Ashida 1 MVA Installation Guide
Ashida 1 MVA Installation Guide
Ashida 1 MVA Installation Guide
DI-1 DI-2 DI-3 DI-4 DI-5 DI-6 DI-7 DI-8 DI-9 DI-10
6 7 8 9 10 11 Wiring Wiring 1 3
already already
connected connected
OTI-T WTI-T BUCH-A BUCH-T MOG-A PRV-T Battery AC Fail CB CB
&OTI-A Low CLOSE OPEN
&WTI - A
The wires coming from CTs of R, Y and B phase and neutral are to be connected 1, 2,
3 & 4 terminals of TB2.
The 5 no. terminal of TB 4 ( +ve supply for trip circuit) is to be connected to 13 of TB 3
and wire from 6 no. terminal is to be connected to +ve of trip coil (check the contactor
connected to J3 output before connecting +ve of trip coil) .
Wire from 14 no. terminal of TB 3 is connected to –ve of trip coil as shown in diagram.
For wiring inside the RMU, looping of wire coming from 13 th terminal of TB 3 should be
done to NO & NC contacts (this wire will act as common).
1st terminal of TB3 should be connected to NO (in breaker open condition) & 3rd terminal
of TB3 should be connected to NC (in breaker open condition).
When the wiring is complete as per drawing, connect the laptop with front port of Asihda
relay.
Changes to be made in settings file of the relay according to site:
Analog input:
Reporting Data Type Input
Index
2700 ShortFloatingPoint IA MAG
2701 ShortFloatingPoint IB MAG
2702 ShortFloatingPoint IC MAG
2703 ShortFloatingPoint FAULT L1
2704 ShortFloatingPoint FAULT L2
2705 ShortFloatingPoint FAULT L3
2706 ShortFloatingPoint FAULT IN
Digital input:
Reporting Data Type Input
Index
1001 SinglePoint OTI Trip
1002 SinglePoint WTI Trip
1003 SinglePoint Bucholz Alarm
1004 SinglePoint Bucholz Trip
1005 SinglePoint MOG & OTI &
WTI Alarm
1006 SinglePoint PRV Trip
1007 SinglePoint Battery Low
1008 SinglePoint AC Fail(use SF6
Healthy instead
were available)
1009 SinglePoint CB ON
1010 SinglePoint CB OFF
Digital Output:
Reporting Data Type Input
Index
703 DoubleCommand (1st Jout3(For Trip)
BIT)
Steps to upload patch file:
Check IP, Subnet Mask and Default Gateway using HMI.
Go to Network & Internet Settings -> Ethernet -> Change adapter options -> Ethernet
Internet Protocol Version 4(TCP/IPV4) Properties.
Assign IP, Subnet Mask and Default Gateway (Relay’s IP will be Laptop’s Gateway &
relay’s Gateway will be Laptop’s IP).
Open command Prompt, ping to relay by typing command :
Ping 172.30.29.6(use relay IP accordingly) –t
If continuous ping exist that means relay is communicating with laptop else check
connection again.
Go to Global -> Port 1 scroll down to protocol.
Disable protocol using HMI.
Now type http:\\ 172.30.29.6(use relay IP accordingly) in web browser.
Ashida page will open enter username: admin and password: admin#321.
Go to settings and upload patch file.
IP of relay will change after uploading patch file, set the desired IP and enable
protocol.
Go to Network -> Mobile WAN change APN type from automatic to manual.
Go to Network -> L2TP-VPN create new file edit basic information name, server
IP and port according to the image below.
Change MTU to 1500 and submit.
Go to Tools -> Now reboot the modem for activating these settings.