! Warning
Please keep well the units Operation Manual and Installation Manual for further reference
3 UNIT MAINTENANCE................................................................................................................................................ 4
4 SAFETY INSTRUCTION............................................................................................................................................. 5
5 TROUBLESHOOTING ................................................................................................................................................ 6
Note: Installation and maintenance are to be performed only by qualified persons who are familiar with
local code and regulation, and experienced with this type of appliance
Caution: Sharp edges and coil surfaces are a potential injury hazard. Please avoid touching them
Warning: Moving machinery and electrical power is hazardous. And it may cause severe personal
injury or death. Disconnect and lock off power before installing or servicing the unit
McQuay reserve the right to make changes in design and construction at anytime without prior notice.
1 General Introduction
Multi-connected inverter air conditioner units are most suitable for commercial building, office room, hotel, which includes the outdoor units and
multi-indoor units; The most advantage of this product range is unconventional outdoor units with inverter compressor, To meet different
requirements, there are many indoor units for options: ceiling concealed indoor units, ceiling cassette indoors units, wall mounted units,celling
duct indoors units, horizontal ceiling mounted and vertical floor standing indoor units;
● Outdoor Units: MDS-E Series
Product range: MDS080ER5、MDS100ER5、MDS120ER5、MDS140ER5、MDS160ER5、MDS180ER5、MDS200ER5、MDS220ER5、
MDS240ER5、MDS260ER5、MDS280ER5、MDS300ER5、MDS320ER5、MDS340ER5、MDS360ER5、MDS380ER5、MDS400ER5、
MDS420ER5、MDS440ER5、MDS460ER5、MDS480ER5、MDS500ER5、MDS520ER5、MDS540ER5、MDS560ER5、MDS580ER5、
MDS600ER5、MDS620ER5、MDS640ER5、MDS660ER5、MDS680ER5、MDS700ER5、MDS720ER5.
Feature: The outdoor units are compact, and elegant design with low noise; the compressor is with advanced technology of inverter, can
meet the stageless energy level adjustment from 50% to 130%;
Nomenclature,
MDS 100 E R 5 - F SA D
Applied region Omitted:China,D:Hong Kong,E:Other region.
Description of the unit
Power supply features F:380-415V/3N~/50Hz
For R410A refrigerant
Heat pump(omitted if cooling only)
Design serial No.
Cooling capacity No.100 means 10HP
McQuay multi-connected inverter air unit
MCK 028 W P - 07 A IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of the unit
Power supply features A:220-240V~/50Hz
Type of additional heater
07-07X100W electric heater
Omitted-no additional heater
For R410A refrigerant
Design serial No.
Cooling capacity No.(W) 028-2800W
McQuay Ceiling cassette
MCK 036 V P 2- A IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of the unit
Power supply features A:220-240V~/50Hz
MDB 125 V P - F IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of unit
Power supply features F:380V/3N~/50HzA:220-240V~/50Hz MDB125/140VP
MCM 056 V P - A IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of unit
Power supply features A:220-240V~/50Hz
For R410A refrigerant
Design serial No.
Cooling capacity No.,056-56X100W
McQuay ceiling exposed/floor standing unit
2 Operation Instruction
● Setting the indoor temperature
When unit is in cooling mode, it is recommended that indoor temperature is 5℃ lower than the outdoor temperature. It is conducive to
preserve the electric power, setting the indoor temperature increase of 1℃ in cooling mode or reduce 2℃ in heating mode.
Too high or too low indoor temperature will make people feel uncomfortable; It is suggested that in cooling mode , setting temperature
range: 26~28℃, In heating mode, the setting temperature range18~23℃;
● Clean the air filter
If the filter is filled with dirt, will reduce the air flow volume, in worst condition will cause unit failure; if units stop running too long, it is a
must to clean the filter first;
● Close window and prevent the heat exchange between indoor and outdoor
When cooling and heating, try not to open window and door, prevent the heat exchange between indoor and outdoor;
To use curtain to prevent the sunshine directly enter inside of room;
● Keep necessary ventilation
To keep indoor air quality, from time to time, it shall let the fresh air into the room;
● To set up the On/Off timer
When sleeping or nobody in house, please set up the On/Off timer to switch off the air conditioning.
3 Unit Maintenance
! Warning
Before maintenance service, please shut off the power supply and stop indoor and outdoor units
4 Safety instruction
4.1 Safety notice items:
● When units are operating
Do not use any sharp article to press the bottom of controller;
Do not twist and pull the cable of controller;
Do not use any chemical detergent to clean the wiring controller;
Do not put any barrier between the inlet and outlet of air both indoor and outdoor units;
● When units are in failure
Do not repair by yourself, contact with the local service agents for help;
If the wiring controller or remote controller show the malfunction code, contact with the local service agents for help;
If any refrigerant leakage is found, stop the units and call the local service agents for help, and keep the inside room ventilated;
● Long time not use the air conditioning
To use the units again after a long time no usage of air conditioning, to run units in fan mode for 4~5 hours,
To shut off the power, do not the unit is in standby status;
When restart the units, please power on 6 hours in advance and let unit in standby status;
● To relocate the unit
To reinstall or move the units to other place, contact with the local service agents for help;
Improper installation will cause power leakage and fire disaster;
Improper installation will cause refrigerant leakage and hurt of human being and environment;
4.2 User instruction
Before using the inverter unit, the user must know the followings:
● Cooling mode, temperature range : Indoor 15~24℃ (WB), Outdoor -5~52℃ (DB) , relative humidity ≤ 90%.
● Heating mode, temperature range : Indoor 15~27℃ (DB), Outdoor -23~15.5℃ (WB) , relative humidity ≤ 90%.
● Voltage fluctuation range,Fluctuations in grid frequency range and phase voltage unbalance rate:
Voltage fluctuation range is within ±10%; Fluctuations in grid frequency range is within ±1% (Applied for all units);
Phase voltage unbalance rate between any two phases shall be below 2% of the rated voltage (applied for 3-phase units).
● Refer to the indoor controller manual to know how to control the indoor unit operation mode;
● Storage temperature of unit is -25℃ ~65℃.
● If user can not solve the failure problem, contact with the local service agents for help;
● Please keep the children away from the units;
● Only professional technician can do the installation , maintenance and reparation;
● All the indoor units power shall be supplied unified , shut off the main power switch before any maintenance;
● When select outdoor units, do the selection properly ; The total capacity of the indoor unit should be controlled during 0.5 to 1.3 times the
capacity of the outdoor unit, and indoor unit should also be considered the coefficient of simultaneous using and capacity loss of long
connecting tube. If the capacity of the indoor units is too large, the room will cause the cooling or heating capacity of each units
insufficient.
● To prevent the inference of TV , radio and audio;
● Do not put any article at location of air inlet and outlet of indoor units;
● Indoor units shall not be set up to impact each other;
5 Troubleshooting
● If the followings unit malfunction occurred, please follow the below simple checking step to fix :
Symptom analyses Solution
Indoor temperature is higher (heating) or lower (cooling)
Compressor stop and but Re – set up the temperature
than setting temperature
fan work normally
When heating and defrost mode, indoor unit is just running Waiting for 10minutes
Power off Check and connect the power
Units do not work Set up the re-start function Wait or cancel timer On
Fuse broken in main power supply Replace the fuse
Cooling or heating not Air filter too dirty Clean or replace the filter
enough or too much Return air barrier Remove the barrier
Low battery Replace the battery
Remote controller unreadable
Wrong installation of battery Install properly
Condensing water in front Humidity too high Dehumidify
panel Setting temperature too low Set the higher indoor temperature
● If user can not fix the problem, please contact the local service agent for assistance, meanwhile record the malfunction code by wired
controller and indication light of units self-checking function; Following is the malfunction code could display in the wired controller:
Indication light twinkle related to the code of malfunction:
● When a wired controller is used for control, it displays fault codes. The following table provides fault codes on the wired controller and
lamp panel. When the PC software is used to monitor operating of the inverter air conditioner unit, the PC directly displays these fault
causes. These codes make maintenance rather convenient, saving both time and expense. In addition, faults of the outdoor unit are also
displayed on the digital tube of the outdoor unit control board. When characters in the table are displayed on the digital tube, see Basic
Character Legends for Reference.
1 A1 The indoor capacity exceeds outdoor's minimum allowable range Off Blinking Blinking
2 A2 Not existing model or wrong combination Off Off Blinking
3 A3 The indoor amount exceeds the maximum allowable quantity Off Off Blinking
4 A4 Driver board type isn't suited to main controller Off Off Blinking
5 A6 2# Exhaust temperature sensor fault On Blinking Blinking
6 A7 Exhaust temperature exceeding the allowed range 2# On Blinking Blinking
7 A8 Compressor over-current alarm 2# - - -
8 A9 Compressor weak magnetic protection alarm 2# - - -
9 AA Radiator overheating alarm 2# - - -
10 AC AC input over-current alarm 2# - - -
11 AD EEPROM of drive board malfunction alarm 2# - - -
12 AO DC busbar under-voltage 2# - - -
13 C0 DC busbar under-voltage 1# Off Blinking On
14 C1 AC input under-voltage 1# Off Blinking On
15 C2 AC input over-current stop 1# On Blinking Off
16 C3 Input voltage sampling malfunction 1# Blinking On Off
17 C4 DSP and PFC communication malfunction 1# Blinking On Off
18 C5 Radiator/PIM sensor malfunction 1# Off On Blinking
19 C6 DSP and communication board communication malfunction 1# Blinking On Off
20 C7 Outdoor unit and 1# drive board communication malfunction Blinking On Off
21 C8 Compressor over-current alarm 1# - - -
22 C9 Compressor weak magnetic protection alarm 1# Off On Blinking
23 CA Radiator overheating alarm 1# - - -
24 CC AC input over-current alarm 1# - - -
25 CD EEPROM of drive board malfunction alarm 1# Off On Blinking
26 CE Fixed speed compressor 1# over-current alarm Off On Blinking
27 CF Fixed speed compressor 2# over-current alarm Off On Blinking
28 E0 System malfunction Off Off Blinking
29 E1 Exhaust temperature sensor malfunction of Compressor1 (TH2) Off Blinking Blinking
30 E2 Ultra-low superheat degree protection Off Blinking Blinking
31 E3 4WV/CHECK VAVLE/EXV malfunction Blinking Blinking Off
32 E4 Exhaust temperature sensor malfunction of Compressor2 (TH3) Blinking Blinking Off
33 E5 Communication malfunction of household billing system and outdoor units Blinking Blinking Off
34 E6 The indoor capacity exceeds outdoor's maximum allowable range Off Off Blinking
35 E7 All indoor units and outdoor units communication malfunction On Blinking On
36 E8 IPM over-current stop 1# On Blinking Off
37 E9 Compressor drive failure 1# On Off Blinking
38 EA Compressor over-current 1# On Off Blinking
39 EB Open phase of compressor drive input voltage 1# Off Blinking On
40 EC IPM current sampling malfunction 1# On Blinking Off
41 ED Radiator or PIM overheating stop 1# Off On Blinking
42 EE Driver's PIM precharge failure 1# Off On Blinking
Silk-screen
LED
Green Red Yellow Red
Silk-screen
LED
Green Red Yellow Red
Silk-screen
LED
Green Red
0/O 5/S A F R
1 6 B H T
2 7 C L U
3 8 D N Y
4 9 E P
7 Technical Parameter
Multi INVERTER Units
MDS080E MDS100E MDS120E MDS140E MDS160E MDS180E MDS200E MDS220E MDS240E
Model
R5 R5 R5 R5 R5 R5 R5 R5 R5
Cooling capacity(kW) 25.0 28.0 33.6 40.0 45.0 50.5 56.0 61.6 68.0
Heating capacity(kW) 28.0 31.5 37.8 45.0 50.6 56.9 63.2 69.5 75.8
Power 380-415V/3N~/50Hz
Noise dB(A) 58 59 60 60 61 61 62 62 62
W×D×H(mm) 990*840*1780 1350*840*1780 1990*840*1780
Weight (kg) 208 209 242 304 327 329 414 439 442
Power consumption in
5.66 6.48 8.85 10.25 11.85 14.31 15.28 17.43 19.39
cooling (kW)
Ampere in cooling (A) 10.7 12.8 15.9 18.3 21.8 26.2 27.5 29.3 33.3
Power consumption in
6.81 7.78 9.67 10.48 12.70 14.95 15.70 17.60 19.90
heating (kW)
Ampere in heating (A) 12.6 14.5 17.3 18.5 22.3 27.0 28.8 29.5 34.1
Max.indoors-quantity 13 16 16 20 20 24 24 28 28
Refrigerant R410A
gas tube welding
Connecting
liquid expanded copper tube
LiquidΦ(mm(in)) 9.52(3/8〃) 12.7(1/2〃) 15.88(5/8")
GasΦ(mm(in)) 22.23(7/8") 28.6(1-1/8")
(Mode) (Master) (Slave) (Slave) (Mode) (Master) (Slave) (Slave) (Mode) (Master) (Slave) (Slave)
MDS260ER5 120 140 MDS420ER5 120 120 180 MDS580ER5 180 180 220
MDS280ER5 120 160 MDS440ER5 120 140 180 MDS600ER5 180 200 220
MDS300ER5 120 180 MDS460ER5 120 160 180 MDS620ER5 180 220 220
MDS320ER5 180 140 MDS480ER5 120 180 180 MDS640ER5 220 220 200
MDS340ER5 180 160 MDS500ER5 180 180 140 MDS660ER5 220 220 220
MDS360ER5 180 180 MDS520ER5 180 180 160 MDS680ER5 220 220 240
MDS380ER5 120 120 140 MDS540ER5 180 180 180 MDS700ER5 220 240 240
MDS400ER5 120 120 160 MDS560ER5 180 180 200 MDS720ER5 240 240 240
(Note:the above model amitted MD S*ER5,such as the 120 representa tive of MDS120ER5.)
MCC022 MCC025 MCC028 MCC032 MCC036 MCC040 MCC045 MCC050 MCC056 MCC063 MCC071
Model
VP VP VP VP VP VP VP VP VP VP VP
Cooling capacity(W) 2200 2500 2800 3200 3600 4000 4500 5000 5600 6300 7100
Heating capacity(W) 2500 2800 3200 3600 4000 4500 5000 5600 6300 7100 8000
Power 220-240V~/50Hz
Sound level dB(A) 29 31 32 34 37 37 40
W×D×H(mm) 900*599*199 1100*599*199
Weight(kg) 26 26 27 28 28 33 33
Power input(W) 43 47 57 62 96 98 138
Fan number 2 3
Air flow H : m³/h 430 600 630 730 900 1050 1200
ESP(Pa) 10Pa ,(0/30Pa adjustable)
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing, overload
Pump head 700
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 6.35(1/4”) 9.52(3/8”)
GasΦ(mm(in)) 9.52(3/8”) )
12.7(1/2” 15.88(5/8”)
Electrical heater
Model of indoor Capacity(W) Power input(W) Power
MCK028VP/WP 700 700 220-240V~/50Hz
MCK032VP/WP 700 700 220-240V~/50Hz
MCK036VP/WP 700 700 220-240V~/50Hz
MCK040VP/WP 700 700 220-240V~/50Hz
MCK045VP/WP 700 700 220-240V~/50Hz
MCK050VP/WP 1400 1400 220-240V~/50Hz
MCK056VP/WP 1400 1400 220-240V~/50Hz
MCK063VP/WP 1400 1400 220-240V~/50Hz
MCK071VP/WP 1400 1400 220-240V~/50Hz
MCK080VP/WP 1400 1400 220-240V~/50Hz
MCK090VP/WP 2100 2100 220-240V~/50Hz
MCK100VP/WP 2100 2100 220-240V~/50Hz
MCK112VP/WP 2100 2100 220-240V~/50Hz
MCK125VP/WP 2100 2100 220-240V~/50Hz
MCK140VP/WP 2100 2100 220-240V~/50Hz
MCK160WP 2100 2100 220-240V~/50Hz
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃;
Condensate pump
Model Power Power consumption (W) Pump lift (m)
220-240V~
MDS-CP24 10.8 0.7
/50Hz
220-240V~
MDS-CP120 12.0 1.2
/50Hz
Person
Item Failure Description Action Result
/Date