5.0

Appendix 2: Diversity Factor (DF)

Updated: 21st March 2008

Dining Hall/ Canteen


Health Hostel Lab

Quarters
Mosque
School

Office
Hall

Building

Computer
Essential

Essential

Executive

Science
School
Non-

Lamp/ Fan 0.8 0.8 0.9 0.9 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

13A S/S/O 0.1 0.4 0.4 0.4 0.4 0.1 0.4 0.4 0.4 0.6 0.6 0.5

15A S/S/O 1 1 1 1 1 1 1 1 1 1 1 1

AC Motor
1 1 1 1 1 - 1 1 1 1 1 1
Pump

Outdoor
1 1 1 1 - - - - 1 1 1 1
Lighting

Water Heater - - - - - - 1 1 - - - 1

Cooker Unit 1 1 1 - - - - - - - - -

Isolator 1 1 1 1 1 1 1 1 1 - - -

Note: * DF may be relook based on the day and night profile usage.