View Machine Edition: Installation Guide
View Machine Edition: Installation Guide
INSTALLATION GUIDE
PUBLICATION VIEWME-IN003G-EN-P–June 2009
Supersedes Publication VIEWME-IN003F-EN-P
Contact Rockwell Customer Support Telephone — 1.440.646.3434
Online Support — http://www.rockwellautomation.com/support/
Copyright Notice © 2009 Rockwell Automation, Inc. All rights reserved. Printed in USA.
This document and any accompanying Rockwell Software products are copyrighted by Rockwell Automation, Inc. Any
reproduction and/or distribution without prior written consent from Rockwell Automation, Inc. is strictly prohibited.
Please refer to the license agreement for details.
Trademark Notices Allen-Bradley, ControlLogix, Data Highway Plus, DH+, Data Highway II, FactoryTalk, Logix5000, PanelBuilder,
PanelView, PLC-2, PLC-3, PLC-5, Rockwell, Rockwell Automation, Rockwell Software, RSAssetSecurity, RSLinx,
RSLogix, , RSView, RSView Administration Console, SLC, VersaView, and WINtelligent,are registered trademarks of
Rockwell Automation, Inc.
Any Rockwell Automation software or hardware not mentioned here is also a trademark, registered or otherwise, of
Rockwell Automation, Inc.
Other Trademarks ActiveX, Microsoft, Microsoft Access, SQL Server, Visual Basic, Visual C++, Visual SourceSafe, Windows, Windows
ME, Windows NT, Windows 2000, Windows Server-, Windows XP, and Vista are either registered trademarks or
trademarks of Microsoft Corporation in the United States and/or other countries.
Adobe, Acrobat, and Reader are either registered trademarks or trademarks of Adobe Systems Incorporated in the
United States and/or other countries.
Oracle is a registered trademarks of Oracle Corporation.
ControlNet is a registered trademark of ControlNet International.
DeviceNet is a trademark of the Open DeviceNet Vendor Association, Inc. (ODVA)All other trademarks are the
property of their respective holders and are hereby acknowledged.
Warranty This product is warranted in accordance with the product license. The product’s performance may be affected by system
configuration, the application being performed, operator control, maintenance, and other related factors. Rockwell
Automation is not responsible for these intervening factors. The instructions in this document do not cover all the
details or variations in the equipment, procedure, or process described, nor do they provide directions for meeting every
possible contingency during installation, operation, or maintenance. This product’s implementation may vary among
users.
This document is current as of the time of release of the product; however, the accompanying software may have
changed since the release. Rockwell Automation, Inc. reserves the right to change any information contained in this
document or the software at anytime without prior notice. It is your responsibility to obtain the most current information
available from Rockwell when installing or using this product.
i
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
Reinstalling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Starting applications automatically. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Running applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Using sample applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
ii
1 Introducing FactoryTalk View Machine
1 • Placeholder
Edition
About FactoryTalk View Machine Edition
FactoryTalk® View Machine Edition is software for developing and running human-
machine interface (HMI) applications. FactoryTalk View Machine Edition is designed for
monitoring and controlling automated processes and machines.
For information about using FactoryTalk View Machine Edition to create and run
applications, see the FactoryTalk View Machine Edition User’s Guide and Help.
For information about upgrading FactoryTalk View Machine Edition from a previous
version, see the Release Notes.
1
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
Additional software
The FactoryTalk View Machine Edition CD also includes four additional software
products:
FactoryTalk® Services Platform installs software that is shared among the
components of FactoryTalk View. The FactoryTalk Services Platform must be installed
before FactoryTalk View Studio or FactoryTalk View ME Station can be installed.
RSLinx® Enterprise™ is a communication server built around FactoryTalk technology
to assist in developing and running your FactoryTalk View Machine Edition applications.
It is an OPC® 2.05 compliant server and will run on a variety of platforms ranging from
dedicated PanelView Plus terminals to desktop computers.
RSLinx® Classic™ is software that provides communications to a wide range of
devices, such as Logix5000 processors. RSLinx Classic is an OPC-compliant data server.
RSLinx Classic is available for personal computers only.
Adobe® Reader® 9.0 is software for reading and printing the online FactoryTalk View
Machine Edition User’sGuide. This FactoryTalk View Machine Edition Installation Guide
is also available online. For information about viewing the online books, see Chapter 5.
2
• • • • •
1 • INTRODUCING FACTORYTALK VIEW MACHINE EDITION
1 • Placeholder
FactoryTalk View Studio tools
These tools are installed with FactoryTalk View Studio:
Application Documenter is software that provides detailed information about
FactoryTalk applications.
Application Manager is software for renaming, copying, deleting, backing up, and
restoring applications.
DeskLock is software that prevents Windows 2000, Windows XP, Windows
Server 2003 R2, Windows Vista, and Windows Server 2008 users from exiting the
FactoryTalk View application at run time. You can use this tool to set up a customized
desktop and to prevent access to Windows functions. You cannot use DeskLock if you
are running your application on a PanelView Plus or PanelView Plus CE terminal.
ME Firmware Upgrade Wizard is software for installing new firmware releases on
an ME terminal.
ME Transfer Utility is software for moving a run-time machine-level application
(.mer file) from the development computer to PanelView Plus or PanelView Plus CE
terminals.
Tag Import and Export Wizard is software for importing or exporting the
FactoryTalk View tag database.
Diagnostics Viewer is used to view FactoryTalk Diagnostics messages using the
Windows Event Viewer.
FactoryTalk tools
FactoryTalk tools are installed when you install FactoryTalk Services Platform. They are
available from the Windows Start menu.
3
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
4
2 Installing and activating FactoryTalk View
2 • Placeholder
on personal computers
This chapter describes:
system requirements.
installing FactoryTalk® View Machine Edition and related software.
activating FactoryTalk View.
starting FactoryTalk View Studio and using sample applications.
System requirements
To run FactoryTalk® View Studio, the recommended requirements are:
Personal computer with an Intel® Pentium® 4 processor (2 GHz or faster
processor recommended).
Memory (RAM). 1 GB (or more).
Hard disk space. Minimum 100 MB.
Operating system. One of:
If you are planning to upgrade your operating system from an earlier version to
Windows XP Professional, see Answer ID 29104 (previously Tech Note
#P88739858) for information about how to perform the upgrade. If you do not
follow the recommended procedure, you will no longer be able to create or use
FactoryTalk View applications.
5
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
FactoryTalk View Studio is tested and supported on operating systems installed from
original Microsoft media only.
Floppy disk drive. Activation keys for upgrades to RSView Machine Edition
products are supplied on a floppy disk. FactoryTalk® View Activation does not
require a floppy disk drive, although you can use floppy disks or other removable
media to transfer activations from one computer to another.
Installing
The steps below explain how to install FactoryTalk® View Studio, FactoryTalk® View
ME Station, FactoryTalk® Services Platform, FactoryTalk Activation Server, and
RSLinx® software from the FactoryTalk View Machine Edition CD to your computer.
To start installation:
1. Close all open Windows programs.
2. Place the FactoryTalk View Machine Edition CD in your CD-ROM drive. The CD
should start running automatically.
If the CD does not start automatically, run D:\Setup.exe, where D is the drive
containing the CD.
When the CD window opens, these options are displayed:
Open Installation Instructions
Install FactoryTalk View Machine Edition
Open Release Notes
Watch Install Video
If you are installing the FactoryTalk View ME software for the first time on a clean machine,
click Watch Install Video to see a video with detailed installation instructions.
6
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
The gray text pane on the right provides information about the options on the left. When
you move the mouse cursor over an option on the left, the text on the right describes what
2 • Placeholder
selecting the option will do. You can also exit the installation CD from this window.
When the Adobe installation process starts, close the FactoryTalk View Machine
Edition installation CD by clicking Exit in the text pane on the right. Adobe
installation cannot complete if the CD is open. After you have clicked Finish in the
Setup Wizard for Adobe Reader, restart the FactoryTalk View Machine Edition
installation.
To successfully upgrade from RSView Enterprise 4.00 to FactoryTalk View 5.00 or later, it is essential
that you follow these steps in the order they are listed.
Click Install FactoryTalk View Machine Edition to perform these installation steps:
7
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
the Windows Control Panel. You must uninstall these products first, before uninstalling
FactoryTalk View Machine Edition.
For more information about upgrading FactoryTalk View Machine Edition from a
previous version, see the Release Notes.
8
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
2. Uninstall the products in the lower list, if any, using the Windows Control Panel.
2 • Placeholder
Do not manually uninstall the Windows Firewall Configuration Utility. Doing so will
cause a fatal error. Allow FactoryTalk View to uninstall the program automatically in
the next step.
3. When you have finished uninstalling all the programs in the lower list, click OK to
uninstall the products in the upper list.
4. If FactoryTalk Services Platform is one of the programs uninstalled, you are asked
whether you plan to revert to an earlier version of FactoryTalk Services Platform or
FactoryTalk Automation Platform. Click Yes for more information about reverting.
Click No to continue with the uninstall.
9
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
or
10
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
2 • Placeholder
4. At the end of the installation process you are given the opportunity to view the
FactoryTalk View Machine Edition Release Notes. If you do not wish to view the
Release Notes at this time, clear the check box.
5. You are also given the opportunity to install the FactoryTalk Activation Server. You
must upgrade FactoryTalk Activation software to version 3.02 or later in order to
acquire new activations or use borrowed activations.
Do one of the following:
If activation is present from a previous installation, or you do not intend to use
FactoryTalk Activation on this computer, clear the check box, and then click
Finish. Previous activations cannot be borrowed.
If you removed a previous activation, or if you are installing FactoryTalk View
Machine Edition for the first time, or if you intend to borrow activations, leave the
check box selected, and then click Finish.
If you choose not to install the FactoryTalk Activation Server software now, you can
install it later.
For more information about activation, see page 15.
11
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
12
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
2 • Placeholder
2. Follow the on-screen instructions. In the serial number text box, enter any 10-digit
number.
3. You are given the opportunity to view the RSLinx Enterprise Release Notes. Make
your choice, and then click Finish.
13
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
Installation summary
The installation does the following:
installs the shared components for the FactoryTalk Services Platform.
installs FactoryTalk View Studio and FactoryTalk View ME Station in \Program
Files\Rockwell Software\RSView Enterprise. This folder contains the FactoryTalk
View Studio software and tools.
installs RSLinx Enterprise in \Program Files\Rockwell Software\RSLinx Enterprise.
This folder contains the RSLinx Enterprise files.
(optionally) installs RSLinx Classic in \Program Files\Rockwell Software\RSLINX.
This folder contains the RSLinx Classic files.
adds a \Program Files\Rockwell Software\RSUtil folder. This folder contains
Rockwell Software utilities you can use for activating FactoryTalk View Studio if you
are upgrading from RSView Machine Edition.
adds a folder containing bitmap image files that you can use on graphic objects. This
file is located in:
(Windows 2000) \Documents and Settings\All Users\Documents\RSView
Enterprise\Images
(Windows XP and Windows Server 2003) \Documents and Settings\All
Users\Shared Documents\RSView Enterprise\Images
(Windows Vista and Windows Server 2008) \Users\Public\Public
Documents\RSView Enterprise\Images
adds a folder containing sample applications for FactoryTalk View Studio and stores
applications that you create. This file is located in:
(Windows 2000) \Documents and Settings\All Users\Documents\RSView
Enterprise\ME\HMI projects
(Windows XP and Windows Server 2003) \Documents and Settings\All
Users\Shared Documents\RSView Enterprise\ME\HMI projects
(Windows Vista and Windows Server 2008) \Users\Public\Public
Documents\RSView Enterprise\ME\HMI projects
adds a folder containing graphic library component files and image files used in the
library displays .This file is located in:
(Windows 2000) \Documents and Settings\All Users\Documents\RSView
Enterprise\ME\Libraries
(Windows XP and Windows Server 2003) \Documents and Settings\All
Users\Shared Documents\RSView Enterprise\ME\Libraries
(Windows Vista and Windows Server 2008) \Users\Public\Public
Documents\RSView Enterprise\ME\Libraries
14
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
adds a folder containing graphic displays, global object displays, and image files used
for Logix5000 process faceplates. This folder is located in:
2 • Placeholder
(Windows 2000) \Documents and Settings\All Users\ Documents\RSView
Enterprise\ME\Faceplates
(Windows XP and Windows Server 2003) \Documents and Settings\All
Users\Shared Documents\RSView Enterprise\ME\Faceplates
(Windows Vista and Windows Server 2008) \Users\Public\Public
Documents\RSView Enterprise\ME\Faceplates
Activating
FactoryTalk View Machine Edition uses activation files to activate its software packages.
Without activation, FactoryTalk View Studio runs for a grace period of seven days, and
then runs in demo mode, allowing two hours of use and no more than five displays
(including the three default displays).
Without activation, FactoryTalk View ME Station also provides a seven-day grace period
before running in demo mode on personal computers. Activation is not required for
PanelView™ Plus and PanelView Plus CE terminals.
There are two methods for activating FactoryTalk View Machine Edition:
using FactoryTalk Activation Server software to download and transfer activation
files.
using an Activation disk containing EvRSI activation files. This method is available
only if you are upgrading from a previous version of RSView Machine Edition
software.
FactoryTalk Activation will replace EvRSI activation in a future release. If you are
using EvRSI activation, please contact your local Rockwell Automation Sales office or
Technical Support for information about migrating your activations to FactoryTalk
Activation.
FactoryTalk Activation
FactoryTalk Activation provides a secure, software-based system for activating Rockwell
Software products and managing software activation files. With FactoryTalk Activation,
there is no need for a physical “master disk” or any physical media; instead, activation
files are generated and distributed electronically.
15
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
You can also find detailed information, instructions, and troubleshooting tips in the
FactoryTalk Activation Help.
After installing the FactoryTalk Activation software, click Start > All Programs >
Rockwell Software > FactoryTalk Activation > FactoryTalk Activation Help.
Activation files
FactoryTalk View Studio uses the activation files RSV.STUDIO or RSVME.STUDIO.
For FactoryTalk View ME Station running on a personal computer, the particular
activation files depend on the licensing you purchase, and determine how many displays
your applications can contain:
RSVME.250 comes with a license for 250 displays
RSVME.RUN comes with a license for 75 displays.
RSVME.30 comes with a license for 30 displays.
RSVME.15 comes with a license for 15 displays.
16
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
6. The FactoryTalk Activation tool and FactoryTalk Activation wizard open. To obtain
activations now, follow the on-screen instructions. If you do not want to obtain
2 • Placeholder
activations now, close the wizard and tool.
You can use the FactoryTalk Activation tool and wizard to obtain activations at a later
time, as described in the next section.
You must have an active Internet connection to obtain activation files.
17
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
18
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
2 • Placeholder
2. Run the FactoryTalk Activation Tool and then click the Current Activations tab.
3. To verify that the activations you want to borrow are available, subtract the number of
activations currently in use and borrowed, from the total number of activations. Also
verify that the activations you want can be borrowed. Activations that can be
borrowed show a number in the Borrowed column. If no activations have already been
borrowed, the Borrowed column shows 0. Activations that cannot be borrowed show
n/a in the Borrowed column.
4. To borrow a single activation, click the row that corresponds to the activation you
want to borrow, and then click Borrow. To borrow more than one activation, click
Borrow All, or select the rows for the activations you want to borrow and then click
Borrow.
5. In the Borrow Activation window, indicate the date and time when the borrowed
activations will expire. The default value for the date and time is set to the earliest
expiration date found in the group of borrowed activations. This is the maximum
amount of time before the group of borrowed activations will expire.
6. Make sure the Borrow as System user for services check box is selected. If this
check box is not selected, FactoryTalk View will no longer be activated when you
disconnect from the activation server.
19
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
7. Click OK.
8. Click Exit to close the FactoryTalk Activation Tool. You can now disconnect your
computer from the network.
FactoryTalk Activation will replace EvRSI activation in a future release. If you are
using EvRSI activation, please contact your local Rockwell Automation Sales office or
Technical Support for information about migrating your activations to FactoryTalk
Activation.
20
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
one or more activation files. For example, if your company purchases four
FactoryTalk View Studio installations, you require four activation keys.
2 • Placeholder
Multiple copies of the same software require activation keys with matching serial
numbers. All of the activation keys can be on the same Activation disk.
a program called EvMoveW.exe that moves activation keys to and from computers.
a program called ResetW.exe that reactivates a damaged activation key.
You can move activation keys to and from the Activation disk. The programs
EvMoveW.exe and ResetW.exe always stay on the Activation disk.
For more information about using the Activation disk, see the Activation Help.
Starting
You can start FactoryTalk View Studio manually, or you can set up the program to start
automatically when Windows starts.
For information about starting FactoryTalk View ME Station on a PanelView Plus
terminal, see Chapter 3. For information about starting FactoryTalk View ME Station on a
PanelView Plus CE terminal, see Chapter 4.
Starting automatically
To start FactoryTalk View Studio automatically each time Windows starts, include a
shortcut in the Windows Startup folder.
21
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
When you first install FactoryTalk View, sample applications are accessible to all users. For
information about setting up users and granting them access to applications, see Chapter 11,
“Setting up security,” in the FactoryTalk View Machine Edition User’s Guide.
22
• • • • •
2 • INSTALLING AND ACTIVATING FACTORYTALK VIEW ON PERSONAL COMPUTERS
2 • Placeholder
1. In FactoryTalk View Studio, in the New/Open Machine Edition Application dialog
box, click the Existing tab.
2. Click the name of the sample application to open.
3. Select a language for the application.
4. Click Open.
23
3 Running FactoryTalk View ME Station on
3 • Placeholder
PanelView Plus terminals
This chapter describes:
system requirements.
reinstalling FactoryTalk® View ME Station and related software.
starting FactoryTalk View ME Station and using sample applications.
System requirements
To run FactoryTalk® View ME Station on a PanelView™ Plus terminal, the minimum
requirements are:
Available Memory (RAM). 64 MB.
Available Flash Storage space. 32 MB.
Installing
The PanelView Plus terminal comes with FactoryTalk View ME Station already installed.
Reinstalling
If necessary, you can reinstall or upgrade FactoryTalk View ME Station on the PanelView
Plus terminal using the Firmware Upgrade Wizard. The wizard reinstalls FactoryTalk
View ME Station and RSLinx® Enterprise™ as well as other programs.
To determine what is included in any firmware upgrade, please refer to Answer ID 33326
(previously Tech Note #Q154160016) in the Rockwell Automation Knowledgebase.
25
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
Starting
FactoryTalk View ME Station starts and the FactoryTalk View ME Station dialog box
opens automatically when the PanelView Plus terminal starts up.
Running applications
Before you can run an application on the PanelView Plus terminal, you must transfer it to
the PanelView Plus terminal.
PanelView Plus Compact terminals can load and run only Compact Machine Edition
applications. PanelView Plus terminals can load and run Compact Machine Edition
applications as well as non-Compact, regular applications.
For information about transferring applications to the PanelView Plus terminal and
preparing to run them, see Chapter 16, “Transferring applications to a PanelView Plus or
PanelView Plus CE terminal,” in the FactoryTalk View Machine Edition User’s Guide, or
see the PanelView Plus Terminals User Manual.
26
• • • • •
3 • RUNNING FACTORYTALK VIEW ME STATION ON PANELVIEW PLUS TERMINALS
3 • Placeholder
FactoryTalk View® Studio comes with sample applications that highlight features of the
product. Most of these applications have two run-time versions, designed for two different
screen resolutions.
For example:
objects_640x480.mer
objects_800x600.mer
The sample applications are located at this path on the development computer:
(Windows 2000) \Documents and Settings\All Users\Documents\RSView
Enterprise\ME\HMI projects
(Windows XP and Windows Server 2003) \Documents and Settings\All Users\Shared
Documents\RSView Enterprise\ME\HMI projects
(Windows Vista and Windows Server 2008) \Users\Public\Public Documents\RSView
Enterprise\ME\HMI projects
HMI projects contains a folder for each sample application.
FactoryTalk View ME Station starts automatically on the PanelView Plus terminal. You
just need to select the application to run.
27
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
28
4 Running FactoryTalk View ME Station on
4 • Placeholder
PanelView Plus CE terminals
This chapter describes:
system requirements.
reinstalling FactoryTalk® View ME Station and related software.
starting FactoryTalk View ME Station and using sample applications.
System requirements
To run FactoryTalk® View ME Station on a PanelView™ Plus CE industrial computer, the
minimum requirements are:
Available Memory (RAM). 64 MB.
Available Storage Card space. 32 MB.
Installing
The PanelView Plus CE terminal comes with FactoryTalk View ME Station already
installed.
Reinstalling
If necessary, you can reinstall or upgrade FactoryTalk View ME Station on the PanelView
Plus CE terminal using the Firmware Upgrade wizard. The wizard reinstalls FactoryTalk
View ME Station and RSLinx® Enterprise™ as well as other programs.
To determine what is included in any firmware upgrade, please refer to Answer ID 33326
(previously Tech Note #Q154160016) in the Rockwell Automation Knowledgebase.
29
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
Starting
You can start FactoryTalk View ME Station manually, or you can set up the program to
start automatically when the PanelView Plus CE terminal is turned on.
Starting automatically
You can set up FactoryTalk View ME Station to start automatically and run a particular
application when the PanelView Plus CE terminal is turned on. For more information, see
the PanelView Plus Terminals User Manual.
Running applications
Before you can run an application on the PanelView Plus CE terminal, you must transfer it
to the PanelView Plus CE terminal.
PanelView Plus Compact terminals can load and run only Compact Machine Edition
applications. PanelView Plus CE terminals can load and run Compact Machine Edition
applications as well as non-Compact, regular applications.
30
• • • • •
4 • RUNNING FACTORYTALK VIEW ME STATION ON PANELVIEW PLUS CE TERMINALS
For information about transferring applications to the PanelView Plus CE terminal and
preparing to run them, see Chapter 16, “Transferring applications to a PanelView Plus or
4 • Placeholder
PanelView Plus CE terminal,” in the FactoryTalk View Machine Edition User’s Guide, or
see the PanelView Plus Terminals User Manual.
31
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
32
5 Getting the information you need
5 • Placeholder
This chapter describes:
using the FactoryTalk View Machine Edition User’s Guide.
downloading the PanelView Plus Terminals User Manual.
using the FactoryTalk View Studio Help.
accessing Rockwell Automation technical support services.
33
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
34
• • • • •
5 • GETTING THE INFORMATION YOU NEED
5 • Placeholder
To see the
topics in a
book, click
the +.
To see a
topic, click
the topic.
35
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
To see a topic,
double-click it,
or select the
topic and then
click the Display
button.
36
• • • • •
5 • GETTING THE INFORMATION YOU NEED
5 • Placeholder
Type the word to
search for here,
and then click List
Topics.
Scroll through
the list to find
the topic you’re
looking for.
When you find
the topic,
double-click it
to go to that
topic.
37
• • • • • FACTORYTALK VIEW MACHINE EDITION INSTALLATION GUIDE
38
• • • • •
5 • GETTING THE INFORMATION YOU NEED
a description of what happened, and what you were doing when the problem occurred
a description of how you tried to solve the problem
5 • Placeholder
You might also be required to provide information about the FactoryTalk View add-ons
and updates that are installed on your computer.
39