PRISMIC® A12

Excitation
Controllers
The PRISMIC® A12 excitation
controller has been designed
to control the excitation of
a brushless generator. It
incorporates the latest digital
micro controller technology to
make it the most
comprehensive and compact
controller available.
A12

Introduction Key Features • Externally mounted display interface


The PRISMIC® A12 is based upon proven • Complete excitation system mounted computer (Optional)
technology and combines the experience on a plate • Automatic and manual excitation
and hardware of the complete range of limiters
• Available either as a single unit or as a
BRUSH PRISMIC® products.
high integrity twin configuration
The following limiters are included:
It includes, additional features such • Integrated Power System Stabiliser
(optional) • Under Excitation Limiter
as integrated speed detection, power
system stabiliser and synchronisation. • Integrated auto synchroniser (optional) • Over Excitation Limiter
• Integrated speed detection eliminating • Over Flux (V/Hz) Limiter
The PRISMIC® A12 is produced on a need for separate speed switch • Stator Current Limiter
plate mounted system either as a single
• Rotor earth fault detector input • Fast Acting Field Current Limiter
channel or twin channel arrangement.
included eliminating the need for • Terminal Voltage Limiter
separate unit
As a twin system each controller acts
as a hot standby for the other and is • Negative forcing of exciter field voltage Automatic transfer of control to hot
independently controlled with auto • Modes of operation include generator standby channel initiated by:
tracking, and smooth transfer. An terminal voltage control, power factor • Over Voltage Monitor Triggered
optional colour display screen is also control, VAr control and offload VArs • Under Voltage Monitor Triggered
available. • Digital Outputs • Over Excitation Monitor Triggered
• Analogue Input Signal for special • Under Excitation Monitor Triggered
application
• Over Flux Monitor Triggered
• Auxiliary power supply input allows
• Voltage Sensing Error
easy setting of unit without PMG
supply present • The PRISMIC® A12 includes the
following communication port
• Manual Reference
- 1 x RS232 service port
• Soft start for controlled application of
excitation - 1 x CANbus port for communication
with hot standby unit in twin
• Diode Failure Detection and Indication•
configurations
• HMI (Human Machine Interface)
- 1 x CANbus port available for
software for advanced maintenance
connection of display interface
diagnostics and downloading of data
computer
• Oscilloscope style trending and
- 1 x RS485 / RS232 Modbus RTU port
analogue data logging (5ms resolution)
for SCADA/ DCS communications
via HMI
- 1 x PROFIBUS port (optional)
• Event Logging
Ratings
Max continuous output current MW
Leading Power Factor Lagging Power Factor
20A 0.8 0.85 0.9 0.9 0.85 0.8

Max 10 second output current


Stato
30A r Lim
it

Excitation supply voltage:


Single phase 85 to 264V
Underexcitation Overexcitation
Excitation supply frequency:

Roto
Limiter Limiter
48Hz to 480Hz

r Lim
it
Underexcitation Overexcitation
Nominal sensing voltage: Monitor Monitor
100V to 120V
Auxiliary power supply:
24V d.c. Underexcited Mvar Overexcited

Voltage sensing phases: Limiter and Monitor Settings


Either 3 phase or 1 phase
Nominal generator frequency:
50Hz or 60Hz
Current transformer input nominal:
Either 5A or 1A
Current transformer input burden:
Less than 0.5VA
Maximum field voltage for forcing:
75% of available PMG voltage*
Minimum field voltage:
75% of available PMG voltage*
Voltage adjustment range
Selectable from +/-10% to +/-25%
Accuracy of control
+/-0.2%
Operating temperature range:
-20DegC to +50 DegC
Storage temperature range
20DegC to +80 DegC
Dimensions
570x699x185mm (HxWxD)
Weight:
31kg