Aircon Midterm Ipapasa

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 19

Eugenio I T.

Gonzalo BSME IV-A

LOCATION: 14.12⁰ N Latitude


TIME: 3:00 P.M.
DATE: May 21
3 Story Commercial Building
SOLAR HEAT GAIN THROUGH GLASS

CONDITIONS DB %RH
OUTDOOR 37 70
ROOM 25 50
DIFFERENCE 12 20

SIDE OF NO. OF
NO. OF WALL NO. OF DOOR
THE WINDOW & AREA
FLOOR DIRECTION & IT’S & IT’S
BUILDI IT’S in m2
DIMENSIONS DIMENSIONS
NG DIMENSIONS
2 3.5 x 2 1 D1
Front East - - 23
1 2.5 x 2
Ground Rear West - - 3 3.5 x 2 1 D2 23
Floor Right
North - - 2 2.5 x 2 1 D2 12
Side
Left Side South - - 3 2.5 x 2 1 D1 19
Front East 6 W3 1 2.5 x 4 6 D2 40
Typical
4 D2
2nd Floor Rear West 4 W3 - - 24
and 3rd 1 D1
Floor Right
North 2 W2 - - - - 4.2
Side
Left Side South 2 W2 - - - - 4.2
Eugenio I T. Gonzalo BSME IV-A

Table 17.9, Refrigeration and Air Conditioning 3rd Edition, 558-567

SIDE OF HEAT AREA OF GLASS,


HEAT GAIN PER
FLOOR THE DIRECTION GAIN*, m2 (windows, walls
SIDE, W
BUILDING W/m2 & doors)

Front East 41 23 943


Rear West 451.71 23 10389.33
Ground
Right Side North 86.93 12 1043.15
Floor
Left Side South 41 19 779
TOTAL HEAT GAIN OF FLOOR: 13154.48

Front East 41 34 1394


Rear West 451.71 20 9034.2
Typical 2nd
Right Side North 86.93 4.2 365.106
Floor and
3rd Floor Left Side South 41 4.2 172.2
TOTAL HEAT GAIN OF FLOOR: 21931.012
TOTAL SOLAR HEAT GAIN THROUGH GLASS 35085.492

SOLAR HEAT GAIN THROUGH WALLS AND ROOF


Table 18.1, Refrigeration and Air Conditioning 3rd Edition, 576
Wall Materials

Thermal
fo fi
Material Conductivity, k
Density W/m2K W/m2K
(W/m⁰K)
Concrete 1.73 1920
23 5
Plaster 8.65 1885

Roof Materials

Thermal
Material Density
Conductivity,k (W/m⁰K)
Concrete 1.73 1920
Plywood 0.1 544
PUF (Polyurethane Foam) 0.0173 30
Eugenio I T. Gonzalo BSME IV-A

Wall Details
Wall height: Ground Floor 5m
Second & third floor 4m
Concrete thickness: 15cm (all floors)
Plaster thickness: 0.015cm (all floors)
Formula:

1 1 ∆ x concrete ∆ x plaster 1
= + + +
U f i k concrete k plaster f o
1 1 0.15 0.015 1
= + + +
U 5 1.73 8.65 23

U =3.01W /m2 K

∆ t 'e =[ ( t o−t i ) −8.3 ]−(∆ T dr−11.1)( 0.25)

∆ t 'e =[ ( 37−25 )−8.3 ] + ¿]

∆ t 'e =4.225

kg
mass of wall per area= 1920
( m3 )
( 0.15 m+0.015 m )

kg
mass of wall per area=317
m3

Roof Details
15 cm RCC slab with 4 cm PUF (Polyurethane Foam) & 7mm Plywood
Formula:

1 1 ∆x ∆x ∆x 1 1
U = = + concrete + Polyurethane Foam + Plywood + +
R f i k concrete k Polyurethane Foam k Plywood f o airgap
1 1 0.15 0.04 0.007 1 1
U= = + + + + +
R 23 1.73 0.0173 0.1 2.2 4.8

U =3.18/m 2 K
Eugenio I T. Gonzalo BSME IV-A

kg
(
mass ofroof per area= 1920
m3 )
∗0.15 + ( 30∗0.04 ) + ( 544∗0.007 )

kg
mass ofroof per area=293.008
m3
Te @ 3 PM (⁰C): 17.47
Te’ @ 3PM (⁰C): 17.47 + 4.225=21.69

Table 18.9, Refrigeration and Air Conditioning 3rd Edition, 602-605

DIRECTION Te @ 3 PM (⁰C) Te’ @ 3PM (⁰C)


East 7.3 11.525
West 10.6 14.825
North 4.4 8.625
South 13.9 18.125

GROUND FLOOR

Q E=( 3.01 W /m 2 K ) ( 97 ) m2 ( 11.525 K )=3364.95 W

Q W =( 3.01W /m 2 K ) ( 117 ) m 2 ( 14.825 K )=5220.92 W

Q N =( 3.01 W /m 2 K ) ( 68 ) m2 ( 8.625 K )=1765.365 W

Q S =( 3.01 W /m 2 K ) ( 71 ) m2 ( 18.125 K )=3873.49 W

2ND FLOOR

Q E=( 3.01 W /m 2 K ) ( 78 ) m 2 (11.525 K )=2705.84 W

Q W =( 3.01W /m 2 K ) ( 92 ) m2 ( 14.825 K )=4239.21 W


Eugenio I T. Gonzalo BSME IV-A

Q N =( 3.01 W /m 2 K ) (59.8 ) m 2 ( 8.625 K )=1552.48W

Q S =( 3.01 W /m 2 K ) ( 67.8 ) m 2 ( 18.125 K )=3698.91 W

3RD FLOOR SLAB

QSLAB =( 3.18 W /m2 K ) ( 200 ) m2 ( 21.69 K ) =13794.84 W

SIDE OF HEAT AREA


HEAT
FLOOR THE DIRECTION GAIN*, EXPOSE, ΔTe(⁰C)
GAIN, W
BUILDING W/m2K m2

Front East 3.01 97 11.525 3364.95


Rear West 3.01 117 14.825 5220.92
Ground
Right Side North 3.01 68 8.625 1765.365
Floor
Left Side South 3.01 71 18.125 3873.49
TOTAL HEAT GAIN OF FLOOR: 14224.73

Front East 3.01 78 11.525 2705.84


nd
Typical 2 Rear West 3.01 92 14.825 4239.21
Floor and
3rd Floor Right Side North 3.01 59.8 8.625 1552.48
Left Side South 3.01 67.8 18.125 3698.91
rd
3 Floor
3.18 200 21.69 13794.84
Slab
TOTAL HEAT GAIN OF FLOOR: 38187.72
TOTAL SOLAR HEAT GAIN THROUGH WALLS AND ROOF
52412.45

OCCUPANCY LOAD

Degree of No. of Person Sensible Heat Latent Heat Heat Gain (W)
SH LH
Eugenio I T. Gonzalo BSME IV-A

FLOOR ACTIVITY (Approximation (W) (W)


1st Floor Seated at Rest )
10 67 33 67 330
Office Work 7 70 60 490 420
Standing 18 70 60 1260 1080
Moderate
10 80 80 800 800
Work
Seated, very
15 70 50 1050 750
light work
Eating in the
40 85 75 3400 3000
Restaurant

Typical 2nd &


6030
3rd Floor Resting 90 67 33 2970

Seated at Rest 10 67 33 670 330

Standing,
Walking 10 70 60 700 600
slowly

TOTAL HEAT GAIN 14467 10280

Note:
Value of Sensible and Latent Heat was taken from this address
http://www.engineeringtoolbox.com/metabolic-heat-persons-d_706.html

LIGHTING LOAD
Type of Lamp Used: Fluorescent

HEAT
Eugenio I T. Gonzalo BSME IV-A

LOAD
ILLUMINATIO FROM HEAT GAIN
FLOOR PLACE N LIGHTS AREA
(lumens/m2) (W)
(W/m2) (m2)

132
1st Floor RESTAURANT 500 16.65 2197.8

3.35
DRUG STORE 150 24 80.4

HALLWAY 200 6.7 24 160.8

OFFICE 500 16.65 19.5 324.675


TOILET AND
BATHROOM 500 16.65 24 399.6
STOCK ROOM 150 3.35 18 60.3
WAITING
150 3.35 24 80.4
AREA
GROCERY 500 16.65 180 2997
COMPUTER
500 16.65 24 399.6
SHOP

SUB-TOTAL: 6700.575
nd
TYPICAL 2
To 3rd Floor ROOMS 500 16.65 300 4995
LOBBY 250 8.35 54 450.9
HALLWAYS 200 6.7 60 402
SUB-TOTAL OF TYPICAL 2nd To 3rd Floor 11695.8
TOTAL HEAT GAIN= 1.25 x 18396.375 = 22995.47W 22995.47

APPLIANCE LOAD
HEAT GAIN
SENSIBLE LATENT
SH LH
FLOOR APPLIANCE QUANTITY HEAT HEAT
(W) (W)
(W) (W)
Eugenio I T. Gonzalo BSME IV-A

1st FLOOR TELEVISION 2 75 ____ 4400

PRINTER 1 320 ____ 640

CASH REGISTER 2 48 ____ 48

COFFEE
3 1050 450 2100 1350
MAKER

-
FREEZER 2 320 320

-
REFRIGERATOR 2 690 690

WATER COOLER 1 1750 1750

COMPUTER 18 75 2250

SUB
12198 1350
TOTAL

TYPICAL
rd TELEVISION 14 75 - 2100
FLOOR
FL
TOTAL HEAT GAIN 14298 1350

INFILTRATION LOAD 1st


TEMPER
ATURE
HEIGH AIR INFILTRATIO HEAT
AREA, m² DIFF/ FACTOR REMARKS
T, m CHANGE N, cmm GAIN, W
HUMIDIT
Y DIFF
468 5 0.5 19.5 12 20.4 (4773.6) Refrigeration and
Airconditioning C.P.
468 5 0.5 19.5 0.0188 50000 (18330)
Arora 3rd Edition

VENTILATION LOAD 1st


Eugenio I T. Gonzalo BSME IV-A

HEAT
NO. OF CMM/ VENTILATION, TEMP DIFF/
APPLICATION FACTOR GAIN , REMARKS
PERSONS PERSON cmm HUM DIFF
W

Office 5 0.283 1.415 12 20.4 346.392


Restaurant 40 0.323 12.92 12 20.4 3162.816
Hallways 20 0.075 1.5 12 20.4 367.2
Mini Grocery 20 0.283 5.66 12 20.4 1385.568
Computer Shop 10 0.325 3.25 12 20.4 795.6
Table 6.1;
Drug store 5 0.198 0.99 12 20.4 242.352
ASHRAE
TOTAL HEAT GAIN (SENSIBLE) 6299.928
Standards
Office 5 0.283 1.415 0.0188 50000 1330.1
Restaurant 40 0.323 12.92 0.0188 50000 12144.8
Hallways 20 0.075 1.5 0.0188 50000 1410
Mini Grocery 20 0.283 5.66 0.0188 50000 5320.4
Computer Shop 10 0.325 3.25 0.0188 50000 3055
Drug store 5 0.198 0.99 0.0188 50000 930.6
TOTAL HEAT GAIN (LATENT) 24190.9
FLOOR SENSIBLE AND LATENT HEAT 1st
EFFECTIVE FLOOR SENSIBLE HEAT, W 61922.858
EFFECTIVE FLOOR LATENT HEAT, W 31920.9
GRAND TOTAL HEAT LOAD, W 93843.758 GROUND FLOOR
GRAND TOTAL HEAT LOAD, TR 26.66
AREA PER TON, m²/TR 18

INFILTRATION LOAD 2nd


TEMPERAT
HEIGHT AIR INFILTRATIO URE DIFF/ FACTO HEAT
AREA, m² REMARKS
,m CHANGE N, cmm HUMIDITY R GAIN, W
DIFF
432 4 2 57.6 12 20.4 (14100.4) Refrigeration and
Airconditioning C.P.
432 4 2 57.6 0.0188 50000 (5414.4)
Arora 3rd Edition

VENTILATION LOAD 2nd


Eugenio I T. Gonzalo BSME IV-A

HEAT
NO. OF CMM/ VENTILATION, TEMP DIFF/
APPLICATION FACTOR GAIN , REMARKS
PERSONS PERSON cmm HUM DIFF
W

Bedroom 55 0.283 15.565 12 20.4 3810.312 Table 6.1;


Hallways 15 0.075 1.125 12 20.4 275.5 ASHRAE
TOTAL HEAT GAIN (SENSIBLE) 4085.812
Bedroom 55 0.283 15.565 0.0188 50000 14631.1
Hallways 15 0.075 1.125 0.0188 50000 1057.5
TOTAL HEAT GAIN (LATENT) 15688.6
FLOOR SENSIBLE AND LATENT HEAT 2nd
EFFECTIVE FLOOR SENSIBLE HEAT, W 41957.638 SECOND FLOOR
EFFECTIVE FLOOR LATENT HEAT, W 19588.6
GRAND TOTAL HEAT LOAD, W 61546.238
GRAND TOTAL HEAT LOAD, TR 17.5
AREA PER TON, m²/TR 25

INFILTRATION LOAD 3rd


TEMPERAT
HEIGHT AIR INFILTRATIO URE DIFF/ FACTO HEAT
AREA, m² REMARKS
,m CHANGE N, cmm HUMIDITY R GAIN, W
DIFF
432 4 2 57.6 12 20.4 (14100.4) Refrigeration and
Airconditioning C.P.
432 4 2 57.6 0.0188 50000 (5414.4)
Arora 3rd Edition

VENTILATION LOAD 3rd


Eugenio I T. Gonzalo BSME IV-A

HEAT
NO. OF CMM/ VENTILATION, TEMP DIFF/
APPLICATION FACTOR GAIN , REMARKS
PERSONS PERSON cmm HUM DIFF
W

Bedroom 55 0.283 15.565 12 20.4 3810.312


Table 6.1;
Hallways 15 0.075 1.125 12 20.4 275.5
ASHRAE
TOTAL HEAT GAIN (SENSIBLE) 4085.812 Standards
Bedroom 55 0.283 15.565 0.0188 50000 14631.1
Hallways 15 0.075 1.125 0.0188 50000 1057.5
TOTAL HEAT GAIN (LATENT) 15688.6
FLOOR SENSIBLE AND LATENT HEAT
EFFECTIVE FLOOR SENSIBLE HEAT, W 57852.478 GROUND FLOOR
EFFECTIVE FLOOR LATENT HEAT, W 19588.6
GRAND TOTAL HEAT LOAD, W 77441.078
GRAND TOTAL HEAT LOAD, TR 22
AREA PER TON, m²/TR 20

DUCT CALCULATION 1st FLOOR


EQUAL FRICTION METHOD
RSH = 61.9KW
RLH = 31.9KW
OASH = 6.3KW
OALH = 2.4KW
RSHF = 61.9/(61.9 + 31.9) = 0.66
ERSH = 61.9 + (0.1) (6.3) = 62.53
Eugenio I T. Gonzalo BSME IV-A

ERLH = 31.9 + (0.1) (2.4) = 32.14


ESHF = 62.53/(62.53 + 32.14) = 0.66
ERSH
( cmm )d∨Q v =
( 0.0204 ) ( t i −t ADP ) ( 1−BPF )

BY USING PSYCHROMETRIC CHART


t ADP=7

62.53
( cmm )d∨Q v =
( 0.0204 ) ( 25−7 )( 1−0.1 )

Q v =189.21 cmm∨3.15 m 3 /s
A

(Reference: Refrigeration and Air Conditioning by C.P. Arora Table 21.8, Page 731)

Controlling factor CONTROLLING FACTOR : FRICTION


MAIN DUCTS MAIN DUCTS BRANCH DUCTS
SUPPLY RETURN SUPPLY RETURN
450 600 450 480 360

SUPPLY DUCT
FROM Fig. 21.15 Duct friction chart
FRICTION LOSS = 1.7 Pa/m
DUCT DIAMETER = 0.63m = 63cm
RECTANGULAR DUCT = 70cm x 48cm

RETURN DUCT
Q v =¿ 189.21 – 51.47= 137.74 cmm = 2.29m3/s
A

FROM Fig. 21.15 Duct friction chart


FRICTION LOSS = 0.85 Pa/m
DUCT DIAMETER = 0.66m = 66cm
RECTANGULAR DUCT = 74cm x 50cm
DUCT CALCULATION 2nd FLOOR
Eugenio I T. Gonzalo BSME IV-A

EQUAL FRICTION METHOD


RSH = 42KW
RLH = 19.6KW
OASH = 4.1KW
OALH = 15.7KW
RSHF = 42/(42 + 19.6) = 0.68
ERSH = 42 + (0.3) (4.1) = 43.23
ERLH = 19.6 + (0.3) (4.1) = 20.83
ESHF = 43.23/(43.23 + 20.83) = 0.67
ERSH
( cmm )d∨Q v =
( 0.0204 ) ( t i −t ADP ) ( 1−BPF )

BY USING PSYCHROMETRIC CHART


t ADP=7

43.23
( cmm )d∨Q v =
( 0.0204 ) ( 25−7 )( 1−0.3 )

Q v =168.18 cmm∨2.8 m3 / s
A

(Reference: Refrigeration and Air Conditioning by C.P. Arora Table 21.8, Page 731)

Controlling factor CONTROLLING FACTOR : FRICTION


MAIN DUCTS MAIN DUCTS BRANCH DUCTS
SUPPLY RETURN SUPPLY RETURN
180 300 240 180 180

SUPPLY DUCT
FROM Fig. 21.15 Duct friction chart
FRICTION LOSS = 0.3 Pa/m
DUCT DIAMETER = 0.83m = 83cm
RECTANGULAR DUCT = 90cm x 64cm

RETURN DUCT
Eugenio I T. Gonzalo BSME IV-A

Q v =¿ 168.18 – 33.38= 135 cmm = 2.25m3/s


A

Duct velocity, C = mpm or 7.5m/s


FROM Fig. 21.15 Duct friction chart
FRICTION LOSS = 0.9 Pa/m
DUCT DIAMETER = 0.63m = 63cm
RECTANGULAR DUCT = 74cm x 50cm

DUCT CALCULATION 3nd FLOOR


EQUAL FRICTION METHOD
RSH = 58KW
RLH = 20KW
OASH = 4.1KW
OALH = 15.7KW
RSHF = 58/(58 + 20) = 0.74
ERSH = 58 + (0.3) (4.1) = 59.23
ERLH = 20 + (0.3) (4.1) = 21.23
ESHF = 59.23/(59.23 + 21.23) = 0.74
ERSH
( cmm )d∨Q v =
( 0.0204 ) ( t i −t ADP ) ( 1−BPF )

BY USING PSYCHROMETRIC CHART


t ADP=7

59.23
( cmm )d∨Q v =
( 0.0204 ) ( 25−8 )( 1−0.3 )

Q v =243.99 cmm∨4.1 m3 /s
A

(Reference: Refrigeration and Air Conditioning by C.P. Arora Table 21.8, Page 731)

Controlling factor CONTROLLING FACTOR : FRICTION


MAIN DUCTS MAIN DUCTS BRANCH DUCTS
Eugenio I T. Gonzalo BSME IV-A

SUPPLY RETURN SUPPLY RETURN


180 300 240 180 180

SUPPLY DUCT
FROM Fig. 21.15 Duct friction chart
FRICTION LOSS = 0.24 Pa/m
DUCT DIAMETER = 1.3m = 130cm
RECTANGULAR DUCT = 96cm x 88cm

RETURN DUCT
Q v =¿ 243.99 – 33.38= 210.61 cmm = 3.5m3/s
A

FROM Fig. 21.15 Duct friction chart


FRICTION LOSS = 0.1 Pa/m
DUCT DIAMETER = 1m = 100cm
RECTANGULAR DUCT = 96cm x 88cm
Eugenio I T. Gonzalo BSME IV-A

SUPPLY (GROUND FLOOR)


VOLUME ACTUAL ACTUAL
PRESSURE DUCT DUCT
LENGTH FLOW DIAMETER AREA VELOCITY PRESSURE DUCT DUCT
SECTIONS LOSS WIDTH HEIGHT
RATE WIDTH HEIGHT
(mm) (cu.m/s) (m) (sq.m) (m/s) (mmH2O) (mmH2O) (mm) (mm) (mm) (mm)
AB 3.150000 0.630000 0.311724 10.000000 6.116208 0.00 700 480 700 480
BF 2.450000 0.570000 0.255176 9.300000 5.289908 0.00 600 460 600 460
FK 1.400000 0.460000 0.166190 8.400000 4.315596 0.00 500 360 500 360
KM 0.700000 0.370000 0.107521 7.200000 3.170642 0.00 420 280 420 280
CD 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
CE 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
FG 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
HI 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
HJ 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
KL 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
KP 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
MN 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
MO 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180
EF 0.350000 0.280000 0.061575 6.000000 2.201835 0.00 380 180 380 180

RETURN (GROUND FLOOR)


VOLUME ACTUAL ACTUAL
PRESSURE DUCT DUCT
LENGTH FLOW DIAMETER AREA VELOCITY PRESSURE DUCT DUCT
SECTIONS LOSS WIDTH HEIGHT
RATE WIDTH HEIGHT
(mm) (cu.m/s) (m) (sq.m) (m/s) (mmH2O) (mmH2O) (mm) (mm) (mm) (mm)
AP 2.290000 0.660000 0.342119 7.500000 3.440367 0.00 740 500 740 500
PQ 2.040000 0.620000 0.301907 7.100000 3.083180 0.00 780 420 780 420
QR 1.540000 0.550000 0.237583 6.800000 2.828135 0.00 580 440 580 440
AB 1.290000 0.480000 0.180956 6.200000 2.351070 0.00 620 320 620 320
BD 1.040000 0.460000 0.166190 6.000000 2.201835 0.00 500 360 500 360
DI 0.540000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
PF 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
QG 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
QH 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
BC 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
DE 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
JK 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
JL 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
MN 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
MO 0.250000 0.350000 0.096211 5.100000 1.590826 0.00 440 240 440 240
Eugenio I T. Gonzalo BSME IV-A

SUPPLY (SECOND FLOOR)


VOLUME ACTUAL ACTUAL
PRESSURE DUCT DUCT
SECTION LENGTH FLOW DIAMETER AREA VELOCITY PRESSURE DUCT DUCT
LOSS WIDTH HEIGHT
S RATE WIDTH HEIGHT
(mm) (cu.m/s) (m) (sq.m) (m/s) (mmH2O) (mmH2O) (mm) (mm) (mm) (mm)
AB 2.800000 0.830000 0.541060 5.000000 1.529052 0.00 860 680 860 680
BE 2.300000 0.770000 0.465662 4.800000 1.409174 0.00 780 640 780 640
EH 1.800000 0.730000 0.418538 4.600000 1.294190 0.00 700 640 700 640
HK 1.300000 0.630000 0.311724 4.200000 1.078899 0.00 640 540 640 540
KN 0.800000 0.480000 0.180956 4.700000 1.351070 0.00 620 320 620 320
NP 0.550000 0.420000 0.138544 3.400000 0.707034 0.00 460 320 460 320
BC 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
BD 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
FG 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
HJ 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
HI 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
KM 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
KL 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
NO 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
PQ 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190
PR 0.250000 0.340000 0.090792 2.800000 0.479511 0.00 280 190 280 190

RETURN (SECOND FLOOR)


VOLUME ACTUAL ACTUAL
PRESSURE DUCT DUCT
SECTION LENGTH FLOW DIAMETER AREA VELOCITY PRESSURE DUCT DUCT
LOSS WIDTH HEIGHT
S RATE WIDTH HEIGHT
(mm) (cu.m/s) (m) (sq.m) (m/s) (mmH2O) (mmH2O) (mm) (mm) (mm) (mm)
AB 2.250000 0.870000 0.594467 4.000000 0.978593 0.00 840 720 840 720
BC 2.050000 0.820000 0.528101 3.900000 0.930275 0.00 840 680 840 680
CD 1.850000 0.800000 0.502654 3.800000 0.883180 0.00 800 680 800 680
DE 1.650000 0.780000 0.477836 3.700000 0.837309 0.00 780 680 780 680
AF 1.450000 0.730000 0.418538 3.600000 0.792661 0.00 760 700 760 700
FG 1.250000 0.700000 0.384845 3.400000 0.707034 0.00 740 560 740 560
GH 1.050000 0.650000 0.331830 3.200000 0.626300 0.00 720 480 720 480
HI 0.850000 0.630000 0.311724 3.000000 0.550459 0.00 700 460 700 460
IJ 0.650000 0.520000 0.212371 2.800000 0.479511 0.00 680 340 680 340
JK 0.450000 0.480000 0.180956 2.500000 0.382263 0.00 620 320 620 320
KL 0.250000 0.370000 0.107521 2.200000 0.296024 0.00 620 200 620 200
B 0.200000 0.360000 0.101788 2.100000 0.269725 0.00 580 200 580 200
C 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
D 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
E 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
F 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
I 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
J 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
K 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
L 0.200000 0.270000 0.057255 2.100000 0.269725 0.00 440 150 440 150
Eugenio I T. Gonzalo BSME IV-A

SUPPLY (THIRD FLOOR)


VOLUME ACTUAL ACTUAL
PRESSURE DUCT DUCT
SECTION LENGTH FLOW DIAMETER AREA VELOCITY PRESSURE DUCT DUCT
LOSS WIDTH HEIGHT
S RATE WIDTH HEIGHT
(mm) (cu.m/s) (m) (sq.m) (m/s) (mmH2O) (mmH2O) (mm) (mm) (mm) (mm)
AB 4.100000 1.300000 1.327322 5.000000 1.529052 0.00 960 880 960 880
BE 2.300000 0.830000 0.541060 4.200000 1.078899 0.00 960 600 960 600
EH 1.800000 0.770000 0.465662 4.100000 1.028135 0.00 960 520 960 520
HK 1.300000 0.670000 0.352565 3.800000 0.883180 0.00 880 440 880 440
KN 0.800000 0.530000 0.220618 3.300000 0.666055 0.00 720 340 720 340
NP 0.550000 0.480000 0.180956 3.000000 0.550459 0.00 620 320 620 320
BC 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
BD 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
FG 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
HJ 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
HI 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
KM 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
KL 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
NO 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
PQ 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
PR 0.370000 0.420000 0.138544 2.700000 0.445872 0.00 460 320 460 320
RETURN (SECOND FLOOR)
VOLUME ACTUAL ACTUAL
PRESSURE DUCT DUCT
SECTION LENGTH FLOW DIAMETER AREA VELOCITY PRESSURE DUCT DUCT
LOSS WIDTH HEIGHT
S RATE WIDTH HEIGHT
(mm) (cu.m/s) (m) (sq.m) (m/s) (mmH2O) (mmH2O) (mm) (mm) (mm) (mm)
AB 3.500000 1.000000 0.785398 4.000000 0.978593 0.00 960 880 960 880
BC 3.180000 0.980000 0.754296 3.900000 0.930275 0.00 960 840 960 840
CD 2.860000 0.930000 0.679290 3.800000 0.883180 0.00 960 760 960 760
DE 2.540000 0.900000 0.636172 3.700000 0.837309 0.00 960 720 960 720
AF 2.220000 0.860000 0.580880 3.600000 0.792661 0.00 920 680 920 680
FG 1.900000 0.820000 0.528101 3.500000 0.749235 0.00 900 640 900 640
GH 1.580000 0.750000 0.441786 3.500000 0.749235 0.00 840 560 840 560
HI 1.260000 0.670000 0.352565 3.200000 0.626300 0.00 760 500 760 500
IJ 0.940000 0.620000 0.301907 2.900000 0.514373 0.00 700 460 700 460
JK 0.620000 0.520000 0.212371 2.600000 0.413456 0.00 640 360 640 360
KL 0.330000 0.430000 0.145220 2.400000 0.352294 0.00 480 320 480 320
B 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
C 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
D 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
E 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
F 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
I 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
J 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
K 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
L 0.320000 0.420000 0.138544 2.400000 0.352294 0.00 460 320 460 320
Eugenio I T. Gonzalo BSME IV-A

You might also like