Short Circuit Force Calculation For 132 KV Substation at Noida-Sector 62
Short Circuit Force Calculation For 132 KV Substation at Noida-Sector 62
NOIDA-SECTOR 62
Three phase initial symmetrical short circuit current (rms) I’’k3 = 22000 A
System frequency f = 50 Hz
2. Conductor data
Busbar selected
Outer diameter D0 = 60 mm
Inner diameter Di = 40 mm
3. Refference
5. Formulae used
5.6 Calculation of VR
fc/f VR
<=0.05 1.8
0.05….1.0 1-0.615log(fc/f)
>1.0 1
SHORT CIRCUIT FORCE CALCULATION FOR 132 kV SUBSTATION AT
NOIDA-SECTOR 62
Left Right
Calculation
Left Right
Dynamic force due to left & rigth spans (in N) Fd = 68.59 77.60
Total dynamic force due to left & right spans (in N) = 146.19
SHORT CIRCUIT FORCE CALCULATION FOR 132 kV SUBSTATION AT
NOIDA-SECTOR 62
FOR 132KV CT
Support Arrangement
Refer OGA
Equipment Dimension (Terminal to Terminal ) in m 0.5 m
Left Right
Calculation
Left Right
Dynamic force due to left & rigth spans (in N) Fd = 42.66 45.49
Total dynamic force due to left & right spans (in N) = 88.15
SHORT CIRCUIT FORCE CALCULATION FOR 132 kV SUBSTATION AT
NOIDA-SECTOR 62
Left Right
Calculation
Left Right
Dynamic force due to left & rigth spans (in N) Fd = 74.19 46.56
Total dynamic force due to left & right spans (in N) = 120.75
SHORT CIRCUIT FORCE CALCULATION FOR 132 kV SUBSTATION AT
NOIDA-SECTOR 62
FOR 132KV VT
Support Arrangement
Refer OGA
Equipment Dimension (Terminal to Terminal ) in m 0 m
Left Right
Calculation
Left Right
Dynamic force due to left & rigth spans (in N) Fd = 13.99794026 23.327522499638
Total dynamic force due to left & right spans (in N) = 37.33
SHORT CIRCUIT FORCE CALCULATION FOR 132 kV SUBSTATION AT
NOIDA-SECTOR 62
Left Right
Calculation
Left Right
Dynamic force due to left & rigth spans (in N) Fd = 17.964023333113 13.0634125997973
Total dynamic force due to left & right spans (in N) = 31.03