Doc # CONSUL-FOR-SER-016

FIELD SERVICE REPORT


Rev # 01(25-Sep-15)
THREE PHASE UPS
Page # 1 Of 1
Service Request No: Order No: Call Received ON & Time:
1100988574 6000947829 02-APR-2021 15:03
Contact Person: MR RAJESH
Customer Name & Address: Contact Number: 9962906617
CHENNAI INSTITUTE OF TECHNOLOGY
Mail Id: RAJESKANNANS@CITCHENNAI.NET
MANGADU RD, SARATHY NAGAR, CHENNAI, TAMIL NADU
600069 Web Site:
Warranty Period: FROM 05-MAR-2016 TO 04-JUN-2021
Product Name: Model: Sub Model: Serial Number: Capacity: Unit Status:
THREE PHASE FALCON 5K 000020160100050471 120 KVA WARRANTY
UPS
Battery Make: AH: Model: Battery Bank: Quantity: Batch code:
EXIDE 65 SMF 1 50 4SK030720009439
Call category: Customer Complaint: Call Status:
WARRANTY PM CALL WTY PM COMPLETED
Engineer Diagnosis / Observation: TO CHECK UPS AND BATTERIES , TO DO ONLINE PM PROPERLY
Corrective Action: SINCE SHUTDOWN TIME IS NOT GIVEN, ONLINE PM HAS BEEN DONE. UPS IS WORKING WELL AND ALL THE PARAMETERS ARE
CHECKED. DUST FORMATION IN BATTERIES AND UPS ARE CLEANED WELL. BACKUP HAS BEEN CHECKED AND FOUND TAHT THAT 1 BATTERY
ARE IN WEAK CONDITION DURING CHARGING AND DISCHARGING & UPS IS WORKING NORMAL IN BOTH MODES.
Technical Suggestion if any: NIL
Spares Replaced if Any:
Spares Need to Replace if Any:
I/P Volts I/P Current Rectifier DC Volts Battery O/P Volts O/P Current Frequency Temperature
Important RN YN BN NE RA YA BA - Volt Amps UN VN WN UA VA WA I/P O/P Ambi HS
PN +VeE
Parameters
225.5 226.5 228.5 1 21 37 26 VeE 675.5 -- 230 229.3 232.2 24 23 21 50 50 25 30
-- -- --
Application:SYSTEM LOAD , Connected Equipment Details: SYSTEM LOAD
Customer Remarks:
Engineer Signature:
Reported Complaints Have Been Call Attended Date Time:
Rectified,Servicing Done to Our Satisfaction. We 17-JUN-2021 11:50 Unit Working Status: Engineer Name:
agree to pay your Charges for the same if Call completed Date Time: WORKING OK KAUSHIK.B
applicable 17-JUN-2021 12:28
17-JUN-2021 11:58
Customer Photo Customer Sign Unit Serial Number Display Site

MR RAJESH

NO
IMAGE

17-JUN-2021 12:28 17-JUN-2021 11:57 17-JUN-2021 11:57 17-JUN-2021 11:58


Branch / ASP:- 119, 120, 120A, ELECTRICAL & ELECTRONICS INDUSTRIAL ESTATE, PERUNGUDI, CHENNAI

Corporate Office:- Fuji Electric Consul Neowatt Pvt Ltd., 119, 120, 120 A Electrical and Electronics Industrial Estate, Perungudi, Chennai-600 096, Tamil Nadu, India

Customer Care Number : +91 781000 9955 Email: support.fei@fujielectric.com Web: fujielectric.co.in & india.fujielectric.com

PRODUCTS OFFERING
Three Phase UPS / Single Phase UPS / Harmonic Filters / Servo Stabilizers / Solar Inverter / AC Low Voltage Drives / AC Medium Voltage Drives / Servo Systems / HMI / Motion Control /
Instrumentation / Automation / Control Panels / Power Semiconductors

SERVICES OFFERING
Annual Maintenance Contracts (CAMC & LAMC) / Battery Monitoring System / Battery Replacement/ Commissioning/ Engineering/ Power Audits / Remote Monitoring/ Rental UPS And Stabilizers /
Repairs/ Replacements./ Retrofits/ Stabilizer Oil Replacement / Training
FIELD SERVICE REPORT Doc # CONSUL-FOR-SER-011
THREE PHASE UPS - BREAKDOWN Rev # 01(25-Sep-15)
PREVENTIVE MAINTENANCE Page # 1 Of 2

PM Request No: Order No: Call Received ON & Time:


1100988574 6000947829 02-APR-2021 15:03
Total DC Bus Voltage:
UPS Configuration : Standalone 1*1 DC+(V): 338 DC-(V): 338
676
Monitoring Software : NO SNMP : Mode Bud:
Stored Data & Alarm's logs Downloaded: NO SD Card Data and Alarms Logs Downloaded: NO

Preliminary Checks
FIELD SERVICE REPORT Doc # CONSUL-FOR-SER-011
THREE PHASE UPS - BREAKDOWN Rev # 01(25-Sep-15)
PREVENTIVE MAINTENANCE Page # 1 Of 2

1 UPS Room Cleaness OK 8 Battery Room Cleaness OK


2 UPS Room Ventilation OK 9 Battery Room Ventilation OK
3 Condition of Ventilation Equipment OK 10 Tightness of switch gears OK
Fire Extinguisher Type (CO2 Type
4 Fire Extinguisher Installed NO 11 NA
Recommended)
5 Tightness of Power Cable ( External) YES 12 Tightness of Power cable Internal OK
6 PCB Fitted Securely YES 13 Control connections as per electrical Drawing YES
Tightness of AC Capacitor Crimping &
7 OK 14 Re-tighten all battery cables YES
Connections
Remarks if any: To check UPS and batteries , to do online pm properly
Battery Parameters
SL No Voltage On Charging Voltage on Discharging
1 13.5 12.2
2 13.4 12.5
3 13.5 12.4
4 13.3 12.2
5 13.5 12.4
6 13.3 12.5
7 13.5 12.3
8 13.4 12.3
9 13.4 12.4
10 13.3 12.3
11 12.2 10
12 13.3 12.4
13 13.5 12.4
14 13.3 12.2
15 13.3 12.4
16 13.2 12.2
17 13.4 12.3
18 13.5 12.3
19 13.5 12.3
20 13.4 12.3
21 13.4 12.4
22 13.5 12.1
23 13.4 12.6
24 13.7 12.4
25 14 12.5
26 13.8 12.6
27 13.5 12.6
28 13.3 12.2
29 13.3 12.2
30 13.4 12.2
31 13.5 12.6
32 13.5 12.6
33 13.5 12.4
34 13.2 12.2
35 13.3 12.3
36 13.4 12.3