Professional Documents
Culture Documents
Leakage Inductance Behavior of Power Transformer Windings Under Mechanical Faults
Leakage Inductance Behavior of Power Transformer Windings Under Mechanical Faults
Leakage Inductance Behavior of Power Transformer Windings Under Mechanical Faults
1
ITCE'15, [V. Behjat et al.: Leakage Inductance Behavior of Power Transformer Windings under Mechanical Faults]
Radial forces due to the short circuit currents are Calculation of the transformer leakage inductance using
produced by axial leakage flux act outwards on the outer magnetic cores has long been an area of interest to engineers
winding and lead winding conductors to endure stretch stress involved in the design of power and distribution
[11]. Beside, these forces cause inner winding to experience transformers. This is required for inspection the performance
compressive stress [9]. Different types of deformations due of the transformers before actual assembly of them [14].
to the radial forces can be occur, but amongst all of them There are several techniques for the leakage inductance
buckling type of deformation has been mostly reported in evaluation in transformers using different analytical and
transformer windings [13]. Fig. 1, presents radial forces in numerical methods. But most of the analytical methods are
cylindrical windings that initiate to buckling deformation. not accurate, especially when the axial height of HV and LV
winding are not equal [15]. Major analytical methods which
are mostly employed by utilities and researchers include
Flux Element Method and Energy Element Method where
these methods are valid only for normal operating conditions
(no fault) and fully based on construction of transformer
which means that the effect of the core material is not taken
into account [14-19].
(a) Radial forces (b) Outer winding (c) Inner winding
acting on inner and deformation deformation
A. Flux Element Method
outer windings
The magnitude of the leakage flux is a function of the
Fig.1. Electromagnetic radial forces and windings radial deformation forms geometry and structure of the transformer. Flux element
(Buckling). method is based on this fact that the leakage inductance is
defined as the ratio of the total leakage flux to the current
flowing in the windings. This method has certain limitations
B. Axial Forces
such as no core material effect on leakage inductance value
and some approximation is required to achieve a solution.
Axial forces that produced by radial stray flux density, act
on all winding and cause them to displacement or lead The considered assumptions for this method are [14, 15]:
conductors to tilting or bending. If windings are not placed 1) The leakage flux distribution in the winding and the
symmetrically or windings height is unequal, Ampere-turn space between them must be in the axial direction of the
mismatch between LV and HV will strengthen axial forces. windings.
Titling and bending of the conductors between spacers are 2) The leakage flux is uniformly distributed along the
one of the most common deformations due to axial forces radial length of the windings.
[1]. Axial forces acting on windings which lead them to 3) The leakage flux in the space of two windings is
displacement or tilting of the transformer windings is shown divided equally between them.
in Fig. 2. 4) The axial height of the HV and LV windings is equal.
With regard to above assumptions, the leakage flux for
each winding of a two-winding transformer is calculated as
follows:
N N Bds N Hds (1)
S
S
0
2
ITCE'15, [V. Behjat et al.: Leakage Inductance Behavior of Power Transformer Windings under Mechanical Faults]
density, and µ0 is the permeability of vacuum. Calculating and the total stored energy yields:
and replacing magnetic flux in above equation, leads to [6]:
W m W LV W HV W air _ gap (11)
2
0 N Il mt d s (2)
lC 3 2 Consequently, leakage inductance reflected to the primary
side can be expressed as the following simplified respect [4]:
Consequently, the leakage inductance for each winding
can be computed by using: 0 N 12 lm 1 d 1 lm2 d 2 d2 d2 (12)
L eq (1) l mg d g 2 1
L (3) h 3 3 12 12
I
N 2 l mt d s (4) For windings with unequal heights, it is proposed to use
L 0
lC 3 2 the average value of the heights of the windings h=
(h1+h2)/2, along with (12). Another approach that used in
and reflecting leakage inductance to the primary side some programs such EMTP [17], for windings with unequal
becomes: heights, is to apply the average height only for the gap
2
N between the two windings. Thus, equation (12) becomes:
L eq (1) L1 1 L 2 (5)
N2 lm d l d l mg d g d 22 d 12 (13)
L eq (1) 0 N 12 1 1 m 2 2
3 h1 3h2 hg 12 12
where N is number of the primary or secondary winding
turns, lmt is mean length of the primary or secondary turns, I where h is axial height of windings, hg=(h1+h2)/2 is
is rms current of the primary or secondary windings, lC is the average height of the windings that is applies only for the
axial height of windings (same for primary and secondary), d gap between windings, d is radial depth of primary or
is the radial depth of primary or secondary winding, and s is secondary winding, dg is radial depth of the gap between
the radial gap between the primary and secondary windings. windings, and ri is LV winding inner radius. Fig. 4 shows the
transformer parameters that used to leakage inductance
calculation using energy element method.
B. Energy Element Method
2 Wm (6)
L Fig.4. Parameters of transformer for calculating the leakage inductance
I2 using energy method
where Wm is the stored energy in magnetic field produced IV. WINDING DEFORMATION MODELING AND LEAKAGE
by a current I flowing in the windings that obtained by INDUCTANCE CALCULATING USING 3D FEM MODEL
magnetic computing based on Maxwell equations. The
magnetic field energy Wm stored in a volume V is expressed Classical analytical approaches, based on an axial flux
as: distribution, can lead to considerable error if the windings
1 1 (7) have unequal heights and if they are located far from the
W m B . Hdv 0 H 2 dv
V
2 V
2 core yokes and have some limitations [6]. The finite-element
method is a most applicable numerical technique that
Additionally, the stored energy of the windings LV, HV, provides higher accuracy than analytical methods and any
and radial air space between them must be calculated complex geometry with core material consideration can be
separately as follows [6]: analyzed. In this section, at first the leakage inductance of
the test subject transformer is calculated using all mentioned
0 N 22 I 22 ri
d 22 equations to validate the accuracy of FEM model. Then,
W LV (8)
d 2 different deformation states are modeled by changing
h 3 12 physical dimensions and positions of the windings.
0 N 12 I 12 ri d 2 d g d 1 d 12 (9) For calculating leakage inductance of windings using 3D
W HV d1
h 3 12 FEM model, after making the geometry model of the
transformer and description the physics of materials,
0 N 12 I 12 dg (10)
W air _ gap ri d 2 d g problem must be solved with rated value of windings
h 2
3
ITCE'15, [V. Behjat et al.: Leakage Inductance Behavior of Power Transformer Windings under Mechanical Faults]
1,784 mm
TABLE III
LEAKAGE INDUCTANCE CHANGES UNDER OUTER WINDING (HV) RADIAL
DEFORMATION ACCORDING TO FIG. (6-B)
Deformation Leakage Inductance Leakage Inductance
Level mm [mH] Changes [%]
0 30.39251754 0%
1 2 30.45850026 0.2171 %
2 4 30.53188949 0.4586 %
Fig.5. Geometrical structure of the transformer used as a case study 3 6 30.61315274 0.7259 %
4 8 30.68571100 0.9647 %
5 10 30.77111726 1.2457 %
A. Leakage Inductance Changes under Windings Radial 6 12 30.85751770 1.5300 %
7 14 30.93954600 1.7999 %
Deformation 8 16 31.04610848 2.1505 %
Reflected leakage inductance to the primary side of the 9 18 31.13548600 2.4435 %
10 20 31.23358488 2.7674 %
test object transformer in healthy state calculated by
analytical methods and FEM model is given in table I. With
respect to this table, resulted value from FEM model is more
B. Leakage Inductance Variation under Windings Axial
accurate. As illustrated in Fig. 1, radial deformations almost
Displacement
are in buckling type. Inner and outer windings deformation
is modeled by changing winding physical dimensions in 3D The leakage inductance increases in transformers with
FEM model of the transformer. Tables II and III present the unequal windings height. Also, axial forces that lead to
leakage inductance variations under different levels and tilting, bending or displacing of winding conductors will be
different types of radial deformation according to Figs. 6(a) more sever in these transformer types. Using FEM model
and 6(b) respectively. can provides axial deformation and displacement simulation
with high accuracy. When axial electromagnetic forces act
on the windings, they can cause the HV winding to move
HV axially with respect to the LV winding [9], as shown in Fig.
7. Moving HV winding from initial position leads leakage
LV
LV
36° (10 %) Deformation
inductance to change, since the value of radial leakage flux
0-16 mm depression changes. So, in this section, the effects of outer winding
(HV) displacement on leakage inductance are investigated.
(a) The simulation results are presented in table IV.
HV
LV
36° (10 %) Deformation
0-20 mm convexity
HV
(b)
Fig.6. Inner and outer windings radial deformations (a) inner winding
deformation (b) outer winding deformation Fig.7. Outer winding axial displacement (Only one phase of three phases is
shown).
4
ITCE'15, [V. Behjat et al.: Leakage Inductance Behavior of Power Transformer Windings under Mechanical Faults]
TABLE IV
REFERENCES
LEAKAGE INDUCTANCE VARIATION UNDER OUTER WINDING (HV)
DISPLACEMENT ACCORDING TO FIG. (7)
Displacement Leakage Inductance Leakage Inductance [1] Mehdi Bagheri, Mohammad Salay Naderi, and Trevor Blackburn,
Level mm [mH] Changes [%] “Advanced transformer winding deformation diagnosis: moving
0 30.39251754 0% from off-line to on-line”, IEEE Trans. Dielect. Elect. Insul., vol. 19,
1 2 30.39560982 0.0102 % no. 6, pp. 1860–1870, Dec. 2012.
2 4 30.39670210 0.0138 % [2] Z. W. Zhang and W. H. Tang, “Finite-element modeling for analysis
3 6 30.40885251 0.0537 % of radial deformations within transformer windings”, IEEE Trans.
4 8 30.41321596 0.0681 % Power Del., vol. 25, no. 5, pp. 2297–2305, Oct. 2014.
5 10 30.44360407 0.1681 % [3] Amir Abiri-Jahromi, Masood Parvania, Françicos Bouffard, and
6 12 30.48208115 0.2947 % Mahmud Fotuhi-Firuzabad, “A two-stage framework for power
7 14 30.50154499 0.3587 % transformer asset maintenance management”, IEEE Trans. Power
8 16 30.52212627 0.4264 % Syst., vol. 28, no. 2, pp. 1395-1403, May.2013.
9 18 30.57163778 0.5894 % [4] T. Y. Ji,W. H. Tang, and Q. H.Wu, “Detection of power transformer
10 20 30.61166800 0.7211 % winding deformation and variation of measurement connections
using a hybrid winding model,” Elect. Power Syst. Res., vol. 87, pp.
39–46, 2012.
[5] J.R. Secue and E. Mombello, “Sweep frequency response analysis
V. DISCUSSION (SFRA) for the assessment of winding displacements and
deformation in power transformers”, Elsevier, Electric Power Syst.
Research, Vol. 78, pp. 1119-1128, 2008.
All analytic equations have shown that leakage inductance [6] S. V. Kulkarni and S. A. Khaparde, “Transformer Engineering:
is increases with the radial depth of winding increases, and Design and Practice”, Boca Raton, FL: CRC, 2004.
[7] Mathieu Lambert, Frédéric Sirois, Manuel Martínez-Duró, and Jean
inductance decreases with increasing the winding heights. Mahseredjian, “Analytical Calculation of Leakage Inductance for
On the other hand, the radial depth between two inner and Low-Frequency Transformer Modeling”, IEEE Trans. Power Del.,
outer windings has greatest impact on leakage inductance vol. 28, no. 1, pp. 507–515, Jan. 2013.
value compared to other parameters such as windings radial [8] M. Florkowski and J. Furgal, “Transformer winding defects
identification based on a high frequency method”, Measurement Sci.
depth, windings axial height or space between inner winding
Techn., doi:10.1088/0957-0233/18/9/012, 2007
and core limb. Also, the results obtained by FEM model, [9] J. A. S. B. Jayasinghe, Z. D.Wang, P. N. Jarman, and A. W. Darwin,
show that when deformations or displacement occurred in “Winding movement in power transformers: A comparison of FRA
the windings, cause the leakage inductance shifts from initial measurement connection methods,” IEEE Trans. Dielect. Elect.
value. Radial deformations causes the gap between two Insul., vol. 13, no. 6, pp. 1342–1349, Dec. 2006.
[10] W. J. McNutt, W. M. Johnson, R. A. Nelson and R. E. Ayers,
windings increased see Fig. 6, so the leakage inductance "Power Transformer Short-Circuit Strength-Requirements, Design,
value rises. With HV winding axial displacement according and Demonstration", IEEE Trans. Power App. Syst. Vol. 89, pp.
to the Fig. 7, radial leakage flux value at the top and bottom 1955-1969, 1970.
of the windings increments, so the leakage inductance [11] S.V. Kulkarni and S.A. Khaparde, Transformer Engineering Design
and Practice, Marcel Dekker, Inc., New York, USA, 2004.
increases. However, with respect to the Tables [II-IV], [12] R. M. Del Vecchio, B. Poulin, P. T. Feghali, D. M. Shah, R. Ahuja.
although the leakage inductance value is changed, but this Transformer Design Principles (Second ed.), CRC Press (Taylor and
variation is very low and in some cases are negligible. Francis Group), FL, USA, 2010.
Specially, value of leakage inductance changed very slightly [13] D. Allan, H. Moore, Electric Power Transformer Engineering, CRC
Press LLC, FL, USA, 2004.
when the winding displaced in axial direction. Nevertheless, [14] A. Naderian Jahromi, Jawad Faiz, and Hossein Mohseni, “A fast
winding mechanical defects detection by using leakage method for calculation of transformers leakage reactance using
inductance value or short circuit impedance measurement is energy technique”, IJE Trans. B: Applications, Vol. 16, no. 1, Apr.
impractical. Because, the winding mechanical defects that 2003.
[15] K.Karsai, D.Kerenyi, and L.Kiss, “Large Power Transformers”,
are most reported faults in transformers, must be early Hungary, Elsevier, 1987.
detected before transformer is failed but that impossible by [16] Kassim Rasheed Hameed, “Finite element calculation of leakage
using with this less sensitive method. reactance in distribution transformer wound core type using energy
method”, Journal of Engineering and Development, Vol. 16, no.3,
Sep. 2012.
[17] ATPDraw, ver. 5.7. [Online]. Available: http://www.emtp.org
VI. CONCLUSION
Most reported windings deformation and major
analytical methods which are employed by utilities and
researchers are presented in this paper. Depending on the
relationship that the value of leakage inductance relies on
dimensions and positions of transformer windings, the
effects of winding various deformations and displacement on
leakage inductance value are investigated by FEM. The
results of winding defects modeling show the low sensitivity
of this approach for detecting mechanical deformation faults
in power transformers. Hence, this method is an improper
method and can’t be used to early detection winding
mechanical faults such as movement and/or deformation.