Professional Documents
Culture Documents
B9000UK
B9000UK
B9000 3/3
60 - 80 - 100 - 125 - 160 - 200 - 250 - 300 KVA
Three-phase UPS
... we commit
B9000 combines management of THD and power factor, low
cost of ownership and power protection in a highly reliable
solution guaranteed by the most advanced technology
INFORMATION AND COMMUNICATION
Low THDi and power factor High efficiency reduces overall
TECHNOLOGY
performance enhance compatibility cost of ownership
• Data centers with input mains and generators
• Server farms The BORRI B9000 UPS uses a new input The B9000 operates at a high efficiency
• Communication rooms IGBT rectifier and an advanced PFC (Power of up to 94%, which reduces utility costs.
• Broadcast Factor Control) capable of keeping input Moreover higher system efficiency reduces
• Networking current Total Harmonic Distortion (THDi) facility air conditioning costs, increasing
at a low level (< 3%), as well as the input overall reliability. Because of the technology
CRITICAL ELECTRICAL ENGINEERING power factor very close to unit (0,99). and topology used, no additional losses
The key benefits are that the UPS is are generated to get low input harmonics
• Industrial controls therefore compatible with the upstream or input/output galvanic isolation.
• Manufacturing machinery source, the mains or any kind of generator Additionally, Eco-mode function can be
• Process equipment and the transfer of power between source set. In this intelligent mode, the mains line
• Transportation and load is more efficient. This results in a is continuously being monitored in order to
• Building automation saving in terms of scale of sources, cables supply with high reliability the load by the
and protective devices. same line. If the line is downgraded and
required to be conditioned, the inverter
supports the load in less than 4msec.
Once the load is accessed to properly
operate in this way, in Eco-mode efficiency
is considerably increased, allowing high
energy saving.
unexpected breakdowns
User-friendly interface
Front access
Communication
Options
Monitoring, managing • RS232 serial port
• Parallel capacity/redundancy
and shutdown software • USB port
• Isolation transformer
• EPO
• External bypass
• External battery cabinets
Optional
• Battery switch box
• Web/SNMP
• Battery thermal probe
• ModBus
• Transformers for voltage adaption
• Relays
• Top cable entry
• Modem
• Remote panel
Printed in Italy 03-2008 - ART & PRINT: DEDALO Printing snc - Bibbiena (Ar)
Rating 60 kVA 80 kVA 100 kVA 125 kVA 160 kVA 200 kVA 250 kVA 300 kVA
Capacity (kVA/kW) 60/48 80/64 100/80 125/100 160/128 200/160 250/200 300/240
Dimensions WxHxD (mm) 815x1670x825 1200x1900x860
Weight (kg) 580 600 630 662 720 870 1020 1200
Input/output connection Hardwired (dual input)
Battery External, 300 cells
Input
Nominal voltage 220/380, 230/400, 240/415 Vac three phase
Voltage range -20%, +10% from nominal
Frequency 50/60 Hz (45–65 Hz)
Power factor 0,99
Current distortion (THDi) < 3%
Output
Nominal voltage 220/380, 230/400, 240/415 Vac three phase
Frequency 50/60 Hz
Voltage regulation ±1% static; ± 5% dynamic 100% load change, <20 ms recovery time
PF acceptable without de-rating Lagging to 0.9 leading
Overload capacity 101–125% for 10 min (on-line); 126–150% for 1 min (on-line);
1000% for 1 cycle (bypass)
Efficiency >93%
(Eco-mode) >98%
Options Parallel capacity/redundancy; isolation transformer; external bypass;
external battery cabinets, battery switch box; battery thermal probe;
transformers/autotransformers for voltage adaption; top cable entry
User Interface
Front panel Graphical LCD display, mimic with LED’s and keyboard
Standard communication ports RS232 serial port, USB port, Remote Emergency Power Off input,
battery switch monitoring port
Optional Web/SNMP, ModBus, relay, modem cards; remote panel;
monitoring, managing and shutdown software
Environmental
Operating temperature 0°C – +40°C
Storage temperature -10°C – +70°C
Altitude <1000 m
Audible noise at 1 meter (dBA) <60
Standards and Certification
Marking CE
Safety IEC EN 62040-1
EMC IEC EN 62040-2
Test and Performance IEC EN 62040-3
Quality ISO9001 :2000
Photo: Borri Files & Alessandro Ferrini - (Ar)
BORRI S.p.A.
Via 8 Marzo, 2 - 52012 Bibbiena - (Arezzo) ITALY
Tel. +39 0575 5351 - Fax. +39 0575 561438
info@borri.it - www.borri.it