHT
FAN RELAY SURGE PROTECTION 750g

TERMINAL CONNECTION EXTERNAL DIMENSION

10
100 107.1
13 14 15 16 17 18 19 20 21 22 23 24 Unit :mm
Temperature Controller KN804
A B B- A B B- A B B-
T.MAX TRIP

A B B-
SCAN
AUTO ℃ ALARM
FAN
MAN FAULT

CH 1 CH 2 CH 3 CH 4 100 COM
CH 89.8
Pt100Ω
PRG ON FAN ON BUZZER ON
Pt100Ω Pt100Ω Pt100Ω
SENSER
MODE

SENSER SENSER SENSER RES ET
TEST

PRG ▲
FAN
T.MAX
STOP MAN ENT

54 T/X-
COMMUNICATION
T/X+ RS-485
53
52 - 122
DC4~20mA
51 + PANEL CUTTING SIZE
AC100~270V
ALARM TRIP FAULT FAN 50/60Hz
OUT OUT OUT OUT DC100~300V
92
1 2 3 4 5 6 7 8 9 10 11 40 41 42

87.6 92

A 304 ,875-1 Maesonggosaek-Ro, Gwonseong-Gu, Suwon-City


Neuron Tech Gyeonggi-Do, Korea, 441-230 www.neurontech.kr
TEL : +82-31-227-4504 / FAX : +82-31-298-1962
TEMPERATURE
CONTROLLER

KN805-P
USER MANUAL
(사용자 메뉴얼)

Temperature Controller KN804


KN 805-P

T.MAX HH ALARM
SCAN
AUTO °C HI ALARM
FAN
MAN FAU LT ALARM

PRG ON
CH
FAN ON BUZZER ON

MODE
TEST

T.MAX
RESET FAN PRG ▲
STOP MAN ENT

Neuron Tech
www.neurontech.kr

Neuron Tech
CONTENTS
목 차

● Caution for Safety -------------------- 2


안전을 위한 주의사항
1. Specifications -------------------- 6
사양
2. Connection Diagram -------------------- 7
단자대
3. Feat u res ----------------------------- 8
특징
4. Name of Each Part ---------------------- 10
각부 명칭

5. Setting Manual ---------------------- 12


설정 메뉴얼

6. Example of Wring -------------------- 13


FAN 결선도

7. External Dimension and Panel Cutting Size ----- 14


외형도및 판넬가공치수도

-1-
안전을 위한 주의사항

안전을 위한 주의사항은 제품을 안전하고 올바르게 사용하여 사용자의 안전과


사고나 위험을 미리 막기위한 내용으로 잘 읽고 반드시 지켜주십시오 .

주의사항은 경고 와 주의 의 두가지로 구분되며 그 의미는 다음과 같습니다.

경고 지시사항을 위반할 시 심각한 상해나 사망이 발생할 가능성이 있습니다.

주의 지시사항을 위반할시 상해나 제품의 손상 ,물질적인 손해의 가능성이


있습니다.

경고
1. 전원
1) 기기의 보호와 고장방지를 위해 정격 전원전압 이내에서 사용하십시오.
2) 기기의 설치 시 감전방지와 기기 손상을 방지하기 위해 배선의 결선이 완료된
이후에 결선을 확인하고 전원을 투입하십시오.

2. 동작상의 주의
1) 본 기기의 이상이 중대한 사고에 연관되는 경우엔는 출력부분에 보호장치를
추가 설치하는 것을 권장합니다.
2) 가스 중에서 사용을 금합니다. (방폭 구조가 아닙니다.)
3) 화학물질이 있는곳에서 사용하지 마십시오. 전기 누전 및 감전의
위험이있습니다.
4) 통전중에 단자를 만지거나 풀지마십시오.
감전이나 오작동의 원인이됩니다.
5) 근처에 물이있거나 몸이젖어있을때 제품을 만지지마십시오.
감전의 위험이 있습니다.
6) 어린이가 만질수있는 장소에 설치하지마십시오.

3 .결선및 보수상의 주의
1) 본기기의 결선은 사용설명서나 부착된 단자설명서 같이 해당번호에 정확하게
결선하십시오. (단자 볼트는 단단히 잠그십시오.)
오결선 시 기기 파손 및 오동작 및 화재의 원인이 됩니다.
2) 보수시 필히 외부전원 스위치를 0FF 하고 출력부의 연결 외부 회로 전원을
차단후 보수,탈착하여 주십시오. 감전 고장의 원인이 됩니다.
3) 본 기기를 분해하거나 개조 수리는 절대하지마십시오.
감전 화재및 재품손상 ,오작동 고장의 원인이 됩니다.
4) SENSOR 를 교환할시에는 전원을 필히끄고 교환하십시오.
감전 화재의 제품의손상 오작동 고장의 원인이 됩니다.
5) 본 기기의 부품은 수명이있으며 경년변화 부품을 포함하고 있습니다.
구입일로 부터 1 년동안 보증기간 입니다.
단, 고객의 과실 및 천재지변의에 의한 고장은 제외 됩니다.

-2-
주의

1. 취부 및 결선상의 주의
1) 취부 시 기기의아래위 고정물 (출고 시 포함)로 단단하게 고정 하십시오
2) 전원에 유도 노이즈 등이 심한경우 절연트랜스 및 노이즈 제거회로를
사용할 것을 권장합니다.
3) 물이 들어갔을 때는 필히 점검을 받으십시오.
감전과 화제의 원인이 됩니다.
4) 리드선은 저항이 작고 난연성이 있는 것을 사용하십시오.
5) 출력과 입력 신호선은 필히 분리하여 사용하십시오.

2.취급상의 주의

1) 출력 Relay 를 정격에 여유 없이 부하를 접속하여 빈번하게 동작할 시에는


Relay 수명이 정격보다 짧아지므로 외부에 릴레이 를 추가하여 사용하십시오
Relay 전기적 수명--------약 10 만회 (정격부하시)

2) 각 설정을 정확하게 설정하시고 운전 전에 입력과 출력 이상 유무를 확인 하십시오

3) SENSOR 가 단선 또는 SHORT 일 때는 " FuL " 표시 합니다.


이때 SENSOR 를 교환 시에는 필히 전원을 OFF 하십시오
고장 및 오동작의 원인이됩니다.

4) 제품을 떨어뜨리거나 충격을 주지 마십시오 외관이 손상 됩니다.

5) 유기 용제로 제품을 닦지 마십시오 외관이 손상 됩니다

6) 다음과 같은 여건에서의 사용을 피하십시오.


: 주의 온습도가 사용조건의 온습도 범위를 초과하는곳
: 가연성 가스나 부식성 가스에 노출 되는곳
: 기름 물 수증기 철분 염분이 많은곳
: 방수 구조가 아니므로 옥외나 물 비등에 노출되는곳
: 직사광선에 바로 노출되는곳
: 온습도 변화가 심하여 결로 현상이 발생하는곳.

-3-
Caution for Safety
Caution for safety, aims at securing safety of user and preventing accident
or danger in advance by using it safely ,so read and follow it well.
Caution matters are divided into ‘warning’ and ‘caution’ whose meanings
are as follows
Violating instruction may cause serious damage or
WARNING death
Violating instruction may cause injury product
CAUTION damage or material loss.

WARNING
1.power
1) use it within rated voltage in order to protect equipment and prevent and
prevent trouble.
2) ln order to prevent electric shock and equipment damage when installing
equipment check wiring after finishing wiring and than input power.
3) use standard wiring and terminal for connecting power .this can cause
electric shock and fire.
2.caution for operation
1) lf abnormality of this equipment is related to serious accident, it is
recommended to install protection device in addition.
2) Do not use this equipment in the gas (This is not explosion-proof structure).
If this equipment is exposed to gas do not operate power switch and
so on but operate ane it when it is sage after venting the space.
3) Do not use in the place with chemical materials, There is danger of electric
leakage and electric shock.
4) Do not touch or loosen terminal when there is applied lt can cause electric
shock or mal -operation.
5) Do not touch the product when there is water around or when body is wet.
There is danger of electric shock.
6) Do not install the equipment in the place where children can touch the
equipment.

3. Caution for wiring and maintenance


1) Perform wiring for this equipment exactly into relevant number as show in
the instruction manual or terminal instruction. (Tighten terminal bolt firmly)
mal-wiring can cause equipment damage, mal- operation of fire .
2) Perform repair or assembling after turning off external power switch and
interrupting external circuit power. It can cause electric shock or trouble.
3) Never disassemble reform or repair equipment lt cause electric shock fire
product damage mal-operation or trouble.

-4-
4) Replace sensor after turning off power by all means. Lt can cause electric
shock.
Fire product damage mal-operation or trouble.
5) The components of this equipment have life period and include year -passing
components There is 1 year of guarantee period from purchasing date.
However. Trouble due to customer mistake and natural disaster is excluded.

CAUTION
1.caution for attachment and wiring
1) Fix the equipment firmly with the fixing device (included during shipment
below and above the equipment when attaching equipment.
2) lf there is severe induction noise in the power ,it is recommended to us
insulation transformer and noise removal circuit.
3) Twisted wiring of power line is effective for noise
4) lf water enters receive checking by all means.
5) Use lead wire which has low resistance is non-combustible.
6) Use output and input signal lines by separation them by all means. Use
shield wire for input signal wire and be away from load or high voltage.
7) Use sensor of non-grounding type.

2.Caution for handling


1) when operation output relay frequently by connecting load without
allowance in rating, relay life can be shorter rating so use it by adding relay
to outside. *Electric life of relay --About 100.000 times (under rated load)
2) Make each setting exactly and check abnormality in input and output,
3) lf sensor is single or short it is displayed “---”.
turn off voltage by all means when replacing sensor at this time .
It can cause trouble and mal -operation
4) Do not drop this product nor give shock this product. It can cause trouble
or mal-operation
5) Do not wipe the product with organic
solvent lt can cause damage in appearance .
6) Avoid use in the following condition.
: ln the place where surrounding temperature and humidity exceed the
temperature and humidity scope in usage condition.
: ln the place exposed to combustible gas or corrosive gas.
: ln the place where there is much oil water steam iron or salt.
: ln the place which is not waterproof structure exposed to outside water
or rain.
: ln the place directly exposed to direct sunshine.
: ln the place where freezing phenomenon takes due to severe
change of temperature and humidity.

-5-
KN805-P DIGITAL TEMPERATURE CONTROLLER
Free voltage (파워 전압)
(AC1 00~ 240V 50~60Hz,DC 100 ~300V )
4 sensor input(Pt100Ω) (센서 입력 (Pt100Ω))
Op eration settin g function for each chan nel(run/stop)
cautio n:”stop ”s eleced channel is not dis played. Temperature Controller KN805-P
(각 채널 운전 설정 기능 (run/stop)
주의:”stop” 설정 채널은 제어,디스플레이 동작 없음.) T.MAX TRIP
T emp, max sto rag e functio n for each channel
(각 채널 최고 온도 값 저장 기능.)
SCAN
AUTO °C ALARM
FAN
Fan auto / manual fun ction MAN FAULT
(펜 자동/수동 사이클 기능)
Buzzer functio n (fault, alarm, trip)
(부저기능(Fault, Alarm, Trip))
●ONLY KN805-P
PRG ON
CH
FAN ON BUZZER ON
T est functio n for each inp ut channel
(각 채널 테스트기능)
C hannels scan nin g( 채널모드)
MODE
TEST

SCAN : ch1-2-3-4 scann ing( 2 sec )
AUTO :auto matic hottest scanning T.MAX
RESET FAN PRG ▲
MAN
MAN :manual functio n STOP ENT

Scan time s etti ng function(2~10 sec)


(스캔 타임 설정 기능 (2~10 sec))
Ou tputs delay time setting function (출력 지연 타임 설정 기능)
Fan ( 0.1~6.0 sec)
Alarm, Trip ( 0.5~10.0 sec )

1.Specification ( KN805-P )
DIMENSION 100(W)X100(H)X132(D)mm
INPUT MEASURERING CYCLE 100m SEC
ACCURACY +/- 0.5°C ( Full Scale)
INPUT 4 INPUT Pt100 Ω- 3WIRE(DIN IEC 751)
AMBIENT TEMPERATURE & HUIDTIY OPERATION -32 TO 131℉ / 10 TO 90% RH)
MEASURING RANGE - 50~250°C
TEMPERATURE INDICATION 1°C
OUTPUT CONTACTS CAPACITY TRIP,ALARM AC 250V 5A(Resistance Load)
FAN AC 250V 10A(Resistance Load)
CONTACT DC 30V 10A(Resistance Load)
ANALOG OUTPUT DC 4~20mA (RANGE: 0~200°C ) Load Resistance Max 600 Ω
(INPUT/OUTPUT ISOLATION)
COMMUNICATION SERIAL RS-485 MODBUS RTU (OPTION: RS-232)
(INPUT/OUTPUT ISOLATION)
DATA STORAGE 10 YEARS
POWER SUPPLY FREE VOLTAGE
AC 100V TO 240V 50~60Hz,DC 100~300V

POWER 7 VA
CONSUMPTION
DIELECTRIC STRENGTH AC 2000V FOR 1MIN
INSULATION DC 500V 100M ohm MINIMUM
RESISTANCE
WEIGHT 750g
- 6-
2. Conection Diagram ( KN805-P )
단자대

◎ Connection Diagram

13 14 15 16 17 18 19 20 21 22 23 24

●ONLY KN805-P
54
53
52
51

1 2 3 4 5 6 7 8 9 10 11 40 41 42

*NOTE
(1)FAULT OUT contact type “B”.
When the unit is powed the fault relay 7-9 closed and
it opens again in case of fault condition.
(2)”ALARM,TRIP OUT” on delay time.
Factory preset setting values: 3 sec
(3)”FAN OUT” on delay time.
Factory preset setting values: 0.5 sec
(*주의: 전원이 투입되고 정상 운전시 단자 7 번- 9 번 닫힘, 전원 OFF 또는 FAULT 발생시 7번- 9번 열림.)
-7-
3.특징

전원 입력이 FREE VOLTAGE ( AC 90~26 0 V , DC 100~300V) 로 외부전원의 변화와


SURGE 등의 악조건에서도 안정적으로 작동합니다.
4 입력으로 변압기 온도를 표시하고 운전 중 온도에 따라
경보출력 ( ALARM , TRLP) FAN 을 제어합니다.

TEMP .MAX기능 -현재까지의 동작중 변압기의최대온도를 저장


확인이 가능합니다.

DATA 저장 기능이 있어 T, MAX 값 각 제어온도 설정치를 기억합니다.


( 반영구적)

T MAX, 치는 동작 중 RESET 을 시키지않는 한 전원 OFF 후에도


저장됩니다.

각 설정치도 동작 중 설치를 변경하지않는 한 전원 OFF 후에도 저장됩니다.


FAN OUP 기능 - FAN ON FAN OFF 설정치와 측정온도를 비교하여 외부
FAN 을 CONTROL 합니다.

* 출력동작도

OUTPUT SPECIFICATIONS( △: setting temp)

ALARM,TRIP

ALARM,TRIP ON

FAN OUT

FAN OFF FAN ON

-8-
3.Features
Power input is free voltage (AC 90~260V,DC 100~300V) and it is stably
operated even at bad condition such as outside power change,
surge etc
Temperature of transformer is measured and displayed and
alarm output (alarm trip) and fan is controlled according to
temperature.
It is possible to set each setting temperature in program type
according to program key
Temp max function -lt is possible to check the highest
temperature of transformer during operation up to now.
Data storage function memorizes T .MAX value and each control
temperature setting values.(Semieternal) T.MAX value is stored
even after turning power it is reset during operation .
Each setting value is also stored after turning off power unless
setting value is changed during operation .
Fan out function -lt is possible to control outside fan by
comparing fan on and fan off setting values and measured
temperature.

* Output Operating Diagram

OUTPUT SPECIFICATIONS( △: setting temp)

ALARM,TRIP

ALARM,TRIP ON

FAN OUT

FAN OFF FAN ON

-9-
4.각부의명칭

(1)Temp. Max (21)TEMP&SETTING DISPLAY


DISPLAY LED
(2)SCAN MODE (20)CHANNEL DISPLAY
DISPLAY LED Temperature Controller KN805-P
KN804

(3)AUTO MODE (19)TRIP OUTPUT DISPLAY LED


DISPLAY LED T.MAX TRIP
SCAN
AUTO °C ALARM
FAN (18)ALARM OUTPUT DISPLAY LED
(4)MAN MODE MAN FAULT
DISPLAY LED
(5)COMMUNICATION PRG ON
CH
FAN ON BUZZER ON
(17)FAN AUTO OUTPUT DISPLAY LED
DISPLAY LED

(6)PROGRAM MODE
MO D E
TEST
▲ (16)FAULT OUTPUT DISPLAY LED
DISPLAY LED RESET ▲
FAN PRG
T.MA X
(7)FAN MANUAL OUTPUT STOP MA N ENT
(15)MODE CHANGE / TEST SWITCH
DISPLAY LED
(8)BUZZER ON (14)UP SW ITCH
DISPLAY LED
(9)T . MAX CHECK SWITCH (13)DOWN SWITCH

(10)STOP/RESET S WITCH (12) P ROGRAM MODE/SETTING SWITCH

(11)FAN MANUL ON/OFF SWITCH

* 동작및설정

(1)T.MAX: 측정온도중가장높은온도값을 저장함


FUNCTIONS (2)SCAN : 각채널을 일정시간 주기로 표시함
(3)AUTO : 각채널 중 가장높은 온도 채널을 표시함
(3)MAN : 각채널을 수동으로 상하키로 선택한 채널을 보여줌
(16)FAN : F AN ON/OFF 자동으로 동작함을 표시함
(17)ALARM: ALARM ON/OFF 자동으로 보여줌
(18)TRIP : TRIP ON/OFF 자동으로 보여줌

(8)T.MAX: T.MAX값 동작스위치


(9)STOP/RESET: STOP 은 BUZZER 동작 정지 스위치
조작 KEY RESET 은 T.MAX MODE 에서 기존 저장값을
삭제 함( 3 초간누름)
(10)FAN MAN: FAN 동작을 수동으로 ON/OFF 스위치
(11)PRG/ENT: PROGRAM MODE 전환 스위치( 3 초간 누름)
설정값 변경 및 저장 함

(12)DOWN: 측정채널 낮은채널로 이동


PROGRAM SETTING 값 내림.
(13)UP : 측정채널 높은채널로 이동
PROGRAM SETTING 값 올림.
(14)MODE/TEST: DISPLAY MODE ( SCAN, AUTO, MAN ) 전환키
TEST MODE 키 ( 3 초간 누름)

- 10 -
4. N ame of Each Part ( KN805-P )

(1)Temp. Max (21)TEMP&SETTING DISPLAY


DISPLAY LED
(2)SCAN MODE (20)CHANNEL DISPLAY
DISPLAY LED Temperature Controller KN805-P
KN804

(3)AUTO MODE (19)TRIP OUTPUT DISPLAY LED


DISPLAY LED T.MAX TRIP
SCAN
AUTO °C ALARM
FAN (18)ALARM OUTPUT DISPLAY LED
(4)MAN MODE
MAN FAULT
DISPLAY LED
(5)COMMUNICATION PRG ON
CH
FAN ON BUZZER ON
(17)FAN AUTO OUTPUT DISPLAY LED
DISPLAY LED

(6)PROGRAM MODE
MO D E
TEST
▲ (16)FAULT OUTPUT DISPLAY LED
DISPLAY LED RESET ▲
FAN PRG
T.MA X
(7)FAN MANUAL OUTPUT STOP MA N ENT
(15)MODE CHANGE / TEST SWITCH
DISPLAY LED
(8)BUZZER ON (14)UP SW ITCH
DISPLAY LED
(9)T . MAX CHECK SWICTH (13)DOWN SWITCH

(10)STOP/RESET S WICTH (12) P ROGARM MODE/SETTING SWITCH

(11)FAN MANUL ON/OFF SWITCH

* Operating ( KN805-P )

(1)T.MAX: Monitoring unit shows the highest temperature recorded


by the sensor and the last reset
FUNCTIONS (2)SCAN : Control device displays in scansion all activated
channels(each 2 seconds)
(3)AUTO : Control device automatically displays the highest
temperature channel
(3)MAN :Channel temperature manual reading through cursor keys
(17)FAN : F AN is automatically controlled by fan on and fan off
setting value
(18)ALARM:When the measurement temperature is over ALARM
setting value, ALARM ON
(19)TRIP :When the measurement temperature is over TRIP
setting value, TRIP ON
(9)T.MAX : T.MAX value check key (SCAN,AUTO,MAN mode only)
OPERATION (10)STOP/RESET: STOP -> (When the buzzer on) The " STOP/RESET”
KEYS key is pressed the buzzer will stop.
RESET(In T.MAX MODE)->The current T.MAX
value delete and record again
(“STOP/RESET” key 3 seconds pressing)
(11)FAN MAN: FAN o peration the button which the ON/OFF
operation with a manual operation.
(12)PRG/ENT: PROGRAM MODE(“PRG/ENT”key 3 seconds pressing)
Program setting function key
(13)DOWN: W hen Program setting value change DOWN.
(14)UP : When Program setting value change UP.
(15)MODE/TEST: DISPLAY MODE ( SCAN,AUTO,MAN ) change key
TEST MODE k ey
( "MODE/TEST” key 3 seconds pressing)
- 11 -
5.Setting Manua (설정메뉴얼)

KN805-P
After power supply The display shows the measurement temperature .
Tem per atur e Controller

T.MA X TR IP
SC AN
A UTO
MA N
℃ A LA RM
FAN
FAULT
( 전원이 투입되면 측정모드로 온도 값이 표시 됩니다.)
PRG ON
CH
FAN ON BUZZER ON
PRG PRG

Pressing ENT key 3 seconds. ( ENT 키를 3 초간 누릅니다)
MODE
TEST

T.MAX
R ESE T FAN PRG ▲
STOP MAN ENT

PRG ON PRG ON led turns on (PRG ON 램프에 불이 들어옵니다)

F an on " FAN ON " Setting display. ( " an on " 설정 표시입니다)


PRG
ENT

" FAN ON " Setting value changes.


( " FAN ON " 설정 값을 변경합니다)
Save the changed setting value.( 설정한 값을 저장합니다.)
PRG
ENT

F an o FF" FAN OFF " Setting display.(" F an oF F " 설정 표시입니다 )


PRG
ENT

" FAN OFF " Setting value changes.


( " FAN OFF " 설정 값을 변경합니다)
Save the changed setting value.( 설정한 값을 저장합니다.)
PRG
ENT

AL arm S etting " ALARM ON " Setting display


PRG (" AL arm S etting " 설정 표시입니다.)
ENT

" ALARM ON " Setting value changes


(" ALARM ON " 설정 값을 변경합니다.)
Save the changed setting value. (설정한 값을 저장합니다.)
PRG
ENT

Tr ip S etting " TRIP ON " Setting display


PRG (" Tr ip S etting " 설정 표시입니다.)
ENT

" TRIP ON " Setting value changes


(" TRIP ON " 설정 값을 변경합니다.)
Save the changed setting value. (설정한 값을 저장합니다).
PRG
ENT

C om Id “COM ID " Communication ID setting display


PRG
(“ C om Id " 통신 어드래스 설정 표시 입 니다.)
ENT

" COM ID " Setting ID value changes


(" COM ID " 어드래스 설정 값을 변경합니다. )
Save the changed setting value. (설정한 값을 저장합니다).
PRG
ENT

Return to first display (처음 화면으로 돌아옵니다.)


PRG
*Anywhere in the program by pressing ENT key 3 seconds or key operation
is not longer than 30 seconds in the measurement mode is changed.
(*프로그램 안에서 어디서든 ENT 키를 3 초간 누르거나 키 동작이 30 초간 없으면
PRG

측정모드로 전환 됩니다 . )
* Measurement mode (*측정모드)
PRG ON PRG ON led turns off. (PRG ON 램프 불이 꺼집니다.)
- 12 -
6.Example of Wiring ( Kn805-P )
FAN 외결선도
◎ In case of Phase (단상 결선도)

POWER SOURCE 13
(USER SUPPLY)
1 ¢ AC 220V 60Hz 42
R T 14
1 3
41
15
40 16
MCCB
17
R1 T1 11
18
10
19
9
20
8
21
7
22
6
23
5
24 ONLY KN805-P
4
51
3
52
2
53
1
54

◎ In case of Three Phase( 삼상 결선도)


POWER SOURCE
(USER SUPPLY) 13
1 ¢ AC 220V 60Hz
R S T 42 14
1 2 3 41 15
40 16
MCCB

R1 S1 T1 17
11
18
10
19
9
20
8
21
7
22
6
23
5
24
MC 4 ONLY KN805-P
51
U V W 3
EOCR 52
2
53
1
54

- 13 -
7.Extermal Dimension and Panel Cutting Size
외형도 및 판넬가공치수도

◎ Extermal Dimension (외형도 ) Unit : mm

10
100 107 . 1

Tem perature Controller KN804

T.MAX HH ALARM
SCAN
AUTO ℃ HI ALARM
FAN
MAN FAULT ALARM

100 PRG ON
CH
FAN ON BUZZER ON 90

M ODE
TEST

T. MAX
RESET FAN PRG ▲
STOP M AN ENT

122

90

◎ Panel Cutting Size ( 판넬가공치수도)

92

92

- 14 -
Neuron Tech
16598
경기 수원시 권선구 매송 고색로 873 , A 30 4
A 304 ,873, Maesong Gosaek Ro, Suwon-City
Gyeonggi-Do, Korea, 16598
TEL : +82-31-227-4504 / FAX : +82-31-298-1962
www.neurontech.kr

You might also like