Professional Documents
Culture Documents
Electrical Technology
Electrical Technology
Io
-
C,
*
J.
=.
o
UJ
F
J
CS
o
lrf
F(
b
1f$
UJ
sJVON Z14L
ELECTRICAL TECHNOLOGY
SJ VAN ZYL
- 5TH EDITION
Published by:
lg rata
P O Box 6201
Vandsrbijlpark
1900
Tel: 082 852 0340
@ LERATo 2011
ISBN : 978-0-9814483-3-G
l*;
ELECTRICAL TECHNOLOGY
SJ VAN ZYL
- sTH EDITION
TABLE OF CONTENTS
ii
---
CHAPTER SEVEN - ALTERNATING AND DIRECT CURRENT DISTRIBUTION
7.I INTRODUCTION 191
7.2 REQUIREMENTS FOR GOOD DISTRIBUTION SYSTEMS !92
7.3 CLASSIFICATION OF DISTRIBUTION SYSTEMS T92
7.3.T NATURE OF CURRENT T92
7.3.2 TYPE OF CONSTRUCTION 193
7.3.3 CONNECTION SCHEME 193
7.4 CONNECTION CIRCUITS OF DISTRIBUTION SYSTEMS 193
7.4.L RADIAL DISTRIBUTION SYSTEMS 193
7.4.2 RING DISTRIBUTION SYSTEM 194
7.4.3 INTER-CONNECTED SYSTEMS 195
7.5 DIRECT CURRENT DISTRIBUTION SYSTEMS 196
7.5.1 DIRECT CURRENT RING DISTRIBUTOR T97
7.6 ALTERNATING CURRENT DISTRIBUTION SYSTEMS 205
EXERCISE 7 2TB
iv
CHAPTER ONE
1.1 WATTMETERAPPLICATIONS
a \o
I(E
lo
t-
l(1)
l(^
lftt
\_c
ao,-
ldr
IE
l-c
lP
/lio
P = V.Lcos 0
r0
li P_
J J
(J (J
L L
U U
For example, if the current coil is reversed, it results in the network shown in
Figure t.2.. tthe+terminal of thepotential coil isconnectedtothelinecontainingthe
current coil and the meter is reading upscale, the power is flowing through the
wattmeter from circuit A to circuit B. If a wattmeter indicates a reverse reading when
it is normally phased, i.e. the + ends of the voltage and current coils are connected
together, it means that the voltage and current are more than 90' out of phase' In
sulh cases the terminals of either the current coil or the voltage coil can be reversed.
for the reading to be fonruard and of the correct value'
A single wattmeter can be used to measure the power of any balanced three-phase
systeir without breaking the phases, The system can be star-connected or delta-
connected. Figure 1.3 shows tire connection of a single wattmeter in a star-connected,
three-phase lold when a neutral wire is available. The wattmeter measures the phase
power that is then multiplied by three to find the total power in a balanced load'
Figure 1.4 shows the connection of a single wattmeter in a delta-connected, three-
phase load. The current coil of the wattmeter is connected in one line and the voltage
coil is connected alternately between this line and the other two lines' The total power
is then determined from the two readings on the wattmeter, This method is not of as
much universal application as the two-wattmeter method, because it is restricted to
balanced loads onlY,
t
Figure 1.3: Single wattmeter connected in a balanced, three-phase, star-connected
system
The current Iu through the current coil of the wattmeter is the phasor difference of Iu5
and I.u, i.e. the phasor sum of I35 ond I.u reversed.
F
V.u
Figure 1.5: Phasor diagram for the voltages and currents of Figure 1.4
When the voltage coil of the wattmeter is connected to line b, the voltage will be V"u
and the phase difference between this voltage and the current will be (30' - 0). The
reading on the wattmeter will be:
= Vao.Ia.cos (30'- O)
= J3 .Von.Io6.cos (30'- S)
Where: =
Vor., phase voltage in V
Iph = Phase current in A
When the voltage coil of the wattmeter is connected to line c, the voltage will be V".
and the phase difference between this voltage and the current will now be (30' + 6).
The reading on the wattmeter will now be:
= J3 .von.Ioh.cos (30' + O)
Lr
The voltage return for each wattmeter is connected to the line with no wattmeter in it.
In single-phase systems one wattmeter is required to measure the power. It is clear
that two wattmeters are needed to measure the total power in a three-wire, three-
phase system. This method will work whether the system is balanced or not, The
readings of the wattmeters are simply added together and the sum is the total power
going down the three-phase (or n-phase) line, Using instantaneous values for an
unbalanced, three-wire, star-connected load can prove Blondell's theorem.
Wa+Wc = Vab,!a+vcb,ic
is* i6 -f i. = Q
16 = -16-16
And:
The two-wattmeter method gives true power in the three-phase circuit without regard
to balance the waveform provided in the case of a star-connected load. The neutral of
the load is isolated from the neutral of the power source. If there is a neutral
connection, the neutral wire should not carry any current. This is possible only if the
load is perfectly balanced and there are no harmonics present'
The two-wattmeter method can also be used for a three-phase, four-wire system in
which the neutral wire carries the neutral current. In this method, the current coils of
the wattmeters are supplied from current transformers insefted in the principal line
wires in order to get the correct magnitude and phase differences of the currents in the
current coils of the wattmeter, The reason being that in the three-phase, four-wire
system, the sum of the instantaneous currents in the principal line wires is not
necessarily equal to zero/ as is the case in a three-phase, three-wire system.
0
The current Iu does not pass through a wattmeter and can be eliminated. In any three-
phase system:
I.+16+I. - 0
.'' Ib = -Iu-I.
.'. Total active power = Vun.Iu + Vnn(- Iu * I.) + Vcn.Ic
= Vab.Ia * Vs6.Is
W = Wu+W.
Where: W = total active power measured by two wattmeters in W
wa = active power reading on wattmeter a
w. = active power reading on wattmeter c
Thus, at any instant the total active power is given by the sum of the two wattmeter
readings, This is true for balanced or unbalanced loads as well as star- or delta-
connected loads. To find the power factor from the two-wattmeter readings in
balanced loads, the star-connection of the three equal impedances shown in Figure 1.7
must be considered. The phasor diagram for the abc sequence is shown in Figure 1,8,
A lagging current with phase angle 0 is assumed.
V.u Vu.
V.n
V.u
Figure 1.8: Phasor diagram (abc phase sequence) for the voltages and currents of
Figure 1.7
With the wattmeters in lines a and c (Figure 1.1), their readings are:
W3 = Vu5.I;.cos Zrvjb
tY:'= 3oo+o
w6 = V35.I6.cos (30o + 0)
Then: Wu + W. = J3 .VL.IL.cos O
And: Wu - W. = JE .Vr.tr.sin O
Therefore:
tan d = Jtf*'-*')
(.W. + W. J
Thus, the tangent of the impedance angle is J5 times the ratio of the difference
between the readings on the two wattmeters and their sum. With no knowledge of the
lines in which the wattmeters are connected nor of the phase sequence, it is not
possible to distinguish between + $ and - $, However, when both the meter location
and the phase sequence are known, the sign can be fixed by the following equations.
For a positive phase sequence (abc):
or: tan6=
"[tr#)
or: tan d = J3f
*'-w')
[W. +W. J
For a negative phase sequence (cba):
tand = J5f*t-*.)
(W. +Wb J
Or: tan d = *.
Jrf(.W5 -*t )
+w, )
!(o
a
!q.)
P(J
qJ
c
o
(J
I
rO
E
o
!
L
o
I
L
P
o
(t
Figure 1,9 shows that the current coils are connected in series with the lines, which
means that the currents in the wattmeters are \ne currents. One terminal of each
voltage coil is connected to a line, and the othdr terminals of the voltage coils are
connected together. The voltage coils are therefore connected in a star configuration.
Thus, the voltage coils form a balanced, star-connected system. The voltage across
each coil is therefore
5, *" voltage across each voltage coil lags the line voltage by
30" in a positive phase sequence system, and leads the line voltage by 30' in a
negative phase sequence system.
10
---
)
Il'no'ii"';l?;"Jiil:'"xnf il:#H*:ln::u;"#i"T"#,'ffrr:,?,.1*:.;ml,jl
Wo = V6n.I6n.Cos ZFn
lbn
11 :
t__ I
I
t
t
I
I
W. = V.n.I.n,cos ,rY^
-Im
Since the voltage coils form a balanced, star-connected system, the voltage across each
voltage mil lags the line voltage by 30' for a positive phase sequence and leads the line
voltage ry 30" for a negntive phase sequence. Thus, the reading on the wattmeter in
each line:
wa = .r".*.(zicbt3o.)
f
%= (zf-t to")
H:r-m
w. =
f;+*(zi%i3o.)
Where: +: rcgilhphffiqsEe
- : FdiE Fl e serFlentB
L2
CHAPTER TWO
2,L INTRODUCTION
The generation, transmission and distribution of electricity are accomplished by three-
phase alternating currents. An alternating current circuit having a single alternating
current voltage source is called a single-phase circuit. Electrical power is delivered from
a source/ such as an alternating current voltage generator, to a load by means of two
wires, This arrangement is called a single-phase, two-wire system.
Vun Vo.
-.__r
\/ L--rrJ w
Three-phase, Single-phase Single-phase
three-wire supply (V11n")
supply (V1'n") ,roor, [I+.'l
(J:;
Figure 2.1: connection of different supplies to a three-phase, four-wire system
(equivalent circuit to Figure 2.4)
Most consumers are fed from a single-phase alternating current supply. One wire is
called the live conductor and the other wire is called the neutral conductor. The neutral
conductor is usually connected to earth via protective gear. The standard voltage for a
single-phase alternating current supply is 220 V. The majority of single-phase supplies
are obtained by connection to a three-phase supply as shown in Figure 2.1. A poly-
phase circuit is a circuit containing more than one alternating current source and three
or more wires, Upon these wires appear alternating current voltages having different
phase angles. The most common poly-phase circuits are those containing three
alternating current sources and three or four wires.
13
These three-phase circuits are widely used in the electrical power industry to transmit
power from generating stations to metropolitan areas and to distribute that power to
individual consumers.
2.2 THREE.PHASESYSTEMS
. Fewer ripples in the direct current output when alternating current is conveted to
direct current
A three-phase supply is generated when three coils are placed 120' apaft and the
whole rotated in a uniform magnetic field as shown in Figure 2.2. A three-phase
voltage is basically three single-phase voltages. Each voltage is separated from the
next by a phase angle of 120'. The same basic structure found in the single-ffise
generator can therefore be used to generate the three voltages simply by equipping the
rotor with three separate windings. If the windings are spaced 120" apaft, the voltages
induced in these windings will then be shifted from each other by 120' of phase, as
required. This concept is implemented in practical three-phase generators, but the
physical structure is somewhat different. Electromagnetic induction occurs when there
is relative motion between a conductor and a magnetic field, In other words, either the
conductor or the field may be moving while the other is stationary, In practical three-
phase generators however, the three windings (conductors) are stationary and the
magnetic field is rotated, as shown in Figure 2.2.
.o ^t^. a
14
The windings are embedded in the stator and direct current (the excitation) is passed
through brushes and slip rings to the field winding on the rotor, The field produced by
the rotor as it turns, cuts the conductors of the three stator windings. Since the stator
windings are 120" apart, the rotating magnetic field induces voltages that are separated
in phase by 120'. A three-phase generator commonly located in a power station
produces three-phase power. The rotor is driven by a prime mover, i.e. a turbine, and
the rotor poles are excited by direct current. The stator has a three-phase distributed
winding. The axes of the phase windings are displaced from each other by 120
electrical degrees, as shown in Figure 2.2.
Sinusoidal voltages are induced in the stator phases when the rotor is rotated, For a
balanced system, the voltages have equal amplitudes and are 120" displaced in phase,
as shown in Figure 2.4. The equivalent circuit of the stator windings is shown in
Figure 2.3. In this case the windings have a common connection labelled n, called the
neutral, and the windings form a star-connected network. Since the neutral line n is an
output, the output is said to be three-phase, four-wire. The windings can also be delta-
connected.
Figure 2.1 shows a circuit equivalent to Figure 2.3 and consisting of three alternating
current generators. Shown in Figure 2.3 is the plot of the three voltages, v36, v6 dhd
V"n. Each voltage is taken with respect to the neutral n. Three wires, called lines,
therefore carry a three-phase, alternating current supply. The currents in these wires
are known as line currents and potential differences between the lines are known as
line voltages. The fourth conductor, known as the neutral, is often used with a three-
phase supply,
15
V.n
I
i
t--'' )(i "-
: 120. L20
"
Figure 2.4: Sinusoidal form of the phase voltages of a three-phase generator, each
with respect to the neutral
If the three-phase windings shown in Figure 2.3 are kept independent, then six wires
are needed to connect a supply source to a load. The three phases are usually
interconnected to reduce the number of wires. This can be done in two ways, namely a
star-connection and a delta-connection. Sgglgg1_qilhlggpha5_9- Supdies, are usually
c91n_eq!9^Q i0-.St?Lwhereas three-phase loads may be connected either in delta or star.
The double-subscript notation is used to avoid confusion in the direction of voltage and
current. When the double-subscript notation is applied to alternating current circuits,
the sequence of the subscripts indicates the direction in which the current or voltage is
assumed to be positive. Figure 2.5 represents an alternating current source connected
in series with an impedance. The voltage across the impedance is designated V"o to
symbolise that the potential of a is positive with respect to b. Thus, if an arrow
representing the direction of this voltage is drawn alongside the impedance, the head
of the arrow should point towards the end that is at higher potential, i.e. towards a in
Figure 2.5,
Vao
Iao H
H -
f \,_,/ _
IO
t
The current through the impedance flows from a to b and is therefore designated f"s.
The phase sequence is the order in which the three phases attain theii maximum
values. The phase sequence can be determined by the order in which the phasors
representing the phase voltages pass through a fixed point on the phasor diagram if
the phasors are rotated in an anti-clockwise direction. The phase seque:nce in
Figure 2.6 is positive or abc. The phase sequence is quite important in the thiee-phase
distribution of power. In a three-phase motor for example, if two phase voltages are
interchanged, the sequence will change and the direction of rotation of the molor will
be reversed.
V."
Figure 2.6: Phasor diagram for a positive phase-sequence, showing phase and line
voltages (Vu as reference)
The phase sequence can also be described in terms of the line voltages. Drawing the
line voltages on a phasor diagram, the phase sequence can be determined by Jgain
rotating the phasors in an anti-clockwise direction. The sequence can be determined
by noting the order of the passing first or second subscripts. In the system of Figure
2'6, the phase sequence of the first subscripts passing the fixed point is abc, itre
phasor diagram is always started with the reference, from where the rest
of the
voltages are drawn according to the specified sequence. The voltages in Figure 2.6 will
be:
%= VpnZO'V
V6 = Vp6Z-120" V
Vc = Vpnl120" V
Van = VrZ3Oo V
Vn. = Vr-Z-9Oo V
Vca = VrZ150" V
I
t7
-
Where: Vpr, = phrevolbge
Vr- = line volbge
The phase sequence can also be negative or cba as shown in Figure 2.7.
(D
V.u
Figure 2.7: Phasor diagram fgr a negative phase-sequence, showing phase and line
voltages (Vu as reference)
Va = VpnZ0o V
Vo = Vpr.Z120'V
Y, = Yp6l-120" V
Vau = VrZ-30" V
Yo, = VtZ-150'V
Vca = VlZ90" V
Remember:
The voltage giyen is always the line voltage, unless othenvise stated.
In a posiUve phase sequence system, the line voltage leads the corresponding
phase voltage by 3O".
In a negaUve phase sequelrce system, the line voltage lags the corresponding
phase voltage by 3O".
1B
L2.2 BALANCED STAR-CONNECTED,
THREE.PHASE SYSTEMS
Figure 2,8 shows^the
windings of a three_phase
be three or rour output generatol
rines, whicrrL[::fl?;:rt":lTll?:-.onnected in star. rhere can
three-phase, three-wire .on"L.tui
ii''r""lprffi:?:ilT,.?:id*l ou u
'nrllr'.un
"'
Stator
Rotor
Field winding
Neutral n
Direct current
excitation
c
rnree- [
Phase 1 b
output I a
,?"lJ:f ,:,rl;:
;Iti:i"",""",:Eni?t:il#:'titi,,1:?itTffi :Ji;:",:ff fi
rl";ffi :*iililI,ffii:lil"il:,..,,:""i';:t-l'r'ttr#nril1+.r1hll$;tr
19
Eun
za a(tr
In
o
c)
V,
(E
-c
o-
I
o
OJ
L
-c
I
o
F
/ Figure 2.9: Phase and line quantities in a symmetrical, three-phase, four-wire, star-
connected supply
Figure 2,4 shows the three phase voltages in sinusoidal form, The corresponding
phasor diagram is shown in Figure 2.10. The maximum value of each phase voltage in
Figure 2.4 is E^, so that:
= E6n161Z0o V
= Em@)Z-LZlo Y
= Ecnln)ZI2lo Y
z0
\
"q
E
Lbn
Figure 2.1O: Phasor diagram of the phase voltages shown in Figure 2.9
Thus, the sum of the phase voltages is zero, regardless of the nature
of the load'
rigui! 2.11 show that the line voltage E65 cdh be determined by using Kirchhoffs
voltage law.
E*-Eun+E6n - 0 . 6b
i:.
E
Lab - Lan Lbn
= ll0 - Ll-r20
= iE Epr,1'f30" V
i"u
Similarly: Lbc - Eun - E.n
J5 Epr.1'yZ-90'V
2L
And: E.u = fu,-E=.
= J3 Epn1.12150'V
If these three Kirchhoft equations are added, the sum of the line w{1zqes is also zerro.
is .,'3 times Ereater
These equations also show that the magnitude of the line vollages
than the magnitude of the phase voltages. Thus, in a three-phase, startonnected
system:
n
EL = 6-on
Eun
I" = I.n
Frgure 2.12 shows a phasor diagram of the line and phase voltages. From the phasor
diagram (positive phase sequence) it can be seen that:
. The line voltages, like the phase voltages, are 120o apaft.
. The angle between the line currents and the corresponding line voltages is
{30' + 0) with the current lagging the voltage.
:mm Frgure 2.9 it is apparent that each line current equals the phase current in the
rr*rndirg to which the line is connected. This means that:
Iu = Iun
Iu = Iun
I. = I.n
in general, in a three-phase, star-connected system:
11 = Ipn
Using Kirchhoffs current law at the star point n, the current in the neutral conductor,
flowing towards the neutral point, is:
In= Iu+I5*I.
When the phase currents, as well as the line currents, are equal in magnitude, the
system is balanced. This also means that the impedances of the load are equal. In
this case, the current in the neutral wire will be zero,
Figure 2.13 shows the windings of a three-phase generator connected in delta. There
are just three output lines, which means that every delta-connected system is a
three-phase, three-wire system.
Stator
Rotor
Field winding
Figure 2.13 shows the phasor diagram for the output voltages of a three-phase, delta-
connected system.
Ean = EtlOo Y
eab = Eab(my Sin <Ot
Eo.^ = Etl-120'V
23
Lca -
ELllzT v
A_
Lca -
E646y sih (CIt + 120') V
E.u
E
Lah
E
Lbc
Figure 2.14: Phasor diagram for the output voltages of a delta-connected system
(pps)
Figure 2.15 shows a delta-connected system. The phase quantities are those within the
source and the line quantities are those in the output lines connected to the load. It is
eminent from Figure 2.15 that the line and phase voltages are equal.
24
when Kirchhoffs current raw is appried at
node a of the derta road in Figure 2.15:
Ia-IaO*Ica=0
Iu=136-I.g
Similarly: 16=I5s-166
And: I.=Is6-16.
By adding these equations, it will be seen
that:
Ia+Ib*I. = Q
Ir = 6ton
Figure 2.16 shows a phasor diagram of
the rine vortages and currents.
25
-
The line currents lag their respective phase currents by 30o.
The angle between the line currents and the corresponding line voltages is
(30o + $) with the current lagging the voltage.
Supply Load
aIa a
za
l''\t:'
E." Ean Vau V.u '/r".
26
I.u
b
I5
Iu. b
En. u"t
Ic
26
Example 2.1
Vun is given as 24010" V. Use a negative phase sequence and calculate the line
currents. Draw a phasor diagram of the line and phase currents,
Vab = IarZuo
\,vbc
- Ia*Za,
(Ji)Q+ozeo') = (rbcx1B.2 - j6.9)
Ib. = 2L.3572L1O.750 A
%u = I.u.Z.u
I.u L5.8022155.560 A
27
Current in each line:
= Iab - Ica
= 25.9BLl-66.87' - 15.8021155.56'
= 39.L251-51,O5" A
I6 = In. - Iub
Ic = I.u - Ib.
tgure 2.19: Phasor diagram for phase and line currents (not to scale)
28
Supply
Load
a Ia a
c b c _Iu.b
I6
Eu. Vn.
Ic
Example 2.2
The load is supplied from a 50-Hz, symmetrical, three-phase supply with vca =
and a positive phase sequence. Calculate the line currents,
- 44ay
%u
V.u
Vn.
29
V35 = 136.235
V56 = I6s,Z5s
4402_60 = (Ib)(24.2239.6)
Iu. = 18.1822-99.6'A
V.u= I.u,Z.u
440ZIB0' = (IcaX15.1 2-76.6)
I.u = 29.1392-LO3.4'A
16 = 166-166
= 23.4042-3.4' - 29.139 l-103.4"
= 4O.4L9241.83" A
15 = 156-165
30
Supply Load
a Ia a
u"l za
b
% N-
c b
I6
Eo. Vu.
Ic
Using Kirchhoffs voltage law around the terminals in the star-connected load, the
relationships between the phase and line voltages are:
V36+V6-Vu= 0
Vao = Va-Vu
Vs6*Vs-Vu = 0
V56 = V5-Vg
V.u+Vu-V.= 0
V.u = V.-Vu
When the load is unbalanced, Millman's theorem or star-delta conversion can be used
to do any calculations regarding the load.
Example 2.3
Zu = (28.2 - j18,2) o
26 = (22.4 + j16.4) O
Z, = (32.6 + j12.6) O
31
Take V5. as reference with an abc-rotation.
2.3.L Calculate the voltage drop in phase a if the impedance in this phase suddenly
risesto infinity.
2.3.2 Calculate the current in phase c if the impedance in this phase becomes short-
circuited.
2.3.7
vc
32
Vcb = Icb(Zc + zb)
3802180" = (Id)(22.4 + jL6.4 + 32.6 + j12.6)
T-
lcb - 6.tI2Zt52.2 A
= r"
Vr= Ir.Z,
= (6.712tI52.2)(32.6 + jL2.6)
= 213,6162L73.33V
Using Kirchhoffs voltage lawl
%-V.*V." = 0
Vu = V.-V.u
= 2I3.6I6t173.33" - 3B1t-LZO"
= 354.589Z93.S8 V
This example can also be solved using line b:
Vao
l"
c
Figure 2.25: Three-phase, three-wire star-connection with phase
a open-circuit
Y6r= 16r(Z6+Zr)
38020' = (16)(22.4 + jI6.4 + 32.6 + jIZ.6)
I6s = 5.11.22-27.8 A
-f6
33
F
V6 = Is.Z6
= (6.LIZI-27.8')(22.4 + j16.4)
= 169.6828.4L V
Va-Vun-Vn = 0
* Vu= V66 * V5
= 3B0lL20 + L69.6818.4'
354,597293.58" V
2.3.2 r
vac
)
tur t'/4
Vu.= Iu.,Zu
380260" = (IacX2B.2
-j18.2)
Iac = 11.322292.84'A
V66 = I6a.Z6
34\
.-r' \FY
ib " 'i\'
-
-t--
1
Supply Load
a I" a
za za
E
E.u Lab Van V.u
zc Zo zc 26
c b
I5
Eo. Vn.
Ic
Four-wire systems are useful when two different load voltages are required. These
voltages are the line voltage and the phase voltage that is J3 times smaller than the
line voltage. It is eminent from Figure 2.27 that the voltage across each impedance of
the star-connected load is equal to the phase voltage of the source, Since these load
voltages equal the phase voltages of the source and the sum of the phase voltages is
zero, the sum of the load voltages is also zero, whether the load is balanced or not.
In a four-wire system, the neutral is available to keep the star point at earth potential.
With only three lines connected to an unbalanced, star-connected load, the star point of
the three load impedances is not at earth potential and is marked with s instead of n.
The voltages across the three impedances can vary considerably from line to neutral.
The voltage V.n is known as the displacement neutral voltage or the star-point
potential.
Figure 2.28: Representation of the star-point potential in relation with the phase
voltages in an unbalanced, three-phase, three-wire, star-connected load
Refer to Figure 2.9 and Figure 2.28. Millman's theorem states that if any number of
linear impedances, i.e.2u,26 and 2", meet at a common point n, and the voltages from
another point s to the free ends of these impedances are known, the voltage drop
between the neutral of the source (generator) and the floating neutral of the load is
given by:
1
Yu=
1
1
Yu=
z,
1
t- -
?
I-lis s -:'+: ':'ir. h'lillman's theorem states that parallel-connected current sources
c?- r€ '?=,=:=::, a single equivalent current source. This is also applicable in the
r3-r ,,,-t-i :'E-= t -::rneced voltage sources can be reduced to one equivalent
ir r3J€ :":,-= --*s i an unbalanced, three-wire, star-connected load, the star-point
:i::e-:,? --- 1r= --,1- e:e: dlrectly by using Millman's theorem. In triangle ans in
Fg-'e I -! -s.E *.*:l-,:Fs 'r'cltage law:
*r -:---
36
Vb" = Eun - Vrn
%n+%r-Ern = 0
%n+V.r-Ecn = 0
V". = E"n_V"n
Example 2.4
37
D
Using Millman's theorem to find the neutral displacement voltage:
Vu, = Eu-Vrn
= 37O.3342-L79.32V
v., = E.-Vrn
*_ fio l-90" 1r
-.,3.363132.32.
./3
-.--
= 379.093Z-II.8.4' V
Current in each phase:
Vu' = Iu'Zu
10.635 /._24.31o = (I)(I7.52_34.2.)
Ia = 0.60829.89" A
V55 = 16.2g
370.334t_179j2 = (IbX13,9Z6B.1.)
Io = 26.4232LL2.58 A
V., = I.,2.
379.093 t_L1B.4o = (I)(I4.2t_49.7")
I. = 26.6971-68.7'A
3B
eJ.5i4 DELTA-STAR (A-y) coNvERSIO N
Zn,
Zun(Zo' +ZJ
Z" + Zn-= Zao +2y- +Z*
39
F
Z,rr(Zu +Z^t)
Similarly: 76*7, =
7"6 +26, +Z*
Z*(7,0, +Zuo)
And: 7u+2" =
Zu6 +76..+Zn
Thus: 7u-26 =
Zor.7
- + Z u.Z - Z,o,Z u,o - Z,or.Z
-
",o
2"6 +26.- +7o
z7zab -zbc.zab
Zu6 +76.. +Zo
Zab'2""
Therefore: 7"=
Zaa *Zy +2.^
7^a'Z*
Similarly: '' Zaa -Zg -Z.u
tLc Z*'2.
And: - Z"b +Ze +2.
Note that each of the impedances is equal to the product of the impedances in the two
closest branches of the delta network, divided by the sum of the impedances in the
delta network,
Example 2.5
2.5.L Calculate the total impedance of the network, using delta-star conversion,
2.5.2 Calculate the current drawn from the supply,
40
(7.8 + j12.3) o
Z"o'Zu
Zu = lu6 + 26,- +Zo
= 9.2462-32.70 t,
7 -
L?- <
Z^..2-^
2"6 +26, +Zo
= 7.1472_14.26o e
The star as shown in
Figure 2.32 nowrepraces
the derta in Figure 2.31.
47
-
(7.8 + j12.3) o
6.12727r.92'O
7.147t-r4.26 0 9.246t-32.7" O
(13.4 - je,3) o
Zt= 7u+(7.8+j12.3)
= 2O.558261.840 O
Zz= 7,+(13.4-j9.3)
= 23.L4LZ-28,55o O
a- -
La-
Zt'Zz
Zr+2,
t6r.84")(23.r4rt -28.55")
= (20.558
20.558 z6L.U" + 23.I4I t 28. 55'
-
15.42L220.O50 cr
a_
z-- 76+23
= 9.246 z-32.7o + L5.421 220.050
22.26910.750 d2
2.5.2 L- LZ
38020'= (r)(22.26s20.7s") '
l= L7.O6424.75 A
42
1" 25s STAR-DELTA (y-A) coNvERSTON
z2-
7 7. z;b'zbc.zca
(Zao +Zo, +Zu)2
z2=
Z6c'Zcd'Zab
7, 7
(Z"a +Z.6,- +Zo)2
7 7-
1c'La
zz*,zuo,zo,
G;irrn;f
Adding these three equations give:
Z (Z ao + Zo.^ + Z
Z*Z6+Z6Zr+Zr.Zu = ^o.Z,or.Z
o u)
(Zua + 6.- +Zu)z
zab'Zbc.zca
Zu6 +2y- +Zu
43
Example 2.5
Za = I2.0IZB7 35' a
Zo = 19'57145'54'{>
7, = L6.92/-6L7B Q
Conveft the load to an equivalent delta-connected load to find the phase currents and
then calculate the star-point potential. Take V5 as reference.
Solution:
vulr2lo
Eo,l30o
Ea6ZL50o
Y6200
vc/-r20o
Zu'70
7,x = 7.-r 7x *
zc
.35') (L9 .57 245,
(L2.01 zB7 54 ")
= t2.01187.350 + 19.57145.540 + 16.922-61.78"
= 22,462287.90 O
a a r 1 r
77
-C'-d
L^--L.aL-A
-
zb
(16.92t - 6t.78.)(tz.0ttg7 .35")
= 16.92'-$1,78o + t2.0I287.350 +
19.57 245.54"
= L9.42!l-19.42o O
44
Current in each phase of the delta-connected loadr
r-Vao
rab_
d
3601150"
= 22.452287.9"
= L6.O27262.1o A
r-Vca
l^.
-
/' cA
360 t-90"
19.42rt-19.42
= 18.5372-70.58'A
Ia = Iuo-Ica
= 16.027162.10 - LB.537l-70.58"
= 31.675187.580 A
Vu, = Iu.Zu
= (3I.675 zB7.5BoX12.0 I tB7 .35o)
= 380.4172174.93V
V'n = Vu-Vu'
= l-l[:ooz]zo"l - 3*o.4t7tt74.s3"
\J3)
= 311.5375228'030 V
Example 2.7
Zu = (L5.6 + j12.4) o
26 = (I5.2 - 18.3) o
Z" = (24.I + j16.7) o
45
2.7.r use star-delta conversion to calculate the currents drawn from the supply,
2.7.2 Calculate the voltage across each impedance in the load.
2.7.t
E,"160o
Ev6lIB0o
v^l-L50" vbz-30
o
E,orZ-60
Delta-connected im pedances :
7"n= 7^+2,6+'4"
Lc
(15.5 + jtz.4)(Ls.2- j18.3)
= 15.6 + j12.4 + I5.2 - j18.3 +
24.1+ j16.7
= 45.25652-22.270 Q
7or= Zn+zc+t+
la
(1s,2 - j18.3X2a.1+ j16.7)
= 15.2 - j18.3 + 24.I + j16.7 +
15.6 + j12,4
56.9192-26.570 C)
7_
L+z-*7''7u
zb
(24.1+ j16.7x1s.6 + jt2.4)
z4.t + j16.7 + 15.6 + j12.4 +
ls.2 - j18.3
56.457262.20 A
46
lr
F
C.ru.r"ent f
in each phase of the
delta_connected load:
,i
Iao = %!-
Zao
4402780"
= as.ag22 _ 22fi
= 9.6742_157.190 A
T, -
.DC -
Vu.
zo,
4402_69.
66sl6z_16r;r
= 6.5752_33.430 A
T-Vca
rca
-
z^_
k
440Zffi,
id.os? z6n"
= 7.8492_2.20 A
Current in each line of
the delta_connected load:
Iu = Iuo-I.u
= 9.6742_LS7.Ig" _ 7.B4gZ_2.2o
= t7.tt2Z_169.37o A
Io = Io.-I"n
= 6.5752_33.430 _ 9.6742_757.tgo
= I4.4OSZO.51o A
I. = I.u-Ib.
= 7.8492-2.20 - 6.575Z_33.430
= 4.O72ZS4.OSo A
2'7.2 %s = I6.Zu
= (17.1122_168.37)(1s.6 + j12.4)
= 341.0O64_t2g,ggo V
47
E
Vb, = Ia'Zo
= (74.40s t0.s1ox ls.2 - j 18.3)
342.685t49.780 V
V., = Ir.7"
= (4.0722s4.6sox24, 1 + jL6.7)
LLg.394289.370 V
Apparent power consists of real (active) power and reactive power, This power
ignores the phase relationship between the current and the voltage, When this phase
angle is 0o, the apparent power equals the active power. When the phase angle is 90',
the apparent power equals the reactive power, The apparent power is defined to be:
S= E.I
Complex power also consists of real (active) power and reactive power, However,
the phase relationship between the current and voltage is included in this power.
Active power is unidirectional and reactive power reverses direction twice each field
cycle and results in reactive energy near the oscillating source. This energy directly
i nfl uences, affects a nd im its operationa I characteristics.
I
Ite
,tul zz+
Sx = E.Ix
Where: E = the rms value of the supply voltage
Ix = the complex conjugate of the rms value of the current
4B
The conjugate of a quantity is the mirror image of that quantity. If the current is
T. = l0 A, the conjugate of this current will then be I = l-0 A, as shown in Figure 2.36.
I*:Il-e
Figure 2.36: Phasor diagram showing I and its conjugate I*
The complex power is then:
S* = EL\.IZ-j
= E.Iz(9 - 0)
= PljQ
P = E.I.cos$ = I2.R
Q = E.I.sin$ = r2.x
Where: P = real or active power in W
cos$: powerfactor
Q = reactive power in VA'r
Gos$ = cos Zl
The magnitude of the complex power is simply what was called apparent power, and
the phase angle of the complex power is the power factor angle. The relationship
between the complex power, active power and reactive power is shown in Figure 2.37
and in Figure 2.38. In Figure 2.37 it is shown that the phasor current in be split into
two components. The active component that is in phase with the voltage and the
reactive component that is 90' out of phase with the voltage:
factive = I.cos $
Ireactive = Lsin d
49
figurd Z.Zl: Representation of the active and reactive components of current
The in-phase component produces the real (active) power and the quadrature
component produces the reactive power, In Figure 2.38 it can be seen that, if the
reactive power Q is positive, the load is inductive, the power factor is lagging and the
complex power S lies on the positive side of the positive real x-axis.
Figure 2,38: Power triangles showing lagging and leading power factor
If the reactive power Q is negative, the load is capacitive, the power factor is leading
and the complex power S lies on the negative side of the positive real x-axis. If the
reactive power Q is zero, i.e. the load is resistive, the power factor is unity and the
complex power S lies along the positive real x-axis. It is impoftant to know that
complex power is conserved like energy. This means that the total complex power
delivered to any number of individual loads is equal to the sum of the complex powers
delivered to each individual load, regardless of how the loads are interconnected,
50
2,4 REACTIVE POWER
E
Figure 2.39: A pure resistive circuit
Figure 2,39 shows a pure resistive circuit with a switch. Figure 2.40 shows the
resulting waveforms when an alternating voltage is applied to this circuit, The current
waveform is exactly like the voltage waveform, which means that at each time instant
Ohm's Law is obeyed. The power dissipated in the resistor is the instantaneous
product of the current and voltage. The power is therefore a direct current component
that alternates at double frequency. However, the power dissipation is always positive,
51
-t
The waveforms of the voltage and current, shown in Figure 2.42, show that, due to the
inductance of the coil, the current can't keep up with the voltage at the moment when
the switch is closed. The current therefore lags the voltage for a few cycles and then
attains a steady alternating value, with its waveform lagging the voltage waveform by
90'.
The mean product of the voltage and current is zero, as the magnetising current in this
case carries mo power. Power flow oscillates positively and negatively at twice system
frequency amd hence the name reactive power. When an open-circuit transmission
line is connerted tn a voftage source/ the line can absorb a large amount of electric
charge dure b rapffiihnce. When the switch is closed, a surge of current into the line
occurS.
52
This current reduces to a steady alternating value that is required
to keep the line
electrically charged atthe applied voltage. In ttris case, the current
waveform leads the
voltage waveform by 90'. There is theiefore again no transfer
of real power. 1y5;.
load is connected to a transformer or transmission line, the load
current is added to the
reactive current' This means that the total current iags or leads
ilre vortaje ty-an
angle less than 90', depending on the ratio of the current corresponding
to t-he active
power loss in the load and the reactive power required to energise
the transmission line
or the transformer' The instantaneous power flow therefore cJnsists of
a constant level
plus an offset alternating reactive power. All practical electrical
components have
resistance' The current flowing in these components therefore causes resistive
losses
and heating. The heating can restrict the load-carrying capability of a transmission
line
or transformer or the output capability of a generator. Reactive power involves
current
flow and therefore creates losses just like aitive power. However, the total current
is
the phasor sum of active and reactive components of the currents. Therefore,
component ratings have to be carefully chosen to match the reactive requirements
of a
circuit.
53
.d
EXERCISE 2.L
2. Refer to Figure 2.43 and calculate the line current I.. The load is connected to a
symmetrical, three-phase, cba-rotation supply with Eu = 24010o Y.
18256.3"O
7'O
54
ll A balanced, three-phase, 360-V, four-wire, negative phase sequence supply with E5 as
reference, is connected to a star-connected load with the following load impedances:
7u= L2.Bz-32.8o o
Zo= 2I'412I'4o e)
4 = 37.92-87.90 f)
",u I Calculate the line currents.
4e Calculate the neutral current.
.r43 Calculate the total complex, real and reactive power in the load.
This load is connected to a thr,ee-phase, 400-V, 50-Hz supply, Take Enu as reference
with a positive phase-sequence.
55
7. A balanced, three-phase, three-wire, cba-rotation supply with V"r =- 360 V, is
connected to a star-connected load with the following load impedances:
za = 12.81-32.80 Q
26 = 2lAl2L4o e)
zc = 37.91-87.9" Q
7.t Calculate the line currents.
7.2 Calculate the total power consumed.
7.3 Draw a coniplete phasor diagram of the voltages and the currents.
za = (13.6 - j12.8) o
26 = (L7.7 + j19.4) O
Z, = (12.7 + j10.5) O
8.1 Use Millman's theorem and calculate the voltage between the neutral point of the load
and eath.
8.2 Calculate the line currents.
56
1il
(8.4 + j3.6) o
(12.4 -j7.s) o
-l (7.5 +j4.8) o
57
IT
11. The phases in the load of an unbalanced, star-delta system consists of the following
components:
This load is connected to a positive phase sequence, three-phase, 60-Hz supply with:
L2. A three-phase, star-delta system with a negative phase sequence and V6. = 390l25o V
at 50 Hz, has the following load impedances:
13. Consider Figure 2.45. Use delta-star conversion and calculate the current drawn from
the supply.
73.25t42.25" O
14.5239.4" O B.tt57.L O
16.55250.6'O L0.22r0.2 0
E = 360V,50H2
-
Figure 2.45: Parallel network for Question 13
5B
2"5 POWER MEASUREMENT IN THREE.PHASE SYSTEMS
Example 2.8
A single wattmeter is used to determine the power in phase cof an unbalanced, three-
phase, delta-connected load. The load is supplied from a balanced, three-phase,
380:V, alternating current source. The voltage coil is connected to lines b and c. The
load consists of the following impedances:
Take E.u as reference with a positive rotation and calculate the reading on the
wattmeter.
59
Figure 2.45(b): Positive (abc) phase sequence with E.u as reference
r-Vn.
Ihr
-
Lb,
380 1L20"
6.2+ j9.6
= 33.252262.86. A
T_ Vca
rca - zca
38020
=
4.8-W
43.914256.310 A
W.= V.5.I..cos zf
= (380X11.52l)cos(- 60' - 37.09')
= - 540.367 W
50
Example 2.9
cos 0= 0.39
0= 57.050
tand = J5f*.-*..]
l.W. *W. l
Since the reading on Wu is negative, it means that the wattmeter in line a reads down
scale. It is therefore obvious that, when the power factor is less than 0,5, the reading
on Wu must be negative.
61
Example 2.10
Pout
2.10.1 n = D.
'ln
18.04
0.82
Pin
Pin = 22 kW
W"+W. = 22kW
cos0 = 0.82
0= 34.920
tan0 =
n(w, - w" )
t'[w.
*.1
tan34.e2o=
=
"[ry)
8.867 kW
W. - Wu
But: W.+Wu = 22
W. = 22-Wa
And: W.-Wu = 8.867
And: W= = 5'5555 kW
62
Wa+Wc =22
6.5665 + Wc =22
And: Wc = 15.4335 kW
D
I motor
2.70.2 c-
Jmotor -
a"torotor
22
=
0s2
27.8482-34.920 kVA
CoS = 0.86
$636
Otoao = 30'680
Sload =
loaa
COS $1es6
72,8r
0,86
= L4.8952-30.680 kVA
'Stot J3 ,v..I,
42.7L6 x t03 ( Js Xseoxr,)
.'. Ir LL2.4LT A
Example 2.11
Refer to Figure 2.47 and prove Blondell's theorem. The load is supplied by a balanced,
three-phase, three-wire supply system with a positive phase sequence at
Eu. = 48010'V,
63
i
(8.2 + j17.4 a (18,3 + j1s.1) o
(24.2-j16.4) f)
c
E""
60'
r-Val
r*- =-
/aa
_ ffi1ffi"
18.3 - 115.1
: *?5l.LAA7o A
64
T- Vn.
rbc - zn
4E0z-ffi"
=
24.2- jr6.4
L6.41952-25.880 A
T_ Vca
rca - za
4BOIIffi"
=
8.2 + jIn
= 25.L9121L5.490 A
= 6524.699 W
D_
rca - V.u.I.u.cos Zrv;
D- Ps6*P6s*P63
= 7489.9L9 + 6524.699 + 5203.698
19218.316 W
65
I.= I.u - Io.
39.3752L30.580 A
W3 = V65.I3.cos zi%b
= (480X33.661)cos (600 + 27.73o)
= 639.967 W
W.= V.5.I.,cos z['o
(480X39,375)cos (120o - 130.58o)
18578.591W
W= Wa+Wc
= 639.967 + 18578.691
19218.658 W
Example 2.12
za = 24.8/36" Q
26 = 721-75" Q
zc = 18.61840 Q
Use Millman's theorem and determine the power absorbed by the load using the two-
wattmeter method if the wattmeters are connected in lines a and c respectively. Take
E" as reference.
66
vbclgjo
vb1l20o
valjo
vcaz-rs}" vubl-30"
vcl-Izgo
Figure 2.49: Negative (cba) system with Eu as reference
Vrn = %.%+V6.Y6+V..1
Yu +Y5 +Y.
38020",3802120",3901-720
(43)(24.8236") (J3)(722-7s) (J:xra.6ze+.)
=1rl_!1
24.8236"' I2l-75"' 18.6zg4"
= 356.5112-169.59"V
Voltage in each phase of the load:
Vu, = Vu-V.n
= 3Bo
lo" - 3s6.6rrt-169.59.
J3
= 573.76426.45"V
%, = V.-Vrn
380 z -I20"
= _-_E- _ 356.6Lr2_169.s9"
= 27L,7882-27.52V
Current in each phase of the load:
Vu, = Iu.Zu
573.764t6.45. = (Iu)(24.8t36.)
Iu = 23.1362-29.55 A
67
V., = Ir.Z"
27I.7BBZ-2752 = (IcX1B.6ZB4")
I.= [4.6L2Z-L11.52' A
w. = vgs.Is.cos zYd
Example 2.13
6B
Eo"
r-Vao
raD- =-
laa -
36010"
= 11.45 + j14.44
= 19.5352-51.59. A
I5. = -Ss-
lb,
3@t-L20"
= 17.53 + j24.22
= L2.O4lZ-l74.l A
T-Vca
rca - =-
lca
3ffi2120"
= 20.08 + jI6.n
= 13.761280.13. A
Active power in each phase of the load:
= 4369.246W
Pb. = V5..16.,cos Z[tr
(360X12.04l)cos(- 120" + 174.t')
254t,783 W
16=I36-Is6
= 19.5352-51.59' - l3.76tl90.l3
= 3O.4762-7t.29" A
= Iu. - Iub
= I2.04IL-I74.L - 19.5351-51.59'
= 27.9182149.74'A
= I.u - Ib.
= 13.761 t80, 13' - I2.04LIL7 4.I'
= 2O.5OtZ45.9o A
Since the voltage coils form a balanced, star-connected system, the voltage across each
voltage coil lags the line voltage by 30" (positive phase sequence). Thus, reading on
6:;." d!*e++'r""**'..w
wattmeter in each line:
u+
w. = J3
.Iu,.o, 1 zf,o
ra
t :0")
= 4759.475W
70
wn = $.t6..o, ( zr;%.r 3o')
rr
J3
= (#),r r18)cos(- 120" - 14s.74.- 30")
= 2878.49 W
w.=
f.t.,.or1zl"tso";
= ro1)cos(120. - 4s,e. - 30.)
[#),m
= 3O74.9 W
W = Wa *W5 +W.
= 4759.475 + 2878.49 + 3074.9
= LO7L2.865 W
Example 2.14
36.5t36.6 A
25.5t25.5"a
77
Refer to Figure 2.51. The unbalanced, three-phase, four-wire load is connected to a
symmetrical, three-phase supply of 440 V. Calculate the readings on the wattmeters to
find the total power drawn by the load, Use E5. as reference with a negative phase
sequence.
Vun = Iun,Zun
4401-90' ( J5 X1.,Xs6.6236.6')
I"n 6.94'-Z-126.60 A
Vun Iun'Zon
V.n = Irn'Zrn
4402150' = dt)e,)(25.522s.5.)
I"n = 9.9622124,5" A
T2
Wu= Vun,Iun.cos z{an
= - 7s.s')
t#)(5.583)cos(30'
= 994.08 W
W. = V.n.I.n.cos ZtV;
= (#)(e.e62)cos(lso' - 124.s")
= zzellszw
W = Wu *Ws +W.
= 1415.569 + 994.08 + 2284.L62
= 4593.811W
73
EXERCISE 2.2
za = L2.4139" A
26 = 18.6l-56'A
zc = 2L.726I" {l
2. Two wattmeters are connected to an unbalanced, three-phase, star-delta system with a
positive phase sequence. The following readings were taken:
T-
rab - 10,55231.50 A at a power factor of 0.85264 lagging
a-
Lbc - 20.23t25.20 A
Zr" = 30.34t-90.90 0
The load is connected to a 360-V, 50-Hz supply. Prove Blondell's Theorem if the current
coils of the wattmeters are connected to lines b and c.
3, The following impedances are connected in delta in the load of a three-phase sytem:
74
-the following
three impedances are connected in the load of a three-phase, delta-star
system with a positive phase sequence:
1 = (72.4 + j15.5) O
1 = (15.6 + j9.3) O
L = (9.6 + j18.2) o
The voltage measured between lines a and c 1.25 ms after passing through zero was
205.6545 V,
Z, = (12.4+ j21.3) o
Zy = (18.6 + j28.4) o
7- = (21.7 - j9.9) o
5.1 Use Millman's theorem and calculate the readings on the wattmeters.
5.2 Use the given and calculated values and prove Blondell's theorem.
z, = 22.22390 Q
26 = 15.52550 O
za = 16.21-450 Q
A wattmeter is connected in the system with its current coil in line b and its voltage coil
between lines a and b, Take Vu6 as reference with a positive phase sequence and calculate
the reading on the wattmeter.
7_
Lbc - 42.6172 0
a_
Lab 272-4Bo o
-
Zru = 1832360 A
Prove Blondell's theorem when two wattmeters are connected in lines b and c respectively.
75
i
B. The circuit in Figure 2.53 is connected to a 440-V, 50-Hz, symmetrical, three-phase supply
with a positive phase squence. The complex power in 25. is 18.28 kVA with a power factor
of 0.76 lagging. Use E6. as the reference phasor.
9, Prove Blondell's theorem for a load that is supplied by a sinusoidal, balanced, three-wire,
three-phase, cba-rotation supply system that is represented by the equation:
Za = 21'5129" {>
7o = 15.8242 Q
Z< = 25j182 A
10. A three-phase load has a power factor of 0.72lagging, The power in the load is known to
* 27 .6 kW. Calculate the reading on each of two wattmeters connected in lines a and b of
the load to measure the total power. The load is connected to a symmetrical, three-phase
suppty with a positive phase sequence,
76
:L. The power supplied to a three-phase, delta-connected induction motor is measured by two
wattmeters connected in lines a and c. The motor is supplied from a three-phase,
cba-rotation , 440-V, 50-Hz source. When the motor is running on a light load the
wattmeter readings are 564 W in line c and 358 W in line a.
-1. When a no-load test is performed on the motor in Question 11, the wattmeter readings are
now 924 W and - 444 W respectively.
Ia r3.92-sz o
L3.6t45" O I5.723L" O
Ic tB.L/28'o 12.It52 0
I6 I5.6t77" O
14, Two wattmeters are now connected in lines a and c between the supply and the load tn
Figure 2.54. Use the given and calculated values and prove Blondell's theorem.
77
15, The two-wattmeter method is used to measure the active power drawn by a balanced,
three-phase, delta-connected load. Each branch of the load draws 3260 W at a power
factor of 0,82 lagging. The load is supplied from a 240-V, 50-Hz, positive phase sequence
supply. Take Eu6 as reference and calculate the readings on two wattmeters connected in
lines a and c to determine the total power.
17. If a wattmeter is connected in each line of the load in Question 16, calculate the readings
on the wattmeters and show that the sum of these readings is equal to the total power
calculated in Question 16.
za = 455236$ {l
26 = 25.51-45.5" Q
zc = 36.6225.5 Q
19. The two-wattmeter method is used to measure the active power drawn by a balanced,
three-phase, star-connected load. Each branch of the load draws 2970W at a power factor
of 0.856 lagging. The load is supplied from a 380-V, 50-Hz, cba-rotation supply. Take E5.
as reference and prove Blondell's theorem when two wattmeters are connected in lines b
and c to determine the total power.
1n = 22.65258,3'Q
Zy = 19j5145.1'O
z= = 24.85169.8 Q
Take E= as reference and calculate the total power delivered to the load by using the load
voltages and cunent.
7B
I
j
21. If a wattmeter is connected in each line of the load in Question 20, calculate the readings
on the wattmeters and show that the sum of these readings is equal to the total power
calculated in Question 20.
79
CHAPTER THREE
3.1 INTRODUCTION
',1
Ec Ec
(a) (b)
BO
Consider Figure 3. 1(a):
E. = EaZOo
;LA
Eo = Eal24oo
= crz, Eu
E. = EalIzOo
= o,Eu
1+o(+cx,2 = 0
1+cx,+cr2 = 1-1
-0
Also, multiplying any phasor by a3 is the same as multiplying by 1. In the j notation:
= 0,25 + 0.75
=l
B1
3.1.1 POSTTTVE PHASE-SEQUENCE
Ea
E5
Eu
Eu
Ec
82
RESOLUTTON OF AN UNBALANCED, THREE-PHASE SYSTEM OF
PHASORS INTO ITS SYMMETRICAL COMPONENTS
The original system shown in Figure 3.4 can be resolved into three symmetrical
component systems as shown in Figure 3.5,
Ea = Vao+Vu1 +Vu2
Eo = Vuo*V61 +V62
Vnz
Vco
Vaz Voo
Vao
p.p,s n.p.s
B3
Eu Vus+u2.V.1 *o.Vs2
E. Vss*cx,,V31 +cr2.Vu2
So that: e
%o = *( Ea + 56+ E.)
- Voo
=%o
Multiplying by o and by a2:
From which:
cr. =
Ec uVus*cr2.Vu1 +Vu2
And hence:
Vuz =
+
(E" + a2.Eu + u,E6)
84
And: Vc2 = az.Yuz
It can be seen from Figure 3.6 that the symmetrical components of each phase sum to
the original phasors,
Vat
Vco
Figure 3.6: Symmetrical components of each phase summed to the original phasors
Figure 3,7 shows that the resultant of the original system is equal to the sum of the
zero phase-sequence components. This is true of any unbalanced, three-phase system.
A balanced, three-phase, asymmetrical system will resolve into p.p.s and n.p.s
components only, A three-phase, symmetrical system will have positive phase
sequence components only. These components will be equal to the original phasors.
Ec \Eu+E.
Ea
-u:h E5+Es
Eoh
Figure 3.7: Resultant of the original system equals the sum of the zero phase-
sequence components
r The currents in a balanced three-wire system with no earth fault present will
resolve into p.p,s components only.
B5
. The currents in a three-wire system with an eafthed star-point will resolve into
p.p.s, n.p.s and z,p.s components when a single-phase to earth fault is present.
The growth of an earth fault current will therefore be indicated by an increase in the
z.p,s components. The growth of an unbalanced load in a three-wire system will be
indicated by an increase in the n.p.s components. If the growth of an eadh fault
current or unbalanced load can be detected and measured separately from the other
components, relays can be arranged to trip the suitable circuit breakers when the level
of unbalance exceeds reasonable limits. Minor unbalance is normally caused by
unequal ph6se loading but harsh unbalance will be caused when a phase-to-phase fault
occurs.
In the circuit shown in Figure 3,8, the resistance and inductance of the impedance 21
are such that the current through this impedance lags the voltage across the
impedance by an angle of 60". 22 is a pure resistor and the resistance value of Zz is
equal to that of 21. The circuit in Figure 3.8 detects n.p.s components but not p.p's
components since the relay measures the phasor sum ( Er + Ez ).
<_<-
E1 Ez
Figure 2.62
In order to detect p.p.s components and not n.p,s components, the impedances 21 and
22 must be interchanged, as shown in Figure 2.63. '
B6
+<-
E2 E1
Figure 3.8
The detection of p.p.s components can be used in overload protection. The detection
of n.p.s components can be used to limit the level of unbalance, To limit the degree of
unbalance is mainly important when referring to the currents in the stator windings of a
three-phase alternator, If the stator currents consist of p.p.s components only the
magnetic field that is set up by these currents rotates at synchronous speed in the
same direction as the rotor. There is therefore no relative motion between the stator
field and the rotor, If the stator currents contain some n,p.s. components, the field
that is due to the n.p.s components only, rotates at synchronous speed in the opposite
direction to that of the stator. This is due to the fact that a negative phase sequence is
equivalent to a symmetrical system of phasors rotating in a clockwise direction.
---r--
Figure 3.10
87
i
If the n,p,s component field exceeds limits set by the design of a machine, extensive
rotor damage may result from overheating. Eddy currents that are induced in the rotor
iron mainly cause overheating. In four-wire systems, the circuits shown in Figure 3.8
and Figure 3.9 will be disturbed by z.p.s. components. Cross-connected current
transformers, as shown in Figure 3.10, are used to exclude z.p.s components from the
detecting relays. Since the z,p,s component currents of each phase are synchronized,
each cross-connected current transformer secondary provides a low impedance path
that diverts practically all of the z,p.s components from the measuring circuit.
+ +
12 I1
22 71
Figure 3.11
In the circuits shown in Figures 3.11 and 3.12, the resistance and inductance of Zldre
such that the current through this impedance lags the voltage across it by an angle of
60". Zz is a pure resistor. The resistance value of this resistor is equal to that of Zt
The circuit shown in Figure 3,11 is arranged to detect p.p.s components only. The
circuit shown in Figure 3,12 is arranged to detect n.p.s components only,
8B
_+
I1
71
Figure 3.12
. The positive phase-sequence voltages (Vur, V61 and V.1), the negative phase-
sequence voltages (Vuz, Vuz and V.2) and the zero phase-sequence voltages (Vus,
V56 and V.6) separately form balanced systems of voltage. Hence, they are called
symmetrical components of the unbalanced system.
. The symmetrical components do not have separate existence. They are only .
. The negative and zero phase-sequence currents are zero in a balanced, three-
phase system.
B9
. In a three-phase, unbalanced system, the magnitude of the negative phase-
sequence component cannot exceed that of the positive phase-sequence
component, If this would happen, the phase sequence of the resultant system
would be reversed.
Example 3.1
Calculate the positive-, negative- and zero-sequence components of the following set of
three unbalanced voltage phasors:
Y" = 2252-38" V
Yo = 775169" V
Y, = !4021150 V
Indicate on approximate diagrams how the different sequence components are located.
vbl - cr2.V"r
vc1 - ct'Var
Var
90
Yaz = +(%+a2.V5+a.V.)
= +(22st-3Bo + r7sz309o + L4ozz3so)
= 146.9642-61..980V
Vu, = CLVa2
= L46.964/.(-61.98' + 120')
= 146.9642.58.020 V
Vcz = d2.Vaz
= 746.9642(-61.98' + 240')
= 1'46.9542178.020 V
Voz
V.z
V"z
Figure 3.14: Negative phase-sequence components for Example 3.1
Vao= *(V.*V5+V.)
= !{zzsz-zeo + r75t69o + r4ottrso)
= 78.69L24Oo V
= Vuo
= V.o
%o Vuo %o
:,i
i.(i
1l {' i
i
.ti 91 :l
!
;fr
ii
I
a
lfl
-J
Example 3.2
rrao- In
-
T
27.31ffi"
3
= 9.Ll64o A
Ia= Iao+Iu1+Iu2
= 9.L1640 + i+.SZ-+So + 22.511050
= 21.386266.820 A
In= 156+I51+I52
= Iu6+cx2.Iu1 *o,162
= 9.1 z640 + 14.5 t(-45o + 2400) + 22.5 t(L05o+ 1200)
28.3562-L56.110 A
I.= Ico+Ic1+Ic2
I6e*cx,I31 +a2.lu2
9.Lt64o + 14.52(-450 + 1200) +22.51(L05o + 2400)
33.7L2229.O30 A
92
Example 3.3
Vun = I72l7BoV
Vbn = 196 Z4Bo V
Vcn = 185 l-702o V
3.3.1 Use a positive phase-sequence and calculate the impedance of the load.
3.3.2 Calculate the complex powelin each phase of the load,
3.3.3 Calculate the total complex power in the load.
3.3. i Iun = Iu
= Iao * 161 * 162
= l9.7l72o + L6.42-24o + 12.61360
= 36.O72230.890 A
Inn = Iu
= Iuo * 161 * I52
= Iao * cx2,Iu1 + cr,Iu2
= 18.72720 + 16.42(-240 + 240") + 12.62(360 + 120")
= 23.L751L45.O7o A
I.n = I.
= Ico * Is1 * Is2
= Iao * + a2,Iu2
cr,Iu1
I = !8.7172" + L6.41(-24o + 120") + L2.61(36o + 240')
= 22.225275.99o A
z - V.n
"
La-
I.n
I72l7B"
36.072t30.89"
= 4.768247.110 O
93
a - Von
"
LA_
Inn
L96Z4B"
?3.L75 2145.07"
8.4572-97,070 c)
%n
zr=
I.n
t85/-r02"
22.225t75.99"
8.3242-177.990 c,
Siln = Vnn'I[n
\=
-cn V.n.Iln
94
Example 3.4
Ial = 12.62-10" A
Iaz = 15.3 l72 A
The voltage drops across the phases of the load are:
va = B4IBZ"Y
V5 = L26l-60"Y
vc = I04I4BV
3.4.1 Calculate the impedances of the load.
3.4.2 Calculate the total active and reactive power in the load using the symmetrical
vofta ge. a nd cqf rgn!:
99-mp91gnt9 .o[ !l-e_.
In
3.4.I I"n = 3
18.62-45"
= 3
= 6,22-450 A
Iu= Iao4Iur+Iu2
= 6.22-45' + L2.61-70 + 153272
= 22.952220.34'A
In= Iuo*I51+I52
= Iao * o2,Iu1 + cr,Iu2
= 621-45 + 12.62230' + I5.32I92'
= 25.4052-137.33'A
I.= Ico*161*162
= Iao * a.Iu1 + cx2.Iu2
= 6.21-45" + I2.6ZLL0" + 15.31372.
= LL.O3Z-2O.78" A
95
va
Z"=
Ia
84ZB2"
=
22.952t20.34"
3.6626L.65. Q
7_V
V^
"
LA
Ib
t26t-60'
25.405 t - 137.33.
= 4.96277.330 c)
1_
Lr
4
" Ic
I04 Z4B"
fl.432-20.78"
9.429168.780 c)
3.4.2 Vao =
*(v.*V6+V.)
= t {a+zez + Lz6t-60' + Lo4t4B)
5L.O492t9.59. V
Va1 =
I ry. * '.vb + *2.vc)
= t {e+zez' + 126z60' + ro4z299')
= 47.298z4L.150 V
va2 -
I {v. + a2,v6 + a,v.;
= ! {e+zez + tz6ztlo" + ro4z168')
= 80.0392154.!20 V
2032.355 W
And: Y 5889.324 VAr
96
Example 3.5
The current flowing to a delta-connected load through line a is 12.55 A, Calculate the
symmetrical components of the line currents if line c is open circuit. Take the current
in line a as reference.
Iu = 12.5510" A
I.=0A
H
Io = 12'551180'A
Iu, = {(Iu+a.Is+u2.I.;
t {tz.sszo" + tz.Ssz3ooo + o)
7.246/-300 A
Iut cr2,Iur
7.2462(-30' + 240')
7,246z-'-500 A
I.t 0'Iat
7.2462(-30 + 120')
7.246z900 A
97
Iaz = | {I, * cx2.I6 + a.I.;
= ! {tzsszo. + r2.55t420o + o)
= 7.2462300 A
T-
Lb2 ct'Iaz
-
= 7.2461(30' + 120')
7.246t1500 A
Ic2 = o2.Tu,
7.2462(30 + 240')
= 7.246z-900 A
Example 3,5
An analysis of the currents flowing in the direction of the load in line b shows that the
positive and negative phase sequence currents are2L6l-48" Aand 27.31II2'A. The
current flowing in the neutral towards the star point of the supply is 33.3242' A.
3.6.1
.
lM-
In
5
33.3t42"
=
3
= IL,LZ42o A
9B
Ibn = I5s*I51*162
ILLt4zo + 2L6l-4Bo + 27.3tII2o
20.835t53.220 A
T_
ran - I6s*I31*I32
156*cr.I51 +u2.I62
IL.L z42o + 2L.6 t(-48o + 1200) + 27 .3 t(IIzo +2400)
48.422229.9450 A
Icn = I.6*I.1*I.2
= 156*cr2.151 *o.Inz
LL.IZ4Z" + 2t.62(-48o + 240") + 27.32(rl2o + 1200)
= 35.O22-L47.960 A
Vbn = Idn'Zan
= (20.835 t53,22.X 1 5 -j 1 5)
44L.97728.22'V
V.n = Irn'Zrn
= 1062.553245.190 V
99
V.u = V.n - Vun
= L672.39Ls2-LOs.69" V
1m
EXERCISE 3
1.. A three-phase, four-wire, star-connected supply with a positive phase sequence supplies
* loads that are unequally distributed on the three phases. An analysis of the currents
flowing in the direction of the load are the following:
Va = 1502-1Bo V
V5 = I3BZ72oV
Vc = 190147oV
Using the symmetrical components of the voltage and current in phase a, calculate the total
reactive power in the three-phase system.
Iao = 22'8l-670 A
Iar = I2'9135o A
Iaz = LB.3l123o A
3. Resolve the following three-phase system of voltages into its symmetrical components:
Va = 2402510 A
V6 = 2I5l-Il0o A
V. = 2601930 A
101
4. In a three-phase, four-wire, star-connected load, the symmetrical components of the
current in line a are:
Iar = 2'62-10o A
Iaz=2ZIBloA /
Iao = L'4175o A
The phase sequence is abc and the voltage drops across the phases of the load are the
following:
Yan = I27lL27"V
Van = 145l-610 V
Yrn = 16521080 V
LS.i n three-phase, four-wire, symmetrical supply with a phase sequence of abc supplies an
unbalanced, star-connected load of the following impedances:
7un = I2.6t63" A
Znn = L4.51-4B Q
zrn = 72.9145" Q
An analysis of the currents flowing in the direction of the load in line b shows that the
positive and negative phase sequence currents are 18.6l-42' A and 2L.3IL0B' A. The
current flowing in the neutral towards the star point of the supply is 27.6239" A.
r02
7. A three-phase, four-wire, symmetrical supply with a phase sequence of abc supplies an
unbalanced, star-connected load of the following impedances:
Zu = (12.9 + j15.1) O
26 = (t6.4 - j12.6) o
Z. = (15.8 + j11.9) O
An analysis of the currents flowing in the direction of the load in line c shows that the
positive and negative phase sequence currents are 24.61-42' A and 2I.92702' A. The
current flowing in the neutral towards the star point of the supply is 36.9242' A.
103
CHAPTER FOUR
4.L INTRODUCTION
Any connection between two points of a power system is an inter-connector, but the
name is usually used for a connection between two alternators, power stations or
supply network. Inter-connection increases the amount of current which flows when a
short circuit occurs on a system and requires the installation of breakers able to
interrupt a larger current. The disturbance caused by a short-circuit on one system
may spread to inter-connected systems unless proper relays and circuit breakers are
provided at the point of inter-connection. Not only must the inter-connected system
have the same nominal frequency, but also the synchronous machines of one system
must remain in step with the synchronous machines of inter-connected systems.
r_ Bus_bafs___-, r
ll
*T*ry*T*
Transformers
tnter-connector
J I
To the load on the bus- To the load on the bus-
bars of power station A bars of power station B
F@ure 4,1 shot''"s a line diagram of two power stations joined by an inter-connector.
Tlne inter--ccnnector is connected to the bus-bars of each power station through
Fansfor'ners, Each power station also has a feeder-load connected through a
transfo,rrer ro nts hus-bars. The power sent across the inter-connector will depend on
the $earr s*Ftrf'r, tc c"e iurbines of each power station.
104
For example, if the feeder load on the bus-bars of power stations A and B are each 50
MW and the output of the generators on the bus-bars of power station A is 30 MW, the
output of the generators on the bus-bars of power station B must then be 70 MW. 20
MW must therefore be transmitted across the inter-connector from power station B to
power station A. The output of the generators depends only on the power supply to
their prime movers. Thus, the power transmitted from point to point in an inter-
connected network depends ultimately on the steam supplies to the prime movers.
When more than one path is available between inter-connected points, the proportion
of power transmitted by each path may be controlled. The total remains, however,
depend on the load conditions. The control of the power transmitted over the country
is centralised in the control rooms of the generating divisions and in the national control
room. These maintain communication with the generating stations coming under their
control and issue instructions to station engineers to increase or reduce the load on
stations. The control room engineers thus control the frequency and the loading of
transmission links in the network.
Reactive power devices, i.e. reactors, capacitors and synchronous machines are used to
control the bus-bar voltage for improved power transfer and stability, A major
requirement of voltage control devices is to counteract voltage variation across the
supply network components. The supply network is mainly inductive and when power
is transmitted across the inter-connector, there will normally be a large reactive voltage
drop in the inter-connector. The magnitude of this voltage drop will depend on the
impedance of the inter-connector and on the power factor at which the power is
transmitted. This voltage drop may be accommodated in a number of ways. Assuming
that power is being transmitted from power station B to power station A, Figure 4.1:
. A voltage boost in the appropriate direction may be injected into the inter-
connector. This can be done either by an induction regulator or by a series
boosting-transformer, The series boosting transformer is now of less impoftance
due to the modern practice of incorporating on-load tap-changing gear in main
transformers, This, in effect, pedorms the same function as the series boosting-
transformer,
r05
. The secondary terminal voltages of the inter-connector transformers may be held
constant. The voltage drop in the inter-connector may be accommodated by
adjusting the relative phase of the voltages at the sending and receiving ends of
the inter-connector by means of a synchronous phase modifier. Synchronous
phase modifiers are only used on transmission links of some hundreds of kilometres
in length.
V = Vn.coS6+Vx'Sin6
Or: V = I.R.cos6+LX,sin6
Vp.cos 6 is the resistive voltage drop that is in phase with the load current. Vx.sin 6 is
the reactive voltage drop that is 90" out of phase with the load current. If the power
factor is leading, the reactive voltage drop is negative and in the opposite direction.
The ratio of the reactive voltage drop to the resistive voltage drop is larger than one
until a power factor of 0,98 is reached. In this case the ratio will be one. The
magnitude of the resistive voltage drop is larger than that of the reactive voltage drop
when the power factor is larger than 0.98. That means that, the lower the power
factor, the worse the voltage regulation.
r06
LR.cos 5
Regulation
I.X.sin 5
Bus-bar voltage
Generating sets are becoming increasingly large. Not only is the initial cost per kVA of
power stations of very large capacity lower than that of smaller power stations, but
their efficiencies are substantially higher. Hence, regardless of geographical position, it
is more economical to use these efficient power stations to full capacity twenty-four
hours a day and transmit energy considerable distances, than to use more and less
efficient local power stations. Therefore, the main base load met by these large power
stations, must be inter-connected so that they feed into the general system and not
into a particular load.
ro7
In an inter-connected network consisting essentially of loops, continuity of supply is
maintained, since substations can be fed from either direction.
,rrrr{
l',-*"nnector
Rotor phase winding
In Figure 4.4, the phasors OA, OB and OC represent the input values of the line-to-
neutral voltages of this inter-connector. The circles drawn at A, B and C of these
phasors, represent the loci of the rotor phase emfs as the rotor position is varied with
respect to the stator.
108
Figure 4.4
The phasors Aa, Bb and Cc in Figure 4.4 represent the voltage boosts introduced by
the induction regulator when the rotor position is such as to cause these voltage boosts
to lead on their respective line-to-neutral voltages by 90o, The phasors OA, OB and
OC represent the resultant voltages V. , Vo and V.. It will be seen that the induction
regulator has altered the phase of the voltages as well as introducing a voltage boost.
To eliminate this phase displacement, a double poly-phase induction regulator is
employed. Two rotors are assembled on a common shaft in the regulator, The
connection diagram for this regulator is shown in Figure 4.5. The rotor windings of
each regulator are connected in series with the inter-connector, The stator windings
are star-connected but the phase sequence of one regulator stator is reversed with
respect to the other.
The reversal of phase sequence to the stator of one regulator has the effect of
eliminating any phase displacement in the resultant voltage boost in the inter-
connector,
109
Thus, when the shaft of the double regulator is displaced, both rotors move by the
same angular amount. However, if the emf induced in one rotor leads its former value,
then the emf induced in the other rotor lags by the same amount, The reason for this
is that the rotating fields in the regulators rotate in opposite directions. It is often
convenient to reverse the functions of the stator and the rotor windings in induction
regulators used for boosting. The rotor then carries the primary winding. This has the
advantage of requiring only three connections to the rotor instead of six, and the inter-
connector current flows in the stator instead of the rotor,
Figure 4.6 shows a transformer having variable tappings in the secondary windinb, nt
the position of the tap is varied, the effective number of secondary turns is varied.
Hence, the emf and output voltage of the secondary winding can be altered. In supply
networks, however, tap changing has normally to be peformed on load. That is,
without causing an interruption to supply. The arrangement shown in Figure 4.6 is
unsuitable for this purpose.
If the tapping position is to be altered from position a to position b and the contact
with position a is broken before contact with position b is made, an open circuit results.
If, on the other hand, contact with position b is made before contact with position a is
broken, the coils connected between these two tapping points are short-circuited. The
coils will then carry damagingly heavy currents. In both cases, switching would be
accompanied by excessive arcing. The diagram in Figure 4.7 shows one type of an on-
load tap-changing transformer. With switch e closed, all the secondary turns are in
circuit. If the reactor short-circuiting switch is also closed, half the total current flows
through each half of the reactor. Since the current flow in each half of the reactor is in
opposition, no resultant flux is set up in the reactor and there is no inductive voltage
drop in the reactor. If it is now required to alter the tapping point to position d, the
reactor short-circuiting switch is opened, The load current now flows through one-half
of the reactor coil only so that a voltage drop occurs in the reactor, Switch d is now
closed, so that the coils between tapping point d and tapping point e are now
connected through the whole reactor winding, A circulating current will flow through
this local circuit. The value of this current is be limited by the reactor, Switch e is now
opened and the reactor short-circuiting switch is closed, thus completing the operation.
110
Reactor
Mid-point tap
Short-circuiting switch
Variation in the excitation of a synchronous motor alters the power factor at which the
motor works. As the excitation of the motor is increased, the power factor passes from
a lagging, through unity, to a leading power factor. This characteristic of the
synchronous motor is used to correct the power factor of loads taking a lagging
current, When it is used in this way, the motor always acts with a leading power factor
and is often referred to as a synchronous capacitor. When the synchronous motor
is used as a means of controlling the voltage of a transmission line, the name
synchronous phase modifier is usually preferred. The reason being that, in this
application, the machine may be adjusted to take either leading or lagging current.
The motor is connected in parallel with the load at the receiving end of the line. The
action of the synchronous phase modifier in controlling the voltage of a transmission
line is best understood by reference to the phasor diagram shown in Figure 4.8. For
simplicity, the phasor diagram shown is that of a short line where the effects of
capacitance are neglected.
It should be understood, however, that this method of control is mostly applied to long
lines where, with other methods of control, the voltage drop along the line would be
excessive.
111
]H
Figure 4.8
In Figure 4.8, OA represents the receiving-end voltage V',. OE represents the receiving-
end current, I,, lagging on the receiving-end voltage by phase angle $,1. OF and OG
represent the active and reactive componeflts (I3.s;u" and l,..u.s;u.) of the current,
respectively. AB represents the voltage drop I*7 caused by the active component of
current that leads V, by the phase angle of the tine impedan.u, *fon-'i+l'lZ is the
L l.R/l
line impedance. BC represents the voltage drop IB,Z caused by the reactive component
of current. BC is lagging I*7 by 90o since I, is lagging Iu by 90o when the load power
factor is lagging. In an unregulated line the sending-end voltage V,1, is the phasor sum
of Y,,Iu.Z and I,.2. If the sending-end and receiving-end voltages are now to be held
constant at the same value, then, line OD, representing the new value of the sending-
end voltage V52, Irust be at some point along the arc AD, whose centre is O and radius
is OD. If the same power is to be sent along the line as previously, the voltage drop
iu.Z will remain the same. The reason is that the active component of current must
remains the same,
'The synchronous phase modifier may therefore be used to control the voltage drop of a
rtransmission line. If the sending-end voltage is maintained constant, then the modifier
will be over-excited to take a leading current at the usual condition (on full-load at a
lagging power factor). If the line has been unregulated, the receiving-end voltage will
increase compared with its value. On no-load, on the other hand, the modifier would
be under-excited and would take a lagging current in order to offset the voltage rise
that occurs at the receiving en of a long unregulated line when the load is removed.
The power that may be sent along a transmission line is limited by either the power
loss in the line reaching its permissible maximum value, or by the voltage drop in the
line reaching the maximum value which can be conveniently dealt with. In long
transmission lines it is the voltage drop which limits the power that-can be sent. Thus,
if synchronous phase modifiers are used to regulate the voltage, the line can deal with
more power, Since voltage drop in the line and associated plant is not the first
consideration when synchronous phase modifiers are used to control the voltage,
current limiting reactors may be incorporated in the system to reduce the maximum
shott-circuit current should a fault occur, The principal disadvantage apart from cost of
using synchronous phase modifiers is the possibility of their breaking from synchronism
and causing an interruption to the supply.
113
4.7 AUTOMATIC LOAD DISPATCHING
In some systems a computer monitors the outputs and inter-connected loadings
continuously and automatically control the output of the power station and of each
plant within the power station. This compares the net transfer of power with the
scheduled transfer, Any difference between the scheduled and the actual power
transfer is called system requirement, which may be negative or positive. The function
of the computer is to determine the desired generation for each power station and to
send a signal to the power station. This signal will cause each station to work at the
desired outfiut. The difference between the actual and required output of a power
station is called the power station requirement. If each of the power stations is
delivered the required output for economical loading and the net power transfer over
the inter-connector is the scheduled value, both the system requirement and the sum
of the station requirement will be zero. When an increase of load on the system
occurs, the additional power will flow into the system through the inter-connector.
Power can basically flow from one point to another if there is a difference in voltage
between those two points. The potential difference causes active and reactive power
to flow between the two points. It can happen that P flows from a and that Q flows
from b. However, it can also happens that P is transferred from a while Q is
transferred to a. The potential difference between two points can be as a result of a
magnitude difference, as shown in Figure 4.9. It can also be as a result of a phase
difference, as shown in Figure 4.10.
Vau
V5 v"
The voltage V3s will cause a current flow between points a and b.
t--
The angle 6 is known as the load angle, Power will flow from the leading to the
lagging voltage.
Some standard formulas can be derived to calculate the power flow between two
points. It must be kept in mind that these standard formulas are actually based on the
principle of complex power. The positive and negative signs in Figure 4.11 show the
polarities during the positive cycle.
Figure 4.11
)
Machine A is the leading machine and machine B is the lagging machine. Consider the
"flow" of active power and reactive power of machine A in Figure 4.II. If the values of
the active power and reactive power are positive, it means that the direction of the
current flow is correct and that this machine will transfer active power and reactive
power. If these values were negative, it means that the direction of the current flow
will be in the opposite direction and that this machine will actually receive active power
and reactive power. The opposite will obviously happen to machine B in Figure 4,11.
These statements can be summarised as follows:
ft, E,t
115
If current Iu5 is considered, the voltage drop Vu5 is used. If current I6u is considered,
the voltage drop V5u is used, Consider the phasor diagrams in Figures 4.L3 and 4.14.
E6
Vuo-Eu+E5 = Q
,7
./\
=^/\
\"
E5
V56*E6-Et = 0
Vrj = Iij'Z
Vni = Vi1pt)-V:fonl
116
Ejl0
E16
Sl=Pu+iQu Si=Pn*iQu
will lag the voltage V; by an angte p ana ) will lag the voltage V; by an
angle B.
) as the load angle'
The angle between the voltages V; and V; is S' This angle is known
Figure 4.t6 shows a phasor diagram of these conditions'
Figure 4.16: Phasor diagram for the voltages and currents in the
inter-connected system shown in Figure 4'15
Pi = Vi.Iii.coS 0
Where: $ : angle between Vland I;1
Lt7
But I1i consists of the two components I; ( * ) anA I, 1) ). fnus:
P; = V1.Ii;.cos $
= Vi(Ii - I1)cos S
= Villi cos B - I; cos (B + 5)l
. = u'[]*"F - ]*"G.0)]
Also: Q; = V;,I11,sin $
= Vi(Ii - I;)sin Q
= n[+.*"(p-6) - ].*"ul
And: Qi = Vi[Ii sin (B - 6) - I; sin B)]
= u[].",n(B-6) - ].''"u]
From Figure 4.15 it can be seen that:
SI= Sjrro.o+ SI
Si=Silr,ouo-si
It is impodant to remember that these four formulas are derived under the following
assumptions:
. Vi is leading V;,
118
Ifphase values are used in the standard formulae, the complex power per phase is
obtained. If line values are used, the total complex power is obtained.
Example 4.1
Two power stations, A and B, work at BB kV and deliver power to their respective
consumers as follows:
4.IJ Use the complex power method to calculate the active and reactive power
received and transferred.
4.LZ Calculate the final loadings on the two power stations'
, V'(on) - vitonl
4.L.t
'z
t.. =
BBZB'_ BB
(5(t.zs + j5.6e)
= L,2L7ZL6.39o kA
Vi = BBzB" kV Vi = BBz0' kv
(1.25 + js.6e) o
119
j i. o,i
sI- J5.v', r;
= ( JE Xsazs ")(L.2r7 t-t6.39o)
L85.4962-8.390 MVA
s; = J5.v,.Ii
= ( J5 Xsezo
o)(r.2r7 t-L6.39o)
ta5.4962-16.390 MVA
4.1.2 Ja - sjrrouor * sl
= 720t35.02o + L85.4962-8.390
864'.208z.26.540 MVA
Sil= Slrro.or - Si
559.088256.O40 MVA
Example 4.2
Two power stations, A and B, supply individual loads of respectively 465 MVA at a
power factor of 0,8064 lagging and 395 MVA at a power factor of 0.715 lagging, The
two power stations are in phase at 96 kV. Power stations A and B are linked by an
inter-connector with an impedance of (1.63 + j6.72) ohms per line, The phase of the
inter-connector at power station A is advanced by means of a phase regulator, in order
to increase the real power load of the power station to"6qg"UW,
r20
Vi = 9626 kV V = 9620"kV
Pu = 600 MW
(1.63 + j6.74 a
c*
4.2.L Ja(loa0 - 465236.250
= (37s + j27s) MVA
o= Pa - Pa(toad)
600 - 375
225 MW
\t.2
Pi = *lcosp-cos(p +6)]
L
5- 9.80
9629,8
-T---E- 9620"
9.469294.90 kV
V:
Iu=
z
9.469294.9"
L8 + jdn
1.369218.530 kA
tzL
4.2.3 "
Qi= Str,nB-sin(B+s)l
z'
= 9g fsin 76.370 - sin (76.370 + 9,Bo)]
6.915 '
= -34.557 MVAr
tt.2
Pr=
.L *lcos (p - 6) - cos B]
= 215.876 MW
tt.2
Qi.L= *[sin(B-S)-sinB]
= 9g [sin (76.37o - 9.Bo) - sin 76.370]
6.915 '
= -72.357 MVAr
s]= S]rro.or* SI
= 465t36.25o + (225 - j34.557)
= 646.366221.8350 MVA
S; ^*
LL
Jb(loa0 - ^*
Jj
4.2.4 PU = 3.Ii .R
= (3X1.36e)11,63)
= 9.165 MW
r22
Example 4.3
Two three-phase generating power stations, A and B, are linked together through a
4B-kV inter-connector. Power station B supplies a load to its consumers of 375 MVA at
a power factor of 0.875 lagging. The impedance of the inter-connector is
(1.86 + j8.42) ohms per phase. The load on the generators at power station A is 1BB
MVA at a power factor of 0.86 lagging. The local load taken by consumers of power
station A is 131i5 MW.
4.3.1"Use standard formulae and calculate the phase difference between the voltages
of power station A and power station B.
4.3.2 Calculate the active power received by power station B.
4.3.3 Calculate the power factor of power station B.
4.3.4 Calculate the power factor of the load supplied to the consumers of power
station A.
Vi = 4BZ5 kV V: = 4820" kv
SI = lggz:0.68' MVA
(1.86 + j8.42) o
Pa(road) = 131.5 MW
Pi = Pa - Pa(load)
161.686 - 131.5
30.168 MW
r23
\/.2
Pi =
)tcosB-cos(B+s)l
30.168 = g* lcos77.54o - cos (77.s4o * a)l
8.623'
$= 6.560
tt2
D.-
4.3.2 rJ -
I t.or (P - 5) - cos Bl
g* -
=
8.623 'lcos (77.54o- 6.s6") cos77.54of
= 29.429 MW
lt.2
4.3.3 e;= I trin (B - s) - sin Bl
=
gf gin (77.54o - 6,s6o) - sin 77.5401
8.623'
= -8.294 MVAr
Jb- Silrrouo - si
= 375 t28.96 - (29.429 - j8.294)
= 35392L232.440 MVA
tt.2
4.3.4 Qr =
I ttin B - sin (B + 5)l
g* lsin77.54o - sin (77.s4 + 6,s6")l
8.523'
- 4.878 MVAr
c* - sltrorot
Ja - * sl
188230.68' = Slrro.o + (30.168 - j4.B7B)
c-
Ja(load) - 465.705237.470 MVA
724
COS $21636; = COS 37.470
= 0.794lagging
Example 4.4
Two power stations, A and B, are in phase at 132 kV. These power stations supply 840
MVA at a power factor of 0.791 lagging. An inter-connector with an impedance of
12.61860 ohms per phase, links station A with station By means of a phase B.
regulator at B, the phase of the inter-connector at B is advanced so that station A
receives 221.3 MW from station B.
4.4.L Use standard formulae and calculate the angle of advance at power station B.
4.4.2 Calculate the final loading on each power station when the load is divided
equally between the two stations.
v?
4.4.L Pi= [cor (P - 5) - cos B]
I
227.3 = ryLfcos
L2.6
(86" - b) - cos 86.]
5- 9.2850
4.4.2 Qi =
$tr'no-sin(B+s)l
Wlsin
12.6
86. - sin (86. + 9.285.)l
2.51 MVAr
D.-
rl-
I ti'B - cos (B + s)l
= Wfcos
12.6
86" - cos (86. + 9.285.)]
223.838 MW
v,2
trin (P - s) -
Q= f sin Bl
ryLfsin
12.6
(86" - 9.28s") - sin 86"]
= - 33.638 MVAr
r25
c-,. q-
Ja - "a(load) -
= 420t37.72o -(22r.3 - j33.638)
3tt.o46269.120 MVA
Sil= slrrouo + sl
420237.72o + (223.838 + j2.51)
= 6L3.6r9t25.010 MVA
Example 4.5
Two power stations, A and B, work at I3ZltB" kV and L32lI2" kV respectively. The
two power stations are connected via an inter-connector with an impedance of
7.5275" o/line, The power stations supply their separate consumers as follow:
r32lIB" t32zr2
=
J: J:
7.9772LO5" kV
VU I,:.7
Sl= JgVIi
(Ji Gzz ztB " X 1.06362-30' )
243.L722-12" MVA
126
''. / Pi = 237.858 MW
And: Qi = - 50.558 MVAr
si = Js v, ri
(i ztz" )(L.0636 t-30'
Gsz )
= 243.!721-18'MVA
D.=
.J 23r.27 MW
And: Qi = -75.L44 MVAr
750t48" + 243.L72t-12"
896.667234.42" MVA
5b= ^*
Su(toao - ^*
5j
O.7855lagging
O.2972lagging
4.5.3 Pi = Pa - Pa(toad)
= 690 - 501,848
= 188.152 MW
tt2
D- + s)l
ll -
I t.or P - cos (P
l-r.-.r21
188.152 = I t"? |lcos zs'- cos (75" + s)l
l7.s I'
f= 4.76'
r27
Power station B should be operating at:
rB'-4.76" = L3.24'
Example 4.6
Two power stations A and B are synchronised at BB kV, Power station A delivers
424 MVA to its consumers at a power factor of 0.7L93 lagging. The final loading on
power stati6n B is 545139" MVA, The two power stations are inter-connected by a
transmission line with a resistance of 2.4 o and an inductive reactance of 7.6 o. The
excitation voltage of the generator at power station A is increased with 5.6820/o and the
input power to the generator is changed as such that the load anqle - is 72.5oh of the
phase'impedance angle. c
4.6.r Use standard formulae and calculate the final loading on power station A.
4.6.2 Calculate theggpg***.rumco._.El.l"gXp,,Syr1gl that can be delivered to the congume15
at power station B. --'-
4.6.3 Calculate the total reactive power absorbed by the transmission line.
1-
4.6.1 z-- 2.4 + j7.6
= 7.97272,47" A
$= !2.5o/o x 72.47"
9.06'
D.-
lt - ''z
v'[!,cosp-Scos(B+5)]
z
tt
[#) *'
os(72.47')- (72.47'+ e,06")]
[[ #).
= 175.52 MW
V. V.
Qi = vif
7f
.sin P -; sin (B + s)]
e3
= g3lI )rinrzz.47.\-i
* )r,n o2.47"-e.06")
L\7.e7) \7.e7) ')
I
= 19.145 MVA'r
128
sjrrouo r si
= 424t44o +(175.62 + j19.146)
573.926.133.130 MVA
4.6.2 R= vit
f ,.o, (B - 5) -) cos ot
q= \/..sin (B - s) v sin
vit
f - ;f 01
tt
[(#)'
in(72.47"- e.06') -
[#),''"
rr.o, tf
- 8.277 MVA'r
5b silrro.o - sl
4.6.3 eu = Qi-Q
= 79.146 + 8.277
= 27.423 MVA'r
Example 4.7
t29
4.7.L Usg standard formulae and calculate the percentage tap changing of the tap-
changing transformer at power station B.
4.7.2 Calculate the final loadings on both power stations.
4.7.3 Calculate the power factor at both power stations.
4.7.4 Calculate the percentage power factor improvement on the load of power
station B,
Vi =
-ut.6t-+ac
2a
8.462!@
=
(zxo.oe6)
8.462+9.28
0.t92
= 92.45 kV
o/o taP =
V -vi
vj
92,45 - BB
=
BB
5.O57o/o
\/.
D-
4.7.2 lt- *.cos
L
B(Vi- Vi)
= i'?'.9lf*s
\10,198 r'
78.6e")(e2,4s - BB)
7.912 MW
130
V.
Pj.L = j.cos F(Vi- Vi)
/ ss-- \.l(cos 78.69'X92.45 - BB)
= I( 10.1s8 /'
= 7.531 MW
V.
q.L= j.sin F(V,- Vi)
Sl=Slrro.o-Sl
= 66At5f - (7.531 + j37.654)
= 626,2522.49.37" MVA
sil= Sirro.o+ sl
= 325136 + (7.9t2 + j38,2)
= 354.827140.24" MVA
= 5.987o/o
131
EXERCISE 4
1. Two power stations, A and B, work at BB kV and deliver power to their separate consumers
as follow:
An inter-connector with an impedance of Z = 7.25177" ohms per line joins power station A
with power station B, The voltage at A is advanced with an angle of 9.3o with respect to
the voltage of B.
1.1 Use the complex power method and calculate the active power and reactive power
received and transferred.
1.v Write down the final distribution of active and reactive power between the two power
stations.
1.3 Calculate the final power factor at the generators of each power station.
2. Two power stations, A and B, which are in phase at 132 kV, supply 650 MVA at a power
factor of 0.9063 lagging. An inter-connector with an impedance of (1.45 + j8,35) ohms
per line, links station A with station B. By means of a phase regulator at B, the phase of
the inter-connector at B is advanced in order that station A receives 242 MW from station
B. Use standard formulae to solve the following questions.
2.1 Calculate the angle of advance at power station B.
2.2 Calculate the final loading on each power station when the load is divided equally between
the two stations.
2.3 Calculate the active power loss in the inter-connector.
3, Two power stations, A and B, work at 66 kV and deliver power to their separate consumers
as follow:
3.1 Use the complex power method and calculate the power and reactive power received and
transferred through the inter-connector.
3.2 Calculate the final loading on each of the two stations.
3.3 Calculate the power factor of the inter-connector.
3.4 Calculate the active power loss in the inter-connector.
r3z
4. Two power stations, A and B, which are in phase at BB kV, supply respective loads of
452.25 MVA at an inductive power factor of 0.7071 and 545.25 MVA at a lagging power
factor of 0,88295. An inter-connector with an impedance of 2.45274" ohms per line, links
station A with station B. By means of a phase regulator at A, the phase angle of the
voltage at A is advanced in order to increase the loading of station A to 715 MW.
4,1 Use standard formulae and calculate the angle of advance at power station A.
4.2 Calculate the transmission line power loss.
5. Two power stations, A and B, are linked by means of an inter-connector and transformers
having a combined impedance of (2.43L + jI3.7B7) ohms per line. The station voltages are
equal at 132 kV. Individual loads on stations A and B are 125 MVA at a lagging power
factor of 0.743I and 145 MVA at a lagging power factor of 0,8387 respectively. A
synchronous phase modifier is used to advanced the phase angle at A in order to tranfer
75 MW from A to B.
6, Two three-phase power stations, A and B, are connected by a 66-kV inter-connector with
an impedance of (1.96 + j9.57) ohms per phase. The total load on the generators at A is
5B.B MW ht a lagging power factor of 0.8. The local load connected directly to the bus-bar
of A is 39.3 MW at a lagging power factor of 0.707L. Power station B delivers 42,8 MVA at
a power factor of 0.6 lagging to its consumers.
6.i Use standard formulae and calculate the phase difference between the voltages of stations
A and B,
6,2 Calculate the load, in MW, received by station B from station A.
6.3 Calculate the power factor of station B.
7. Two power stations, A and B, which are in phase at BB kV, supply 540 MVA at a power
factor of 0.8071 lagging and 450 MVA at a power factor of 0.71 lagging. An inter-connector
with an impedance of (1.351 + j10.398) ohms per phase, links station A with station B. By
means of a phase regulator at station B, the phase of the inter-connector at B is advanced,
This causes the loading of station B to increase by 215 MW.
133
B. The voltage of two power stations, A and B, is in phase at 132 kV. Power station A supply
loads with a rating of 720 MVA at a lagging power factor of 0.673. Power station B supplies
loads with a rating of 650 MVA at a lagging power factor of 0.798. The two power stations
are now connected through an inter-connector with an impedance of (1.288 + j12.455)
ohms per phase. The phase of the voltage at power station A is now changed so that the
total active power supplied by this power station increases to 750 MW.
8,1 Use standard formulae and calculate the change in phase angle of the voltage at power
station A.
8,2 Calculate the pbwer loss in the inter-connector.
8.3 Calculate the current flow through the inter-connector.
8.4 Calculate the total complex power supplied by each power station,
9. Two power stations, A and B, operate at 72 kY and deliver power to their respective
consumers as follows:
These two- power stations are joined with an inter-connector with an impedance of
(0.936 + j8.956) o/line. The voltage of power station A is advanced with an angle of 72o
lvith respect to the voltage of power station B.
-4,1 Use the complex power method and calculate the power and reactive power received and
tra nsferred th rough the inter-connector,
9.2 Calculate the power and reactive power absorbed by the inter-connector.
9.3 Calculate the final loading on each of the two power stations.
10. Two power stations, A and B, deliver power to their respective consumers of 408 MVA at a
power factor of 0.22495 lagging and 376 MVA at a power factor of 0.6018 lagging. A
current of 7045216.625" A flows through an inter-connector between the two power
stations, while a voltage of 6425293.625" V is measured across the inter-connector. The
voltage at power station A is advanced to deliver power through the inter-connector to
power station B. The power on the generators at power station A is given as 448 MVA at a
power factor of 0.559 lagging.
134
Two power stations, A and B, supply loads of 184 MVA at a power factor of O.7O7I lagging
ffi and 196 MVA at a power factor of 0.82 lagging respectively. The two power stations work
in phase at 66 kV. An inter-connector with an impedance of 3.9l\2o ohms per phase, link
the two power stations. The voltage at power station B is increasedtoT4 kV in order that
power station A receives 175 MW from power station B,
11.1Use the complex power method and calculate the final loading on each power station.
11.2 Use standard formulae and calculate the active and reactive power send by power
station B.
12. Two power stations, A and B, supply a load of 378 MVA at a power factor of 0.766 lagging.
The two power stations work in phase at 66 kV. An inter-connector with an impedance of
3.9z&2o ohms per phase, links the two power stations, The voltage at power station B is
increased to 69 kV to send 175 MW to power station A.
12.1Use the complex power method and calculate the final loading on each power station if the
load is divided equally between the two power stations,
12,2 Use standard formulae and.calculate the active power loss in the inter-connector.
13. Two powerstations, A and B, are in phase and supply the following loads:
An inter-connector with an impedance of (0.61 + j6.97) ohms per line, links power
station A with power station B. By means of a phase regulator at power station A, the
phase of the inter-connector at this station is advanced by 29.2L'to increase its loading to
1070 MVA at a power factor of 0.788 lagging.
14. Two power stations A and B, are synchronised at 132 KV. The loading on the generators
of power station A is 820 MVA at a power factor of 0,809 lagging. Power station B delivers
640 MVA at a power factor of 0.7547 lagging to its consumers. The two power stations are
inter-connected by a transmission line with a resistance of 1.35 e and an inductive
reactance of 6.35 A. The excitation voltage of the generator at power station B is
increased with 3.03olo and the input power to the generators at power station B is changed
as such that the load angle at power station B is 10.9olo of the transmission line impedance
angle.
14.1use standard formulae and calculate the final loading on power station B.
14'2 Calculate the maximum complex power that can be delivered to the consumers at power
station A.
14.3 calculate the total reactive power absorbed by the transmission line,
135
15. Two power stations A and B, which are in phase at 132 kV, are inter-connected by means
of a 72 km aluminium transmission line with an effective conductor diameter of 25 mm.
Power station A delivers 450 MVA to its consumers at a power factor of 0.7193 lagging.
Power station B delivers 245 MW to its consumers at a power factor of 0.809 lagging. The
voltage at power station B is delayed by 6' with respect to the voltage at power station A.
The resistance yalue of the line is 25olo of the reactance value of the line. The resistivity of
the aluminium is 0.0285 pO.m, Use standard formulae:
16. Two power stations A and B work at 8826' kV and 66275" kV respectively to supply their
separate customers as follow:
16,1Calculate the total active and reactive power delivered or received at each bus bar.
16.2 Calculate the active and reactive power loss in the inter-connector,
16.3 Calculate the final active and reactive power loadings on each power station.
16.4If the phase-regulator at power station A is adjusted such to reduce the loading at power
station A by 75 MW, calculate the operating angle of power station A.
r-1'!
17, Two power stations supply loads to their separate consumers as follow:
17.1 Calcutate the percentage tap changing of the transformer at power station B.
17,2Calculate the final loading on both power stations.
17.3Calculate the final power factor of both power stations,
17.4Calculate the active and reactive power loss in the inter-connector,
17.5The percentage power factor improvement of power station A,
18, Two power stations supply loads to their separate consumers as follow:
The two power stations are inter-connected with an overhead aluminium transmission line
of 84.4 km with an effective diameter of 32 mm. The two power stations are in phase at
BB kV. The voltage at power station B is delayed by 5% with respect to the voltage at
power station A. The value of the resistance of the transmission line is 25olo of its inductive
reactance value. The resistivity of aluminium is 0.0284 pQ.m.
18.1Use the complex power method and calculate the final loading on power station B.
18.2 Use standard formulae and calculate the percentage power factor change of the loading on
power station A.
18.3 Calculate the active and reactive power loss in the inter-connector.
19. Two three-phase power stations A and B, are in phase at a voltage of BB kV. The two
power stations are linked by a transmission line with an impedance of B.IZB2'O/line. The
power stations supply power to two separate systems as follow:
A synchronous phase modifier is used at power station A to increase the active power on
this power station to 42A MW while the demands from the consumers stay the same,
19.1Use standard formulae and calculate the value of the load angle at power station A.
19'2 Use the complex power method and calculate the final loadings on the two power stations.
r37
20, Two three-phase power stations A and B, are in phase and supply power to two separate
systems at 132 kV. The loads are:
The voltage at power station A is delayed to transfer active power to the power station by
means of an inter-connector with an impedance of L2lB2' filline. The power loss in the
inter-connectoris 3.9 MW. Use standard formulae:
21. Two power stations A and B work at BBZ5' kV and BBzl2 kV respectively to supply their
separate customers as follow:
21.1Calculate the totalactive and reactive power delivered or received at each bus bar.
21.2 Calculate the active and reactive power loss in the inter-connector.
21.3 Calculate the final active and reactive power loadings on each power station.
2L.4If the phase-regulator at power station B is adjusted such to reduce the loading at power
station B by 45 MW, calculate the operating angle of power station B.
22. Two power stations, A and B, which are in phase at 132 kV, supply 720 MVA at a power
factor of 0.707t lagging. A transmission line with an impedance of BAZB2" o/phase link
the two power stations. By means of a phase regulator at power station B, the phase of
the inter-connector at power station B is advanced such that power station A receives
124 MW from power station B.
The loads to the consumers remain the same. Use
standard formulae:
138
CHAPTER FIVE
POWER ECONOMICS
5.1 INTRODUCTION
The objectin the design and operation of a power station is to generate electric energy
safely, efficiently and economically. The economical success of any electricity company
depends on the economic viability and reliability of the supply. The supply and demand
of electrical energy is very different from any other product produced to be sold to
consumers. Electrical energy has to be supplied on the time that it is demanded by
consumers. There is no simple storage system that can be used to supply additional
energy during peak time demands. This is a unique situation end necessitates the
production of sufficient electrical energy to meet the demand of consumers at any time.
This means that accurate forecasting of load requirements at various given times must
be maintained in order to recommend the necessary power output for a certain time of
the day, week, month or year.
The maximum demands of various consumers are not likely to occur all at the same
time. This means the maximum demand on the power station is always much less than
the sum of the maximum demands of the various consumers. The diversity factor is
therefore:
This ratio is always higher than one and should be as high as possible. This factor can
be increased by offering tariff incentives to consumers using energy during off-peak
times.
139
5.2.2 ENCOURAGEMENT OF POWER FACTOR CORRECTION
A power station should ideally supply power at full load, but for technical and
economical reasons this is not achieved. The load is therefore not constant for the
whole year. A measure of the effective use of a power station over an arbitrary period
of time is required and this is called the load factor. It can be defined in terms of
power as:
anualoutputin kW- h
ko=
max imum possible anauloutputin kW- h
anual energy converted
(in stalled kW capacity )(n umber of ho u rs in one year)
The rms and average values of the annual load curue can be found in the usual way
and should not be confused with the sinusoidal waveform of the load current. The
form factor can be found by the equation:
,l+ru"
When using Kelvin's Law to find the most economical c.s.a. (cross-sectional area) of a
transmission line, the rms value of the annual load curve is used. This can be found by
multiplying the maximum value of the load current per annum by the load and form
factors, since:
-
s.2.4 LOSS FACTOR
The loss factor for a transmission system consists of the following ratio:
The loss factor differs from the load factor as the copper losses vary as the square of
the load current. There are, however, losses that are independent of the load current.
This can be dielectric losses in cables or iron losses in transformers. These losses
increase the value of the overall loss factor when combined with the copper losses.
Since the loss factor differs from the load factor, the cost of transmitting each kW-h
varies with load in a different way from the cost of generating each kW-h.
The c.s,a. of a distributor is generally determined by the maximum voltage drop that
can be tolerated. In the case of feeders and transmission lines, the initial cost and the
cost of energy loss are more important, The larger the c.s.a., the higher the initial cost
but the lower the energy loss, The initial cost on a complete transmission line
comprises:
. The cost of the conductor itself and is directly proportional to the c.s.a, of the
conductor.
. The cost of towers, insulators and erection of the overhead lines, or in the case of
underground cables, the cost of insulation, laying and jointing of the conductors.
These costs depend to some extend on the conductor c,s.a. but are considered
constant when deriving Kelvin's Law.
L47
5.4 KELVIN'S LAW
the most economical c.s.a. of a conductor is that which
Kelvin's Law states that
makes the annual cost of the energy losses equal to the annual interest and
depreciation charges on the initial cost of the conductor material only.
C=Cr*Cz
Where: c: total annual cost of operating the transmission line
Cr= total annual interest and depreciation charges
Cz= annual cost of energy losses
Cr=P.A+Q
Where: P = constant that depends on the cost per unit volume of the
conductor material used
A= the conductor in cm2
rTrost economical c.s.a. of
Q= constant that depends on the cost of the towers, insulators
and erection
Both the constants P and Q also depend on the interest rate and depreciation charges,
Ignoring leakage resistance, dielectric losses and corona, the annual cost of energy loss
is directly proportional to 12.R.t. I is the load current, R the conductor resistance and t
the time that the current is flowing. Since R is directly proporiional to A:
dc
For C to be a minimum, = 0. Hence:
dA
P- {A2 = o
And: P.A= !
A
L42
5.4.1 LIMITATIONS TO THE APPLICATION OF KELVIN'S LAW
. Kelvin's Law is derived on the assumption that the cost of towers, insulators and
erection are independent of conductor c.s.a. In practice, the cost of these items
increases with conductor c.s.a.
. In the case of very high voltage, steel-cored aluminium overhead lines, the cost of
the conductor material is not a major paft of the initial cost.
. In deriving Kelvin's Law, only the copper losses are considered. At the higher
voltages, corona losses may be comparable with the copper losses.
. When applying the law to underground cables, the c.s.a. obtained may be too small
because dielectric losses are ignored and heat dissipation is more difficult.
. The c.s,a, obtained using the law is based on financial considerations and must be
checked for current densityT voltage drop, corona and mechanical strength.
In general, Kelvin's Law is most useful up to 33-kV lines, However, the concept of
economic current density is sometimes worth considering for higher voltages, The
curve of total cost against conductor c.s.a. is usually very flat near the minimum point,
as shown in Figure 5.1. Therefore, an error of the order of 20olo either way does not
usually make much difference to total annual operating costs. For an impoftant line, at
least two standard conductor sizes on either side of the most economical c.s.a. can be
used to calculate the total annual costs for each, including towers, insulators and
erection.
r43
Total cost (C)
(a
F
a
o
(J
J
Cost cr c.s.a. (P.A)
f
zz.
Constant cost (Q)
t44
5.4.3 GENERATING COSTS
The annual cost of running a steam power station may be divided into the following:
. Fixed costs that is independent of the maximum power and annual energy outputs
and is pat of the cost of the central administrative organization and the capital cost
of the station site.
. Costs which is directly proportional to the annual energy output and is mainly that
of fuel and water.
Since the first two costs are independent of the number of kW-h generated per annum/
these costs are called the standing charges and the last cost is called the running
I
charge. It is difficult to separate these charges precisely. For example, the cost of
maintenance does paftly depend on the kW-h generated per annum. The greater the
load factor, the lower is the cost of each kW-h because the standing charges will be
distributed over more units. In the case of a hydro-electric station, the capital costs are
very high and the running costs are very low. In order to keep down the cost per
kw-h, it is therefore even more important to maintain a high load factor than it is for a
steam station.
Static capacitors and synchronous condensers also have an annual cost charge.
Therefore, as the cost of the maximum demand charge is reduced, the annual cost of
the capacitors or condensers is increased.
C
sin 0 =
A
145
5.6 TARIFFS
. Agricultural
. Combined premises
. Commercial
Domestic premises
Industrial
. Off-peak
2. It applies to electrical energy supplied to any premises during ceftain times of the
day and night. It consists of a kW-h charge lower than (1) plus a fixed quarterly
charge.
145
Example 5.1
A 120-MW power station delivers 120 MW for three hours and 60 MW for nine hours
and is shut off for the rest of the day. The station is shut down for maintenance for
45 days of each year. Calculate the annual load factor of the power station,
anualoutputin kW- h
Load factor =
max imum possible anauloutputin kW- h
(120 x 103X3X36s - 4s) + (60 x 103X9X36s - 4s)
(120x103X365"24)
= O.274
Example 5.2
Electrical energy costs 68.4 c/kW-h and the total interest and depreciation charges is
I2o/o. The copper conductor has a cross-sectional area of 12 mmz and costs R34.50
per kilogram. The copper has a density of 8860 kg/m3 and the resistance of one
kilometre of single conductor is 0.I77 filkm.
2.4 MVA: Ir = -S
J:.v'
2.4xl}6
(6xgs x 103)
= 41.989 A
L47
Energy loss = 12.R.t
( o.vt 10-3 )
"
(41.e8e)'zI A
Jtroool
499,303
kw_h
A
S
1.8 MVA: Ir=
Js.v,
- 1.8 x 106
31.492 A
o.LA
m=:--
10b
(BB6oX1o3 x 1O2XA)
= 106
= 88G(A) k9
557.647
(3668.04XA) =
A
A_
F\- O.3899 cm2
I4B
. TE.d2
5.2.2 /-\-
4
n'dz
0.3899 = 4
d = 0.7O5 cm
5.2.3 r-t A
= 4r.989
0.3899
= 107.692 Alcm2
=
X (36sxr4)
= 22.9305 A
L4.14
k,=
41-989
0.33675
, 22.9305
' 74.74
= L.622
Example 5.3
149
Consider one kilometre of single conductor:
-S
Js.v.
1.5 x 106
(J5Xsr x 103)
= 26,243 A
,
Rms value of the load per annum
= (26.243)(0.s8X1,11)
= 16.743 A
Annual energy loss = I2.R.t
(o.tat * 1o-3 )
= (16.743)2[ n )rzos>rz+l
= 444,477
.A kw-h
150
Example 5.4
300 kVA at a power factor of 0.809 lagging for eight hours per day
120 kVA at a power factor of 0.866 lagging for eight hours per day
75 kVA at unity power factor for eight hours per day
For the remaining time of the year the load varies as follows:
. 90 kVA at a power factor of 0.809 lagging for eight hours per day
o 25 kVA at a power factor of 0.866 lagging for eight hours per day
r No load for eight hours per day
5.4.3 Calculate the total annual running cost of each transformer. The cost of
electrical energy is 75c/kW-h and the annual interest and depreciation charges
are L2o/o.
5.4.4 Calculate the annual lost factor for each transformer.
151
r33.767
kl=
300
o.446
168.3715
k/=
133.767
1.259
5.4.2 Transformer A:
Full-load efficiency = 1-
(300X0.809) + 7
= o.9727
Transformer B:
Ful-toaderriciency - 1- Cm119*#r+e,
= O.9731
Transformer A Transformer B
Copper loss at 300 kVA (s.6XB) = 44.8 kW-h (4.2X8) = 33.6 kw-h
/ rzo \2
Copper loss at 120 kVA t-l
\300/
(s.6XB) = 7.168 kW-h flq)'
\300 /
(4.2X8) = 5.376 kW-h
( ts\2
Copper loss at 75 kVA t-l
\300 /
(s'6XB) = 2'B kw-h (#)' (4.2X8) = 2.1 kw-h
r52
Transformer A:
BB,368
All-day efficienry 1- 3372.96 + 88.368
o.9745
Transformer B:
Transformer A Transformer B
(zs\2
Copper loss at 25 kVA t-l
\300/
(s.6XB) = 0.311kW-h
[#)'
(4.2X8) = 0.233 kW-h
Transformer A:
37.9+3
All-day efficiency 1-
755.68 +37.913
o.9522
Transformer B:
63.257
All-daY efficiencY = 1-
755.68 +63.257
= o.9228
153
Transformer A Transformer B
27716.07 33489.03
1 1
All-year elficiency 995575 .2 + 27716.07 995575 .2 + 33489.03
= O.9729 = 0.9675
5.4.3
Transformer A Transformer B
5.4.4 Transformer A:
= 1.764 kW
L.7& +1.4
Overall loss factor =
1.4 + 5.6
= o.452
154
Transformer B:
(36sX24)
= 2.5 kW
r'323 +2'5
overall loss factor = 2.5 + 4.2
= O.571
Example 5.5
5.5.1 Use the following tariff and calculate the monthly cost:
The first 200 kw-h per kVA of maximum demand in the month 75clkW-h
The next 200 kw-h per kVA of maximum demand in the month 65c/kW-h
Additional kW-h supplied 55c/kW-h
5'5'2 The consumer now improves the power factor of the main load to 0.9455
lagging using loss-free static capacitors with a cost of R1200.00 per month,
Calculate the monthly saving due to this action.
155
5.5.1 For maximum demand:
P = S,cos 0
2250 = (SX0.809)
S = 2781.211 kVA
P = S.cos 0
2250 = (SX0,9455)
S = 2379.693 kVA
156
Total cost = R24642.24 + R368953.86 + R1200
R394795.10
Example 5.6
5.6.1 Calculate the kVA'r rating of loss-free static capacitors required for constant kW
correction to 0,9455 lagging ,
5.6.2 Calculate the kVA'r rating of a synchronous motor required for constant kVA
correction to 0.9455 lagging.
/l
Figure 5.2
L57
After correction: P_ S,cos $
= (746.733)(0.94ss)
706.036 kW (ad in Figure 5,2)
Before correction:
After correction:
c.
Jlaggrng - (746.733)(cos {2)
= (746.733)(sin 19o)
243.1125 kVA (G in Figure 5.2)
Example 5.7
A load with a maximum demand of 750 kVA at a power factor of 0.707I lagging is to
be improved to the most economical power factor. The annual tariff is R35.09 per kVA
and the annual interest and depreciation charges is 12% total. The initial cost of the
loss-free static capacitors is R100.00 per kVA'r.
5.7.r c- (100x0.12)
= R12.00
158
C
sin e
A
LZ
35,09
0.342
e 200
cos e 0.9397lagging
5.7.2 P S.cos 0r
(7s0x0.707)
530.25 kW
159
i
EXERCISE 5
1, A load has a maximum demand of 770 kVA at a power factor 0,7 lagging. The power
factor is improved by connecting a 407 kVA'r static capacitor in parallel with the load,
The capacitor losses are 5.5 W/kVA'r, This capacitor is permanently connected to the
supply, Electrical energy costs 83,3 c/kW-h. The annual tariff is R105.00 per kVA
maximum demand and the annual interest and depreciation costs are R5555.00.
2. A load of 120 kVA has a power factor of 0.7 lagging. An additional motor load of 24 kW
that includes the losses, is added to the existing load. The new load can either be:
2.t An induction motor fitted with loss-free capacitors to improve the power factor from
0.809 to 0.95 lagging, The motor costs R2000.00 and the capcitors cost R50.00/kVA.
2.2 A synchronous in duction motor, costing R100.00/kVA, that can be excited so that the
overall total kVA-load remains the same as before the extension of the load.
The tariff is R40,00 per kVA maximum demand plus 62.4clkW-h. The annual interest
and depreciation charge is 10% for Question 2.L and I2o/o for Question 2.2. The load
remains constant for 150 days and zero for the remainder of the year.
Static capacitors are now connected to to the load end to improve this power factor to
0.9455 lagging. The annual interest and depreciation cost is l2o/o.
160
A cetain load varies as follows for 248 dTER SIX
270 kVA at a power factor of 0.809 lagg
96 kVA at a power factor of o.7O7L tagglT SYSTEMS
60 kVA at a power factor of 0.9455 lagg
le
6
163
5, A ceftain load varies as follows for 248 days per annum:
270 kVA at a power factor of 0.809 lagging for eight hours per day
96 kVA at a power factor of 0.707L lagging for eight hours per day
60 kVA at a power factor of 0.9455 lagging for eight hours per day
For the remaining time of the year the load varies as follows:
72kVA at a power factor of 0.809 lagging for eight hours per day
20 kVA at a power factor of 0.707I lagging for eight hours per day
No load for eight hours per day
5.3 Calculate the total annual running cost of each transformer. The cost of electrical energy
is R0.72/kW-h and the annual interest and depreciation charges are 10olo.
5.4 Calculate the annual lost factor for each transformer.
6. A 66-kV, transmission line transmits a three-phase, balanced load that varies throughout
the year as follows:
The total interest and depreciation charges is l0o/o and electrical energy costs
R0.7llkw-h and. The copper conductor has a cross-sectional area of 10 mm2 and costs
R52.40/kg. The copper has a density of 8.9 Mg/mt and the resistance of one kilometre
of single conductor is 178 ma/km,
161
7. A sub-station transformer supplies 1.2 MW at a power factor of 0.707I lagging.
7.L Calculate the kVA'r rating of loss-free static capacitors required for constant kW
correction to 0.9563 lagging ,
7.2 Calculate the kVA'r rating of a synchronous motor required for constant kVA correction to
0.9563 lagging.
B. An industrial consumer has a constant load of 1800 kW at a power factor of 0,8 lagging
for eight hours per day for 25 days in a month of 30 days. For the remaining time there
is a constantload of 180 kW at a power factor 0.9 lagging.
8,1 Use the following tariff and calculate the monthly cost:
The first 200 kw-h per kVA of maximum demand in the month 69c/kW-h
The next 200 kw-h per kVA of maximum demand in the month 6lc/kW-h
Additional kW-h supplied 52clkW-h
8.2 The consumer now improves the power factor of the main load to 0.96 lagging using
loss-free static capacitors with a cost of R1310.00 per month. Calculate the monthly
saving due to this action.
9, A load with a maximum demand of 600 kVA at a power factor of 0.8 lagging is to be
improved to the most economical power factor. The annual tariff is R40,00 per kVA and
the annual interest and depreciation charges is 10olo total. The initial cost of the loss-free
static capacitors is R110,00 per kVA'r.
152
CHAPTER SIX
PER.UNIT SYSTEMS
6.1 INTRODUCTION
Answers to problems pertaining to electrical power systems are almost always required
in terms of volts, amperes, ohms and kVA. In the process of computation, it is more
convenient to express voltage, current, impedance and power in terms of percent or
per unit, of a selected base or reference value of each of these quantities. The per-
unit value of any quantity is defined as the ratio of the quantity to its base value
expressed as a decimal. The ratio in percent is 100 times the value in per unit. The
electrical characteristics of machines are usually specified by the designers and
manufacturers in terms of percent or per unit.
Any attempt to mathematically model the power system is heavily dependent on circuit
concepts. The fact that power systems are three-phase, is a major complication.
Another important complicating factor is the large number of components. Typical
systems can consist of tens of generators and hundreds of transmission lines and
transformers. Another factor to consider is that transformers distribute the system into
many different voltage sections. These methods of representation must therefore
particularly deal with these factors. Their complicating effects have to be minimised as
much as possible. The basic picture of the power system is the one line diagram, The'
diagram communicates the essential interconnection information with maximum
simplicity, The per-phase equivalent circuit takes advantage of the symmetry inherent
in balanced three-phase circuits, The per-unit system simplifies numerical analysis and
eliminates the paftitioning effect of transformers. All these representations are very
useful in displaying and formulating power system problems.
6.2 PER-UNTTQUANTTTTES
The per-unit system is similar to the percentage system except that all quantities are
expressed as decimal fractions instead of percentages. The base quantities then have
the value of unity (one per unit) instead of 100o/o. It is necessary for power system
engineers to become familiar with and facile in the use of the system because of its
wide industrial acceptance and use. They also take advantage of its analytical
simplifications. Any quantity can be expressed on a per unit base by the equation:
actualvalue
Per unit value =
base value
163
The actual value is the actual value of the voltage, current, power or impedance as it
appears in the power system. The new base value is determined and is usually the
value that leads to confusion in the early stages of applying the per unit system,
To help prevent this confusion, it will help to remember the following rules;
The value of Sno is the same for the entire system concerned once it's been chosen.
The ratio of the voltage bases on either side of a transformer selected, to the same
as the rbtio of the transformer voltage ratings.
The value of Vn5 is a chosen value, but will vary from one zone to another zone,
Once these rules are obeyed, all other base values are related to the power quantities
chosen as base values. This means that the usual electrical laws, as they are known,
still applies. Voltage, current, impedance and power are so related that the selection of
base values for any two of them determines the base values of the remaining two. The
base impedance is that impedance which will have a voltage drop across it equal to the
base voltage when the current flowing in the impedance is equal to the base value of
the current. The base apparent power in single-phase systems is the product of the
base voltage and the base current. Base voltage and base apparent powers are the
quantities usually selected to specify the base.
The actual value is also a value in volts, amperes, ohms, etc. In a power system, a
base power and voltage are selected at a specific point in the system, A transformer
has no effect on the base apparent power of the system, The reason for this being that
the apparent power into the transformer equals the apparent power out of the
transformer. On the other hand, voltage changes when it goes through a transformer,
so the value of V5ur. changes at every transformer in the system according to it turns
ratio. Because the base values change in passing through a transformer, the process
of referring quantities to a common voltage level is automatically taken care of during
per-unit conversion. The per-unit system has the distinct advantage that, with it, all
basic circuit relations apply.
Suauut = Spu.Snu
The per-unit system simplifies many of the problems of circuit analyses. In the
conventional form of calculation using volt and ampere, the solution of a system
involving power lines of several different voltage levels, requires that all impedances
that are to be added, to be transferred to a single voltage level. In the per unit system,
the different voltage levels entirely disappear and a power network involving
generators, transformers and lines (of different voltage levels) reduces to a system of
simple impedances. Further more, machines such as generators and transformers,
when described in the per unit system, have their characteristics specified by almost
the same number, regardless of the rating of the machines.
164
ADVANTAGES OF THE PER.UNIT SYSTEM
. Device parameters tend to fall in a relative narrow range, making inaccurate values
prominently,
. Related to this advantage, the voltage throughout the power system is normally
close to unity.
. Both the percent and per-unit methods of calculation are simpler than the use of
actual volts, amperes and ohms.
The per-unit system also has some disadvantages. Disadvantages may include the
following:
. The system modifies component equivalent circuits, making them somewhat more
abstract. Sometimes phase shifts that are clearly present in the un-scaled circuit,
vanish in the per-unit circuit.
. Some equations that hold in the un-scaled case are modified when scaled into per
unit. Factors such as J: and 3 are removed or added by the method.
As discussed, the per-unit system is very handy to use in the analysing of large power
systems with different voltage levels. In the per unit system, the voltages, currents,
powers and impedances are not measured in there actual SI units as we know them i,e.
volts, amperes, VA or ohms. Instead, each electrical quantity is measured and
expressed as a decimal fraction of some base level. A given per-unit value for an
impedance is the ratio of the voltage drop across the impedance when it is carrying the
rated current of the section of the circuit in which it is connected, and the rated voltage
of that section of the circuit.
165
a
Lpu -
Zactua l'Irated
, ,. , ..,.., (i)
Vrated
As shown, a per-unit quantity is the ratio between the actual quantity and the chosen
base quantity. It therefore follows that:
uou= ii)
#
(
n
Alsol Ipu = grnb .,........ (iii)
Itis usual to take the rated values, i,e, the nameplate values, as the base values.
Ohm's law:
7 Vno
apu(nb) - ..,..,....(v)
L"
Zacual'Ibase(rated;
a - (vi)
-Pu
vbase(rateO
It is known that:
-"'
Lbase = l!t* (viii)
5brr"
-7 Zactual'Sbase
'
-l)U -
V#'"
(ix)
166
6.5.1 THREE-PHASE EQUTPMENT
Since three-phase systems are solved as a single line with a neutral return, the bases
for quantities in the impedance diagram are kVA per phase and volts from line to line.
Although a line voltage may be specified as a base, the voltage in the single-phase
circuit is still the voltage to neutral. The base voltage to neutral is the base voltage
from line to line divided bV JS . This is also the ratio between line to line and line to
neutral voltages of a balanced, three-phase system, As a result of this, if the system is
balanced, the per-unit value of a line to neutral voltage on the line to neutral voltage
base is equal to the per-unit value of the line to line voltage at the same point on the
line to line voltage base. Similarly, the three-phase kVA is three times the kVA per
phase and the base value of the three-phase kVA is three times the per-phase value of
the base kVA. The per-unit value of the three-phase kVA on the three-phase kVA base
is therefore identical to the per-unit value of the kVA per phase, on the kVA per phase
base. The impedance of three-phase equipment is always given as per-phase
quantities. From Equation (i):
a - Zactual/ph'Irated/ph
-pu ,.........(x)
Vated/ ph
But: Ipr' = IL
S b.r" .,........(xi)
-JE.v'
VL
And: Vph = ..,....... (xii)
J3
7 - -Vfu**,
4PU
Zactual'Sbase
(xiii)
V'irtin"t
-
Lnb = -=-
5nn
t67
6.5.2 BASE SELECTTON FOR PER-UNrT QUANTTTTES
The selection of base values is made to reduce the work required by calculations as
much as possible, A base is first selected for some part of the circuit. The base
selected should be one that yields per-unit values of rated voltage and current
approximately equal to unity to simplify calculations. When the manufacturer gives in
percent or per unit the reactance and resistance of a component, the base is
understood to be the rated voltage and kVA of the component, A great advantage in
making per-unit calculations is realised by the proper selection of different bases for
circuits conhected to each other through transformers. To achieve the advantage in a
single-phase system, the voltage bases for the circuits connected through transformers
must have the same ratio as the turns-ratio of the transformer, With such a selection
of voltage bases and the same kVA base, the per-unit value of an impedance will be the
same when it is expressed on the base selected for its own side of the transformer, as
when it is referred to the other side of the transformer and expressed on the base of
that side of the transformer.
ifnetwork calculations need to be done using per-unit values, all the per-unit values
must be caleulated using the same base values. The base units for any electrical
equipment are Sn5, Vn5 ond Zn5. Let:
7
Aactual -
Zpr1q51'Vfi
-------=-
5sn
And: 7
Aactual -
Zpuln6y'V'fu
--------=-
5nn
Therefore:
Ssu = Snn
168
If Vn6 and Snu change, then:
Zpulnb) = r,,.r[*)[#),
If Sn6 changes and Vnu stays the same (Vn5 = Vsu):
a_
apu(nb) -
',*'[+)
If Vn6 changes and Sn6 stays the same (Sn5 = Ssn):
a-
epu(nb) -
'rr,rr[*)
The equation for the new base impedance shows that the same equation is valid for
either single-phase or three-phase circuits. In the case of three-phase, line-to-line
voltage must be used with kVA per phase.
All impedances in any part of a system must be expressed on the same impedance.
base when calculations are done. Sometimes the per-unit impedance of a system
component is expressed on a base other than the one selected as base for the pad of
the system in which the component is located, It is therefore necessary to have some
means of convefting per-unit impedances from one base to another. Reference will
always be made to the high voltage (HV) and low voltage (LV) side of the
transformer.
Example 5.1
169
High voltage (HV) side Low voltage (LV) side
v&("nt) ,'2
vgb(line)
7sa = a
abase -- ---
Ssu ^-
5sn
.t
(4Bo)2
= 24 xL03
= Q2O)2
24 xL03
= 9.6 C) = 2.O17 Q
Zlr, = 0.055 f)
Znv = (0.055)fgl'
\220 )
0.0s5
= 0.262 O 7pu =
2.017
0.262 O.O273Z9O'pu
7ru
9.6
= O.O273190" pu
This shows that the per-unit impedance of a transformer is the same when referred
from one winding to the other. If the per-unit values are used, the equivalent circuit of
the transformer can now be drawn as shown in Figure 6.23.
Zpu = 0.0273190. pu
Vou=1pu Vor=1Pu
t70
Example 6.2
Figure 6.2 shows a schematic diagram of a radial transmission system. Use the
nameplate values of the generator as base values and draw the equivalent circuit for
the system.
Figure 6.2: Single-line diagram for the radial transmission system of Example 6.2
Zpu(nb) = O'2ZSO Pu
Transformer 1: Sn6 r Ssn
Zpulnb) = ,r".r[Fl
[5su /
= (ooB)(#)
= O.L2Z9O pu
L7T
Z tine,S nb
Line: Zpu =
v&
(2.9X60 x 106 )
(t32 x t03)2
= O.OlZ9Oo pu
Transformer 2: Snb # Sso
1_
apu(nb) - trrar[Fl
/ l)su
(o oD(#)
0.056290" pu
Example 6.3
Figure 6.4 shows a schematic diagram of a radial transmission system. Use the
nameplate values of Transformer 1 as base values and draw the equivalent circuit for
the system.
Generator Transformer 1 Transformer 2
Figure 5.4: SinEle-line diagram for the radial transmission system of Example 6.3
772
Generator: Transformer 1: Transformer 2:
d
And: Vn5 + Vsn
a_ _
apu(nb)
''*'[+J[*)'
= ,",(#l#)'
O.2t,/9Oo pu
.a apu(nb) _ O,O8Z9O. pu
a_ Z line,Snu
Line: apu(nb) -
v&
(2.9X40 x106)
=
(t32 x t03)2
O.OO67290'pu
Zpulnb) = t-."[+J
= (o oa[#)
= 0.0933290. pu
173
Zpulsen) = 0.21190" Pu Zpu(rine) = 0'0067290' Pu
Vpulsen) = 1 PU
Example 5.4
Determine the Thevenin equivalent circuit for the network shown in Figure 6.6. Take
Sbur" = 150 MVA ahd Vsssg = I32 kV in the transmission lines.
11 kV t32l7t kv
lOO MVA 1OO MVA
X = 1B%o X= 9o/o
13.8 kV t3zltr kv
150 MVA 150 MVA
X = 22o/o X = 9o/o
22 kV r32l22kV
250 MVA 250 MVA
X = 25o/o X = 10%o
174
Refer all impedances to the common base values:
Generator 1: Zpulnb) =
"*"[+)
(o 1s)[i#-)
= O.27Z9O'pu
6
Transformer 1: Zpulnb) =
'rrar[+)
(oor)(i#)
0.135290" pu
Z ttn"'S nu
Line 1; Zpu =
Vrt
(2.9X1s0 x 106 )
(132 x 103)2
0.02529O'pu
- (vno)'
' Generator 2: Zpulnb) = znurool[*
J
rc.22\fE!)'
' '[ 11 ,l
= O.24629O pu
Ztin"'Sno
Line 2: 7p, =
vto
(4X1s0 x to6)
Trl, " lo1f
O.O34419O" pu
t75
Generator 3: Zpulnb) =
"".,'[+)
= (o2s)t#)
0.1529Oo pu
7_ Z tine.S nb
Line 3:
v&
(sx1s0 x t06)
lrgtlo'tr
O.O43I9O" pu
Figure 6.8: Thevenin equivalent circuit for the network of Example 6,4
176
I
Example 6.5
Figure 6,9 shows a schematic diagram of a radial transmission system. Use the
nameplate values of the transformer as base values and calculate the terminal voltage
on the generator if the load takes full load current at 0.9 pu volts.
Generator Transformer
Pload = J5.V1ou6.I6u6.cos $
T- S b.r.
rbase -
J3,Vour.
1x106
(J3X3,3 x 103)
L74.955 A
T_ Itoad
rpu - I b.."
131.216
=
L74.955
O.752-36.87'pu
Transformer:
Zpulnb) = O'O7Z9O Pu
177
Line: Zpu =
e
(0.48 + i12.8)(1 x 106 )
= (3.3 x to3)2
= O.25Ll8O.27o pu
Vpulsen) = Vpu(toad) * Vpufi) * Vpu(tine)
Vterminal = Vpu1ggny,V535g
= (L088t9.335"X11)
= tL.95819.335'kV
Example 6.6
Figure 6.10 shows a schematic diagram of a radial transmission system. Use a base of
120 MVA and calculate the terminal voltage of the generator in per unit and in kV if the
voltage on the load is to be maintained at 33 kV.
Figure 5.1O: Single-line diagram for the radial transmission system of Example 6.6
Ptoad J3 .V6u6.I6u6,cos $
x
"6 X::
60 106 ( x 1o3XIbadXo.B1)
Itoao t295.96Z-35.9" A
178
rrbase - ---Sbu..
J3.Vbase
120 x 106
---------------------
(J3X33 x 10')
= 2099.455 A
r - Itoad
tse
lb.r"
L295.962 - 35.9'
2099.456
O.6L7l-35.9o pu
Transformer 2: -
Zpulnb) = apu(sb)
(,s^o
|^
)
I
l)so J
(0.12)f!q)
' '17s,/
O.L92Z9O'pu
Vpulno) = Zpulno)'Ipu
a- Ztin"'Snb
Line: Lpu -
v&
(1,86 + j12,8X120 x 106 )
=
(66x103)2
O356ZaL73'pu
Vpu(tine) = Zpultine).Ipu
179
Transformer 1: Zp.,1nu1 = trr,rr[+j
= (o.oe)fEq.)
' '[ 60 ,
= 0.1829O. pu
Vpu(nb) = ZpulnU;'Ipu
,
= (0.18290')(0.617 t-35.9')
= O.tLtLZS4.l'pu
Since the load is used as reference, the per-unit voltage across the load will be
Lzj" pu.
Vlterminat) = Vpgqsgn;'V535s
= (r.3332t4.94"X11)
= 14.653214.940 kV
Example 6.7
Consider the radial transmission system in Figure 6.11. Use the nameplate values of
Transformer 2 as base values and calculate the terminal voltage on the generator if the
load takes full load current at0.942 pu volts.
Generator Transformer 1
kV (1.69 + j11.7) o
66/33 kV
33/11 36 MW
MVA
24.5 MVA
27.5 cos g = Q,796
X=9o/o X=I2o/o lagging
Figure 6.11: Single-line diagram for the radial transmission system of Example 6.7
180
Ptoad = J3 ,V1ou6'I6u6.cos $
rbase= +!ttt-
J3.Vbase
27.5 xL06
=-
(J:Xtt"
103 )
= 1443.376 A
rrpu - Iload
r base
Z-38.L9"
= 2403.957
rqa376
= I.6662-38.19o pu
Ztint:snu
Line: 7-ou =
v6
(1'69 + j1l,7X?.-5 x 106)
= (33x103)2
= O.2985281.78o pu
= (o.oe)
' eE\
'\24.s )
= jo.lol pu
181
Vpu(sen) = Vpu(load) +Vpu6z) *Vpu(tine) *VpuG1)
Vlgen) = Vpu1gg6y.Vg65s
o = (L.655t22,45S.X66)
= 109.23222.455. kV
Example 6.8
Figure 6.12: Single-line diagram for the radial transmission system of Example 6.8
Ptoad = J3 ,V1ou6.I1ou6.cos $
r-ud\e - Sb.r.
J3.vor..
120 x 106
= 2099.455 A
TB2
-t
I toad
Ipu =
Ib.r"
942.517 Z-27"
2099.456
= O.44891-27" pu
Transformer 1: -
Zpulnb) = zpu(qb) I
(s.o )
I
-- /
l)su
o.LoBzsoofgq)
\r44 )
jo.o9 pu
(s''o )
Transformer 2: Zpulnb) = 1e(sb) -
[sqb J
o.os4tsoofEql
\.e6i
j0.105 pu
757.537 2L0,97"
Vpu(sen)
r32
I.L9351LO.97" pu
\,vpg(gen) _ Vpu(load) + Vpugr; + Vpu6zl * Vpu(line)
\,v pu(line)
- O.lg9LZ48.5o pu
Vpu(tine) = Ipg.Zpultine)
- _ril_
_
7 Ztin.'Snb
apu(rine)
Ztin" = 28.625275.5" O
183
R = 7.169 C)
And: L = 88.213 mH
Example 6.9
Refer to the single line diagram of a radial transmission system in Figure 6.13. Use a
voltage-base of 273 kV and a kVA-base of 210 MVA and calculate the actual voltage on
the termindls of the generator. The impedance of the transmission line conductors is
(0.05 + j0,1s) o/km.
Generator Transformer 1
Transformer 2
Transformer 3
Line 1
Line 2
48 km
132/BB kV 12 km
24slr32kv
125 MVA 96 MVA BB/11 kV 36 MW
X = I2o/o X = 9o/o 72MVA cos $ = Q.7gg
X = 10o/o lagging
Figure 6.12: Single-line diagram for the radial transmission system of Example 6.9
T- Snu
lbase -
J5.vno
210 x 106
(J3X11"103)
tto22,t4L5 A
T- Itoaa
Ibur"
?397.B5st-38"
=
17022.1415
= O.2L75Z-38. p.u.
LM
=7go*t*l
_ (o',)[#l#l
= jO.1624 P.u.
Vgb =
[#),"',
147.086 kv
z- (0.0s +j0.1sx48)
7.589527'.s'ss6'o
ZIine'Sno
Lnb
v;b
u
(7.s8ss z71.s6q')919 )
= "10
1r+Z.OaOxfO'1'
= O.O7g7l7t'565" P.u'
vsu =
[F-J*r,
= 98.057 kV
z = (0,0s +j0.1sX12)
= 1,897271.565" O
185
\_(
a_ Ztine,Snu
Lnb
va
(1.897 z7 L .565 ") (2IO xLO 6 )
=
(98.057xtO3)2
= 0.04t427L555" p.u.
snb
Transformet 3: a_
Lnb z^". ryq)'
"" Ssb [%o j
= (o1)(#)[*b-)'
jo.2349 p.u.
Load: vgb -
[tr),",
= t2.257 kV
( tt )
Vo, = t_t
Itz.zst )
o.8972o" p.u.
Vgen = (0.9983/:6.28"X24s)
244.583525.28" kV
.i
. 186
'.-(
EXERCISE 6
a Figure 6.13 shows a schematic diagram of a radial transmission system. Use a base of
96 MVA and calculate the terminal voltage of the generator if the terminal voltage on the
load is to be maintained at 32 kV.
Figure 6.13: Single-line diagram for the radial transmission system of Question 1
2. Refer to Figure 6.14, Use a base of 55 MVA and calculate the terminal voltage of the
generator.
Figure 6.14: Single-line diagram for the radial transmission system of Question 2
Consider the network in Figure 6.15. The load takes full load current at 0.936 pu volts,
{3 Use a base of 700 kVA and calculate the terminal voltage on the generator.
Figure 6.15: Single-line diagram for the radial transmission network of Question 3
187
4" Consider the radial transmission system in Figure 6.16. Use the nameplate values of
Transformer 2 as base values and calculate the terminal voltage on the generator if the
load takes full load current at 0.92 pu volts.
Figure 6,16: Single-line diagram for the radial transmission system of Question 4
'\-/1 210
{r5. Figure 6.17 shows a schematic diagram of a radial transmission system. Use a base of
MVA and calculate the resistance and inductance of the line.
Figure 6.17: Single-line diagram for the radial transmission system of Question 5
6. Consider the radial transmission system in Figure 6.18. Use the nameplate values of
Transformer 1 as base values and calculate the resistance and reactance of the line if the
load takes full load current at 0.945 pu volts.
Figure 5.18: Single-line diagram for the radial transmission system of Question 6
1BB
l
7. Refer to the three-phase network shown in Figure 6.19. Use a base of 48 MVA and
determine the value of the generator terminal voltage.
B. Figure 6,20 shows a schematic diagram of a radial transmission system. Use the
nameplate values of the transformer as base values and calculate the terminal voltage on
the generator if the load takes full load current at 0.915 pu volts.
9, Figure 6,21 shows a schematic diagram of a radial transmission system, Use the
nameplate values of the generator as base values and draw the equivalent circuit for the
system.
Figure 5.21: Single-line diagram for the radial transmission system of Question 9
189
a
10. Figure 6.22 shows a schematic diagram of a radial transmission system. Use the
nameplate values of Transformer 1 as base values and draw the equivalent circuit for the
system.
Figure 6.22: Single-line diagram for the radial transmission system of Question 10
11. Determine the Thevenin equivalent circuit for the network shown in Figure 6.23. Take
= 90 MVA dfld V6u." = BB kV in the transmission lines.
Sbur"
190
EXERCISE 2.t EXERCTSE 2.2 {CONTTNUED}
11.1 30.341242.74" A
EXERCISE 3
1. 635,473 VA'r
EXERCISE 2.2 ,
2. 9.672t0.480 E
L 50.17351*88.03" A
948.1155 W
9209.2155 W 11,5.416.t-L5.78 A
2. 8967.Jg4W
3.1 7.814tL37.76" A
47.6462-13;L98" A
47.7L6t44.64. A
264
EXERCISE 3 (CONTINUED) EXERCISE 4 (CONTINUED)
265
EXER.CTSE4 (CONTTNUED) EXERCISET
1,331 .::
::., .1j5.364 i;_,
5.2 0.9733 : 182.729 V :
0;9746 170.802V :
ErmExsE6
795 31_380 kv
7- 5-tri3j_120kY
a.&97_4,4r kY
€-#{17.560kv
LJITS*
sf; qf7
-*l
f{-E4{!
s-g?3c
7". tr13-4kl:J1e kv
*_ 41 .is-E-F 1Y
]1E6