FOR PULSATION AND PRESSURE CONTROL


A 2820 Blowertrol is a relay-controlled, air operated butterfly valve
mounted to a blower inlet. It has two purposes:
1. To eliminate pulsation occurring in some air systems when the blower
is operating at an extremely low percentage of its rated flow capacity.
2. To maintain blower outlet pressure within ±0.1"wc at a specified down-
stream point.
The Blowertrol air operator requires 4 cfm power at a fairly constant
pressure between 12 and 32 osi. Blowers operating in this pressure
range can be used as the power air source. Supply pressure exceeding
32 osi must be reduced. An external power air source is required for
blowers rated less than 12 osi.
Blowertrols are available for a choice of operating pressure ranges.
Standard units (with -S spring) will control between 8 and 32 osi. For
blowers rated below 8 osi, specify Blowertrol with -Y spring. For blowers
rated above 32 osi, specify -B spring.

3 pipe Blowertrol mounted on the inlet of a


diameters ? Presure tap in side or top
minimum of manifold at point where North American Turbo Blower.
pressure is to be controlled

Relay spring
adjustment plug

5 pipe
diameters Relay
Bleed
minimum
A Vent
Pressure drop across Blowertrol could be 1/6 of rated blower
pressure when 2820 is controlling pulsation (and pressure).
Air Filter When controlling pressure only, drop does not have to be
@ Blowertrol air
that much.
supply (1/2-20
NF tap with
adapter) * A mechanical stop prevents Blowertrol valve from closing
Valve completely. After a shutdown, this allows blower to devel-
disc
Vent ope 12 osi minimum required in discharge line UNLESS
stop
screw downstream air valves are open so wide that 12 osi cannot
Blower
build up due to pressure drop across partially closed
air inlet Blowertrol valve.

Blowertrol
Blower
air inlet

Õ Diagram showing Blowertrol installation. North American mounts


Blowertrol purchased with a blower. If blower pressure is not be -
tween 12 and 32 osi, @ cannot be factory connected. Connections
? and @ must be flush with inside face of pipe. A 7345-02-H is
required only when blower pressure is over 32 osi. See footnote
(e) on back side.

* Diaphragm must be mounted in a vertical plane (see position in photo).


Bulletin 2820
Page 2
d
BLOWERTROL SELECTION CHART FOR NORTH AMERICAN BLOWERS

Blower No. Blowertrol Blower No. Blowertrol Blower No. Blowertrol Blower No. Blowertrol

2308-11/3 2820-7 (4") 2312-11/4 2820-7 2316-31/2 2820-9 2324-14/3 2820-7


2308-14/1 2820-7 2312-19/1 2820-7 2316-35/1 2820-9 2324-19/2 2820-7
b
2308-17/1 2820-7 2312-26/1 2820-8 2316-21/1 2820-10 2324-26/2 2820-8
2308-24/1 2820-8 (6") 2312-35/1 2820-9 2324-35/2 2820-9
2308-31/1 2820-9 (8") 2312-21/1 2820-12 (12") 2324-21/1 2820-10
a c
2308-21/1 2820-10 (10") 2320-19/2 2820-7 2324-33/1 2820-12
2320-26/2 2820-8
2316-14/2 2820-7 2320-35/1 2820-9 2332-19/3 2820-7
2310-11/4 2820-7 2316-19/1 2820-7 2332-28/2 2820-9
2310-19/1 2820-7 2316-17/2 2820-7 2332-21/2 2820-10
2310-26/1 2820-8 2316-26/1 2820-8 2320-35/2 2820-9
e
2310-35/1 2820-9 2316-24/2 2820-8 2320-21/1 2820-10 2344-21/2 2820-10
a e
2310-21/1 2820-10 2316-28/1 2820-9 2320-33/1 2820-12 2344-28/3 2820-9
a
With blower inlet adapter 2-3162-2.
b
With blower inlet adapter 2-3162-1.
c
No Blowertrol is available for 2324-33/1-50 and -60.
d
For Blowertrols larger than 6" on blowers with 20 osi or higher pressure, specify a 2-3674-1 heavier return spring.
e
With blowers developing more than 32 osi pressure, install a 7345-02-H Pressure Regulator in the relay power-air supply line to protect
relay diaphragms.

2400-D Blowers use a 2820-10 Blowertrol.


2400-F Blowers use a 2820-12
2400-G Blowers use a 2831 Total Pressure Blowertrol.

Blowertrols are available in 4" (-7) through 12" (-12) pipe sizes. Standard practice is to select Blowertrol by matching inlet pipe
size of blower.
Blowertrols must always be mounted with the air operating diaphragm case in a vertical plane.
When required, adapter is included with Blowertrol mounted on a North American blower.

ORDER INFORMATION EXAMPLE:


2820 - 7 - S w/adapter for 2308-11/3 Blower
Blowertrol Designation

Code for Pipe Size

Type of Relay Spring


Spring
Operating Pressure designation
8 osi - 32 osi S (standard)
32 osi - 60 osi† B
Below 8 osi Y

Blower Designation with Adapter


† Also order 7345-02-H Regulator

NOTE: For field mounting, also order one R916-2310 adapter: for pressure tap on blower discharge (no additional charge
when ordered with Blowertrol).

WARNING: Situations dangerous to personnel and property can develop from incorrect operation of combustion equipment.