Installation Calculation Report: Model Project 01SLD - 1 - 860 - 6481 Full
Installation Calculation Report: Model Project 01SLD - 1 - 860 - 6481 Full
Installation Calculation Report: Model Project 01SLD - 1 - 860 - 6481 Full
Content
1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4
3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14
1 Project description
1.1 Project general settings
Installation standard IEC60364
Copper Copper
WD 1 1 QA 1 CCM2 Multi-core XLPE 35 1x25 1x25
Copper Copper
WD 7 1 QA 7 AA 7 Multi-core XLPE 35 1x10 1x10
Copper Copper
WD 5 1 QA 5 M1 Multi-core XLPE 35 1x10 1x10
Copper Copper
WD 2 1 QA 2 WC 3 Multi-core XLPE 35 1x35 1x35
Copper Copper
WD 0 1 TA 0 QA 0 Single-core XLPE 10 1x185 1x185
Copper Copper
WD 13 1 QA 13 CA 13 Multi-core XLPE 5 1x16 1x16
Copper Copper
2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 400 Al 35.4 558 12
0
3 Calculation notes
MV/LV transformer TA 0
Rated power 400 kVA
ukrT 4%
PkrT 4.5 kW
System earthing arrangement TN-C
No load secondary voltage Ur0 525V
Ur LV 500V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT or PkrT seized by user
Cable WD 0
Parameters
Length 10 m
Max length NA
Installation method 31
F
Single-core cables on horizontal
perforated tray
Type of cable Single-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 462 A
Sizing constraint Iz
Sizing Information Size-determining phase
Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.98
Standard table reference B-52-21
User correction factor 1
Overall factor 0.98
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 8/36
Selected phase
Cross section area 1x185 mm²
Core Copper
Iz under real conditions 522 A
Selected PEN
Cross section area 1x185 mm²
Core Copper
Circuit breaker QA 0
Ib 462 A
Distance from origin NA
Discrimination Results
UpStream Discrimination Limit
Design current
IL1 IL2 IL3 IN
Discrimination Results
UpStream Discrimination Limit
Cable WD 13
Parameters
Length 5m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 68 A
Sizing constraint Iz
Sizing Information Size-determining phase
Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x16 mm²
Core Copper
Iz under real conditions 100 A
Selected PE
Cross section area 1x16 mm²
Core Copper
LV capacitor bank CA 13
Target P.F. 0.928
Downstream reactive power to 43.1 kvar
correct
Design current
IL1 IL2 IL3 IN
Voltage drop
Cumulated from upstream Circuit
Discrimination Results
UpStream Discrimination Limit
Cable WD 2
Parameters
Length 35 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 155 A
Sizing constraint Iz
Sizing Information Size-determining phase
Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x35 mm²
Core Copper
Iz under real conditions 158 A
Selected PEN
Cross section area 1x35 mm²
Core Copper
Design current
IL1 IL2 IL3 IN
Discrimination Results
UpStream Discrimination Limit
Cable WD 1
Parameters
Length 35 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 114 A
Sizing constraint Iz
Sizing Information Size-determining phase
Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 16/36
Selected phase
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 127 A
Selected PEN
Cross section area 1x25 mm²
Core Copper
Design current
IL1 IL2 IL3 IN
Discrimination Results
UpStream Discrimination Limit
Cable WD 5
Parameters
Length 35 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 30 A
Sizing constraint Voltage drop
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 18/36
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Selected PEN
Cross section area 1x10 mm²
Core Copper
Charge M1
U 500 V
S 25.9 kVA
P 22 kW
I 29.9 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Main) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Voltage drop
Cumulated from upstream Circuit
Discrimination Results
UpStream Discrimination Limit
Cable WD 6
Parameters
Length 40 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 75 A
Sizing constraint Iz
Sizing Information Size-determining phase
Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 21/36
Selected phase
Cross section area 1x16 mm²
Core Copper
Iz under real conditions 100 A
Selected PEN
Cross section area 1x16 mm²
Core Copper
Charge M2
U 500 V
S 64.7 kVA
P 55 kW
I 74.7 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Main) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Discrimination Results
UpStream Discrimination Limit
Cable WD 7
Parameters
Length 35 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 50 A
Sizing constraint Voltage drop
Sizing Information The CSA of cable WD 7 has been
increased from 6 to 10 to comply with the
voltage drop in the circuit.
Size-determining phase
Sized with Ir
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 24/36
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Selected PEN
Cross section area 1x10 mm²
Core Copper
Charge AA 7
U 500 V
S 43.3 kVA
P 36.8 kW
I 50 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Main) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Discrimination Results
UpStream Discrimination Limit
Cable WD 10
Parameters
Length 35 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 30 A
Sizing constraint Voltage drop
Sizing Information The CSA of cable WD 10 has been
increased from 2.5 to 4 to comply with
the voltage drop in the circuit.
Size-determining phase
Sized with Ir
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 27/36
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Selected PEN
Cross section area 1x10 mm²
Core Copper
Charge M4
U 500 V
S 25.9 kVA
P 22 kW
I 29.9 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Main) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Discrimination Results
UpStream Discrimination Limit
Cable WD 11
Parameters
Length 40 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 50 A
Sizing constraint Voltage drop
Sizing Information The CSA of cable WD 11 has been
increased from 6 to 10 to comply with the
voltage drop in the circuit.
Size-determining phase
Sized with Ir
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 30/36
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Selected PEN
Cross section area 1x10 mm²
Core Copper
Charge M5
U 500 V
S 43.3 kVA
P 36.8 kW
I 50 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Main) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Discrimination Results
UpStream Discrimination Limit
Cable WD 12
Parameters
Length 35 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 1%
Ib 34 A
Sizing constraint Voltage drop
Sizing Information The CSA of cable WD 12 has been
increased from 4 to 6 to comply with the
voltage drop in the circuit.
Size-determining phase
Sized with Ir
Project: Model Project 01SLD_1_860_6481 30/06/2021
Page 33/36
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Selected PEN
Cross section area 1x10 mm²
Core Copper
Charge H1
U 500 V
S 29.4 kVA
P 25 kW
I 34 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Main) 1
Harmonic generator No
THDI3 0
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Capacitors 15 QA 13 NSX100B
3.5.2 Circuit WC 3
Busbar WC 3
Parameters
Switchboard Name UC 4
Switchboard Range No preference
Rating (A) 0
IP Undefined
Feeder
Circuit name Protection name Protection type
Load 6 QA 5 NG125N
Load 7 QA 6 NG125N
Load 8 QA 7 NG125N
Load 12 QA 10 NG125N
Load 13 QA 11 NG125N
Load 14 QA 12 NG125N