Professional Documents
Culture Documents
2010 Experimental Study On Inelastic Mechanical Behaviour of Composite Girders
2010 Experimental Study On Inelastic Mechanical Behaviour of Composite Girders
2010 Experimental Study On Inelastic Mechanical Behaviour of Composite Girders
into the design of continuous composite girders, positive bending 2. Experimental study
tends to become smaller and negative bending becomes larger than
that of the conventional design methods [4]. The design section, 2.1. Test specimens
therefore, changes depending on whether or not the tension stiff-
ening effect is taken into account. A total of four simply supported composite girders were tested
Crack control is an important issue in steel and composite con- to simulate a part of them [portion BCD, see Fig. 1(a)], which was
tinuous bridges. There are two approaches for dealing with con- exposed to a negative bending moment adjacent to an internal
crete cracking in composite bridges, one is to prevent cracking us- support of a continuous composite girder. The authors used two
ing prestressing methods and the other is to allow for the forma- types of specimens. Specimen CB-1 was made of normal concrete
tion of cracks within the limit of acceptable widths. Prestressing with studs as shear connectors. Specimen CB-2 was the same as
methods, however, are inconvenient and unreliable due to pre- Specimen CB-1, with the exception that the studs were replaced
stressing losses by the long-term behaviour of concrete. Therefore, by PBL shear connectors. The main characteristics and nominal
it is considered that the control of crack width without prestressing dimensions of the test specimens are shown in Fig. 1 and Table 1.
is a more economical and simple solution [5,6]. In the test specimens, the total lengths of the girders were
Some researchers have studied the cracking property of the 9.5 m. The thickness of concrete deck panels were 105 mm
slabs in composite girder bridges, with a view to the influence of without including haunch. There were 3 layers (upper, middle and
reinforcement ratios, reinforcing bar diameters and spacings on lower) longitudinal deformed reinforcing bars with the diameter of
the width and spacing of cracks. And it is necessary to focus on local 14 mm in concrete slab, and the longitudinal reinforcement ratio
weakening of the tensile capacity of a concrete slab caused by shear is 3.0%, the spacing and arrangement were shown in Fig. 1(c) and
connectors or transverse reinforcement since these factors may (d). The arrangement of transverse reinforcement for specimen
influence the crack spacings and widths [5–8]. On the other hand, CB-1 and CB-2 in the upper and middle layers was the same,
compression in the steel profile can lead to either local phenomena the longitudinal spacing at the middle was 75 mm, while at the
such as buckling of the bottom flange and/or of the web, or global supported regions was 100 mm, and the diameter of them was
phenomena such as distortional lateral torsion buckling [9,10], so 10 mm. However the arrangement of transverse reinforcement
that the width to thickness ratio of the steel flange and that of the in the lower layer was different due to the influence of shear
web should be considered carefully. connectors, the transverse reinforcing bars penetrated the holes
Generally, shear studs are not so stiff to prevent slip between with the same spacing of PBLs in specimen CB-2, while the spacing
the slab and steel girder, even for full shear connection. A perfect of transverse reinforcing bars was two times in comparison with
composite action without any slip cannot be expected due to the that of studs in specimen CB-1, and the the diameter of them was
deformation of shear studs which are often treated as ‘‘ductile’’ 12 mm, the details of the arrangement were shown in Fig. 1(c)
connectors [11]. The PBL was developed in the nineteen eighties and (d).
by the German company for the design of the third bridge over Three rows shear studs with diameter of 16 mm were welded
the Caroni River in Venezuela [12,13]. Push-out test results show on the top flange, with a transverse spacing of 60 mm symmetric
that PBL shear connectors are advantageous from the viewpoint about the centerline of the top flange and a longitudinal spacing of
of fatigue strength [14,15]. It is necessary to investigate the effect 75 mm at the middle section (100 mm at the supported section)
of PBL shear connectors on crack formation and the mechanical for specimen CB-1. Two perforated steel plates with a transverse
behaviour under hogging moments. spacing of 120 mm and a longitudinal spacing of 150 mm (holes)
In this paper, static experimental tests on four half-scale for specimen CB-2, as shown in Fig. 1(e).
models of steel and concrete composite girders with different Vertical stiffeners were welded at supports, loading points to
shear connectors such as studs and PBLs under hogging moments prevent shear buckling failure and crippling of the web before flex-
were cautiously conducted in order to investigate the reduction of ural failure. Also, lateral bracings were installed at each end of the
flexural stiffness and the inelastic behaviour after cracking. Crack beam to allow vertical deflection, however lateral displacements
development, crack widths and strains of the composite section and rotations were restricted to prevent lateral torsional buckling
before and after cracking were observed in the tests. A simple of the beam.
plastic analysis was carried out to estimate the ultimate flexural
capacity of the continuous composite girder. Initial cracking load 2.2. Material properties
and crack spacing were observed and the relations between
crack spacing and transverse reinforcement spacing were studied. Mix proportion of concrete with a design compressive strength
Particularly, the stiffness of the composite section during cracking of 50 N/mm2 is shown in Table 2. The material properties including
was evaluated, because it is important to estimate crack widths, compressive strengths, tensile strengths and Young’s modulus
deflection and stress ranges under service load. The crack width of three cubes at 28 days after the casting of the concrete are
evaluation methods based on design codes for steel and concrete given in Table 3. The characteristic tensile strengths are used in
composite girders under negative bending moment are compared prediction of the cracking resistance of the specimens. The mean
to grasp the differences of evaluated results. It was found that tensile properties of samples cut from the web, the flange and the
crack widths could be controlled appropriately within an allowable reinforcement of the girders are summarized in Table 4.
value in the slab under service load. The strains of reinforcing bars
obtained through the static tests approximately corresponded to 2.3. Loading and measurements
the values calculated through the application of existing tension
stiffening theory. And the test results showed that slips always The tests were carried out in Structure Laboratory of Tongji
occurred for composite girders under hogging moment even University. A concentrated load was applied upward on the bottom
with complete shear connection between the steel and concrete of the steel girder by a hydraulic jack with loading capacity of
components. The test specimen could be considered as the full 1500 kN to simulate the hogging moment. Roller supports and
composite section until the ultimate state which was determined reaction frames were set at both ends of the girder, and the loading
from the relationship between load and slip of shear connectors. equipments are shown in Fig. 1(b) and Fig. 2. After the drying
Therefore, it is expected that the results in this study can be served shrinkage had stabilized, the preloading should be taken into
as a basis for the design of continuous composite girder bridges. account to check the good contact between the support and loading
J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52 39
9500 2000
250 3937.5 5062.5 250 1500
320
2400
50
320
600
87.5
37.511×100=1100 79×75=5925 87.5 22×100=2200 62.5
30 80400 35
35400 110
20 15 4@100=400 80 6080 4@100=400 15 20
20 15
105
8 50
345 100 200 37.5 5×200=1000 187.5 39×150=5850 162.5 11×200=2200 62.5
1015(1005)
860(850)
13(8)
80
30
22(13)
40
15
Table 1
Details of test specimens.
Specimen Type Shear connectors Reinforcements
Transverse spacing (mm) Longitudinal spacing (mm) Transverse spacing (mm) Longitudinal spacing (mm)
Table 2
Mix proportion of concrete.
Strength (N/mm2 ) Aggregate size (mm) Slump (mm) W/C (%) Air (%) Unit content (Kg/m3 )
Water Cement Sand Aggregate Fly ash
equipments, the reliability of all the test equipments and the divided into four levels by force control, the specimens were firstly
workability of all the measurement instruments. The loading was loaded to the crack initiation level of the slab, the second level load
40 J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52
Table 3
Material properties of concrete.
Nominal strength (MPa) Axial compressive strength (MPa) Splitting tensile strength (MPa) Young’s modulus (MPa)
Sample value Representative value Sample value Representative value Sample value Representative value
Table 5
Load capacity of test specimens.
Specimen Design load (kN) Initial cracking (kN) 0.2 mm cracking (kN) Reinforcement yield (kN) Ultimate load (kN) Ultimate displacement (mm)
Test Cal. Ratio Test Test Test Cal. Ratio Test
CB-1-1 134 120 129 0.93 600 900 1200 1123 1.07 51.7
CB-1-2 134 120 129 0.93 500 950 1224 1123 1.09 50.0
CB-2-1 134 180 129 1.40 800 1075 1140 1123 1.02 43.7
CB-2-2 134 160 129 1.24 700 1050 1320 1123 1.18 51.3
Table 6
Stiffness of test specimens.
Specimen F /δ (×103 kN/m) M /φ (×103 kN m2 )
Initial cracking 0.2 mm cracking Reinforcement yield Initial cracking 0.2 mm cracking Reinforcement yield
3000
2500
2000
1500
1000
0
0 1 2 3 4 5 6 7 8 9
(c) Studs.
(4) JTG D62-2004 The splitting tensile strength of concrete is 3.34 MPa, and
the equivalent strain is 125µε according to Chinese concrete
The maximum crack width for rectangular, T and I shape section
structure design code (GB50010-2002) [22]. Fig. 15 shows the
reinforcement concrete component under bending moment was
strain gauge section and position at concrete slab, and Fig. 16
estimated as follows:
shows the relationships between the load and concrete strain at
σss the loading section. Some cracks initiated and propagated through
30 + d
ωR = C1 C2 C3 (7) the position of strain gauges, the crack width became large as the
Es 0.28 + 10ρ
load increased, and the value of the strain increased rapidly.
As + Ap In Fig. 16, it was found that the strain increased linearly up to
ρ= (8)
bh0 + (bf − b)hf the initial crack, and that the strains at the middle of the top slab
were 166µε , 148µε , 160µε and 125µε for each specimen under
Ms the design load. After the first crack initiated, the strains increased
σss = (9)
0.87As h0 rapidly.
44 J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52
-1500 -1000 -500 0 500 1000 1500 2000 -1500 -1000 -500 0 500 1000 1500 2000
CB-1-1(120kN) CB-2-2(180kN)
(a) Initial cracking/mm.
-1500 -1000 -500 0 500 1000 1500 2000 -1500 -1000 -500 0 500 1000 1500 2000
CB-1-1(300kN) CB-2-2(300kN)
(b) Stabilized cracking/mm.
-1500 -1000 -500 0 500 1000 1500 2000 -1500 -1000 -500 0 500 1000 1500 2000
CB-1-1(800kN) CB-2-2(800kN)
(c) Reinforcement yield/mm.
-1500 -1000 -500 0 500 1000 1500 2000 -1500 -1000 -500 0 500 1000 1500 2000
CB-1-1(1150kN) CB-2-2(1150kN)
(d) Before girder failure/mm.
Fig. 9. Crack formation and distribution (Note: The horizontal coordinate represents the distance from the loading point, the grid in blue stands for the place of reinforcement,
and the line colored in red shows the cracks.). (For interpretation of the references to colour in this figure legend, the reader is referred to the web version of this article.)
Table 8
Crack width of test specimens/mm.
Specimen (1) Test (2) AASHTO (3) CEB/FIP-90 (4) JSCE (5) JTG D62
Initial Max. Max. (2)/(1) Initial (3)/(1) Max (3)/(1) Initial (4)/(1) Max. (4)/(1) Max. (5)/(1)
CB-1-1 0.02 0.23 0.17 0.74 0.02 1.00 0.23 1.00 0.03 1.5 0.22 0.96 0.20 0.87
CB-1-2 0.03 0.20 0.17 0.85 0.02 0.67 0.23 1.15 0.03 1.00 0.22 1.10 0.20 1.00
CB-2-1 0.01 0.25 0.17 0.68 0.02 2.00 0.23 0.92 0.03 3.00 0.22 0.88 0.20 0.80
CB-2-2 0.02 0.16 0.17 1.06 0.02 1.00 0.23 1.44 0.03 1.5 0.22 1.38 0.20 1.25
Wm
after cracking, some peak values emerged near the loading point,
Wb
and the strains changed greatly around the loading point. The
Fb1 Fb2 concrete strains of specimen CB-1 were slightly larger than those
of CB-2 under each load level, and PBL shear connectors showed
Fig. 10. Strain gauge section and position of steel girder. good strength property under hogging bending moment region.
J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52 45
(a) Section E.
(b) Section A.
3.5. Strain results of reinforcement colored in dark blue shows the values calculated from using the
rigidity without concrete contribution. The values of εs2 and εsm
were calculated using the equations shown below [23,24].
3.5.1. Basic theory
The relationships between load and strain of reinforcement in (a) Maximum strain after the start of cracking εs2st (at the start of
stationary cracking)
the vicinity of the center of the girder for each specimen are shown
in Fig. 18, in which εs2 and εsm are the maximum and average Nscr
strain values calculated on the basis of Hanswille theory, the line εs2st = + εsh (10)
Es · As
46 J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52
Neutral axis of
un-cracked section
Depth (m)
Depth (m)
Neutral axis of cracked section
-200 -150 -100 -50 0 50 100 150 200 -2000 -1500 -1000 -500 0 500 1000 1500 2000 2500 3000 3500 4000
Depth (m)
Neutral axis of
un-cracked section
Depth (m)
Neutral axis of
cracked section
Fig. 12. Sectional strain distribution (section E) in vertical direction of test specimens.
εsmst
2
1
3
ft
εsmst = εs2st − βm (12)
4
Es · ρs
5
stiffening at the initial cracking and stationary cracking (set at Shear Pcp Pu (kN) ηmean
0.6 and 0.4 respectively). connectors (kN)
EC4 AISC AASHTO GB JSCE Mean
3.5.2. Test results Stud 4.0 54.0 84.4 71.8 73.0 70.0 70.6 17.7
The strains of a longitudinal reinforcement in the middle of slab PBL 10.3 – – – – 24.8 24.8 2.4
near the loading point were measured, Fig. 19 shows the position
of reinforcement strain gauges, and the load–strain relationships
more than 50% of the top flange covered by a deck of sheet steel
were depicted in Fig. 20. The strain increased linearly and slowly
closures.
before cracking. After the start of cracking, the strain near the point
In AASHTO LRFD (2004), the nominal shear resistance of one
where the crack had occurred increased rapidly (a phenomenon
stud shear connector embedded in a concrete deck shall be taken
referred to as strain jump). Until the failure of the specimen,
the reinforcement was continuously deformed and the tension as Eq. (15)
stiffening effect of the reinforcements in the slab was confirmed.
Pu = φ 0.5As fc0 Ec ≤ φ As Fu
p
For the drying shrinkage strain, the authors assumed εsh = (15)
−150µ (conventional design value) for specimens. For the sake of where φ is the resistance factor for shear connectors, φ = 0.85.
comparing test results, the effect of drying shrinkage represents
As provided in the Chinese code for design of steel structures
only the parallel shift of the strain in the horizontal direction at the
(GB 2003) [26], the stud shear bearing capacity is determined by
stationary cracking state, such that εsh is added to the maximum
and average strain values in Eq. (10) to Eq. (12).
Pu = 0.43As fc Ec ≤ 0.7As γ fu
p
(16)
In these figures as a whole, the large strain values are
approximately equivalent to the calculated maximal strains. It where the units are N, mm; fc is the compressive strength of
can therefore be said that appropriate results were obtained by concrete prisms (MPa); and γ is the ratio of the ultimate tensile
using the above mentioned method of calculation with βm = 0.4. strength to the yield strength of the stud.
Although the measured strains scattered to a large extent, both the
In JSCE (2007), the nominal strength of one stud shear connector
maximum strain values as well as smaller ones were considered
embedded in solid concrete is given by
to be included in the measurement results. This indicates that it
is difficult to correctly evaluate the average strains based on the q
test results. However, an average strain value is required to ensure Pu = min 31Ass (hss /dss ) fcd0 + 10 000 /γb ; Ass fsud /γb (17)
the validity of β = 0.6, in the sense that the results obtained in
this study are insufficient. The authors therefore feel that further where the units are N, mm; Ass is the cross-sectional area of a stud
studies should be carried out on this issue in the future. shear connector (mm2 ); hss and dss are the height and diameter of
Fig. 21 shows the strain distribution of reinforcement in the the studs respectively, hss /dss > 4; fcd0
is the design compressive
middle of the slab along the horizontal direction before and after strength of concrete (MPa); fsud is the design tensile strength of the
cracking. For small values of load, the strain distribution along
stud; and γb is the material coefficient, γb = 1.3.
the length was small due to the composite un-cracked section.
As the load increased, cracks initiated and propagated, and the (b) PBL shear connector
strain of reinforcement increased rapidly, and the peak value of Several authors, such as Al-Darzi et al. [27], Iwasaki et al. [28],
reinforcement strain in the figure stood for the concrete crack Machacek and Studnika [29], Medberry and Shahrooz [30],
position. Oguejiofor and Hosain [31], Ushijima et al. [32], and Valente
and Cruz [33] have recently studied the behaviour of the PBL
3.6. Shear connectors connector, mostly from push-out tests. These authors concluded
that the structural response was influenced by several geometrical
3.6.1. Bearing capacity properties such as the number of holes, the plate height, length and
(a) Stud shear connector thickness, the concrete compressive strength, and the percentage
Eurocode 4 specified the design strength of stud shear of transverse reinforcement provided in the concrete slab. And the
connectors which are welded automatically, as Eq. (13) resistance capacity of PBL shear connectors was proposed by JSCE
(2007) as follows
Pu = min 0.8fu (π d2 /4)/γv , 0.29α d2 fc0 Ec /γv
p
(13)
Pu = [1.45{(d2 − φst2 )fcd
0
+ φst2 fst } − 106.1 × 103 ]/γb
where the units are N, mm; d is the diameter of the studs; fu is
73.2 × 103 < (d2 − φst2 )fcd
0
+ φst2 fst < 488.0 × 103 (18)
the ultimate tensile strength of stud (MPa); fc0 is the compressive
strength of concrete cylinders (MPa); Ec is Young’s modulus of 0
where d is the diameter of the Perfo-Bond strip holes (mm), fcd is
concrete (MPa); γv is partial factor (=1.25); α is 0.2(H /d + 1) ≤ 1;
the design concrete compressive strength (N/mm ), φst (mm) and
2
and H is the height of the studs.
fst (N/mm2 ) are the diameter and tensile strength of transversal
In ANSI/AISC 360-05 [25], the nominal strength of one stud
reinforcement that pass through the holes, and γb is the material
shear connector embedded in solid concrete or in a composite slab
coefficient, γb = 1.3.
is given by
(c) Degree of shear connection
Pu = 0.5As
p
fc0 Ec ≤ Rg Rp As Fu (14) In the test specimen, it was intended that the shear connec-
where As is the cross-sectional area of a stud shear connector tions were installed to achieve full shear connections. Ultimate
(mm2 ); Fu is the specified minimum tensile strength of a stud shear strength of the shear connector was determined from equations
connector (MPa); Rg = 1.0 for any number of studs welded in a recommended by different codes, as shown in Table 9.
row directly to the steel shape; and Rp = 1.0 for studs welded To achieve full shear connections, a degree of shear connection,
directly to the steel shape and having a haunch detail with not η which is defined as the strength of the shear connection in a shear
48 J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52
Fig. 21. Strain distribution in horizontal direction (at the center of the top slab).
were directed in the vertical direction on the studs while the strain mate state, however, the values of strain for shear connectors were
gauges were directed in horizontal direction on the Perfo-Bond less than the yield strain. Therefore, the connection between the
strip. Fig. 23 shows the load–strain relationships of stud and PBL steel girder and concrete slab was reliable. And the strain on Perfo-
shear connectors, it was found that the strain increased approxi- Bond strip increased rapidly at the section of hole due to the area
mately bi-linear as the load increased, while the increase of slope reduction, as the No. 9 gauge in Fig. 23(c) showed (the gauge was
after cracking was larger than that before cracking. Under the ulti- failed on CB-2-2 after loading level of 500 kN).
50 J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52
30
1 2 3 4 5 6 7 8
(a) Studs.
1 2 34 9 56 78
150 150 150
75 75 75
(b) PBLs.
Strain(E-6)
(a) CB-1-1.
(5) It is considered that the shear connection would not reach the
ultimate limit state, thus the test specimens could be assumed
as the full composite section until the ultimate limit state. And
the slip behaviour would change according to the boundary
conditions of the composite girders.
Acknowledgments
References
[1] EUROCODE 4. EN 1994. Design of composite steel and concrete structures Part
1.1 General rules and rules for buildings. Brussels: CEN-European Committee
for Standardization; 2005.
[2] Hanswille G. Zur Rißbreitenbeschränkung bei Verbundträgern, Technisch-
Weissenschaftliche Mitteilungen, Institutfür Konstruktiven Ingenieurbau
Ruhr-Universität Bochum, Mittelilung Nr 1986: 86-1 [in German].
[3] Hanswille G. Cracking of concrete mechanical models of the design rules in
EUROCODE 4, Conf. report, Composite construction in steel and concrete III,
ASCE; 1997. p. 420–33.
[4] Oka Atsushi, Ohyama Osamu, Ruter Marcs. Effect of concrete tension stiffness
of dual continuous box girder bridges. In: The 57th annual conference of JSCE
2002. I-345. p. 689–90 [in Japanese].
(b) PBLs. [5] Shim CS, Chang SP. Cracking of continuous composite beams with precast
decks. Journal of Constructional Steel Research 2003;59:201–14.
Fig. 25. Relative slip in horizontal direction. [6] Ryu HK, Kim YJ, Chang SP. Crack control of a continuous composite two-girder
bridge with prefabricated slabs under static and fatigue loads. Engineering
Structures 2007;29:851–64.
4. Conclusions [7] Ramm W, Elz S. Behaviour and cracking of slabs as part of composite beams
in regions with negative bending moments. In: Proceedings of an engineering
The inelastic behaviour of steel and concrete composite girders foundation conference, Composite construction in steel and concrete III. ASCE;
with different shear connectors such as studs and PBLs under 1996. p. 871–86.
[8] Navarro MG, Lebet JP. Concrete cracking in composite bridges: Tests, models
hogging moments have been experimentally investigated in this and design proposals. Structural Engineering International 2001;184–90.
study. The following conclusions may be drawn from the present [9] Kemp AR, Dekker NW. Available rotation capacity in steel and composite
study: beams. The Structure Engineer 1991;69(5):88–97.
[10] Kemp AR, Dekker NW, Trinchero P. Differences in inelastic properties of
(1) The initial crack load calculated with reference to the maxi- steel and composite beams. Journal of Constructional Steel Research 1995;34:
mum negative moment of composite section and the ultimate 187–206.
[11] Mottram JT, Johnson RP. Push tests on studs welded through profiled steel
load calculated by a simple plastic analysis with cracked sec- sheeting. Structure Engineering 1990;68(5):187–93.
tion including reinforcements were similar to those of the test [12] Leonhardt F, Andrae W, Andrae HP. New, improved bonding means for
results. composite load bearing structure with high fatigue strength. Beton-und
(2) The PBL connectors slightly improved the rigidity of the entire Stahlbetonbau 1987;82(11):325–31.
[13] Zellner W. Recent designs of composite bridges and a new type of shear
girder under both the normal serviceability limit state and the connectors. In: Proceedings of the IABSE/ASCE engineering foundation
ultimate limit state in comparison with stud connectors with conference on composite construction. 1987. p. 240–52.
reference to the load–displacement relationship. [14] Hosaka Tetsuya, Sugimmoto Ichiro. Recent steel-concrete composite bridges
(3) The crack width evaluation methods in respective design codes in railways. Bridge and Foundation Engineering 2000;7:31–40 [in Japanese].
[15] Hosaka T, Kaoru M, Hirokazu I. Study on shear strength and design method
for steel and concrete composite girders under hogging mo- of perfobond strip. Journal of Structural Engineering. A. JSCE 2002;48(3):
ments generally agreed with the test results. Crack widths can 1265–72 [in Japanese].
be controlled appropriately within an allowable crack width in [16] Khan QZ, Honda T, Okui Y, Nagai M. A method for crack width evaluation
of continuous composite girder bridges accounting for shear-lag effect.
the slabs under service loads. And the crack spacing was mainly
Structural Engineering/Earthquake Engineering, JSCE 2003;20(2): 131s–141s
dependent on the transverse reinforcement spacing. [in Japanese].
(4) The stiffness of the composite section was similar to that of the [17] Ministry of Communication of China. General code for design of highway
un-cracked composite section before cracking. After cracking, bridges and culverts. JTG D60-2004. Beijing: China Communications Press;
2004 [in Chinese].
the stiffness of the section reduced to cracked section (steel
[18] Ministry of Communication of China. Code for design of highway reinforced
girder plus rebar) with increased load, however the stiffness concrete and prestressed concrete bridges and culverts. JTG D62-2004. Beijing:
did not directly become equal to that of the cracked section China Communications Press; 2004 [in Chinese].
just after cracking occurred. Thus, the tension stiffening effect [19] AASHTO. LRFD bridge design specifications, 3rd ed. Washington, DC. 2004.
[20] Comite Euro-International du Beton. CEB-FIP Model Code 1990. Thomas
between cracks should be considered to evaluate the more ex- Telford; 1993.
act flexural stiffness of the composite section under hogging [21] Committee of steel structure: Standard Specification for steel and composite
moments. structure (Design edition). JSCE. 2007.
52 J. He et al. / Journal of Constructional Steel Research 66 (2010) 37–52
[22] Ministry of Construction of China. Code for design of concrete structure. [28] Iwasaki H, Fujii K, Fukada K, Toyota T, Nakamura H. A consideration on slip test
GB50010-2002. Beijing: China Communications Press; 2002 [in Chinese]. methods for Perfobond shear connector focusing on concrete confinements.
[23] Taniguchi N, Yoda T. Study on a crack formation for composite girders with In: 1st international conference on advances in experimental structural
negative bending. Proceeding of the Japan Society of Civil Engineers 2001; engineering. 2005. p. 871–76.
668/I(54):243–57 [in Japanese]. [29] Machacek J, Studnicka J. Perforated shear connector. Steel and Composite
[24] Kamiya T, Taniguchi N, Ikariyama H, Yoda T. Experiment study on crack Structures 2002;2(1):51–66.
behaviour with repeated load near the middle supports of continuous [30] Medberry SB, Shahrooz BM. Perfobond shear connector for composite
composite girder. Proceeding of the Japan Society of Civil Engineers 2007; construction. AISC Journal 2002;2–12.
63(1):25–34 [in Japanese]. [31] Oguejiofor EC, Hosain MU. Numerical analysis of push-out specimens with
[25] American National Standards Institute (ANSI)/AISC. Specification for structural Perfobond rib connectors. Computers and Structures 1997;62(4):617–24.
steel buildings. AISC 360-05. Chicago. 2005. [32] Ushijima Y, Hosaka T, Mitsuki K, Watanabe H, Tachibana Y, Hiragi H. An
[26] Ministry of Construction of China. Code for design of steel structures. experimental study on shear characteristics of perfobond strip and its rational
GB50017–2003. Beijing: China Planning Press; 2003 [in Chinese]. strength equations. In: International symposium on connections between
[27] Al-Darzi SYK, Chen AR, Liu YQ. An experimental investigation on stud steel and concrete. 2001. p. 1066–75.
and perfobond connectors with push-out test. In: Proceeding of the [33] Valente MIB, Cruz PJS. Experimental analysis of Perfobond shear connection
13th international conference on steel and composite structures. UK:2007. between steel and lightweight concrete. Journal of Constructional Steel
p. 455–62. Research 2004;60:465–79.