ELECTRICAL DESIGN REPORT

Electrical Design Report for

G+3+TERRACE RESIDENCE

Building
Sub-city:- BOLE

Design code: ES-3961/2015

Owner: ATSEDE TAMENE

Prepared By: FASIL W/G, PPEE-031

NOV, 2020 GC.

PREPARED BY: FASIL W/G PPEE 031


Page 0
ELECTRICAL DESIGN REPORT

Content
1. Introduction

2. Illumination level

3. Luminary Calculation

4. Power Calculation

5. A.C.B Calculation

6. Position of fitting

PREPARED BY: FASIL W/G PPEE 031


Page 1
ELECTRICAL DESIGN REPORT

Electrical Design Report

The requirements of installation are mainly dependent up on the type


of work to be carried out in the space in question. The no of
Luminaries for the space is calculated by taking in to account of the
visual task to be carried out in the space, the area of the space,
reflection factor of the ceiling wall and working plane and the room
index and also the maintenance factor.

In all case the reflectance of ceiling wall and working plan are
taken to be 0.7, 0.5, 0.3 respectively maintenance factor of 0.8 are
taken.

For all residence RZB type incandescent Luminaries are used. The
following illumination level is taken for various type of visual task to
be carried out.

No. Visual Task Average Illumination (Lux)

1 Kitchen 500

2 Bed room 150

3 Toilet 100

4 Corridor /Lobby/ 100

5 Balcony 100

6 Verandah 100

7 Living/ dining 200

8 store 200

The room index is calculated from

PREPARED BY: FASIL W/G PPEE 031


Page 2
ELECTRICAL DESIGN REPORT

𝐋𝐗𝐖
K=
𝐇 𝐋 𝐖
Where; L = room length
W = Room width
H = Mounting height of the laminar

Lumen per fixtures

Ø 𝐄𝐟𝐟𝐢𝐜𝐞𝐧𝐜𝐲 𝐗 𝐞𝐚𝐜𝐡 𝐥𝐚𝐦𝐩 𝐰𝐚𝐭𝐭

Number of fixtures
𝐄𝐗𝐀
𝑵𝑶. 𝒇𝒊𝒙𝒕𝒖𝒓𝒆
𝐔𝐅 𝐗 𝐌𝐅 𝐗 Ø

Ø The total luminous flux of lamp

E Average illumination

A Area of working space

UF utilization factor (0.69)

MF Maintenance Factor (0.63)

UF is found from photo metric DATA of chosen luminary.

Space height ratio taken is 1.25 and each lamp has an initial output efficiency of 85 lumen per
watt.

Each room has height of 3 meter and the ceiling to desk height is 2 meters.

So based on this calculative we can determine the number of lemonier (lamp) for every room.

Efficiency

*lumen per fixtures=lumen efficiency (lumen per watt) X each fixture`s watt

*lumen of efficiency is defined as the ratio of lamp output divided by the


total input.

PREPARED BY: FASIL W/G PPEE 031


Page 3
ELECTRICAL DESIGN REPORT

GROUND FLOOR

Parking

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 22
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 3, to use three lamp at the
Ø
ceiling
Kitchen

Ø = Efficiency X each lamp watt = 85 X 36W = 3060Lum


500 X 9
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 3060
= 3, to use three lamps at the
Ø
ceiling.
Maids Bed room

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


150 X 5
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 1, to use one lamp at the
Ø
ceiling
Shower

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 4.7
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 1, to use one lamp at the
Ø
ceiling
Living & dining

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


200X 19.5
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 6, to use sixth lamps at the
Ø
ceiling.

PREPARED BY: FASIL W/G PPEE 031


Page 4
ELECTRICAL DESIGN REPORT

FIRST FLOOR

Shower

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 4.7
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 2, to use one lamp at the
Ø
ceiling. and one mirror lamps.
M. Kitchen

Ø = Efficiency X each lamp watt = 85 X 36W = 3060Lum


500 X 12
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 3060
= 4, to use four lamps at the
Ø
ceiling.
Family

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


200X 58.6
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 17, to use twelfth lamps at
Ø
the ceiling and fifth mirror lamps.
SECOND FLOOR

Shower

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 3
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 1, to use one lamp at the
Ø
ceiling.
Bed room

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


150 X 11
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 2, to use one lamp at the
Ø
ceiling and one mirror lamps.
PREPARED BY: FASIL W/G PPEE 031
Page 5
ELECTRICAL DESIGN REPORT

Closet

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 8
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 1, to use one lamp at the
Ø
ceiling
M. Bed room

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


150 X 26
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 6, to use four lamp at the
Ø
ceiling and two mirror lamps.
M . bath

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 11
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 3, to use one lamp at the
Ø
ceiling. and two mirror lamps.

THIRD FLOOR
Shower

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 3
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 1, to use one lamp at the
Ø
ceiling.
Bed room

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


150 X 11
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 2, to use one lamp at the
Ø
ceiling and one mirror lamps.
Family

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum

PREPARED BY: FASIL W/G PPEE 031


Page 6
ELECTRICAL DESIGN REPORT

200X 26
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 7, to use sixth lamps at the
Ø
ceiling and one mirror lamps.

Student room

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100X 17
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 3, to use three lamps at the
Ø
ceiling .

TERRACE

Shower

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


100 X 3
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 1, to use one lamp at the
Ø
ceiling.
Bed room

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


150 X 11
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 2, to use one lamp at the
Ø
ceiling and one mirror lamps.
Store

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


200 X 9
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 2, to use two lamp at the
Ø
ceiling.

Terrace

Ø = Efficiency X each lamp watt = 85 X 20W = 1700Lum


PREPARED BY: FASIL W/G PPEE 031
Page 7
ELECTRICAL DESIGN REPORT

100 X 9
𝑁𝑂. 𝑓𝑖𝑥𝑡𝑢𝑟𝑒 =
0.4 X 1700
= 1, to use one lamp at the
Ø
ceiling.
Power calculation
Power is calculated for each distribution board by taking in to account the
power of each incandescent lamp having an actual power of less than 100
VA to be 100 VA for incandescent lamp having more than 100 VA actual
proper is taken for single and double flour sent lamp power of 100 & 200 VA
are taken respectively.

To calculate the rating of ACB and cable size or single phase I =

For three phase I=



For each normal socket outlet a power of 200 VA is taken power of 1500 VA
& 3000 VA are taken for water heater and socket cooker (coffee machine)
respectively.
Power calculation SDB- 1F
Power for lighting [(12X20W)] = 240W=0.240KW
Power for lighting [(8X20W)+(4x36W)]= 304W=0.304KW
Power for socket outlet 1X200X4= 800W=0.8KW
Power for socket outlet 1X200X4= 800W=0.8KW
Power for water heater 2X1500 = 15000W=1.5KW
Power for water heater 2X1500 = 1500W=1.5KW
Power for stove 1X3000 = 3000W=3.0KW
Power for stove 1X3000 = 3000W=3.0KW
Total power for SDB- 1F
0.240KW+0.304KWX0.8KWX2+1.5KWX2+3.0KWX2= 11.144KW
Total Power = 11.144KW
D.F = 0.9

PREPARED BY: FASIL W/G PPEE 031


Page 8
ELECTRICAL DESIGN REPORT

S (tot): 11.144KW /0.8= 13.930KVA


Pmax: 11.144KW X0.9 =10.029KW

I = 19.0A, but we select the next higher


√ .
20A
Rating of A.CB =3x20A
Rating of cable size 5x4mm2 according to the size of A.C.B
Power calculation SDB- 2F
Power for lighting [(15X20W)] = 300W=0.300KW
Power for socket outlet 1X200X6= 1200W=1.2KW
Power for water heater 2X1500 = 15000W=1.5KW
Power for water heater 2X1500 = 1500W=1.5KW
Power for Jacuzzi 1X2000 = 2000W=2.0KW
Total power for SDB- 2F
0.300KW+1.2KWX1.5KWX2+2.0KW= 6.500KW
Total Power = 6.500KW
D.F = 0.9
S (tot): 6.500KW /0.8= 8.125KVA
Pmax: 6.500KW X0.9 =5.850KW

I = 30.2A, but we select the next higher 40A

Rating of A.CB =1x40A


Rating of cable size 3x10mm2 according to the size of A.C.B

Power calculation SDB- 3F


Power for lighting [(14X20W)] = 280W=0.280KW
Power for socket outlet 1X200X4= 800W=0.8KW
Power for socket outlet 1X200X4= 800W=0.8KW
Power for water heater 2X1500 = 15000W=1.5KW

PREPARED BY: FASIL W/G PPEE 031


Page 9
ELECTRICAL DESIGN REPORT

Total power for SDB- 3F


0.280KW+0.8KWX2+1.5KW= 3.380KW
Total Power = 3.380KW
D.F = 0.9
S (tot): 3.380KW /0.8= 4.225KVA
Pmax: 3.380KW X0.9 =3.042KW

I = 17.2A, but we select the next higher 20A

Rating of A.CB =1x20A


Rating of cable size 3x4mm2 according to the size of A.C.B
Power calculation SDB- RT
Power for lighting [(10X20W)] = 200W=0.200KW
Power for socket outlet 1X200X5= 1000W=1.0KW
Power for water heater 2X1500 = 15000W=1.5KW
Total power for SDB- RT
0.220KW+1.0KW+1.5KW= 2.700KW
Total Power = 2.700KW
D.F = 0.9
S (tot): 2.700KW /0.8= 3.375KVA
Pmax: 2.700KW X0.9 =2.430KW

I = 13.8A, but we select the next higher 20A

Rating of A.CB =1x20A


Rating of cable size 3x4mm2 according to the size of A.C.B

Power calculation MDB


Power for lighting [(8X20W+5X9W)] = 160W=0.160KW
Power for lighting [(11X20W+3X36W)] = 328W=0.328KW
Power for socket outlet 1X200X7 = 1400W=1.4KW
Power for water heater 2X1500 = 15000W=1.5KW
PREPARED BY: FASIL W/G PPEE 031
Page 10
ELECTRICAL DESIGN REPORT

Power for stove 1X3000 = 3000W=3.0KW


Power for stove 1X3000 = 3000W=3.0KW
Power for bell call 1X50 = 50W=0.05KW
TO SDB-1F= 11.144KW
TO SDB-2F = 6.500KW
TO SDB-3F = 3.380KW
TO SDB-RT =2.700KW
Total power for MDB
0.160KW+0.328KW+1.4KW+1.5KW+3.0KWX2+0.05KW+11.144KW+6.
500KW+3.380KW+2.700KW = 33.162KW
Total Power = 33.162KW
D.F = 0.9
S (tot): 33.162KW /0.8= 41.452KVA
Pmax: 33.162KW X0.9 =29.845KW

I = 56.6A, but we select the next higher


√ .
63A
Rating of A.CB =3X63A
Rating of cable size (5X16) mm2 according to the size of A.C.B
To check a voltage drop from MDB to KWHM and from MDB to SDB is
very short less than 10 meter so no need of checking voltage drop.
LOCATION OF OUT LETS
All dimension is measured from F.F level
Switch =1:30 cm
Junction box = 20 cm
Socket out lets =30 cm
Control Board =1:80cm
Bed size Switch =1m
Water Heater =170m
Stove =30cm
PREPARED BY: FASIL W/G PPEE 031
Page 11
ELECTRICAL DESIGN REPORT

Kitchens socket =1:10m


Bell Push-button: = 1m
Bell Indicate =1:70 cm
So we can use four corner lamps and to ceiling lamp with four down
light each.
Socket Point

One Normal Socket are provided for each table and bed in every room
TV sockets are provided in each room where TV to be installed.

Bed Room Three ordinary socket

Living & Dining Five ordinary socket

Master Bed Room three or four ordinary socket

Corridor one ordinary socket

Toilet one ordinary socket and one power socket for water heater

Master Base one ordinary socket and two power socket for water
heater and Jacuzzi.

Telephone Point

Telephone points are providing in each room conduit of 19/29mm


diameter are to be installed for Telephone Wire /Cable is for ETC
regulation.

Heat and smoke detectors

surface mounted smoke detector are providing in each room conduit of


16/19mm diameters are to be installed and heat detector are
providing were more heat is supposed to be there like kitchen garage
factory etc. the sounder is located at the corridor and it is advisable to
install 30cm below ceiling .

PREPARED BY: FASIL W/G PPEE 031


Page 12
ELECTRICAL DESIGN REPORT

Distribution Board

Plush mounted distribution board containing only miniature


automatic ckt breaker are installed at accessible point even in main
Distributions board the newly designed is according to the total power
required to designed the type of ckt breaker.

Power Calculative

Power is calculated for each distribution board by taking in to account


the power of each incandescent lamp having an actual power of less
than 100 VA to be 100 VA for incandescent lamp having more than
100 VA actual proper is taken for single and double flour sent lamp
power of 100 & 200 VA are taken respectively.

To calculate the rating of ACB and cable size or single phase I = P


V

For three phase I=



For each normal socket outlet a power of 200 VA is taken power of
1500 VA & 3000 VA are taken for water heater and socket cooker
(coffee machine/ respectively/

Scope of the Work

The scope of the work to be covered by the contractor including the


supply & installation of all material, equipment all other. Faculty
necessary for proper and effective operation of electrical system
specified here in the bill of quantities and indicated with drawing.

General Requirement

PREPARED BY: FASIL W/G PPEE 031


Page 13
ELECTRICAL DESIGN REPORT

Installation shall be carried out in accordance with the Ethiopia electrical


power corporation (EEPCOLs) the Ethiopian Telecommunication
corporation (ETC) rule and regulation.

The Ethiopia Electric power corporation supplied power to the main


distribution board with 3 phase 4 wire 380 V/220V 50HZ system. All
material and equipment for this supply connection and measuring
instrument for consumption of power shall be supplied by EEPCO’s
the electrical work including here is shall be excited in the best and
most effective manner and to be completed satisfaction of the engineer
who shall have a power to reject any work and material which is his
judgment are not in a full accordance with the drawing and
specification.

No change shall be done any part of the design without prior


approval of the consultant engineer the work shall meet all
requirement of neat good work man ship and be performed by skilled
election who possess the appropriate classification field of competence
issued by EEPCOs.