Professional Documents
Culture Documents
$Gydqfhg0Rwru3Urwhfwlrq:) Ru7/Sh659Duldeoh) Uhtxhqf/'Ulyhv $$ (GLWLRQ
$Gydqfhg0Rwru3Urwhfwlrq:) Ru7/Sh659Duldeoh) Uhtxhqf/'Ulyhv $$ (GLWLRQ
$Gydqfhg0Rwru3Urwhfwlrq:) Ru7/Sh659Duldeoh) Uhtxhqf/'Ulyhv $$ (GLWLRQ
$GYDQFHG0RWRU3URWHFWLRQ
6,1$0,&63(5)(&7+$5021<*+
)RU7\SH659DULDEOH)UHTXHQF\'ULYHV
A5E46373908
$$
(GLWLRQ
www.siemens.com/drives
Security Information 1
Safety notes 2
Introduction 3
Advanced Motor Protection
Parameters 4
Advanced Motor Protection for
RTD Terminal Connections 5
Variable Speed Operation
Advanced Motor Protection
Manual
and RTD Protection 6
Functions
Troubleshooting 9
Appendix A
ESD guidelines A
AA
A5E46373908A
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.
1 Security Information......................................................................................................................................9
1.1 Security information .................................................................................................................9
2 Safety notes................................................................................................................................................11
2.1 General Safety Information ....................................................................................................11
2.2 Observing the Five Safety Rules............................................................................................12
2.3 Safety Information and Warnings...........................................................................................13
3 Introduction.................................................................................................................................................15
3.1 Background ...........................................................................................................................15
4 Advanced Motor Protection Parameters.....................................................................................................17
4.1 Standard Protections Block Diagram .....................................................................................17
4.2 Introduction ............................................................................................................................23
4.3 Protection Function Enable Types .........................................................................................26
5 RTD Terminal Connections ........................................................................................................................27
5.1 Installation External Wiring.....................................................................................................27
6 Advanced Motor Protection and RTD Protection Functions .......................................................................29
6.1 Top Level Menu and Submenus ............................................................................................29
6.2 Device 12 - Fixed Pickup Overspeed.....................................................................................31
6.3 Device 12 - Variable Pickup Overspeed ................................................................................33
6.4 Device 14 - Fixed Pickup Underspeed...................................................................................37
6.5 Device 14 - Variable Pickup Underspeed ..............................................................................39
6.6 Device 37 - Fixed Pickup Undercurrent .................................................................................43
6.7 Device 37 - Variable Pickup Undercurrent .............................................................................45
6.8 Device 37P - Fixed Underpower Relay .................................................................................48
6.9 Device 38 - Fixed Bearing Temperature Protective Device ...................................................50
6.10 Device 39 - Mechanical Condition Monitor - Fixed Pickup Torque Pulsation.........................51
6.11 Device 46_2 - Phase-Balance Current - Fixed Pickup Negative Sequence Overcurrent
Delay ......................................................................................................................................54
6.12 Device 48 - Incomplete Sequence Relay Device - Maximum Start Time...............................56
6.13 Device 48 - Incomplete Sequence Relay Device - Maximum Stop Time...............................57
6.14 Device 49T - Machine Thermal Model - Fixed Parameter Thermal Overload........................58
6.15 Device 49T - Machine Thermal Model - Variable Parameter Thermal Overload ...................63
6.16 Device 49RTD - Machine Thermal Overload - Fixed Pickup RTD Protection........................70
6.17 Device 50 - Fixed Pickup Instantaneous Overcurrent Device ...............................................80
6.18 Device 51 - Fixed Inverse Time Overcurrent .........................................................................82
6.18.1 Device 51 - Fixed Inverse Time Overcurrent .........................................................................82
6.18.2 Function 51 IEEE Pickup and Reset .....................................................................................86
6.18.3 Function 51 ANSI Pickup and Reset .....................................................................................93
6.18.4 Function 51 IAC Pickup and Reset .....................................................................................102
6.18.5 Function 51 IEC Pickup and Reset ......................................................................................111
6.18.6 Function 51 I2T Pickup and Reset ......................................................................................119
6.18.7 Function 51 I4T Pickup and Reset ......................................................................................121
6.19 Device 55 - Fixed Pickup Maximum Power Factor ..............................................................124
6.20 Device 55 - Power Factor Relay Device (Fixed minimum power factor)..............................126
6.21 Device 59G - Fixed Pickup Instantaneous Zero Sequence Overvoltage .............................128
6.22 Device 59G - Fixed Pickup Definite Minimum Time Zero Sequence Overvoltage...............130
6.23 Device 66 - Notching or Jogging Device - Starts per Hour ..................................................133
6.24 Device 66 - Notching or Jogging Device - Cold Starts per Hour ..........................................134
6.25 Device 66 - Notching or Jogging Device - Hot Starts per Hour............................................135
6.26 Device 66 - Notching or Jogging Device - Maximum Thermal Capacity Used to Start ........136
6.27 Device 81 - Fixed Pickup Overfrequency.............................................................................137
6.28 Device 81 - Variable Pickup Overfrequency ........................................................................139
6.29 Device 81 - Fixed Pickup Underfrequency...........................................................................143
6.30 Device 81 - Variable Pickup Underfrequency ......................................................................145
6.31 Device 81 - Fixed Pickup High Frequency Rate of Change.................................................149
6.32 Changing RTD Type ............................................................................................................151
6.32.1 Changing RTD Type ............................................................................................................151
7 Alarms, Faults, and Logging Messages ...................................................................................................153
7.1 Alarms, Faults, and Logging Messages ...............................................................................153
8 NXGpro AMP Alarms/Faults, Protection Variables, and RTD Status Screens........................................159
8.1 Viewing Protection Variables ...............................................................................................159
8.1.1 AMP Data Screen ................................................................................................................160
8.1.2 AMP Alarms / Faults ............................................................................................................161
8.1.3 RTD Status Screen ..............................................................................................................164
9 Troubleshooting........................................................................................................................................165
9.1 Troubleshooting ...................................................................................................................165
10 Spare Parts Data .....................................................................................................................................167
10.1 AMP Replaceable Spart Parts List.......................................................................................167
A Appendix...................................................................................................................................................169
A.1 IEEE Device Numbers and Functions..................................................................................169
Tables
Table 4-1 Pickup Level Settings for Variable Undercurrent Protection Example ........................................20
Table 4-2 Example of per-unit and engineering unit quantities ...................................................................25
Table 6-1 Advanced Motor Protection Menu - Fixed Pickup Over Speed (ID 7181) ...................................31
Table 6-2 Advanced Motor Protection Menu - Variable Pickup Over Speed (ID 7189)...............................33
Table 6-3 Advanced Motor Protection Menu - Fixed Pickup Underspeed Device (ID 7217).......................37
Table 6-4 Advanced Motor Protection Menu - Variable Pickup Underspeed (ID 7226) ..............................39
Table 6-5 Advanced Motor Protection Menu - Fixed Pickup Undercurrent Device (ID 7256) .....................43
Table 6-6 Advanced Motor Protection Menu - Variable Pickup Undercurrent Device (ID 7266).................45
Table 6-7 Advanced Motor Protection Menu - Fixed Pickup Underpower Relay (ID 7297) ........................48
Table 6-8 Advanced Motor Protection Menu - Mechanical Condition Monitor - Fixed Pickup Torque
Pulsation (ID 7306)......................................................................................................................51
Table 6-9 Advanced Motor Protection Menu - Phase Balance Current - Fixed Negative Sequence
Over Current (ID 7316)................................................................................................................54
Table 6-10 Advanced Motor Protection Menu - Incomplete Sequence - Maximum Start Time (ID 7325)......56
Table 6-11 Advanced Motor Protection Menu - Incomplete Sequence - Maximum Stop Time (ID 7330)......57
Table 6-12 Advanced Motor Protection Menu - Machine Thermal Model - Fixed Parameter Thermal
Overload (ID 7335)......................................................................................................................58
Table 6-13 Advanced Motor Protection Menu - Machine Thermal Model - Variable Thermal Overload
(ID 7352) .....................................................................................................................................63
Table 6-14 Values of the k-Factor Settings ...................................................................................................69
Table 6-15 RTD Protection Menu - Machine Thermal Overload - Fixed Pickup RTD Protection (ID 7429)......70
Table 6-16 Advanced Motor Protection Menu - Fixed Pickup Instantaneous Overcurrent (ID 7515) ...........80
Table 6-17 Advanced Motor Protection Menu - Fixed Pickup Inverse Time Overcurrent (ID 7533) .............82
Table 6-18 IEEE Curve Data Table ...............................................................................................................87
Table 6-19 ANSI Curve Data Table...............................................................................................................94
Table 6-20 IAC Curve Data Table ...............................................................................................................103
Table 6-21 Advanced Motor Protection Menu - Fixed Pickup Maximum Power Factor (ID 7573) ..............124
Table 6-22 Advanced Motor Protection Menu - Fixed Pickup Minimum Power Factor (ID 7582) ...............126
Table 6-23 Advanced Motor Protection Menu - Fixed PickupInstantaneous Zero Sequence
Overvoltage (ID 7563) ...............................................................................................................128
Table 6-24 Advanced Motor Protection Menu - Fixed Pickup Instantaneous Overcurrent (ID 7524) .........130
Table 6-25 Advanced Motor Protection Menu - Starts per Hour (ID 7590) ................................................133
Table 6-26 Advanced Motor Protection Menu - Notching or Jogging - Cold Starts per Hour (ID 7593).....134
Table 6-27 Advanced Motor Protection Menu - Hot Starts per Hour (ID 7598)..........................................135
Table 6-28 Motor Protection Menu - Maximum Thermal Capacity Used to Start (ID 7603) .......................136
Table 6-29 Advanced Motor Protection Menu - Fixed Pickup Overfrequency (ID 7606).............................137
Table 6-30 Advanced Motor Protection Menu - Variable Pickup Overfrequency (ID 7615) ........................139
Table 6-31 Advanced Motor Protection Menu - Fixed Pickup Underfrequency (ID 7645)...........................143
Table 6-32 Advanced Motor Protection Menu - Variable Pickup Underfrequency (ID 7654) .....................145
Table 6-33 Advanced Motor Protection Menu - Fixed Pickup High Frequency Rate of Change (ID 7684)....149
Table 7-1 Advanced Motor Protection Function Event Log Table .............................................................153
Table 7-2 RTD Protection Function Event Log Table................................................................................156
Figures
Proper Use
SINAMICS Perfect Harmony™ GH180 medium voltage drives must always be installed in
closed electrical operating areas. The drive is connected to the industrial network via a circuit-
breaker or contactor that is electrically connected to the VFD control to enable the drive
protection features.
The specific transport conditions must be observed when the equipment is transported. The
equipment shall be assembled/installed and the separate cabinet units connected properly by
cable and/or busbar in accordance with the assembly/installation instructions. The relevant
instructions regarding correct storage, EMC-compliant installation, cabling, shielding and
grounding and an adequate auxiliary power supply must be strictly observed. Fault-free
operation is also dependent on careful operation and maintenance.
The power sections are designed for variable-speed drives use with synchronous and
asynchronous motors. Operating modes, overload conditions, load cycles, and ambient
conditions different to those described in this document are allowed only by special
arrangement with the manufacturer.
Commissioning should only be carried out by trained service personnel in accordance with the
commissioning instructions.
System components such as circuit-breaker, transformer, cables, cooling unit, motor, speed
sensors, etc., must be matched to VFD operation. System configuration may only be carried out
by an experienced system integrator.
DANGER
Danger Due to High Voltages
High voltages cause death or serious injury if the safety instructions are not observed or if the
equipment is handled incorrectly.
Potentially fatal voltages occur when this equipment is in operation which can remain present
even after the VFD is switched off.
Ensure that only qualified and trained personnel carry out work on the equipment.
Follow the five safety rules during each stage of the work.
DANGER
Hazardous Voltage!
● Always follow the proper lock-out/tag-out procedures before beginning any maintenance
or troubleshooting work on the VFD.
● Always follow standard safety precautions and local codes during installation of external
wiring. The installation must follow wiring practices and insulation systems as specified in
IEC 61800-5-1.
● Hazardous voltages may still exist within the VFD cabinets even when the disconnect
switch is open (off) and the supply power is shut off.
● Only qualified individuals should install, operate, troubleshoot, and maintain this VFD. A
qualified individual is "a person, who is familiar with the construction and operation of the
equipment and the hazards involved."
● Always work with one hand, wear electrical safety gloves, wear insulated electrical hazard
rated safety shoes, and safety goggles. Also, always work with another person present.
● Always use extreme caution when handling or measuring components that are inside the
enclosure. Be careful to prevent meter leads from shorting together or from touching other
terminals.
● Use only instrumentation (e.g., meters, oscilloscopes, etc.) intended for high voltage
measurements (that is, isolation is provided inside the instrument, not provided by isolating
the chassis ground of the instrument).
● Never assume that switching off the input disconnector will remove all voltage from internal
components. Voltage is still present on the terminals of the input disconnector. Also, there
may be voltages present that are applied from other external sources.
● Never touch anything within the VFD cabinets until verifying that it is neither thermally hot
nor electrically alive.
● Never remove safety shields (marked with a HIGH VOLTAGE sign) or attempt to measure
points beneath the shields.
● Never operate the VFD with cabinet doors open. The only exception is the control cabinet.
● Never connect any grounded (i.e., non-isolated) meters or oscilloscopes to the system.
● Never connect or disconnect any meters, wiring, or printed circuit boards while the VFD is
energized.
● Never defeat the instrument’s grounding.
● When a system is configured with VFD bypass switchgear (e.g. contactors between line
and motor, and VFD and motor), these switches should be interlocked so that the line
voltage is never applied to the VFD output if the medium voltage input is removed from the
VFD.
● When a system is configured with VFD pre-charge, medium voltage is present on the
primary side of the input transformer and upstream device even though the MV contactor
is not closed.
WARNING
Potential Arc Hazard
● Arcing can result in damage to property, serious injury and even death.
● The equipment has not been tested and rated for arc flash protection.
● Avoiding arc hazard risks is dependent upon proper installation and maintenance.
● Incorrectly applied equipment, incorrectly selected, connected or unconnected cables, or
the presence of foreign materials can cause arcing in the equipment.
● Follow all applicable precautionary rules and guidelines as used in working with medium
voltage equipment.
● The equipment may be used only:
– for the applications defined as suitable in the technical description.
– in combination with equipment and components supplied by other manufacturers which
have been approved and recommended by Siemens.
● Always follow the facility / installation site rules / guidelines for Personal Protectiive
Equipment (PPE) based on the Arc Flash study of that facility.
Additional safety precautions and warnings appear throughout this manual. These important
messages should be followed to reduce the risk of personal injury or equipment damage.
WARNING
Obey Rules to Avoid Risk of Death
● Always comply with local codes and requirements if disposal of failed components is
necessary.
● Always ensure the use of an even and flat truck bed to transport the VFD system. Before
unloading, be sure that the concrete pad is level for storage and permanent positioning.
● Always confirm proper tonnage ratings of cranes, cables, and hooks when lifting the VFD
system. Dropping the cabinet or lowering it too quickly could damage the unit.
● Never disconnect control power while medium voltage is energized. This could cause
severe system overheating and/or damage.
● Never store flammable material in, on, or near the drive enclosure. This includes
equipment drawings and manuals.
● Never use fork trucks to lift cabinets that are not equipped with lifting tubes. Be sure that
the fork truck tines fit the lifting tubes properly and are the appropriate length.
Reset
Over/
Under
Select
Time
Constant
Enable (1)
Disable (0)
Low Pass
Protec!on Variable Filter
(Voltage, Current, Count Pickup
Enable Timed
etc.) 1=pickup
Pickup Output Out Trip or Alarm
Output
> 0=dropout Time Delay >=
+
Pickup Low Pass Σ < (Counter)
Level Filter - Zero Reset
Pickup
Time Delay
Time
Constant
1-(Dropout
Level) Count
Dropout Output
Enable
Time Delay
>=
(Counter)
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Latch Control
1 = latched
Note
Refer to the appendix of this manual and IEEE C37.2 to obtain further information about device
numbers and functions.
The functions that operate in accordance with the standard architecture are:
● Device 12 - Fixed pickup overspeed
● Device 12 - Variable pickup overspeed
● Device 14 - Fixed pickup underspeed
● Device 14 - Variable pickup underspeed
● Device 37 - Fixed pickup undercurrent
● Device 37 - Variable pickup undercurrent
● Device 37P - Fixed pickup underpower
● Device 39 - Mechanical condition monitor - Fixed pickup torque pulsation
● Device 46_2 - Phase-balance current - Fixed pickup negative sequence overcurrent
● Device 49RTD - Machine thermal overload - Fixed pickup RTD protection
● Device 50 - Fixed pickup instantaneous overcurrent
● Device 51 - Fixed pickup inverse time overcurrent
● Device 55 - Fixed pickup maximum power factor
● Device 55 - Fixed pickup minimum power factor
● Device 59G - Fixed pickup definite minimum time zero sequence overvoltage
● Device 81 - Fixed pickup overfrequency
● Device 81 - Variable pickup overfrequency
● Device 81 - Fixed pickup underfrequency
● Device 81 - Fixed pickup high frequency rate of change
The standard block compares a protection variable to a reference which is referred to in the
block diagram as the pickup level. To illustrate, for the fixed underspeed protection, the
reference would be motor speed, and the pickup level would be the Fixed Underspeed Pickup
Level (7218).
The comparator can be configured to make the block an "over" function (a trip or alarm can be
generated when the protection variable is higher than the pickup level) or an "under" function
(a trip or alarm can be generated when the protection variable is lower than the pickup level).
Adjustable low pass filtering is accomplished on both the protection variable and the pickup
level prior to the variables being applied to the greater than or less than comparator function.
A true state (logic one) at the output of the comparator indicates that a pickup is occurring and
that a trip or alarm may result. The pickup condition modifies the threshold of the comparator
with a programmable amount of hysteresis to avoid excessive toggling due to noise in the
reference or protection variable. The amount of hysteresis is determined as a percentage of the
pickup level by the adjustable parameter referred to as the dropout level.
The block uses two counters to control the generation of an alarm or trip output. The output can
be used as a trip signal or as an alarm signal where the alarm can be set to a latched mode or
an unlatched mode. The two counters are the pickup time delay counter and the dropout time
delay counter. The pickup time delay counter is used to delay the time between a pickup and
the generation of a trip or alarm signal. The pickup time delay is a programmable parameter that
can be adjusted over a range that depends on the particular protection variable being used.The
dropout time delay counter is used to delay the reset of the pickup timer if the protection variable
changes such as to cause the pickup signal to return to a false (logic zero) condition.
In the simplest case of operation, the protection variable exceeds the pickup level and remains
there. The pickup time delay counter would start counting until the value of the counter exceeds
the "pickup time delay" and a trip or alarm would be generated. The dropout time delay counter
has no involvement in this simplest type of operation. This case is shown in the top line of figure
Various Pickup and Dropout Time Delay Counter Various Examples of Operation for the cases
of latched and unlatched operation.
Figure 4-2 Various Pickup and Dropout Time Delay Counter Examples of Operation
The dropout time delay counter is used to reset the pickup time delay counter when the pickup
condition disappears. The second line of Various Pickup and Dropout Time Delay Counter
Examples of Operation shows the case where the pickup signal goes to zero for a time greater
than the value of the dropout time delay. The dropout time delay is a programmable parameter
that is shown in figure Generalized Protection Function Block Diagram. The dropout time delay
counter counts up once the pickup signal becomes false and resets the pickup time delay
counter.
The bottom two rows of the second figure shown show more complex behaviors involving
shorter time variations of the pickup signal.
Boolean Logic equations for the counters are
Pickup Counter
● Count = /Pickup timed out * enabled * pickup
● Reset = Reset (ext) + Dropout timed out
Dropout Counter
● Count = /(/Pickup * /Pickup timer) * (/Pickup timed out + /Latch
control * Pickup timed out)
● Reset = /(Dropout timed out + /Dropout) * (Pickup timed out * Latch
control) + Reset (ext)
where:
/ indicates a logical inversion (not)
+ indicates a logical OR
* indicates a logical AND
Table 4-1 Pickup Level Settings for Variable Undercurrent Protection Example
The resulting speed demand dependent pickup levels as shown in the figure titled "Variable
Pickup Undercurrent Graph " shown below.
Undercurrent 50
Pickup Level 40
(%) 30
20
10
0
0 50 100 150 200 250
Speed Demand (%)
Thermal Overload
The thermal overload protection functions use a thermodynamic model of the machine to
predict the total amount of thermal capacity (basically margin to maximum temperature) that
has been used as the machine temperature increases. A value of 100% thermal capacity used
would imply that the machine is at the maximum allowable temperature. The thermal model
uses a k-factor to adjust the value of current at which the machine will eventually reach full rated
temperature at maximum rated ambient temperature. There are also heating, cooling, and
stopped thermal time constants that dynamically adjust the model to match how quickly the
machine will heat up and cool down either when moving or when stopped.
A fixed thermal overload protection function and a variable thermal overload function are
provided. The fixed thermal overload function allows the use of a fixed value (does not vary with
the drive speed demand setting) of k-factor and the time constants. The variable thermal
overload function allows the k-factor, the heating time constant, and the cooling time constant
to be made a function of the speed demand setting. The parameters are programmed over a
range of speed demand setting from 0 to 190% in the same way as the pickup parameters are
set for the variable pickup level protection functions. The k-factor would be adjusted as a
function of speed to account for changes in the machine losses as the electrical frequency
changes. The time constants would be adjusted to account for changes in the heat transfer
characteristics of the machine as the speed changes.
See also
Installation External Wiring (Page 27)
IEEE Device Numbers and Functions (Page 169)
4.2 Introduction
The next chapters of this manual provide a brief of description of each AMP device protection.
Additional technical data, including keypad and tool parameter text, ID, units, and values are
shown in table format which provideds the end-user with easy access to device specific data.
Where applicable, block diagrams, equations, and curves are also provided.
S7-1200 4 Channel
Programmable Resistance 8 Channel
Logic Temperature Resistance Temperature
Controller Detector Detector Module
Module
Power
Ethernet
Ethernet
+24V Power
Switch
Per-unit Values
All the AMP functions use per-unit values to set pickup and dropout levels as well as speed-
based enables. In a per-unit system, engineering quantities (such as voltages or currents) are
normalized to their rated or maximum values. The value of the resultant per-unit values is
typically zero to one although the values can be and are often expressed in percentages. The
AMP system uses percentage values to set per-unit quantities. Voltage, current, frequency,
power, torque, and speed are per-unit quantities in the AMP. Time, temperature, and power
factor are not handled as per-unit quantities and are expressed in units of seconds and degrees
Celsius or Fahrenheit, power factor does not have any associated units. For example,
consider a 1 MW machine with a rated voltage of 4160 V, and a full load current of 162A with
a rated speed of 1785 RPM that is designed to operate with 60 Hz power. This is a four-pole
machine, so the synchronous speed of the machine is 1800 RPM. The relationship between the
engineering units and per-unit quantities are shown in the table titled, "Per-unit Engineering
Unit Quantities".
9)',17(51$/:,5,1* (;7(51$/:,5,1*
%<6,(0(16 %<&86720(5
7%57'
723/& 57'
Figure 5-1 RTD Termination Diagram (for internal and external wiring)
Note
Customer must loop-back (short) all unused RTD inputs. Doing so avoids interference pickup
on unused channels which can couple into the channels that are being used. Ensure all unused
RTD inputs are shorted to earth ground. Refer to figure Internal and External Wiring for Unused
RTD inputs.
Figure 5-2 Internal and External Wiring for Unused RTD Inputs
See also
Standard Protections Block Diagram (Page 17)
Note
Menu 7 is the top of the 7000 series Drive Protect parameters.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 12 provides parameter settings as shown in table Advanced Motor Protection Menu -
Fixed Pickup Over Speed.
Table 6-1 Advanced Motor Protection Menu - Fixed Pickup Over Speed (ID 7181)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds. Fixed
Pickup Overspeed is mutually exclusive with Variable Pickup Overspeed.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 12 provides parameter status as shown in table Advanced Motor Protection Menu -
Variable Pickup Over Speed.
Table 6-2 Advanced Motor Protection Menu - Variable Pickup Over Speed (ID 7189)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds. Variable
Pickup Overspeed is mutually exclusive with Fixed Overspeed.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Note
Setting Fixed Pickup and Variable Pickup Underspeed Protection Parameters
When setting Fixed Pickup and Variable Pickup Underspeed Protection Parameters, ensure
that settings are consistent with drive capabilities and with the settings of the accelerationramp
settings, Refer to the relevant NXGpro Control Manual (A5E33474566) provided with your
drive.
Device 14 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Underspeed.
Table 6-3 Advanced Motor Protection Menu - Fixed Pickup Underspeed Device (ID 7217)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds. Fixed
Pickup Underspeed is mutually exclusive with Variable Pickup Underspeed.
Reset
Time
Constant
1 = Enable
0 = Disable
Low Pass
Motor Speed Count
Filter
Enable Pickup Output Trip or
Time Delay >= Alarm
+ Σ < (Counter) Pickup
Pickup Low Pass Output
1 = pickup Timed
Level Filter - Zero Reset
0 = dropout Pickup Out
Time Delay
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Note
Setting Fixed Pickup and Variable Pickup Underspeed Protection Parameters
When setting Fixed Pickup and Variable Pickup Underspeed Protection Parameters, ensure
that settings are consistent with drive capabilities and with the settings of the accelerationramp
settings, Refer to the relevant NXGpro Control Manual NXGpro Control Manual
(A5E33474566) provided with your drive.
Device 14 provides parameter status as shown in table Advanced Motor Protection Menu -
Variable Pickup Underspeed .
Table 6-4 Advanced Motor Protection Menu - Variable Pickup Underspeed (ID 7226)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds. Variable
Underspeed is mutually exclusive with Fixed Underspeed.
Reset
Time
Constant
1 = Enable
0 = Disable
Low Pass
Motor Speed Count
Filter
Enable Pickup Output Trip or
Time Delay >= Alarm
+ Σ < (Counter) Pickup
Pickup Low Pass Output
1 = pickup Timed
Level Filter - Zero Reset
0 = dropout Pickup Out
Time Delay
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 37 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Undercurrent.
Table 6-5 Advanced Motor Protection Menu - Fixed Pickup Undercurrent Device (ID 7256)
The maximum response time with zero delay (pickup counter=0) is 10 milliseconds. Fixed
Pickup Under Current is mutually exclusive with Variable Pickup Under Current.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 37 provides parameter status as shown in table Advanced Motor Protection Menu -
Variable Pickup Undercurrent .
Table 6-6 Advanced Motor Protection Menu - Variable Pickup Undercurrent Device (ID 7266)
The maximum response time with zero delay (pickup counter=0) is 10 milliseconds. Variable
Pickup Undercurrent is mutually exclusive with Fixed Pickup Undercurrent.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 37P provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Underpower Relay.
Table 6-7 Advanced Motor Protection Menu - Fixed Pickup Underpower Relay (ID 7297)
The maximum response time with zero delay (pickup counter=0) is 10 milliseconds.
Reset
Time
Constant
1 = Enable
0 = Disable
Low Pass
Motor Power Count
Filter
Enable Pickup Output Trip or
Time Delay >= Alarm
+ Σ < (Counter) Pickup
Pickup Low Pass Output
1 = pickup Timed
Level Filter - Zero Reset
0 = dropout Pickup Out
Time Delay
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Description
● Input measurements:
– Uses any RTD protections identified as "bearing"
● Configuration parameters:
– Refer to Device 49 - Machine Thermal Overload for parameters and settings
The maximum response time with zero delay (pickup counter=0) is 50 milliseconds.
Table 6-8 Advanced Motor Protection Menu - Mechanical Condition Monitor - Fixed Pickup Torque Pulsation (ID 7306)
Description
Torque producing current and motor flux associated with motor operation allows for the
calculation of motor torque as the product of torque producing current (iqs) and the machine
magnetic flux (λs). The torque producing current is the component of machine current that is in
phase with the machine voltage. A given machine has a maximum rated value of torque
producing current that combines with any flux producing current to form the overall rated stator
current. The torque producing current (iqs) is scaled using a per unit system with one per unit iqs
equal to the rated value of iqs for the particular machine being used. Similarly, the rated
magnetic flux (stator flux) is scaled such that one per unit flux has been achieved when the
machine exhibits rated voltage at rated speed.
The per-unit torque is then given by:
Tperunit = iqs × λs
Figure 6-8 Per Unit Torque
The torque should be steady and continuous but may contain small amounts of amplitude
variation over time. Typically, these variations occur over fixed amounts of time and tend to
repeat over those fixed amounts of time.
The torque can be resolved into two components, one component being the torque average
value and the other being small amplitude variation (or cyclical component) that can be added
together to obtain the total torque. Torque pulsation protection focuses on the time duration
varying part, specifically the RMS value of the pulsating part of the torque.
The protection calculates RMS torque pulsation by sampling and recording the torque over a
specific length time window. The window of time is selectable and should be chosen to be long
enough to contain several cycles of torque variation. The window will contain N samples of
torque (T(n)). The mean of the dataset is first calculated:
n =1
1
Tmean =
N
∑ T (n)
N
The mean is subtracted from the torque to obtain only the pulsating part. The RMS value of the
remaining pulsating part is calculated:
n =1
1 2
Trms =
N
∑ (T (n ) − T )
N
mean
The RMS torque is used as an input to a standard protection block and can be configured in the
same manner as other protection functions that are based on the standard protection block
diagram.
The maximum response time must be calculated at full speed
.
The Advanced Motor Protection function design for RMS Torque Pulsation is shown below.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 46_2 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Negative Sequence Overcurrent.
Table 6-9 Advanced Motor Protection Menu - Phase Balance Current - Fixed Negative Sequence Over Current (ID 7316)
Description
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds.
The Advamced Protection function design for Negative Sequence Current is shown below.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 48 provides parameter status as shown in table Advanced Motor Protection Menu -
Maximum Start Time.
Table 6-10 Advanced Motor Protection Menu - Incomplete Sequence - Maximum Start Time (ID 7325)
The maximum response time with zero delay (pickup counter=0) is 50 milliseconds.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 48 provides parameter status as shown in table Advanced Motor Protection Menu -
Incomplete Sequence - Maximum Stop Time
Table 6-11 Advanced Motor Protection Menu - Incomplete Sequence - Maximum Stop Time (ID 7330)
The maximum response time with zero delay (pickup counter=0) is 50 milliseconds.
Table 6-12 Advanced Motor Protection Menu - Machine Thermal Model - Fixed Parameter Thermal Overload (ID 7335)
2
i ( t ) ∆t τ
H ( t ) = eq Fa + H ( t − ∆t )
k τ + ∆ t τ + ∆t
One of the inputs to the equation is ieq(t) is the equivalent heating current expressed in per unit.
One per unit current in this context is equal to the rated current of the machine being protected.
Both H(t) and ieq(t) are functions of time while the other variables in the equation are fixed
(although adjustable) parameters.
The equivalent heating current is a function of the RMS value of the stator current and the
negative sequence stator current. ieq(t) is given by:
Where:
Another parameter of the equation is the k-Factor which effectively scales the current, irated. The
k factor is indicative of the amount of additional thermal capacity in the machine beyond
operation at rated current in the rated ambient temperature environment. A k factor of greater
than one implies that additional thermal capacity exists under rated operating conditions. Tau
(τ) is the time constant which determines how fast changes in equivalent stator current affect
the amount of thermal capacity used. The time constant is selected by the model depending on
rather the machine is cooling, heating, or stopped. Delta t (Δt) is the sampling interval used to
calculate the differential (difference) equation. The sampling time is set by the drive
configuration and is on the order of a few milliseconds. The Fa term is used to account for
operation in ambient temperatures other than the maximum rated ambient temperature. The Fa
term is set equal to one unless RTD sensors are used to provide a measured ambient
temperature. A more detailed discussion of the effect of Fa will be given later when the effects
of RTD usage are presented. The time constant determines how quickly changes in effective
current result in changes in the amount of thermal capacity used. A steady equivalent current
will eventually drive the thermal capacity used to a steady state value.
The steady state value of H(t) is given by:
2
i
H steady − state = eq Fa
k
In the case where ambient temperature RTD(s) are not being used then the steady state
equation becomes:
2
i
H steady − state = eq
k
It can be seen that when the per unit (PU) equivalent stator current is equal to the k-Factor, then
the thermal capacity used will eventually reach 100%. Note that H is scaled such that an H
value of 1 corresponds to 100%.
The time constants determine how fast the thermal capacity changes in response to a change
in the equivalent current ieq. There are three time constants that apply during different
operating modes of the machine. The stopped time constant is used when the machine is
stopped. The heating and cooling time constants are used when the machine is running. The
heating time constant is used when the thermal capacity used is increasing and the cooling time
constant is used when the thermal capacity used is falling.
T − Tlim it
Fa = max
Tmax − Ta
Tlimit is the maximum ambient temperature in which the machine is rated to operate. Ta is the
actual value of ambient temperature as measured by the RTD(s) assigned to the "ambient"
group. Ta is set equal to Tlimit in the case where no ambient temperature measurement is
provided making the value of Fa equal to one. Tmax is the maximum operating temperature of the
stator winding. As equation 4 shows, the value of Fa basically scales the steady state value of
the amount of thermal capacity used. A high value of ambient temperature will increase the
amount of steady state thermal capacity used while a low value of ambient temperature will
decrease it. An ambient temperature in excess of Tmax will force the thermal capacity used to the
saturation value of 500%.
The stator group temperature is used to determine a minimum value of thermal capacity used
that is based on the stator temperature reading. The value of thermal capacity used that is
predicted by the model is overridden when the value of thermal capacity used as determined
by the stator RTD(s) is higher when the "use stator RTDs" parameter is selected such as to use
the stator temperature measurement. The thermal capacity used based on the temperature
reported by the stator RTD group is shown in "Thermal Capacity used as determined by Stator
Temperature".
100%
(1 – HCSR) x 100%
0%
Tlimit Tmaxoper Tmax
The variables Tlimit and Tmax are the maximum rated ambient temperature and the maximum
allowable insulation temperature as earlier defined. The variable Tmaxoper is the operating
temperature of the stator at full rated load and at an ambient temperature of Tlimit. The amount
of thermal capacity used when the stator temperature is at Tmaxoper is determined based on the
hot to cold stall ratio (HCSR) in accordance with the equation below:
Note that H is scaled such that a value of H=1 corresponds to 100% thermal capacity used. The
hot to cold stall ratio is defined as the ratio of the rated maximum stall time of a machine which
has been operating at full rated load in a maximum rated ambient temperature environment for
a time period long enough to reach thermal equilibrium to the maximum to the rated maximum
stall time of a machine which has stabilized in the same ambient temperature environment
without operating.
The value of HCSR will presumably be less than or equal to one since the allowable stall time
with a hot stator winding should be less than the allowable stall time with a cold stator winding.
For example, if the allowable stall time of a machine is 5 seconds with a cold stator, and 4
seconds with a hot stator, then the HCSR will be equal to 0.8 and the amount of thermal
capacity used when the stator RTDs report a temperature equal to Tmaxoper will be 20%. When
the stator RTD(s) are enabled, the thermal overload function will report the model predicted
value if that value is greater than 20% or the value of 20% obtained from the stator temperature
measurement.
Table 6-13 Advanced Motor Protection Menu - Machine Thermal Model - Variable Thermal Overload (ID 7352)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds.
The details of the variable thermal overload function are the same as in the case of the fixed
thermal overload function except that three of the model parameters can be varied as a function
of the speed command of the drive (% demand). Please refer to the fixed model function,
(Device 49T - Machine Thermal Model - Fixed Parameter Thermal Overload (ID 7335), for the
specific details and equations of the thermal overload model.
The k-Factor can be varied as a function of the demand to effectively change the value of
current at which the steady state value of the thermal capacity used is equal to 100%. Since
losses increase with increasing frequency, the current required to reach rated machine
temperature is likely to be lower at high speeds. A reduced k factor at higher demand settings
can be used to adjust the steady state value of thermal capacity used to account for such speed
effects. Adjustment of the k factor as a function of the speed demand can also be used to
account for decreased cooling effects at low speeds in cases where the cooling is diminished
at low speeds. Figure " Use of a Variable k-Factor in Variable Thermal Overload Protection
Function" shows an example of how to use the 20 parameters to define a k-Factor variation with
the demand setting. The values of the parameters are given in Table "Values of the k-Factor
Settings". Note that the programmed value at 190% demand is used at all speeds in excess of
190%.
k Factor
1.4
1.2
1
0.8
k Factor
0.6
0.4
0.2
0
0 50 100 150 200 250
Speed Demand (%)
% Demand k-Factor
0 0.7
10 0.8
20 0.9
30 1
40 1
50 1
60 1
70 1.05
80 1.1
90 1.15
100 1.15
110 1.1
120 1.05
130 1
140 0.95
150 0.9
160 0.85
170 0.8
180 0.75
190 0.7
See also
AMP Data Screen (Page 160)
Table 6-15 RTD Protection Menu - Machine Thermal Overload - Fixed Pickup RTD Protection (ID 7429)
The maximum response time with zero delay (pickup counter = 0) is 10 milliseconds for RTDs
1 through 12 is 50 milliseconds.
See also
AMP Data Screen (Page 160)
RTD Status Screen (Page 164)
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 50 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Instantaneous Overcurrent.
Table 6-16 Advanced Motor Protection Menu - Fixed Pickup Instantaneous Overcurrent (ID 7515)
The maximum response time with zero delay (pickup counter=0) is 5 milliseconds.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 51 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Inverse Time Overcurrent.
Table 6-17 Advanced Motor Protection Menu - Fixed Pickup Inverse Time Overcurrent (ID 7533)
Selecting User Prog will display the User Programmed Curve Menu (7538) shown below.
60
50
Trip Time
40
(seconds) Reset Time Pickup Time
30
20
10
0
0 50 100 150 200
RMS Current (%)
The table shown below contains the parameters used to generate the User Programmed
OverCurrent Trip Curve Example diagram.
The time dial multipler (TDM) affects the actual value of the trip time as well as the curve input
data. If the TDM is set to one, then the times in the table will be obtained but the times may also
be scaled with a non-unity value of the TDM setting. The reset type must also be set to "timed"
for the reset values in the table to apply. With reset type set to "instantaneous", an
instantaneous reset will occur when the current falls below the pickup level.
IEEE Curve
The pickup time as a function of current is given by:
τ
Tdo − TDM I pu 2
reset
1−( I )
rms
Figure 6-18 IEEE Reset Curve Equation
Each graphic below depicts the IEEE Curve for each curve type using the data given in the
IEEE Curve Data Table.
IEEE
extremely inverse curve
TDM=1.0
3
10
2
10
(seconds)
trip time
1
10
0
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IEEE
extremely inverse reset time
TDM=1.0
3
10
reset time
(seconds)
2
10
1
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
IEEE
very inverse curve
TDM=1.0
2
10
(seconds)
trip time
1
10
0
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IEEE
very inverse reset time
TDM=1.0
3
10
reset time
(seconds)
2
10
1
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
IEEE
moderately inverse curve
TDM=1.0
2
10
(seconds)
trip time
1
10
0
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IEEE
moderately inverse reset time
TDM=1.0
2
10
reset time
(seconds)
1
10
0
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
ANSI Curve
The pickup time as a function of current is given by:
τ
Tdo − TDM I pu 2
reset
1−( I )
rms
Figure 6-26 ANSI Reset Curve Equation
ANSI
extremely inverse curve
TDM=1.0
2
10
1
10
(seconds)
trip time
0
10
-1
10
1 1.5 2 2.5 3 3.5 4 4.5 5
ANSI
extremely inverse reset time
TDM=1.0
2
reset time 10
(seconds)
1
10
0
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
ANSI
very inverse curve
TDM=1.0
(seconds)
trip time
0
10
ANSI
very inverse reset time
TDM=1.0
2
reset time 10
(seconds)
1
10
0
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
ANSI
inverse curve
TDM=1.0
2
10
1
10
(seconds)
trip time
0
10
-1
10
1 1.5 2 2.5 3 3.5 4 4.5 5
ANSI
inverse reset time
TDM=1.0
2
reset time 10
(seconds)
1
10
0
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
ANSI
moderately inverse curve
TDM=1.0
(seconds)
trip time
0
10
ANSI
moderately inverse reset time
TDM=1.0
5.5
5
4.5
3.5
3
reset time
(seconds)
2.5
1.5
IAC Curve
The pickup time as a function of current is given by:
τ
Tdo − TDM I pu 2
reset
1−( I )
rms
Figure 6-36 IAC Reset Curve Equation
IAC
extremely inverse curve
TDM=1.0
2
10
1
10
(seconds)
trip time
0
10
-1
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IAC
extremely inverse reset time
TDM=1.0
2
10
reset time
(seconds)
1
10
0
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
stator current to pickup current ratio
Figure 6-38 IAC Extremely Inverse Reset Time
IAC
very inverse curve
TDM=1.0
(seconds)
trip time
0
10
IAC
very inverse reset time
TDM=1.0
2
10
reset time
(seconds)
1
10
0
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
IAC
inverse curve
TDM=1.0
(seconds)
trip time
0
10
IAC
inverse reset time
TDM=1.0
5
4.5
3.5
2.5
reset time
(seconds)
1.5
1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
IAC
short inverse curve
TDM=1.0
0
10
(seconds)
trip time
-1
10
-2
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IAC
short inverse reset time
TDM=1.0
1.1
1
0.9
0.8
0.7
0.6
reset time
(seconds)
0.5
0.4
0.3
Tpu = TDM K
I rms E −1
I pu
Figure 6-45 IEC Pickup Curve Equation
Tdo − TDM τ reset
1−( II pu )
2
rms
Figure 6-46 IEC Reset Curve Equation
IEC
inverse curve
TDM=1.0
2
10
(seconds)
trip time
1
10
0
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IEC
inverse reset time
TDM=1.0
2
10
reset time
(seconds)
1
10
0
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
IEC
extremely inverse curve
TDM=1.0
3
10
2
10
(seconds)
trip time
1
10
0
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IEC
extremely inverse reset time
TDM=1.0
3
10
reset time
(seconds)
2
10
1
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
IEC
short inverse curve
TDM=1.0
2
10
1
10
(seconds)
trip time
0
10
-1
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IEC
short inverse reset time
TDM=1.0
2.6
2.4
2.2
2
1.8
1.6
1.4
reset time
(seconds)
1.2
0.8
0.6
IEC
very inverse curve
TDM=1.0
3
10
2
10
(seconds)
trip time
1
10
0
10
1 1.5 2 2.5 3 3.5 4 4.5 5
IEC
very inverse reset time
TDM=1.0
3
10
reset time
(seconds)
2
10
1
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Tdo = TDM I 2 100
pu
I rms
Figure 6-56 I2t Reset Time Equation
2
I t
inverse curve
TDM=1.0
2
10
(seconds)
trip time
1
10
0
10
1 1.5 2 2.5 3 3.5 4 4.5 5
2
I t
inverse reset time
TDM=1.0
500
450
400
350
300
250
reset time
(seconds)
200
150
100
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
I4t Curve
The pickup time as a function of current is given by:
Tpu = TDM 100 4
I rms
I pu
Figure 6-59 I4t Pickup Time equation
Tdo = TDM I100 4
pu
I rms
Figure 6-60 I4t Reset Time equation
Each graphic below depicts the I4t for each curve type .
4
I t
inverse curve
TDM=1.0
2
10
1
10
(seconds)
trip time
0
10
-1
10
1 1.5 2 2.5 3 3.5 4 4.5 5
4
I t
inverse reset time
TDM=1.0
280
260
240
220
200
180
reset time
(seconds)
160
140
120
100
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 55 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Maximum Power Factor
Table 6-21 Advanced Motor Protection Menu - Fixed Pickup Maximum Power Factor (ID 7573)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
6.20 Device 55 - Power Factor Relay Device (Fixed minimum power factor)
Overview
Fixed pickup minimum power factor is used to protect the motor against operation under
conditions of low power factor that would indicate abnormal conditions in the machine. The
fixed pickup minimum power factor function provides a single minimum power factor setting
that produces a trip or alarm condition when the power factor. The function can be enabled
when the speed demand is above a programmable level. The function can also be enabled
once a programmable time period has elapsed since the starting of the motor.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 55 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Minimum Power Factor.
Table 6-22 Advanced Motor Protection Menu - Fixed Pickup Minimum Power Factor (ID 7582)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
The zero-sequence voltage uses a per unit system based on the rated line to neutral voltage of
the machine. A 100% zero sequence voltage will occur when the RMS value of the average of
the three phase voltages with respect to earth ground is equal to the rated machine voltage
(given as a line-to-line voltage) divided by the square root of 3.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 59G provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Instantaneous Zero Sequence Overvoltage
Table 6-23 Advanced Motor Protection Menu - Fixed Pickup Instantaneous Zero Sequence Overvoltage (ID 7563)
The maximum response time with zero delay (pickup counter = 0) is 5 ms. The maxium pickup
time is zero.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
OverZeroSeqVoltage Protection Diagram
Fixed Pickup Instanteous Zero Sequence Overvoltage and fixed Pickup Definite Minimum
Time Sequence Overvoltage use the same diagram. To provide clarity to the end-user, the titles
are repeated so that the graph is adjacent to the text description of the function. This method
of description is applied consistently throught this manual.
6.22 Device 59G - Fixed Pickup Definite Minimum Time Zero Sequence
Overvoltage
Overview
Fixed pickup definite minimum time zero sequence overvoltage is used to protect the motor
against sustained operation under conditions of high zero sequence voltage which could be
caused by high phase to ground leakage or a ground fault. The fixed pickup zero sequence
overvoltage function provides a single zero sequence overvoltage setting that produces a trip
or alarm condition when the zero sequence voltage rises above that value. The function offers
an enable that latches once a programmable minimum speed has been reached. The function
can also be enabled once a programmable time period has elapsed since the starting of the
motor.
Note
The zero-sequence voltage uses a per unit system based on the rated line to neutral voltage of
the machine. A 100% zero sequence voltage will occur when the RMS value of the average of
the three phase voltages with respect to earth ground is equal to the rated machine voltage
(given as a line-to-line voltage) divided by the square root of 3.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 59G provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Definite Minimum Time Zero Sequence Overvoltage.
Table 6-24 Advanced Motor Protection Menu - Fixed Pickup Instantaneous Overcurrent (ID 7524)
The maximum response time with zero delay (pickup counter = 0) is 10 ms. The maximum
pickup time is zero.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
OverZeroSeqVoltage Protection Diagram
Fixed Pickup Instanteous Zero Sequence Overvoltage and fixed Pickup Definite Minimum
Time Sequence Overvoltage use the same diagram. To provide clarity to the end-user, the titles
are repeated so that the graph is adjacent to the text description of the function. This method
of description is applied consistently throught this manual.
Note
The Protection Systems Engineer must ensure that either the fixed or variable Thermal Model
protection parameters are properly set.
A thermal model is required for hot starts, cold starts, and minimum thermal capacity to run. It
is not possible to use these functions without a thermal model. The software is arranged to
automatically enable the fixed thermal model once one the three functions is enabled. That is,
the thermal model cannot be disabled as long as the hot starts, cold starts, or minimum thermal
capacity functions are enabled.
If the thermal model is not configured properly, the system will not be protected as intended.
Device 66 provides parameter status as shown in table Advanced Motor Protection Menu -
Starts per Hour.
Table 6-25 Advanced Motor Protection Menu - Starts per Hour (ID 7590)
The maximum response time with zero delay (pickup counter = 0) is 50 milliseconds.
Note
The Protection Systems Engineer must ensure that either the fixed or variable Thermal Model
protection parameters are properly set.
A thermal model is required for hot starts, cold starts, and minimum thermal capacity to run. It
is not possible to use these functions without a thermal model. The software is arranged to
automatically enable the fixed thermal model once one the three functions is enabled. That is,
the thermal model cannot be disabled as long as the hot starts, cold starts, or minimum thermal
capacity functions are enabled.
If the thermal model is not configured properly, the system will not be protected as intended.
Device 66 provides parameter status as shown in table Advanced Motor Protection Menu -
Notching or Jogging - Cold Starts per Hour.
Table 6-26 Advanced Motor Protection Menu - Notching or Jogging - Cold Starts per Hour (ID 7593)
The maximum response time with zero delay (pickup counter = 0) is 50 milliseconds.
Note
The Protection Systems Engineer must ensure that either the fixed or variable Thermal Model
protection parameters are properly set.
A thermal model is required for hot starts, cold starts, and minimum thermal capacity to run. It
is not possible to use these functions without a thermal model. The software is arranged to
automatically enable the fixed thermal model once one the three functions is enabled. That is,
the thermal model cannot be disabled as long as the hot starts, cold starts, or minimum thermal
capacity functions are enabled.
If the thermal model is not configured properly, the system will not be protected as intended.
Device 66 provides parameter status as shown in table Advanced Motor Protection Menu - Hot
Starts per Hour
Table 6-27 Advanced Motor Protection Menu - Hot Starts per Hour (ID 7598)
The maximum response time with zero delay (pickup counter = 0) is 50 milliseconds.
Note
The Protection Systems Engineer must ensure that either the fixed or variable Thermal Model
protection parameters are properly set.
A thermal model is required for hot starts, cold starts, and minimum thermal capacity to run. It
is not possible to use these functions without a thermal model. The software is arranged to
automatically enable the fixed thermal model once one the three functions is enabled. That is,
the thermal model cannot be disabled as long as the hot starts, cold starts, or minimum thermal
capacity functions are enabled.
If the thermal model is not configured properly, the system will not be protected as intended.
Device 66 provides parameter status as shown in table Advanced Motor Protection Menu -
Notching or Jogging - Maximum Thermal Capacity Used to Start
Table 6-28 Motor Protection Menu - Maximum Thermal Capacity Used to Start (ID 7603)
The maximum response time with zero delay (pickup counter = 0) is 50 milliseconds.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), the drive will either
default to the phase locked loop to obtain motor speed information or the drive will stop.
Device 81 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Overfrequency
Note
Over-frequency is enabled by a minimum speed or by a starting time, both of which can be set
to zero. If set to zero, the function is enabled on start-up.
Table 6-29 Advanced Motor Protection Menu - Fixed Pickup Overfrequency (ID 7606)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds. Fixed Over
Frequency is mutually exclusive with Variable Over Frequency.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Overfrequency Protection Diagram
Fixed Pickup Overfrequency and Variable Pickup Overfrequency use the same diagram. To
provide clarity to the end-user, the titles are repeated so that the graph is adjacent to the text
description of the function. This method of description is applied consistently throught this
manual.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 81 provides parameter status as shown in table Advanced Motor Protection Menu -
Variable Pickup Overfrequency.
Note
Over-frequency is enabled by a minimum speed or by a starting time, both of which can be set
to zero. If set to zero, the function is enabled on start-up.
Table 6-30 Advanced Motor Protection Menu - Variable Pickup Overfrequency (ID 7615)
Advanced Motor Protection Menu - Variable Overfrequency Curve Menu (ID 7616)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds.. Variable
Over Frequency is mutually exclusive with Fixed Over Frequency.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Overfrequency Protection Diagram
Fixed Pickup Overfrequency and Variable Pickup Overfrequency use the same diagram. To
provide clarity to the end-user, the titles are repeated so that the graph is adjacent to the text
description of the function. This method of description is applied consistently throught this
manual.
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 81 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup Overfrequency.
Table 6-31 Advanced Motor Protection Menu - Fixed Pickup Underfrequency (ID 7645)
The maximum response time with zero delay (pickup counter=0) is 20 milliseconds. Fixed
Pickup Underfrequency is mutually exclusive with the Variable Pickup Underfrequency.
Reset
Time
Constant
1 = Enable
0 = Disable
Low Pass
Motor Frequency Count
Filter
Enable Pickup Output Trip or
Time Delay >= Alarm
+ Σ < (Counter) Pickup
Pickup Low Pass Output
1 = pickup Timed
Level Filter - Zero Reset
0 = dropout Pickup Out
Time Delay
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response), when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 81 provides parameter status as shown in table Advanced Motor Protection Menu -
Variable Pickup Underfrequency.
Table 6-32 Advanced Motor Protection Menu - Variable Pickup Underfrequency (ID 7654)
The maximum response time with zero delay (pickup counter = 0) is 20 milliseconds. Variable
Pickup Underfrequency is mutually exclusive with the Fixed Pickup Underfrequency.
Reset
Time
Constant
1 = Enable
0 = Disable
Low Pass
Motor Frequency Count
Filter
Enable Pickup Output Trip or
Time Delay >= Alarm
+ Σ < (Counter) Pickup
Pickup Low Pass Output
1 = pickup Timed
Level Filter - Zero Reset
0 = dropout Pickup Out
Time Delay
Time
Constant
1 - Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
Note
Encoder Loss
Depending upon the value of parameter 1320 (encoder loss response),when a loss of the
encoder occurs, the drive will either default to the phase locked loop to obtain motor speed
information or the drive will stop.
Device 81 provides parameter status as shown in table Advanced Motor Protection Menu -
Fixed Pickup High Frequency Rate of Change.
Table 6-33 Advanced Motor Protection Menu - Fixed Pickup High Frequency Rate of Change (ID 7684)
The maximum response time with zero delay (pickup counter = 0) is 10 milliseconds.
Reset
Time
Constant
1 = Enable
0 = Disable
Time
Constant
Dropout Count
Level Enable Dropout
Output
Time Delay
(Counter) >=
Zero Reset
Dropout
Timed
Dropout Out
Time Delay
Output
Latching
Control
1 = Latched
NOTICE
Specify RTD Type at Time of Manufacture
The AMP is configured to use PT-100 Type RTDs at time of manufacture by default.
Note
All function outputs are visible at the networkms through manual IDs.
See also
AMP Alarms / Faults (Page 161)
'LVSOD\3DUDPHWHUV
(80 0 0) (menu)
After selecting the Display Parameters menu as shown above, scroll using the arrow to select
one of the following picklist variable parameters to display.
The additional screens as discussed in the following paragraphs provide the user with the
ability to view protection variables. These screens are:
● AMP Data Screen
● AMP Alarms / Faults Screen
● RTD Status Screen
See also
AMP Alarms / Faults (Page 161)
Device 49RTD - Machine Thermal Overload - Fixed Pickup RTD Protection (Page 70)
Device 49T - Machine Thermal Model - Variable Parameter Thermal Overload (Page 63)
See also
AMP Data Screen (Page 160)
See also
Device 49RTD - Machine Thermal Overload - Fixed Pickup RTD Protection (Page 70)
Note
The PLC is a ‘key’ to unlock the AMP and RTD functions in the VFD control.
● Should the AMP menu not display properly on the PLC, please check for loose connections
to the PLC and verify that the internal IP address of the VFD is set to 172.17.20.16
(Parameter #9310).
● The PLC contains an encrypted passcode. The passcode only gives access to the PLC
software in the VFD control. This passcode is not required to program the protection
functions of the motor that AMP provides.
● If a PLC issue persists, please contact Siemens Support. This information is contained in
the Service and Support chapter of this manual.
The links below provide the technical specification data for the Advanced Motor Protection
Relay.
https://mall.industry.siemens.com/mall/en/us/Catalog/Search/?
searchTerm=6ES72121AE400XB0
https://mall.industry.siemens.com/mall/en/us/Catalog/Search/?
searchTerm=6ES72315PD320XB0
https://mall.industry.siemens.com/mall/en/us/Catalog/Search/?searchTerm=6EP13315BA10
https://mall.industry.siemens.com/mall/en/us/Catalog/Search/?
searchTerm=6GK2771AA100110
Separate descriptive tables as configured for the devices used in Motor Protection for
SINAMICS GH180 Medium Voltage Variable Frequency Drives are provided in the sections
that follow.
See also
Standard Protections Block Diagram (Page 17)
A.2 Abbreviations
The following table provides a listing of acronyms / abbreviations used in the manual along with
its full nomenclature.
DANGER
Untrained personnel performing work on equipment may cause personal injury, death,
equipment damage, VFD operational integrity
Ensure that only personnel trained by Siemens work on the equipment.
Certain components described in this documentation may be replaced or repaired only by
personnel trained by Siemens.
Work incorrectly performed on the drive can result in damage to the equipment, degrade VFD
operational integrity, and possibly cause physical injury to personnel or even death.
Siemens accepts no liability for any damage that occurs because these instructions have not
been observed, e.g. if an untrained person carries out a repair or replaces components.
Johnson City, TN, USA 800 333 7421 +1 423 262 5710
Nuremberg, Germany +49 911 895 7222 +49 180 5050 222
https://www.industry.usa.siemens.com/drives/us/en/electric-drives/Pages/electric-drives.aspx
● Technical support is available round the clock 24 hours / 365 days a year.
● Your inquiries are delivered directly to the responsible specialist.
● Have all relevant data available and technical support can respond to your inquiry as quickly
as possible.
● Send records, screen shots and photos to the specialists to support fault analysis.
NOTICE
ESD Sensitive Equipment
● Always be aware of electrostatic discharge (ESD) when working near or touching
components inside the VFD cabinet. The printed circuit boards contain components that
are sensitive to electrostatic discharge. Handling and servicing of components that are
sensitive to ESD should be done only by qualified personnel and only after reading and
understanding proper ESD techniques. The following ESD guidelines should be observed.
Following these rules can greatly reduce the possibility of ESD damage to printed circuit
board (PCB) components.
● Always transport static sensitive equipment in antistatic bags.
● Always use a soldering iron that has a grounded tip. Also, use either a metallic vacuum-
style plunger or copper braid when desoldering.
● Ensure that anyone handling the printed circuit boards is wearing a properly grounded
static strap. The wrist strap should be connected to ground through a 1 Megohm resistor.
Grounding kits are available commercially through most electronic wholesalers.
● Static charge build-up can be removed from a conductive object by touching the object with
a properly grounded piece of metal.
● When handling a PC board, always hold the card by its edges.
● Do not slide printed circuit boards (PCBs) across any surface (e.g., a table or work bench).
If possible, perform PCB maintenance at a workstation that has a conductive covering that
is grounded through a 1 Megohm resistor. If a conductive tabletop cover is unavailable, a
clean steel or aluminum tabletop is an excellent substitute.
● Avoid plastic Styrofoam™, vinyl and other non-conductive materials. They are excellent
static generators and do not give up their charge easily.
● When returning components to Siemens Industry, Inc. always use static-safe packing. This
limits any further component damage due to ESD.
NOTICE
Electrostatic discharge
Electronic components can be destroyed in the event of improper handling, transporting,
storage, and shipping.
Pack the electronic components in appropriate ESD packaging; e.g. ESD foam, ESD
packaging bags and ESD transport containers.
To protect your equipment against damage, follow the instructions given below.
● Avoid physical contact with electronic components. If you need to perform absolutely
essential work on these components, then you must wear one of the following protective
gear:
– Grounded ESD wrist strap
– ESD shoes or ESD shoe grounding strips if there is also an ESD floor.
● Do not place electronic components close to data terminals, monitors or televisions.
Maintain a minimum clearance to the screen (> 10 cm).
● Electronic components should not be brought into contact with electrically insulating
materials such as plastic foil, plastic parts, insulating table supports or clothing made of
synthetic fibers.
● Place components in contact with ESD-suited materials e.g. ESD tables, ESD surfaces,
ESD packaging.
● Measure on the components only if one of the following conditions is met:
– The measuring device is grounded with a protective conductor.
– The measuring head of a floating measuring device has been discharged directly before
the measurement.
The necessary ESD protective measures for the entire working range for electrostatically
sensitive devices are illustrated once again in the following drawings. Precise instructions for
ESD protective measures are specified in the standard IEC 61340-5-1.
G G G
E E
H H
I I I I I
F D F D F D
1 Sitting
2 Standing
3 Standing/sitting
a Conductive floor surface, only effective in conjunction with ESD shoes or ESD shoe grounding
strips
b ESD furniture
c ESD shoes or ESD shoe grounding strips are only effective in conjunction with conductive floor‐
ing
d ESD clothing
e ESD wristband
f Cabinet ground connection
Figure A-1 ESD Protective Measures
A L
Arcing, 14 Lock-out / Tag-out procedure, 13
Asynchronous motors, 11
Auxiliary power supply, 11
M
Main entry, 160
C Subentry, 139
Cabling, 11
Commissioning, 11
contact S
hotline, 173
Shielding, 11
website, 173
Starts per Hour, 133
Synchronous motors, 11
E
Electrostatic discharge, 175 T
Electrostatic Protective Measures, 177
technical support
EMC-compliant installation, 11
hotline, 173
Transport, 11
F
Five safety rules, 12 V
Fixed Under Frequency with MSE,
Variable Pickup Overfrequency, 139
Fixed Under Power with MSE,
Variable Pickup Underfrequency, 137, 145
Fixed Over Speed, 31, 54, 56, 57, 134, 135, 136,
Variable Thermal Overload, 63
137
Variable-Speed Drives, 11
Fixed Pickup Instantaneous Zero Sequence
Overvoltage, 128
Fixed Pickup Maximum Power Factor, 124
Fixed Pickup Minimum Power Factor, 126
Fixed Pickup Underfrequency, 143
Fixed Under Power with MSE, 48, 58, 80, 82, 130
G
Grounding, 11
I
Industrial network, 11
Installation, 11
ZZZVLHPHQVFRPGULYHV
6LHPHQV,QGXVWU\,QF
3'/'
+XQW9DOOH\5RDG
1HZ.HQVLQJWRQ3$
8QLWHG6WDWHVRI$PHULFD