K is determined as follows:
OBSOLETE
1. Transient Bias = Disabled
For IEDs set at Is1 = 20%, Is2 = 2 In, k1 = 30%, k2 = 150%:
K must be the highest of:
K = 40 + (0.07 x (If x X/R))
Or
K = 65
This is valid for (If x X/R) d 1000
For higher (If x X/R) up to 1600:
K = 107
For IEDs set at Is1 = 20%, Is2 = 2 In, k1 = 30%, k2 = 100%:
P544&6/EN/TM/E 8-87
8 Application Examples MiCOM P544, P546
Note: It is not necessary to repeat the calculation for earth faults, as the phase reach calculation (3M) is
the worst-case for CT dimensioning.
8-88 P544&6/EN/TM/E