Operation Manual

Multi-connected Inverter Air Conditioner

MDS080ER5 ~ MDS720ER5(ECO-PRO SERIES)


1
MDS1808-A3
Part No: M08019472021

! Warning
Please keep well the units Operation Manual and Installation Manual for further reference

1 GENERAL INTRODUCTION ..................................................................................................................................... 2

2 OPERATION INSTRUCTION .................................................................................................................................... 4

3 UNIT MAINTENANCE................................................................................................................................................ 4

4 SAFETY INSTRUCTION............................................................................................................................................. 5

5 TROUBLESHOOTING ................................................................................................................................................ 6

6 STATUS DISPLAY OF DIGITAL TUBES ................................................................................................................ 11

7 TECHNICAL PARAMETER ..................................................................................................................................... 12

8 MAINTENANCE AND REPARATION RECORD:................................................................................................. 21

Note: Installation and maintenance are to be performed only by qualified persons who are familiar with
local code and regulation, and experienced with this type of appliance
Caution: Sharp edges and coil surfaces are a potential injury hazard. Please avoid touching them
Warning: Moving machinery and electrical power is hazardous. And it may cause severe personal
injury or death. Disconnect and lock off power before installing or servicing the unit

McQuay reserve the right to make changes in design and construction at anytime without prior notice.

©2016 Shenzhen McQuay


2

1 General Introduction
Multi-connected inverter air conditioner units are most suitable for commercial building, office room, hotel, which includes the outdoor units and
multi-indoor units; The most advantage of this product range is unconventional outdoor units with inverter compressor, To meet different
requirements, there are many indoor units for options: ceiling concealed indoor units, ceiling cassette indoors units, wall mounted units,celling
duct indoors units, horizontal ceiling mounted and vertical floor standing indoor units;
● Outdoor Units: MDS-E Series
Product range: MDS080ER5、MDS100ER5、MDS120ER5、MDS140ER5、MDS160ER5、MDS180ER5、MDS200ER5、MDS220ER5、
MDS240ER5、MDS260ER5、MDS280ER5、MDS300ER5、MDS320ER5、MDS340ER5、MDS360ER5、MDS380ER5、MDS400ER5、
MDS420ER5、MDS440ER5、MDS460ER5、MDS480ER5、MDS500ER5、MDS520ER5、MDS540ER5、MDS560ER5、MDS580ER5、
MDS600ER5、MDS620ER5、MDS640ER5、MDS660ER5、MDS680ER5、MDS700ER5、MDS720ER5.
Feature: The outdoor units are compact, and elegant design with low noise; the compressor is with advanced technology of inverter, can
meet the stageless energy level adjustment from 50% to 130%;
Nomenclature,

MDS 100 E R 5 - F SA D
Applied region Omitted:China,D:Hong Kong,E:Other region.
Description of the unit
Power supply features F:380-415V/3N~/50Hz
For R410A refrigerant
Heat pump(omitted if cooling only)
Design serial No.
Cooling capacity No.100 means 10HP
McQuay multi-connected inverter air unit

● Ceiling Concealed Indoor Units:


:MCC-VP/WP/SP Series
Product Range: MCC022SP、MCC025SP、 MCC028SP、MCC032SP、MCC036SP、MCC040SP、MCC045SP、MCC050SP、MCC056SP、
MCC063SP、MCC071SP、MCC080SP、MCC090SP、MCC100SP、MCC112SP、MCC125SP、MCC140SP、MCC160SP、MCC022VP、
MCC025VP、MCC028VP、MCC032VP、MCC036VP、MCC040VP、MCC045VP、MCC050VP、MCC056VP、MCC063VP、MCC071VP、
MCC018WP、MCC022WP、MCC025WP、MCC028WP、MCC032WP、MCC036WP、MCC040WP、MCC045WP、 MCC050WP、
MCC056WP、MCC063WP、MCC071WP。
Feature: Concealed type, space saving, ESP is multiple;
Nomenclature,

McQuay Ceiling MCC 022 V P-10 R B X A IA D


conceal indoor unit
Cooling capacity No.(W) Applied region Omitted:China,
022-2200W D:Hong Kong,E:Other region.
Design serial No. Description of the unit
For R410A refrigerant Power supply features
Type of additional heater A:220-240V~/50Hz
10-10X100W electric heater
Feature of control,filter,and pump
Omitted-no additional heater
Type of connecting pipe Air return model
R:right connecting pipe B:rear air return plenum
L:left connecting pipe D:lower air return plenum

● Ceiling Cassette Indoor Units:


:MCK-VP Series
Product Range: MCK028VP、MCK032VP、MCK036VP、MCK040VP、MCK045VP、MCK050VP、MCK056VP、MCK063VP、MCK071VP、MCK080VP、MCK090VP、
MCK100VP、MCK112VP、MCK125VP、MCK140VP;
Feature: 4 ways air supply evenly, streamlined design, in-build high efficiency filter;
Nomenclature,
MCK 028 V P - 07 A IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of the unit
Power supply features A:220-240V~/50Hz
Type of additional heater
07-07X100W electric heater
Omitted-no additional heater
For R410A refrigerant
Design serial No.
Cooling capacity No.(W) 028-2800W
McQuay Ceiling cassette

©2016 Shenzhen McQuay


3
● Ceiling Cassette Indoor Units:
:MCK-WP Series
Product Range: MCK028WP、MCK032WP、MCK036WP、MCK040WP、MCK045WP、MCK050WP、MCK056WP、MCK063WP、MCK071WP、MCK080WP、MCK090WP、
MCK100WP、MCK112WP、MCK125WP、MCK140WP、MCK160WP
Feature: 8 ways air supply evenly, streamlined design, in-build high efficiency filter;
Nomenclature,

MCK 028 W P - 07 A IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of the unit
Power supply features A:220-240V~/50Hz
Type of additional heater
07-07X100W electric heater
Omitted-no additional heater
For R410A refrigerant
Design serial No.
Cooling capacity No.(W) 028-2800W
McQuay Ceiling cassette

●Ceiling Cassette Indoor Units:


:MCK-VP2 Series
Product Range:MCK036VP2、MCK045VP2、MCK056VP2、MCK071VP2
Feature: 2 ways air supply evenly, streamlined design, in-build high efficiency filter;
Nomenclature,

MCK 036 V P 2- A IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of the unit
Power supply features A:220-240V~/50Hz

2-2 ways air; Omitted-4 ways air

For R410A refrigerant


Design serial No.
Cooling capacity No.(W) 036-3600W
McQuay Ceiling cassette

● Ceiling Duct Indoors Units :MDB-VP Series


Product Range::MDB125VP、MDB140VP、MDB224VP、MDB280VP
Feature: Installed above ceiling with air supply duct working, meet the requirement for long distance air supply;
Nomenclature,

MDB 125 V P - F IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of unit
Power supply features F:380V/3N~/50HzA:220-240V~/50Hz MDB125/140VP

For R410A refrigerant


Design serial No.
Cooling capacity No.,125-125X100W
McQuay Air-cooled cooling duct indoor unit

● Wall mounted units: MWM-WP Series


MDB224/280VP
Product Range: MWM022WP、MWM028WP、MWM036WP、MWM045WP、MWM056WP、MWM071WP.
Feature: elegant design, friendly installation, In-build high efficiency and mould proof filter, easy to detach and clean.
Nomenclature,
MWM 022 W P - A IB D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of the unit
Power supply features A:220-240V~/50Hz
For R410A refrigerant
Design serial No.
Cooling capacity No.(W) 022-2200W
McQuay Wall mounted indoor units

©2016 Shenzhen McQuay


4
● Horizontal Ceiling mounted and Vertical floor standing indoor units:
:MCM-VP Series
Product Range: MCM056VP、MCM071VP、MCM112VP、MCM125VP
Feature: elegant design, friendly installation;
Nomenclature,

MCM 056 V P - A IA D
Applied region Omitted:China,
D:Hong Kong,E:Other region.
Description of unit
Power supply features A:220-240V~/50Hz
For R410A refrigerant
Design serial No.
Cooling capacity No.,056-56X100W
McQuay ceiling exposed/floor standing unit

2 Operation Instruction
● Setting the indoor temperature
When unit is in cooling mode, it is recommended that indoor temperature is 5℃ lower than the outdoor temperature. It is conducive to
preserve the electric power, setting the indoor temperature increase of 1℃ in cooling mode or reduce 2℃ in heating mode.
Too high or too low indoor temperature will make people feel uncomfortable; It is suggested that in cooling mode , setting temperature
range: 26~28℃, In heating mode, the setting temperature range18~23℃;
● Clean the air filter
If the filter is filled with dirt, will reduce the air flow volume, in worst condition will cause unit failure; if units stop running too long, it is a
must to clean the filter first;
● Close window and prevent the heat exchange between indoor and outdoor
When cooling and heating, try not to open window and door, prevent the heat exchange between indoor and outdoor;
To use curtain to prevent the sunshine directly enter inside of room;
● Keep necessary ventilation
To keep indoor air quality, from time to time, it shall let the fresh air into the room;
● To set up the On/Off timer
When sleeping or nobody in house, please set up the On/Off timer to switch off the air conditioning.

3 Unit Maintenance

! Warning
Before maintenance service, please shut off the power supply and stop indoor and outdoor units

● Indoor Unit Maintenance


Part Maintenance Checking step Times/ month
(Recommend)
1. Open the grill
2. Take out the air filter
3. Use brush to clean the air filter with below 40℃ water
Air filter 1
4. After drying, the filter shall be loaded back in situ.
Note: Do not use detergents such as gasoline, dehydrating, benzene substances or
other chemicals.
1. Get rid of the dust and dirt by using cloth and detergent , clean the panel.
Front Panel Note: Do not use detergents such as gasoline, dehydrating, benzene substances or 1
other chemicals. Otherwise it will cause the plastic surface deformation.
1. To check the drain pan and hose are clean or not, if it is dirty, clean it ;
Drain Pan and 2. To check there is no barrier for the condensing water flow out;
3
hose 3. Pay attention to dustproof anti-blocking when the pump is connected, and it
needs cleaning on time to keep smooth flow.
1. To clean the dirt of fins;
Evaporator 1
2. To clean any barrier for indoor air flow.
1. To check the running ampere and voltage is normal or not;
Electrical Part 12
2. To check the electrical connection is fixed or loose.

©2016 Shenzhen McQuay


5
●Indoor Unit Maintenance
Part Maintenance Checking step Times/ month
(Recommend)
Outdoor fan To check the noise level 1
1. To clean the dirt of fins
Outdoor condenser 1
2. To remove any barrier which inhibit the air flow
Compressor Compressor running noise and vibrations 1
1. To check the running ampere and voltage is normal or not
Electrical Part 2. To check the electrical connection is fixed or loose 1
3. To check the controller in normal working conditions
Note: 1.Don not sprinkle water or use combustible sprays, to avoid fault, leakage of power and fire accidence;
2. Not exposure or broiled in the sun when you clean the filter, otherwise it will lead to deformation.
3. Please adjust the maintenance frequency based on the application environment.

4 Safety instruction
4.1 Safety notice items:
● When units are operating
Do not use any sharp article to press the bottom of controller;
Do not twist and pull the cable of controller;
Do not use any chemical detergent to clean the wiring controller;
Do not put any barrier between the inlet and outlet of air both indoor and outdoor units;
● When units are in failure
Do not repair by yourself, contact with the local service agents for help;
If the wiring controller or remote controller show the malfunction code, contact with the local service agents for help;
If any refrigerant leakage is found, stop the units and call the local service agents for help, and keep the inside room ventilated;
● Long time not use the air conditioning
To use the units again after a long time no usage of air conditioning, to run units in fan mode for 4~5 hours,
To shut off the power, do not the unit is in standby status;
When restart the units, please power on 6 hours in advance and let unit in standby status;
● To relocate the unit
To reinstall or move the units to other place, contact with the local service agents for help;
Improper installation will cause power leakage and fire disaster;
Improper installation will cause refrigerant leakage and hurt of human being and environment;
4.2 User instruction
Before using the inverter unit, the user must know the followings:
● Cooling mode, temperature range : Indoor 15~24℃ (WB), Outdoor -5~52℃ (DB) , relative humidity ≤ 90%.
● Heating mode, temperature range : Indoor 15~27℃ (DB), Outdoor -23~15.5℃ (WB) , relative humidity ≤ 90%.
● Voltage fluctuation range,Fluctuations in grid frequency range and phase voltage unbalance rate:
Voltage fluctuation range is within ±10%; Fluctuations in grid frequency range is within ±1% (Applied for all units);
Phase voltage unbalance rate between any two phases shall be below 2% of the rated voltage (applied for 3-phase units).
● Refer to the indoor controller manual to know how to control the indoor unit operation mode;
● Storage temperature of unit is -25℃ ~65℃.
● If user can not solve the failure problem, contact with the local service agents for help;
● Please keep the children away from the units;
● Only professional technician can do the installation , maintenance and reparation;
● All the indoor units power shall be supplied unified , shut off the main power switch before any maintenance;
● When select outdoor units, do the selection properly ; The total capacity of the indoor unit should be controlled during 0.5 to 1.3 times the
capacity of the outdoor unit, and indoor unit should also be considered the coefficient of simultaneous using and capacity loss of long
connecting tube. If the capacity of the indoor units is too large, the room will cause the cooling or heating capacity of each units
insufficient.
● To prevent the inference of TV , radio and audio;
● Do not put any article at location of air inlet and outlet of indoor units;
● Indoor units shall not be set up to impact each other;

©2016 Shenzhen McQuay


6
● Do not put any article at location of air inlet and outlet of outdoor units;
● Do not touch any sharp edge of fins and panel etc;
● Do not use the leakage testing detergent;
● When in low ambient temperature, add the electrical heater; When the bit5 in SW1 code of outdoor is OFF and the ambient temperature is
bellow 0 ℃, the default setting will control the auxiliary electric heating turn on automatically according to temperature difference of
indoor and setting, When the bit5 in SW1 code of outdoor is ON, the auxiliary electric heating must be turned on manually.

5 Troubleshooting
● If the followings unit malfunction occurred, please follow the below simple checking step to fix :
Symptom analyses Solution
Indoor temperature is higher (heating) or lower (cooling)
Compressor stop and but Re – set up the temperature
than setting temperature
fan work normally
When heating and defrost mode, indoor unit is just running Waiting for 10minutes
Power off Check and connect the power
Units do not work Set up the re-start function Wait or cancel timer On
Fuse broken in main power supply Replace the fuse
Cooling or heating not Air filter too dirty Clean or replace the filter
enough or too much Return air barrier Remove the barrier
Low battery Replace the battery
Remote controller unreadable
Wrong installation of battery Install properly
Condensing water in front Humidity too high Dehumidify
panel Setting temperature too low Set the higher indoor temperature
● If user can not fix the problem, please contact the local service agent for assistance, meanwhile record the malfunction code by wired
controller and indication light of units self-checking function; Following is the malfunction code could display in the wired controller:
Indication light twinkle related to the code of malfunction:
● When a wired controller is used for control, it displays fault codes. The following table provides fault codes on the wired controller and
lamp panel. When the PC software is used to monitor operating of the inverter air conditioner unit, the PC directly displays these fault
causes. These codes make maintenance rather convenient, saving both time and expense. In addition, faults of the outdoor unit are also
displayed on the digital tube of the outdoor unit control board. When characters in the table are displayed on the digital tube, see Basic
Character Legends for Reference.

Fault Displayed Fault of Lamp Panel


No. Fault Description
Code
HEAT DRY/TIMER SLEEP/FAN

Fault codes of the indoor unit part:

1 N0 Coil inlet sensor malfunction On On Blinking


2 N1 Coil middle sensor malfunction On On Blinking
3 N2 Coil outlet sensor malfunction On On Blinking
4 N3 Air return/room sensor malfunction On On Blinking
5 N4 Condensate pump (water level switch) malfunction Blinking Blinking On
6 N5 EEPROM storage malfunction of indoor unit Blinking On On
7 N8 Indoor unit and outdoor unit communication malfunction On Blinking On
8 N9 DIP malfunction Blinking On On
MC163/MC164 fault light
Reson1:fan motor stall
flashes 3 times

Reson2:fan motor speed MC163/MC164 fault light


IDU fan malfunction lose flashes 5 times
9 NA Blinking On On
Reson3:main controller and
MC163/MC164 fault light
MC163/MC164
flashes 5 times
communication malfunction
When combine with MDX-C unit:The electric-heater temperature protection/Fan-motor
overload protection/Pressure difference switch disconnection
The filter of the fresh air unit is blocked
10 NC On On Blinking
The program version of the outdoor unit is too low when combine with MDX-C unit
11 NE The environment temperature exceeds fresh-air unit's allowable range Off Blinking Blinking

Fault codes of the wired controller part:

©2016 Shenzhen McQuay


7
1 NB Keypad malfunction of Wired controller - - -
2 ND Fresh air inlet temperature sensor malfunction
3 NF Wired controller and indoor unit communication malfunction - - -
4 N6 EEPROM storage malfunction of wired controller - - -
5 N7 Wired controller temperature sensor malfunction - - -

Fault codes of the outdoor unit part:

1 A1 The indoor capacity exceeds outdoor's minimum allowable range Off Blinking Blinking
2 A2 Not existing model or wrong combination Off Off Blinking
3 A3 The indoor amount exceeds the maximum allowable quantity Off Off Blinking
4 A4 Driver board type isn't suited to main controller Off Off Blinking
5 A6 2# Exhaust temperature sensor fault On Blinking Blinking
6 A7 Exhaust temperature exceeding the allowed range 2# On Blinking Blinking
7 A8 Compressor over-current alarm 2# - - -
8 A9 Compressor weak magnetic protection alarm 2# - - -
9 AA Radiator overheating alarm 2# - - -
10 AC AC input over-current alarm 2# - - -
11 AD EEPROM of drive board malfunction alarm 2# - - -
12 AO DC busbar under-voltage 2# - - -
13 C0 DC busbar under-voltage 1# Off Blinking On
14 C1 AC input under-voltage 1# Off Blinking On
15 C2 AC input over-current stop 1# On Blinking Off
16 C3 Input voltage sampling malfunction 1# Blinking On Off
17 C4 DSP and PFC communication malfunction 1# Blinking On Off
18 C5 Radiator/PIM sensor malfunction 1# Off On Blinking
19 C6 DSP and communication board communication malfunction 1# Blinking On Off
20 C7 Outdoor unit and 1# drive board communication malfunction Blinking On Off
21 C8 Compressor over-current alarm 1# - - -
22 C9 Compressor weak magnetic protection alarm 1# Off On Blinking
23 CA Radiator overheating alarm 1# - - -
24 CC AC input over-current alarm 1# - - -
25 CD EEPROM of drive board malfunction alarm 1# Off On Blinking
26 CE Fixed speed compressor 1# over-current alarm Off On Blinking
27 CF Fixed speed compressor 2# over-current alarm Off On Blinking
28 E0 System malfunction Off Off Blinking
29 E1 Exhaust temperature sensor malfunction of Compressor1 (TH2) Off Blinking Blinking
30 E2 Ultra-low superheat degree protection Off Blinking Blinking
31 E3 4WV/CHECK VAVLE/EXV malfunction Blinking Blinking Off
32 E4 Exhaust temperature sensor malfunction of Compressor2 (TH3) Blinking Blinking Off
33 E5 Communication malfunction of household billing system and outdoor units Blinking Blinking Off
34 E6 The indoor capacity exceeds outdoor's maximum allowable range Off Off Blinking
35 E7 All indoor units and outdoor units communication malfunction On Blinking On
36 E8 IPM over-current stop 1# On Blinking Off
37 E9 Compressor drive failure 1# On Off Blinking
38 EA Compressor over-current 1# On Off Blinking
39 EB Open phase of compressor drive input voltage 1# Off Blinking On
40 EC IPM current sampling malfunction 1# On Blinking Off
41 ED Radiator or PIM overheating stop 1# Off On Blinking
42 EE Driver's PIM precharge failure 1# Off On Blinking

©2016 Shenzhen McQuay


8
43 EF DC busbar over-voltage 1# Off Blinking On
44 F0 Master communicate fail with No.0 Slave Unit On Blinking On
45 F1 Master communicate fail with No.1 Slave Unit On Blinking On
46 F2 Master communicate fail with No.2 Slave Unit On Blinking On
47 F4 Wrong dial setting of outdoor unit Off Blinking Blinking
48 F5 Fixed speed compressor 1# discharge temperature exceeds allowed range Off Blinking Blinking
49 F6 Fixed speed compressor 2# discharge temperature exceeds allowed range Off Blinking Blinking
50 F7 Fixed speed compressor 1# current sensor malfunction On Blinking Blinking
51 F8 Fixed speed compressor 2# current sensor malfunction On Blinking Blinking
52 F9 Plate heat exchanger freeze malfunction On Blinking Blinking
53 FA Fire Alarm Blinking On Blinking
54 J1 AC input under-voltage 2# Off Blinking On
55 J2 AC input over-current stop 2# On Blinking Off
56 J3 Input voltage sampling malfunction 2# Blinking On Off
57 J4 DSP and PFC communication malfunction 2# Blinking On Off
58 J5 Radiator/PIM sensor malfunction 2# Off On Blinking
59 J6 DSP and communication board communication malfunction 2# Blinking On Off
60 J7 Outdoor unit and 2# drive board communication malfunction Blinking On Off
61 J8 IPM over-current stop 2# On Blinking Off
62 J9 Compressor drive failure 2# On Off Blinking
63 JA Compressor over-current 2# On Off Blinking
64 JB Lack phase of compressor drive input voltage 2# Off Blinking On
65 JC IPM current sampling malfunction 2# On Blinking Off
66 JD Radiator or PIM overheating stop 2# Off On Blinking
67 JE pre charge failure 2# - - -
68 JF DC busbar over-voltage 2# Off Blinking On
69 H0 Stop malfunction due to ultra-low superheat degree of air exhaust Off Blinking Blinking
70 H1 Temperature sensor malfunction of main subcool outlet (TH10) Off Blinking Off
71 H2 Suction temperature sensor fault(TH12) Off Blinking Off
72 H3 1# Exhaust temperature sensor fault(TH1) Off Blinking Off
73 H4 Temperature sensor malfunction of branch subcool outlet (TH11) Off Blinking Off
74 H5 Outdoor heat exchanger coil outlet f malfunction (TH9) Off Blinking Off
75 H6 Outdoor environment sensor malfunction (TH8) Off Blinking Off
76 H7 EEPROM storage malfunction of outdoor unit Off Off Blinking
77 H8 High pressure over-high/over-low fault Blinking Off Blinking
78 H9 High pressure sensor malfunction Blinking Off Blinking
79 HA High pressure switch disconnection Blinking Off Blinking
80 HB Low pressure over-low malfunction Blinking Off Off
81 HC Low pressure sensor malfunction Blinking Off Off
82 HD Alarm fault due to ultra-low superheat degree of air exhaust Off Blinking Blinking
83 HE Ambient temperature exceeding the allowed range Off Blinking Blinking
Exhaust temperature exceeding the allowed range OR exhaust temperature switch
84 HF Off Blinking Blinking
disconnection
85 P0 FAN1: over-current Blinking Blinking Blinking
86 P1 FAN1:IPM malfunction Blinking Blinking Blinking
87 P2 FAN1: Drive stall Blinking Blinking Blinking
88 P3 FAN1: Lack phase Blinking Blinking Blinking
89 P4 FAN1: Speed loss Blinking Blinking Blinking

©2016 Shenzhen McQuay


9
90 P5 FAN1: Over speed while startup Blinking Blinking Blinking
91 P6 FAN1: Hall signal malfunction Blinking Blinking Blinking
92 P7 FAN1: Hardware malfunction Blinking Blinking Blinking
93 P8 FAN1: DC busbar under-voltage Blinking Blinking Blinking
94 P9 FAN1:IPM overheating Blinking Blinking Blinking
95 PA FAN1:Communication malfunction Blinking Blinking Blinking
96 PB FAN1: Fatal malfunction Blinking Blinking Blinking
97 PF Outdoor unit and drive board of fan1 communication malfunction Blinking Blinking Blinking
98 U0 FAN2: over-current Blinking Blinking Blinking

99 U1 FAN2:IPM malfunction Blinking Blinking Blinking

100 U2 FAN2: Drive stall Blinking Blinking Blinking


101 U3 FAN2: Lack phase Blinking Blinking Blinking
102 U4 FAN2: Speed loss Blinking Blinking Blinking
103 U5 FAN2: Over speed while startup Blinking Blinking Blinking
104 U6 FAN2: Hall signal malfunction Blinking Blinking Blinking
105 U7 FAN2: Hardware malfunction Blinking Blinking Blinking
106 U8 FAN2: DC busbar under-voltage Blinking Blinking Blinking
107 U9 FAN2:IPM overheating Blinking Blinking Blinking
108 UA FAN2:Communication malfunction Blinking Blinking Blinking
109 UB FAN2: Fatal malfunction Blinking Blinking Blinking
110 UF Outdoor unit and drive board of fan2 communication malfunction Blinking Blinking Blinking
111 00 Communication malfunction with indoor unit 0# On Blinking On
120 01 Communication malfunction with indoor unit 1# On Blinking On
N N N On Blinking On
121 63 Communication malfunction with indoor unit 63# On Blinking On
122 A0 1# Compressor driver malfunction On On Off
123 UE 1# Compressor driver DIP setting error On Off On
124 PE 2# Compressor driver DIP setting error On Off On
125 SA The front of subcooling branch temperature sensor malfunction On On On

©2016 Shenzhen McQuay


10
Displayed normal operating status of the lamp panel:

Silk-screen

MWM Mode Cool Fan Dry Heat Timing Sleep

LED
Green Red Yellow Red

Silk-screen Cool Dry/ Timing Fan Heat


MCC
MDB Mode Cool Dry Timing Fan Sleep Heat
MDBX
LED
Green Red

Silk-screen

Mode Cool Heat Dry Timing Fan Sleep


MCK

LED
Green Red Yellow Red

Silk-screen

MCM Mode Cool Dry Timing Fan Sleep Heat

LED
Green Red

The following symptoms are not faults of the units:


Sometimes odorous gases blow out of units because tobacco smoke, cosmetic odor, and odors from furniture and electrical appliances are
taken into the units. You may hear fizzles when the air conditioner is cooling, heating, started, or stopped. The sounds are generated when
refrigerant flows in the unit.

©2016 Shenzhen McQuay


11

6 Status Display of Digital Tubes


Four 8-section 4-bit digital tubes (red) are configured for the outdoor unit. In the normal running status, the digital tube displays the current
running mode or status. Once any fault occurs, the fault code is displayed first. If multiple faults occur, they are displayed in turn. For the specific
fault codes, see “Unit Troubleshooting” in part 5.
Note: The digital tube will go out when you do not operate any button within 10 minutes. Normal display is retuned if any button is pressed. This
restriction does not take effect when any fault occurs. The digital tube will display the fault continuously.

Meanings of displayed symbols on the digital tube


No. Icon Content No. Icon Content
NULL The outdoor unit is in the dEb: button debugging parameter
1 18
standby status. menu
REST: The outdoor unit is in the SPEC: special button function menu
2 19
reset status.
CST: The outdoor unit is in the NOAE: night noises reduction function
3 20
cooling start process.
COOL: The outdoor/indoor unit is in FAC: Restore factory settings
4 21
the cooling status.
CSP: The outdoor unit is in the BAUD:Set communication speed of
5 22
cooling stop process. units and PC
DST: The outdoor unit is in the PreH: The compressor pre-heating
6 23
defrosting start status. status
DEF: The outdoor/indoor unit is in the CFEE:Set the function of household
7 24
defrosting status. billing
DSP: The outdoor unit is in the IGNO: Leave alone the very
8 25
defrosting stop status. unavailable unit
HST: The outdoor unit is in the FSPD: Choose proper fan gear table
9 26
heating startup process. (15/30)
HEAT: The outdoor/indoor unit is in
10 27 STPR:Set static pressure
the heating status.
HSP: The outdoor unit is in the
11 28 HSRC: Set heat-pump or cool-only
heating stop process.
TEST:Hardware testing mode FRAL: Whether the fire alarm is
12 29 enabled

ERRO: Common error of the outdoor


13 30 FRTP: Select the type of antifreeze
unit
OPEN: Fully open the electronic REFC: Into the cold media charging
14 31 mode
expansion valve by force
Outdoor unit DIP setting error/model CREF: Calculate the K value of
15 32 refrigerant coefficient
setting error
PARA: button setting parameter UREF: Refrigerant filling and frequency
16 33 conversion speed limit
menu
BOOT: prompt in software upgrade
17

Basic Character Legends for Reference


ICON CONTENT ICON CONTENT ICON CONTENT ICON CONTENT ICON CONTENT

0/O 5/S A F R

1 6 B H T

2 7 C L U

3 8 D N Y

4 9 E P

©2016 Shenzhen McQuay


12

7 Technical Parameter
Multi INVERTER Units
MDS080E MDS100E MDS120E MDS140E MDS160E MDS180E MDS200E MDS220E MDS240E
Model
R5 R5 R5 R5 R5 R5 R5 R5 R5
Cooling capacity(kW) 25.0 28.0 33.6 40.0 45.0 50.5 56.0 61.6 68.0
Heating capacity(kW) 28.0 31.5 37.8 45.0 50.6 56.9 63.2 69.5 75.8
Power 380-415V/3N~/50Hz
Noise dB(A) 58 59 60 60 61 61 62 62 62
W×D×H(mm) 990*840*1780 1350*840*1780 1990*840*1780
Weight (kg) 208 209 242 304 327 329 414 439 442
Power consumption in
5.66 6.48 8.85 10.25 11.85 14.31 15.28 17.43 19.39
cooling (kW)
Ampere in cooling (A) 10.7 12.8 15.9 18.3 21.8 26.2 27.5 29.3 33.3
Power consumption in
6.81 7.78 9.67 10.48 12.70 14.95 15.70 17.60 19.90
heating (kW)
Ampere in heating (A) 12.6 14.5 17.3 18.5 22.3 27.0 28.8 29.5 34.1
Max.indoors-quantity 13 16 16 20 20 24 24 28 28
Refrigerant R410A
gas tube welding
Connecting
liquid expanded copper tube
LiquidΦ(mm(in)) 9.52(3/8〃) 12.7(1/2〃) 15.88(5/8")
GasΦ(mm(in)) 22.23(7/8") 28.6(1-1/8")

Model MDS260ER5 MDS280ER5 MDS300ER5 MDS320ER5 MDS340ER5 MDS360ER5 MDS380ER5 MDS400ER5


Combined units 12+14 12+16 12+18 18+14 18+16 18+18 12+12+14 12+12+16
Cooling capacity(kW) 73.6 78.6 84.1 90.5 95.5 101 107.2 112.2
Heating capacity(kW) 82.8 88.4 94.7 101.9 107.5 113.8 120.6 126.2
Power 380-415V/3N~/50Hz
Noise dB(A) 63 63 63 64 64 64 64 65
Weight (kg) 546 569 571 633 656 658 788 811
Power consumption in
19.1 20.7 23.16 24.56 26.16 28.62 27.95 29.55
cooling (kW)
Ampere in cooling (A) 34.2 37.7 42.1 44.5 48 52.4 50.1 53.6
Power consumption in
20.15 22.37 24.62 25.43 27.65 29.9 29.82 32.04
heating (kW)
Ampere in heating (A) 35.8 39.6 44.3 45.5 49.3 54 53.1 56.9
Max.indoors-quantity 32 32 36 36 40 40 44 44
Refrigerant R410A
gas tube welding
Connecting
liquid tube welding
LiquidΦ(mm(in)) 19.05(3/4")
GasΦ(mm(in)) 31.8(1-1/4") 34.9(1-3/8") 38.1(1-1/2")

Model MDS420ER5 MDS440ER5 MDS460ER5 MDS480ER5 MDS500ER5 MDS520ER5 MDS540ER5


Combined units 12+12+18 12+14+18 12+16+18 12+18+18 18+18+14 18+18+16 18+18+18
Cooling capacity(kW) 117.7 124.1 129.1 134.6 141 146 151.5
Heating capacity(kW) 132.5 139.7 145.3 151.6 158.8 164.4 170.7
Power 380-415V/3N~/50Hz
Noise dB(A) 65 65 65 65 66 66 66
Weight (kg) 813 875 898 900 962 985 987
Power consumption in
32.01 33.41 35.01 37.47 38.87 40.47 42.93
cooling (kW)
Ampere in cooling (A) 58 60.4 63.9 68.3 70.7 74.2 78.6
Power consumption in
34.29 35.1 37.32 39.57 40.38 42.6 44.85
heating (kW)
Ampere in heating (A) 61.6 62.8 66.6 71.3 72.5 76.3 81
Max.indoors-quantity 48 48 52 52 54 54 56
Refrigerant R410A
Connecti gas tube welding
ng liquid tube welding
LiquidΦ(mm(in)) 19.05(3/4")
GasΦ(mm(in)) 38.1(1-1/2")

©2016 Shenzhen McQuay


13
MDS560E MDS580E MDS600E MDS620E MDS640E MDS660E MDS680E MDS700E MDS720E
Model
R5 R5 R5 R5 R5 R5 R5 R5 R5
Combined units 18+18+20 18+18+22 18+20+22 18+22+22 22+22+20 22+22+22 22+22+24 22+24+24 24+24+24
Cooling capacity(kW) 157 162.6 168.1 173.7 179.2 184.8 191.2 197.6 204
Heating capacity(kW) 177 183.3 189.6 195.9 202.2 208.5 214.8 221.1 227.4
Power 380~415V/3N~/50Hz
Noise dB(A) 66 66 66 66 67 67 67 67 67
Weight (kg) 1072 1097 1182 1207 1292 1317 1320 1323 1326
Power consumption in
43.9 46.05 47.02 49.17 50.14 52.29 54.25 56.21 58.17
cooling (kW)
Ampere in cooling (A) 79.9 81.7 83 84.8 86.1 87.9 91.9 95.9 99.9
Power consumption in
45.6 47.5 48.25 50.15 50.9 52.8 55.1 57.4 59.7
heating (kW)
Ampere in heating (A) 82.8 83.5 85.3 86 87.8 88.5 93.1 97.7 102.3
Max.indoors-quantity 56 58 58 60 60 60 60 60 60
Refrigerant R410A
Connectin gas tube welding
g liquid expanded copper tube
LiquidΦ(mm(in)) 22.23(7/8")
GasΦ(mm(in)) 44.5(1-3/4")
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃;
3. The noise level is tested in the incomplete anechoic lab under the standard refrigeration condition and got from the value, that from a point
is half of the unit height plus I meter in front of the unit. The real noise value in operation may be a little higher than the tested value due to
the influence of the actual environment; Testing power supply: 380V/3N~/50Hz
4. The width is just for the unit, not including the width of bottom edge.
Combination form of the combined outdoor units

(MDS-E combination form of the combined outdoor unit s)

(Mode) (Master) (Slave) (Slave) (Mode) (Master) (Slave) (Slave) (Mode) (Master) (Slave) (Slave)

MDS260ER5 120 140 MDS420ER5 120 120 180 MDS580ER5 180 180 220

MDS280ER5 120 160 MDS440ER5 120 140 180 MDS600ER5 180 200 220

MDS300ER5 120 180 MDS460ER5 120 160 180 MDS620ER5 180 220 220

MDS320ER5 180 140 MDS480ER5 120 180 180 MDS640ER5 220 220 200

MDS340ER5 180 160 MDS500ER5 180 180 140 MDS660ER5 220 220 220

MDS360ER5 180 180 MDS520ER5 180 180 160 MDS680ER5 220 220 240

MDS380ER5 120 120 140 MDS540ER5 180 180 180 MDS700ER5 220 240 240

MDS400ER5 120 120 160 MDS560ER5 180 180 200 MDS720ER5 240 240 240
(Note:the above model amitted MD S*ER5,such as the 120 representa tive of MDS120ER5.)

©2016 Shenzhen McQuay


14
Ceiling concealed Indoor units
MCC022 MCC025 MCC028 MCC032 MCC036 MCC040 MCC045 MCC050 MCC056 MCC063 MCC071
Model
SP SP SP SP SP SP SP SP SP SP SP
Cooling capacity
2200 2500 2800 3200 3600 4000 4500 5000 5600 6300 7100
(W)
Heating capacity
2500 2800 3200 3600 4000 4500 5000 5600 6300 7100 8000
(W)
Power 220-240V~/50Hz
Sound level dB(A) 31 34 35 37
W×D×H(mm) 1124*469*220 1384*490*250
Weight(Kg) 22 25 27
Power input(W) 47 81 82 123
Fan number 2
H:
Air flow 450 580 800 960
m³/h
ESP(Pa) 15Pa ,(30Pa adjustable)
Drain R3/4
Protection Anti-freezing, overload
Pump head 700
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 6.35(1/4”) 9.52(3/8”)
GasΦ(mm(in)) 9.52(3/8”) 12.7(1/2”) 15.88(5/8”)

Model MCC080SP MCC090SP MCC100SP MCC112SP MCC125SP MCC140SP MCC160SP


Cooling capacity(W) 8000 9000 10000 11200 12500 14000 16000
Heating capacity(W) 9000 10000 11200 12500 14000 16000 18000
Power 220-240V~/50Hz
Sound level dB(A) 43 43 46 47 47 49 49
W×D×H(mm) 1384*490*250 1734*490*250 1994*490*250
Weight(kg) 30 41 41 41 41 47
Power input(W) 157 210 246 276 276 377
Fan number 2 3 4
Air flow H : m³/h 1200 1400 1700 1900 1900 2500
ESP(Pa) 50 Pa , (30 Pa adjustable)
Drain R3/4
Protection Anti-freezing, overload
Pump head 700
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 9.52(3/8”)
GasΦ(mm(in)) 15.88(5/8”)

MCC022 MCC025 MCC028 MCC032 MCC036 MCC040 MCC045 MCC050 MCC056 MCC063 MCC071
Model
VP VP VP VP VP VP VP VP VP VP VP
Cooling capacity(W) 2200 2500 2800 3200 3600 4000 4500 5000 5600 6300 7100
Heating capacity(W) 2500 2800 3200 3600 4000 4500 5000 5600 6300 7100 8000
Power 220-240V~/50Hz
Sound level dB(A) 29 31 32 34 37 37 40
W×D×H(mm) 900*599*199 1100*599*199
Weight(kg) 26 26 27 28 28 33 33
Power input(W) 43 47 57 62 96 98 138
Fan number 2 3
Air flow H : m³/h 430 600 630 730 900 1050 1200
ESP(Pa) 10Pa ,(0/30Pa adjustable)
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing, overload
Pump head 700
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 6.35(1/4”) 9.52(3/8”)
GasΦ(mm(in)) 9.52(3/8”) )
12.7(1/2” 15.88(5/8”)

©2016 Shenzhen McQuay


15
MCC0 MCC0 MCC0 MCC0 MCC0 MCC0 MCC0 MCC0 MCC0 MCC0 MCC0 MCC0
Model
18WP 22WP 25WP 28WP 32WP 36 WP 40 WP 45WP 50WP 56 WP 63 WP 71WP
Cooling capacity
1800 2200 2500 2800 3200 3600 4000 4500 5000 5600 6300 7100
(W)
Heating capacity
2200 2500 2800 3200 3600 4000 4500 5000 5600 6300 7100 8000
(W)
Power 220-240V~/50Hz
Sound level
27 28 28 29 33 33 34 34 36 36 37 38
dB(A)
W×D×H(mm) 700*450*210 900*450*210 1150*450*210
Weight(kg) 17.4 20 24
Power input(W) 32 32 32 37 47 57 57 57 80 80 89 97
Fan number 2 3
Air flow H : m³/h 400 400 400 450 550 620 620 620 800 800 1000 1100
ESP(Pa) 10Pa ,(0/30Pa adjustable)
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing, overload
Gas expanded copper tube
Connecti
on Liqui
expanded copper tube
d
LiquidΦ(mm(in)) 6.35(1/4") 9.52(3/8")
GasΦ(mm(in)) 9.52(3/8") 12.7(1/2") 15.88(5/8")

MCC018 MCC022 MCC025 MCC028 MCC032 MCC036 MCC040 MCC045


Model
WP-10 WP-10 WP-10 WP-10 WP-12 WP-12 WP-12 WP-20
Cooling capacity(W) 1800 2200 2500 2800 3200 3600 4000 4500
Heating capacity(W) 2200 2500 2800 3200 3600 4000 4500 5000
Power 220-240V~/50Hz
Sound level dB(A) 27 28 28 29 33 33 34 34
W×D×H(mm) 700*450*210
Weight(kg) 17.4
Power input(W) 32 32 32 37 47 57 57 57
Fan number 2
Air flow H : m³/h 400 400 400 450 550 620 620 620
ESP(Pa) 10Pa ,(0/30Pa adjustable)
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing, overload
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 6.35(1/4”)
GasΦ(mm(in)) 9.52(3/8”) 12.7(1/2”)

Model MCC050WP-20 MCC056WP-20 MCC063WP-20 MCC071 WP-20


Cooling capacity(W) 5000 5600 6300 7100
Heating capacity(W) 5600 6300 7100 8000
Power 220-240V~/50Hz
Sound level dB(A) 36 36 37 38
W×D×H(mm) 900*450*210 1150*450*210
Weight(kg) 20 24
Power input(W) 80 80 89 97
Fan number 2 3
Air flow H : m³/h 800 800 1000 1100
ESP(Pa) 10Pa ,(0/30Pa adjustable)
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing, overload
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 6.35(1/4”) 9.52(3/8”)
GasΦ(mm(in)) 12.7(1/2”) 15.88(5/8”)

©2016 Shenzhen McQuay


16
Electrical heater
capacity(W) Power input(W) Model Power
1000 1000 MCC022VP 220-240V~/50Hz
1000 1000 MCC025/028VP 220-240V~/50Hz
1200 1200 MCC032/036/040VP 220-240V~/50Hz
2000 2000 MCC045VP 220-240V~/50Hz
2000 2000 MCC050/056VP 220-240V~/50Hz
2200 2200 MCC063VP 220-240V~/50Hz
2200 2200 MCC071VP 220-240V~/50Hz
2200 2200 MCC080SP 220-240V~/50Hz
2200 2200 MCC090SP 220-240V~/50Hz
3400 3400 MCC100SP 220-240V~/50Hz
3400 3400 MCC112SP 220-240V~/50Hz
3500 3500 MCC125SP 220-240V~/50Hz
3600 3600 MCC140/160SP 220-240V~/50Hz

capacity(W) Power input(W) Model Power


1000 1000 MCC022/025/028SP 220-240V~/50Hz
1200 1200 MCC032/036SP 220-240V~/50Hz
2000 2000 MCC040/045/050/056SP 220-240V~/50Hz
2200 2200 MCC063/071SP 220-240V~/50Hz

capacity(W) Power input(W) Model Power


1000 1000 MCC018/022/025/028WP 220-240V~/50Hz
1200 1200 MCC032/036/040WP 220-240V~/50Hz
2000 2000 MCC045/050/056/063/071WP 220-240V~/50Hz
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃;
3. Testing power supply: 220V~/50Hz.
4. The noise level value is got from the testing point -1.4 meter under the unit in the incomplete anechoic lab. In the actual operation, the
noise level may be a little higher influenced by the environment.
5. the air flow is the standard static pressure, ()out is the standard static pressure;
6. The above set parameters in the table, shall be the standard under the static pressure of air volume

©2016 Shenzhen McQuay


17
Cassette indoor unit
Model MCK028VP MCK032VP MCK036VP MCK040VP MCK045VP MCK050VP MCK056VP MCK063VP MCK071VP
Cooling
W 2800 3200 3600 4000 4500 5000 5600 6300 7100
capacity
Heating
W 3200 3600 4000 4500 5000 5600 6300 7100 8000
capacity
Power 220-240V~/50Hz
Sound level dB(A) 30 31 34 39 40
W×D×H(mm) 990*990*340
Weight kg 26 26 30 30 31
Power
55 55 72 92 102
consumption (W)
Number of fan 1
Air flow H :m³/h 600 640 800 1000 1200
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing , overheat
Gas expanded copper tube
Connection
Liquid expanded copper tube
Liquid Φ(mm(in)) 6.35(1/4”) 9.52(3/8”)
Gas Φ(mm(in)) 9.52(3/8”) 12.7(4/8”) 15.88(5/8”)

Model MCK080VP MCK090VP MCK100VP MCK112VP MCK125VP MCK140VP


Cooling
W 8000 9000 10000 11200 12500 14000
capacity
Heating
W 9000 10000 11200 12500 14000 15700
capacity
Power 220-240V~/50Hz
Sound level dB(A) 42 42 43 45 48 50
W×D×H(mm) 990*990*390
Weight kg 35.3 35.3 35.3 35.6 36 36
Power
142 142 144 155 171 204
consumption (W)
Number of fan 1
Air flow H :m³/h 1300 1300 1360 1530 1600 1800
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing , overheat
Gas expanded copper tube
Connection
Liquid expanded copper tube
Liquid Φ(mm(in)) 9.52(3/8”)
Gas Φ(mm(in)) 15.88(5/8”)

Model MCK036VP2 MCK045VP2 MCK056VP2 MCK071VP2


Cooling
W 3600 4500 5600 7100
capacity
Heating
W 4000 5000 6300 8000
capacity
Power 220-240V~/50Hz
Sound level dB(A) 35 37 41 42
W×D×H(mm) 1176*630*345 1176*630*345 1176*630*345 1416*630*345
Weight kg 36.5 42 42 47.5
Power
45 50 69 75
consumption (W)
Number of fan 2 2 2 3
Air flow H :m³/h 580 660 810 1050
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing , overheat
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 6.35(1/4”) 9.52(3/8”)
Gas Φ(mm(in)) 12.7(1/2”) 15.88(5/8”)

©2016 Shenzhen McQuay


18

MCK028 MCK032 MCK036 MCK040 MCK045 MCK050 MCK056 MCK063 MCK071


Model
WP WP WP WP WP WP WP WP WP
Cooling
W 2800 3200 3600 4000 4500 5000 5600 6300 7100
capacity
Heating
W 3200 3600 4000 4500 5000 5600 6300 7100 8000
capacity
Power 220-240V~/50Hz
Sound level dB(A) 30 31 32 33 34 35 37
W×D×H(mm) 950*950*302
Weight kg 23 25
Power
20 30 35 42
consumption (W)
Number of fan 1
Air flow H :m³/h 600 650 700 750 800 900 1000 1100
Drain Φ(mm(in)) φ20.5(OD)
Protection Anti-freezing , overheat
Gas expanded copper tube
Connection
Liquid expanded copper tube
Liquid Φ(mm(in)) 6.35(1/4") 9.52(3/8")
Gas Φ(mm(in)) 9.52(3/8") 12.7(1/2") 15.88(5/8")

Model MCK080WP MCK090WP MCK100WP MCK112WP MCK125WP MCK140WP MCK160WP


Cooling
W 8000 9000 10000 11200 12500 14000 16000
capacity
Heating
W 9000 10000 11200 12500 14000 16000 18000
capacity
Power 220-240V~/50Hz
Sound level dB(A) 37 39 42 44 45 48 50
950*950*30
W×D×H(mm) 950*950*342
2
Weight kg 25 28 30
Power
42 60 72 85 110 130
consumption (W)
Number of fan 1
Air flow H :m³/h 1100 1200 1300 1500 1600 1800 1950
Drain Φ(mm(in)) φ20.5(OD)
Protection Anti-freezing , overheat
Conn Gas expanded copper tube
ection Liquid expanded copper tube
Liquid Φ(mm(in)) 9.52(3/8")
Gas Φ(mm(in)) 15.88(5/8")

Electrical heater
Model of indoor Capacity(W) Power input(W) Power
MCK028VP/WP 700 700 220-240V~/50Hz
MCK032VP/WP 700 700 220-240V~/50Hz
MCK036VP/WP 700 700 220-240V~/50Hz
MCK040VP/WP 700 700 220-240V~/50Hz
MCK045VP/WP 700 700 220-240V~/50Hz
MCK050VP/WP 1400 1400 220-240V~/50Hz
MCK056VP/WP 1400 1400 220-240V~/50Hz
MCK063VP/WP 1400 1400 220-240V~/50Hz
MCK071VP/WP 1400 1400 220-240V~/50Hz
MCK080VP/WP 1400 1400 220-240V~/50Hz
MCK090VP/WP 2100 2100 220-240V~/50Hz
MCK100VP/WP 2100 2100 220-240V~/50Hz
MCK112VP/WP 2100 2100 220-240V~/50Hz
MCK125VP/WP 2100 2100 220-240V~/50Hz
MCK140VP/WP 2100 2100 220-240V~/50Hz
MCK160WP 2100 2100 220-240V~/50Hz
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;

©2016 Shenzhen McQuay


19
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃;
3. Testing power supply: 220V~/50Hz.
4. The noise level value is got from the testing point -1.4 meter under the unit in the incomplete anechoic lab. In the actual operation, the
noise level may be a little higher influenced by the environment.

Wall Mounted indoor unit


Model MWM022WP MWM028WP MWM036WP MWM045WP MWM056WP MWM071WP
Cooling capacity(W) 2200 2800 3600 4500 5600 7100
Heating capacity(W) 2500 3200 4000 5000 6200 7800
Power 220-240V~/50Hz
Sound level dB(A) 35 35 37 40 43 46
W×D×H(mm) 900*205*282 1080*221*304
Weight(kg) 12 12 12 12 16 16
Power consumption(W) 33 33 34 34 35 55
Number of fan 1
Air flow(H :m³/h) 450 480 540 600 800 920
Drain Φ(mm(in)) 20
Protection Anti-freezing, overload
Gas expanded copper tube
Connection
Liquid expanded copper tube
Liquid Φ(mm(in)) 6.35(1/4”) 9.52(3/8”)
Gas Φ(mm(in)) 9.52(3/8”) 12.7(1/2”) 15.88(5/8”)
Notes: 1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃;
3. Testing power supply: 220V~/50Hz.
4. The noise level value is got from the testing point -0.8 meter downwards and 1 meter in front of the unit in the incomplete anechoic
lab. In the actual operation. The noise level may be a little higher influenced by the environment.

Ceiling Duct Indoor unit


Model MDB125VP MDB140VP MDB224VP MDB280VP
Cooling
W 12500 14000 22400 28000
capacity
Heating
W 14000 16000 25000 31000
capacity
Power 220-240V~/50Hz 380-415V/3N~/50Hz
Sound level dB(A) 46 50 54 57
W×D×H(mm) 1227*830*350 1427*830*350 1760*958*515
Weight kg 60 69 131 133
Power consumption (W) 481 620 910 1020
Fan number 2
Air flow H :m³/h 2300 2750 4100 4320
Drain Φ(mm(in)) 19.05(3/4”) 25.4
Protection Anti-freezing, overload
Gas expanded copper tube expanded copper tube
Connection
Liquid expanded copper tube expanded copper tube
LiquidΦ(mm(in)) 9.52(3/8”) 9.52(3/8") 12.7(1/2")
Gas Φ(mm(in)) 15.88(5/8”) 22.23(7/8")

Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃;

3. Testing power supply: 220V~/50Hz.


4. The noise level value is got from the testing point -1.4 meter under the unit in the incomplete anechoic lab. In the actual operation, the
noise level may be a little higher influenced by the environment.

©2016 Shenzhen McQuay


20
Vertical floor standing & horizontal ceiling mounted indoor unit

Model MCM056VP MCM071VP MCM112VP MCM125VP


Cooling
W 5600 7100 11200 12500
capacity
Heating
W 6300 8000 12500 14000
capacity
Power 220-240V~/50Hz
Sound level dB(A) 48 50 52
W×D×H(mm) 1214×670×214 1214×670×249 1714×670×249
kg 39 44 64
Weight
lb 86 97 141
Power consumption (W) 81 116 161
Current(A) 0.40 0.55 0.70
Number of fan 2 3 4
Air flow H :m³/h 1100 1300 1850
Drain Φ(mm(in)) 20.5(4/5”)
Protection Anti-freezing, overload
Gas expanded copper tube
Connection
Liquid expanded copper tube
LiquidΦ(mm(in)) 6.35(1/4”) 9.52(3/8”)
Gas Φ(mm(in)) 12.7(1/2”) 15.88(5/8”)
Model of MEX MEX-18-2SAP-C MEX-22-3SAP-C
Notes:
1. Cooling condition: Indoor D/W bulb Temp. 27/19℃,outdoor temperature: D/W bulb Temp.35/24℃;
2. Heating condition: Indoor D/W bulb Temp. 20/15℃,outdoor temperature: D/W bulb Temp.7/6℃;
Heating capacity in low ambient temp condition: outdoor temperature: Dry bulb Temp.-12℃;

3. Testing power supply: 220V~/50Hz.


4. The noise level value is got from the testing point -1 meter downwards and 1 meter in front of the unit in the incomplete anechoic lab. In the
actual operation, the noise level may be a little higher influenced by the environment.

Condensate pump
Model Power Power consumption (W) Pump lift (m)
220-240V~
MDS-CP24 10.8 0.7
/50Hz
220-240V~
MDS-CP120 12.0 1.2
/50Hz

©2016 Shenzhen McQuay


21

8 Maintenance and reparation record:

Person
Item Failure Description Action Result
/Date

【Note】Fill in the blank and keep it well

Shenzhen McQuay Air Conditioning Co., Ltd.


Address: No.10,Fangkeng Road, Pinghu Street, Longgang District, Shenzhen City, China
Telephone:0755-28456472
Fax:0755-28456469
Post Code:518111

©2016 Shenzhen McQuay


While utmost care is taken in ensuring that all details in the publication are correct at the time of going to press, we
are constantly striving for improvement and therefore reserve the right to alter model specifications and equipment
without notice. Details of specifications and equipment are also subject to change to suit local conditions and not all
models are available in every market.