Professional Documents
Culture Documents
XRIO Converter Manual 7SA522 V4.6 ENU TU2.11 v1.100
XRIO Converter Manual 7SA522 V4.6 ENU TU2.11 v1.100
OMICRON PTL
XRIO Converter
User Manual
V1.100
Contents
1 General Information
The Siemens 7SA522 XRIO converter is designed for testing Siemens 7SA522 distance protection relays
by using the OMICRON Test Universe 2.11 software. The converter provides all necessary data for
testing the distance protection functions (see section 2) of the 7SA522 relays. The converter is tested with
the following relay:
• 7SA522 V4.6
• MLFB: 7SA52214AA004QR4
Note: This converter is tested with the relay described above. It will work with 7SA6522 relays with
firmware version V4.6. It may work with similar relays, too.
Important: The "Relay Parameter Section" with its parameter and ID's has changed according to the
xRIO-Export of DIGSI 4.81. Thus the xRIO-Import for xRIO Converter from V1.100 is only working with
DIGSI 4.81. DIGSI 4.80 will not be compatible any longer by using the xRIO-Converter Series 1.1x.
5 Functional Range
The Siemens 7SA6x XRIO converter implements the following functions:
• 21 Distance (quadrilateral and mho)
• 50, 50N, 51, 51N Overcurrent
• 79 Autoreclosure
For some of the functions listed above use the RIO interface of the Test Universe software. Consequently,
the test modules are configured automatically without using LinkToXRIO.
The following functions are using the RIO interface:
• 21 Distance (quadrilateral and mho)
• 50/51 Overcurrent
9 Converter Structure
The converter is divided into two sections: the 7SA522 section and the RIO section. Both sections consist
of several function blocks. The converter comes up in the standard view; the RIOplus section and the
template controller section can only be seen in the advanced view.
The General Information block contains the parameters which are important for the test report, e.g.
information about the substation and the feeder. Furthermore it contains power system parameters which
are important for the test modules. These parameters are linked to the device part of the RIO section and
are available in the test report.
9.1.2.1 NamePlate
The NamePlate block contains all necessary information to identify the protection device to be tested. This
block contains the relay vendor, serial number, model, the relay location and a description.
9.1.2.2 PowerSystemParameters
The number of phases, phase rotation and the nominal frequency are stored in this block.
All necessary data for testing the impedance starting elements are stored in the StartingElements
subblock.
All necessary data for testing the impedance starting element are stored in the StartingElements
subblock.
9.1.2.7 SwitchOnToFault
This block contains all necessary data to test the switch on to fault protection. The nominal values and the
CT/VT settings used by this protection function can be found here. The main data parameters of the
switch on to fault are:
• MinOperateTime
• MaxOperateTime
• OperateDelayTime
• ResetDelayTime
• CurrentDetectorValue
9.2 RIO
The RIO section of the converter contains all specialized RIO functions which are needed to use the more
specialized test modules (like Advanced Distance or Overcurrent) provided by the OMICRON Test
Universe software.
Warning: Do not change any values in this section. The values have been set using the relay settings of
the Customer Input section.
Note: Do not activate the former test object view in the advanced mode of the XRIO test object. Changing
parameters in this view will disable formulas in the RIO section.
9.2.1 Distance
This RIO distance function provides the necessary values for testing the distance protection functions of
the 7SA522 relay with the Advanced Distance test module. The protection functions supported by this RIO
function include:
• 21 Distance quadrilateral
• 21 Distance mho
The following RIO function for testing these distance protection functions is available:
• Distance
Note: The phase to ground mho distance zones are modeled as loop impedances. The setting values for
these zones can not be seen in the impedance plane!
The following RIO function for testing these overcurrent protection functions is available:
• Overcurrent
The three stages with the smallest pickup values are combined and the resulting characteristic curve is
shown in the RIO overcurrent function block.
Figure 8:-phase fault (grounded net -> the base for the Advanced Distance test module)
Figure 8 shows that in case of the one-phase fault the output of the Advanced Distance test module
always contains unbalanced phase-phase voltages. Consequently, consider different trip times for one
zone during the test. The default values for these parameters are:
• 40 ms for the trip delay (1206)
• 25% of the max unbalance allowed (1223)
These default values cause a circle of influence with a radius of 6.8 ohms. This will affect testing one-
phase faults. The delay of 40 ms causes a large deviation from the nominal value of the trip time.
Example:
T2-1phase = 200 ms, delay for one phase faults 40 ms, this meets a deviation of 20%!
Note: The 1206 and 1223 parameters will cause false trip times in the Advanced Distance test module for
phase-ground faults when the relay is set for isolated or compensated networks. In these cases, check
the trip times manually.