Professional Documents
Culture Documents
System Strength and Inertia Constrained Optimal Generator Dispatch
System Strength and Inertia Constrained Optimal Generator Dispatch
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
Abstract—System strength and inertia inherently provided by 𝑃max Inverter maximum active power output
synchronous generators (SGs) empower a power system to ride Low voltage power logic of an inverter-based generator
through voltage and frequency disturbances. The requirements of 𝑃lvpl
(IBG)
system strength and inertia were not enforced in the National 𝑄 Reactive power
Electricity Market (NEM) of Australia since SGs dominated the
generation fleet in the past. However, the increasing wind and solar 𝑄0 Pre-fault reactive power
generation continuously displaces SGs and consequently reduces 𝑄max Inverter maximum reactive power output
system strength and inertia in the NEM. 𝛿 Voltage angle
This paper proposes a formulation of system strength and 𝜃 Current angle
inertia constrained generator dispatch to reassure NEM 𝛼 Power angle
operational security in light of emerging high renewable
𝐾IBG Droop of the reactive current control of an IBG
penetration. A fault current iterative solver is developed to
evaluate system strength, in which the current limitation and 𝐾SVC SVC reactive power control gain
voltage control logics of inverter-based generators, and the fault 𝐾s Scale factor of the system strength constraint
current contribution from VAR compensators are properly 𝐸⃗ Equivalent voltage of an SG
modelled in the phasor domain. The system strength contribution
factor of an SG is defined to linearize system strength constraint
𝑋 Reactance of an SG
for unit commitment (UC). System and sub-network inertia ⃗L
𝑌 Admittance of the equivalent inductor of an SVC
constraints are also formulated for the UC to limit the rate of ⃗ L0
𝑌 Pre-fault inductance of an SVC
change of frequency (RoCoF) in the event of
⃗C
𝑌 Admittance of the equivalent capacitor of an SVC
generator/interconnector trip. The proposed generator dispatch
formulation can fully meet system strength and inertia ⃗ SVC
𝑌 Total admittance of an SVC
requirements in the NEM. 𝐈 Vector of injected bus currents
Index Terms—System strength, inertia, fault level, generator Is Vector of current outputs from SGs
dispatch, unit commitment.
If Vector of fault currents at fault buses
𝐘 Network admittance matrix
NOMENCLATURE
𝐘𝐟 Vector of fault admittances
A. System Strength 𝐕 Vector of bus voltages
𝑉N Nominal voltage 𝐕𝐬 Vector of terminal voltages of SGs
𝑉⃗ Voltage 𝐃𝐚𝐝𝐣 Adjacency matrix of ideal voltage sources
⃗𝑉0 Pre-fault voltage 𝐉𝐚𝐝𝐣 Adjacency matrix of bolted faults
𝑉⃗pcc Voltage at the point of common coupling 𝐀 Augmented network matrix
⃗ pcc0 𝐛 Vector of network knowns
𝑉 Pre-fault voltage at the point of common coupling
𝒙 Vector of unknown voltages and currents
𝑉Npcc Nominal voltage at the point of common coupling Vector of on/off binary variables of SGs and
𝒙s
𝐼 Current synchronous condensers
𝐼N Nominal current ⃗𝑖 Voltage difference of the ith IBG/SVC between two
Δ𝑉
𝐼max Inverter maximum current output successive iterations
𝐼d Inverter active current output 𝜖 Convergence tolerance
𝐼q Inverter reactive current output 𝑐𝑖𝑗 System strength contribution factor of the jth SG to the
𝐼q0 Pre-fault inverter reactive current ith bus
𝐂 Matrix of system strength contribution factors
𝐼f Fault current
Vector of required minimum fault levels at specified
𝐼s Current output of a synchronous generator (SG) 𝐝𝐦𝐢𝐧
buses
𝑆 Apparent power
𝑆sc Fault level or short-circuit capacity at a bus B. Inertia
𝑃 Active power 𝐻sys System inertia in MWs
𝑃0 Pre-fault active power sys
𝐻min1
Minimum required inertia constrained by the
minimum permissible frequency nadir
sys Minimum required inertia constrained by the
Corresponding author: Ruifeng Yan. 𝐻min2
Huajie Gu, Ruifeng Yan and Tapan Kumar Saha are with power and energy maximum permissible RoCoF
systems research group, School of Information Technology and Electrical 𝐻𝑖 Inertia of an SG in MWs
Engineering, The University of Queensland, Brisbane St Lucia, QLD 4072, ℎ𝑖 Inertia of a synchronous condenser in MWs
Australia (emails: h.gu@uq.edu.au, ruifeng@itee.uq.edu.au,
saha@itee.uq.edu.au). 𝑓0 Nominal frequency of a power system in Hz
Eduard Muljadi is with Department of Electrical and Computer Engineering, 𝑓db Governor dead band in Hz
Auburn University, Auburn, AL 36849 USA (email: mze0018@auburn.edu).
1
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
dominated power systems such as SA are “weak”. The second Adjust the voltage of every IBG and VAR
method models a generator as an independent voltage source Section II-F: compensator according to its control logic
behind a reactance, which is not applicable to an IBG because of Iterative solver
Solve the nodal network equation
its current saturation and voltage control logic. Moreover,
neither of these two methods model VAR compensators.
Converge? NO
Therefore, the key to fault current calculation lies in the proper
modelling of the network, generators and VAR compensators. YES
The proposed fault current iterative solver is shown in Fig.1. Output Output the bus fault current
Passive components (e.g., loads and network impedances) and
Fig. 1. Proposed fault current iterative solver.
active components (e.g., SGs and IBGs) are the inputs. A power
During a low voltage period, the active power output of an
flow calculation is performed to initialize active components’
IBG is restrained to give priority to reactive power injection. For
statuses which are used to augment the nodal network equation.
instance, the low voltage power logic of General Electric (GE)
The iterative solver outputs the fault current at the chosen bus.
2.5 MW wind turbine is shown in Fig.2. When the terminal
With a solved fault current, the fault level of a bus is calculated
voltage of the wind turbine is lower than 0.9 pu, the active power
using (1).
output is restricted by a hard limit. The active current is then
A. Inverter Current Saturation capped according to this low voltage power logic 𝑃lvpl (|𝑉 ⃗ |) as
Vector control regulates real and reactive power outputs of an 𝑃0 ⃗ |)
𝑃lvpl (|𝑉
𝐼d = ⃗|
≤ (5)
inverter. According to the dq0 transformation, the active current |𝑉 𝑉N
𝐼d and reactive current 𝐼q of an inverter are where 𝑃0 is the pre-fault generator active power output and 𝑉N is
𝐼d =
𝑃
≤
𝑃max the IBG nominal voltage.
⃗|
|𝑉 ⃗|
|𝑉
{ 𝑄 𝑄max (2)
𝐼q = ⃗|
≤ ⃗|
|𝑉 |𝑉
3
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
4
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
5
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
𝒈1 (𝑿, 𝑼) = 𝟎
l
l
(26)
𝒈2 (𝑿, 𝑼) ≤ 𝟎 (27) Wind Farm
North Brown Hill
132 MW
where 𝐹 is the quadratic cost function to be minimized. 𝑿 is the
l
l
Synchronous Generator
Davenport 504
vector of binary variables in every dispatch interval over 24 Battery Storage
l
hours, e.g., the on/off status of each SG/SS/SC 𝑥𝑗 and/or 𝑦𝑖 in
each dispatch interval. 𝑼 is the vector of real variables, i.e., the l
l
amount of power and reserve from each generator/storage in Snowtown
l
Clements Gap
369 MW 57 MW
every dispatch interval.
𝒈1 and 𝒈2 are the sets of equality and inequality linear
l
Wattle Poi nt
l Hallett
l
91 MW
95 MW
502 505
constraints in the UC, respectively. Equation (26) refers to the
l
Torrens Island A l
DC power flow equations. Inequality constraints (27) concern 4 x 120 MW The Bluff
53 MW
Torrens Island B
the adequacy of system strength (17), the sufficiency of system 4 x 200 MW l
Quarantine
inertia (22) and sub-network inertia (24), and the operational 4 x 24 MW l
1x128 MW
l
limits of network components (e.g., the maximum/minimum Dry Creek
3 x 52 MW
l Para 507
output of a generator/storage, the power transfer limits of an Starfish Hill
l SVC
interconnector and the bounds on the state of charge of an energy 35 MW Hallett Hill
71 MW
503 506
storage). The formulation of coupling constraints of SGs’ Pelican Point
2x160 MW l Robertstown
minimum uptime/downtime via introducing auxiliary binary 1x158 MW
South East SVC
508
Osborne
variables can be found in [38]. The formulation of power ramp 1x118 MW l 509
l
l
1x62 MW
up/down constraints of a generator over a dispatch interval under Canunda Murraylink
l
automatic generation control can be found in [39]. 46MW HVDC to VIC
l
l
Lake l
Gurobi [40] is used to solve the mixed-integer quadratic Bonney
l
279 MW l
programming problem of the proposed UC. The real-time Ladbroke
Waterloo
111 MW
generator dispatch over every five minutes is solved by AC OPF Grove
2 x 40 MW
l Mintaro
1x90 MW
using MATPOWER [41]. Once the binary unknowns (the on/off
status of every SG/SS/SC) are solved in UC, AC OPF then l Ararat
241 MW
Heywood Interconnector
refines the power output and required reserve from each l Challicum Hills
53 MW
committed generator/storage for every five-minute dispatch. Waubra
Macarthur l 192 MW
420 MW
Mt Mercer Oaklands Hill
V. SIMULATION RESULTS l
l
131 MW 67 MW
Ballarat
Mortons Lane
315 l l
A. Studied Power System 20 MW
l l l
l
l
l l l
[42] closely representing the NEM mainland is used to validate l Yam buk l Terang l
30 MW
Geelong
the proposed system strength and inertia constrained generator l
dispatch. As shown in Fig.6, the SEAPS is further augmented
with 24 SGs, 23 wind farms and one TESLA battery storage in
l
its Area 5 (SA) and Area 3 (Victoria (VIC)), which can reflect Portland
148 MW
the wind generation capability of the NEM by the end of 2018
Fig. 6. South Australia and Victoria power systems [42, 43].
[43]. Four SGs in Torrens Island A power plant in SA are
assumed to be retrofitted with synchronous condensing clutches
and can run as SCs. A projection of daily load and wind
generation of the SEAPS derived from the NEM review [44] is
shown in Fig.7. Overall, the augmented SEAPS has 82 SGs, 4
SSs, 23 wind farms, 1 battery storage, 5 SVCs, 217 buses and
363 branches.
Currently, SA is the only state with the risk of system strength
and inertia shortage [2, 4]. Davenport, Para and Robertstown
substations are chosen as fault level nodes by AEMO in SA [2],
as highlighted by the red color in Fig.6. The NEM mainland has
a long and less meshed network connected by three major AC Fig. 7. A projection of daily system load and wind generation [44].
7
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
8
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
Fig. 13. Wind curtailment in South Australia and the state of change (SoC) of
Hornsdale battery ((a) and (c) from AC OPF result, (b) from UC result).
SA spot price is considerably lifted with the inclusion of both
system strength and inertia constraints, as shown by the dashed
black line in Fig.14. However, SCs are able to reduce the spot
price during the period of peak wind generation, and to retain
almost the same price as if without these constraints during the
rest of the day, as represented by the dashed green line in Fig.14.
Fig. 11. Inertia in South Australia and Heywood interconnector power flow ((a)
from UC result, (b) from AC OPF result).
VI. CONCLUSION
In the near future, power systems dominated by IBGs will be
operated closer to their technical boundary limits due to the
reduced system strength and inertia. This paper proposed a fault
current iterative solver to evaluate the system strength of a
Fig. 12. Largest instantaneous RoCoF in South Australia following a frequency power system integrated with a large amount of IBGs, and
disturbance (estimated by Eq.(A.2) according to UC and AC OPF results). defined the SSCF to linearize system strength constraint for the
Meanwhile, Hornsdale battery is charged to further decrease UC. The constraints of both system and sub-network inertia are
wind spillage between 0:00 and 5:00, as shown in Fig.13(c). The also introduced to the UC to limit post-contingency RoCoF. The
battery is discharged during load peaking time in the morning to proposed system strength and inertia constrained generator
sell stored wind energy, as marked by the dashed red line in dispatch can well satisfy the requirements of system strength and
Fig.13(c). inertia under high renewable penetration.
E. Cost Comparison With the proposed inertia constraints, RoCoF can be well
restricted within the secure band in case of N-1 generator trip or
The purpose of generator dispatch is to minimize the
single interconnector trip or the simultaneous disconnection of
electricity spot price under the precondition that operational
multiple interconnectors. Electricity spot price goes up with the
security can be maintained. The SA electricity spot price is
constraints of system strength and inertia, but SCs can greatly
calculated every five minutes by considering SA generator
reduce spot price while providing adequate short-circuit power
outputs and the Heywood interconnector power flow solved by
and inertia.
9
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
Case Bus 1 Bus 2 Bus 3 Fault Bus PSS®E (2c) Proposed solver Error
A Wind SG SG Davenport 18.7872 pu 18.0618 pu 3.86%
B Wind SG Wind Para 27.8988 pu 27.0035 pu 3.21%
Robertstown 24.5069 pu 23.7972 pu 2.90%
TABLE II. BENCHMARKING RESULTS OF THREE-PHASE FAULT CURRENTS The fault currents at three fault level nodes in SA in Case 3 are
IN CASE A
listed in TABLE VII. PSS®E has consistent network
Fault Bus No PSS®E (2c) Proposed solver Error convergence errors in Case 3 which only has one SG in SA.
4 6.6636 pu 6.5821 pu 1.22% Consequently, the voltage sag propagation following a fault is
5 6.8761 pu 6.8224 pu 0.78%
6 6.6016 pu 6.5321 pu 1.05%
widely spread in SA, which can significantly increase
7 9.8260 pu 9.8165 pu 0.10% convergence difficulties for PSS®E. The proposed solver
8 8.5701 pu 8.5684 pu 0.02% simplifies the network voltage calculation to the solution of a
9 9.8120 pu 9.7801 pu 0.33%
system with linear equations (13), which helps to overcome the
network divergence problem of PSS®E.
TABLE III. BENCHMARKING RESULTS OF THREE-PHASE FAULT CURRENTS
IN CASE B
TABLE VII. BENCHMARKING RESULTS OF THREE-PHASE FAULT CURRENTS
Fault Bus No PSS®E (2c) Proposed solver Error IN CASE 3
4 6.5072 pu 6.5143 pu 0.11%
5 6.9059 pu 6.8105 pu 1.38% Fault Bus PSS®E (2c) Proposed solver
6 6.1893 pu 6.14231 pu 0.76% Davenport Diverge 12.4404 pu
7 8.2648 pu 8.2594 pu 0.07% Para Diverge 10.7863 pu
8 7.8736 pu 7.8478 pu 0.33% Robertstown Diverge 14.9735 pu
9 6.7941 pu 6.7359 pu 0.86%
B. Primary Frequency Control
2) NEM Mainland Power System
The case settings of the NEM mainland power system are 1) RoCoF
listed in TABLE IV. Wind penetration is defined as the Post-contingency frequency dynamics considering LFR are
percentage of wind generation over the total generation in a state conventionally modelled by the aggregated swing equation as
(e.g., SA or VIC). Case 1 has medium wind penetration in SA [47]
and all the SGs in SA are online. Case 2 investigates the high 𝑑𝑓(𝑡)
RoCoF inst =
wind penetration in SA and only four gas-powered SGs in 𝑑𝑡
Torrens Island power station are running. Case 3 studies the peak 𝑓0 sys sys
= (𝑝 (𝑡) − 𝑝elec (𝑡) − 𝐾LFR 𝑃load (𝑓(𝑡) − 𝑓0 ))
wind penetration at 92.6% with the operation of only one 2𝐻sys mech
gas-powered SG in Torrens Island power station. (A.1)
A three-phase bolted fault is applied to three fault level nodes where RoCoF inst is the instantaneous RoCoF in Hz/s following
10
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
11
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
12
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2019.2957568, IEEE
Transactions on Sustainable Energy
13
1949-3029 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.