Type 1 Structural Drawing
Type 1 Structural Drawing
DESIGN SPECIFICATIONS
* Provide a clear cover of 1.5" for beams, 0.75" for slabs and 3" for footings,
4 d b ≥ 2 1 2"
if not otherwise mentioned.
2- Design Load r D
d
5- Structural System b
Splice
- 2 Storeyed R.C Building
a - Self-Weight of Construction Materials r
- Brick Masonary Infill Wall D = Minimum inside diameter of bend
Unit Weight D = 2r = 6 d b for No. 3 through 8
Material Unit - Intermediate Moment Resisting Frame
12 d b
= 8 d b for No. 9, 10 and 11
6
Lb/ft3
db
Natural Soil 115.0 Splice Length
,3
SPIRAL ARCHITECTS.
r
"
m
r
in
Splice in tension ( Deformed Bars )
.
D = 2r
D = Minimum inside diameter of bend
b- Floor Load Concrete Cover = 4 db for No. 5 and smaller Splice Length
= 6 db for No. 6, 7 and 8
Design Load (Lb/ft3) Concrete Protection for Reinforcement ( net concrete cover ) Splice in compression ( Both Plain and Deformed )
Slab Load Type
Unit Weight Unit The following minimum thickness of concrete cover outside of the outermost steel are specified. d
b
d
20 Lb/ft2 Dead Load b
Floor Slab
40 Lb/ft2 Live Load Splice Length (in)
20 Lb/ft2 Dead Load Note Bar Dia.
Plain Bars Deformed Bars
Roof Slab Not exposed directly to
20 Lb/ft2 Live Load Exposed directly to weather or in contact with d b, ( in ) Tension Compression
Tension Compression
Particulars weather or not in contact * Splice the lower bars within a distance of ( clear span) / 4 from f y= 40 ksi f y= 50 ksi f y= 60 ksi f y= 40 ksi f y= 50 ksi f y= 60 ksi
ground the support, if splice is necessary.
with ground 3/8 18 16 16 16 16 16 16 16
* Splice the upper bars within a middle third of clear span,
Footing * 3 in (Side & End Cover) if splice is necessary.
1/2 24 20 16 16 16 16 16 18
5/8 30 25 16 18 22 17 19 23
3 1 * Do not splice any bar within the cantilever span.
Remark:
Slabs and Walls in 2 in. but 1 . for No.5 (16mm) and smaller bars 3/4 36 30 21 26 31 20 23 27
4 2
c- Wind Load * Do not splice more than 50 % of total at any section. 7/8 42 35 28 35 42 24 26 32
1 1 48 40 37 46 55 27 30 35
Beams and Columns 1 in 2 in
- Wind Speed = 100 mph ( Yangon Area ) 2
If concrete is poured in direct contact with the ground without the use of forms, a cover of at least 3 in, shall be provided.
d- Earthquake Load However, it may be reduced, but not to be less than 50mm.Ifat least 3 in thick (1:3:6) lean concrete is placed under the footing. DESIGN SPECIFICATIONS
28 MAY 2021
Bar Spacing ( For maximum size of aggregate 625mm )
1 July 2021
Yangon Area 0.7g 0.2g Anchorage ( Beam - Column Connections ) Anchorage ( Beam - Girder Connections )
The following minimum anchorage lengths shall be The following minimum anchorage lengths shall be
Long - period transition period TL= 6 Sec provided, if not otherwise mentioned. provided, if not otherwise mentioned.
Minimum clear
Type of member Maximum c/c spacing
spacing
1
Beam 1 in -
-
3
3- Specification of Standard Materials Strength Column
1
1 db (or) 1
1 -
2 2 Ld1 Ld1 Ld1 Ld1
Issue / Date:
Revision/ Date:
Plot Date:
Approved by:
Checked by:
Concrete Compressive Stength
3h (or) 18" (one-way slab) Ld2 Ld2
- Fcu = 30 MPa
Ld2 Ld2
- f'c = 24 MPa (~3450psi) Slab/Stair 3 in ( to save labour ) 2h (or) 18" (two-way slab)
Plain Bars Deformed Bars Plain Bars Deformed Bars
Reinforcing Bar Yield Strength Temp. & shr.steel:5h (or)18"
- fy = 50000 psi Anchorage Length in inches Anchorage Length in inches
Type-1-Structural Drawing
≤ L/8 ≤ L/8
File Name :
DESIGN SPECIFICATIONS DESIGN SPECIFICATIONS
DESIGN SPECIFICATIONS
STRUCTURAL NOTE
h
Main bars as shown in beam schedule Main bars as shown in beam schedule
16mm Ø 24"
18mm Ø 27"
Drawn by: TK
(between the middle third of the clear span) 22mm Ø 41" A A B
L/3 25mm Ø 46" 6 x longitudinal bar diameter
L Concrete Protection for Reinforcement S ≤
6"
The following minimum concrete cover shall be provided for reinforcement. Tension lap splice within center half of
L1
member length enclosed with transverse L1
reinforcement
Sr. No. Min: Cover
U MYINTTAR
(1) Concrete cast against and permanently exposed to earth 3"
Concrete Cast to Earth or Weather
(2)
2"
No.6 through No.8 bars 0.25 x ( smaller of "C 1" or "C 2" )
Splice Detailing (for beam) Bottom Steel
No.5 bars, W31 or D31 wire, and smaller 1.5" Lo Lo S ≤ 6 x longitudinal bar diameter
Concrete Not Exposed to Weather or in Contact with Ground
Sx
Slabs, Walls, Joints
No.14 and No.18 bars 1.5"
Bar Dia. Splice Length
2h 2h Smaller than No.14 bars 0.75" 4" ≤ S x = 4 + [( 14 - h x ) / 3] ≤ 6"
10mm Ø 16" (3)
Beams , Columns h x = max. value of " x " on all column faces
Project Owner :
h
12mm Ø 16"
16mm Ø 18" Primary Reinforcement, Ties, Stirrups, Spirals 1.5" x ≤ 14" on center
Drawing Title :
Project Title :
1:50
Splice Length Splice Length 18mm Ø 21" 6 d b ≥ 3"
Shells, Folded Plate Members 0.01 ≤ g ≤ 0.06 6 d b extension
20mm Ø 23"
Scale:
L/4 L/4 6 db ≥ 3"
X X X 6 db
L Section-(A-A) C1 135° db 90°
Section-(B-B)
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
F-1
F-2
F-2
F-2
[6'-7"]
2.00m
B
F-2
F-3
F-3
[8'-6"]
2.60m
B
F-2
F-2
F-5
F-4
[8'-6"]
2.60m
[42'-8"]
13.00m
Foundation Plan
C'
F-1
F-2
2.40m
[7'-10"]
D
F-2
F-4
F-4
Note: Footing
3.40m
[11'-2"]
1
F-6
F-6
0.46m 0.46m
[1'-6"] [1'-6"]
FOUNDATION PLAN
SCALE 1:20
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
[6'-7"]
2.00m
B
[8'-6"]
2.60m
B
[8'-6"]
2.60m
[42'-8"]
13.00m
C'
3.40m
[11'-2"]
1
SCALE 1:20
RETAINING WALL PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
PB-2
PB-2
PB-2
PB-3
PB-1 PB-1
B
[2']
0.60m
PB-2
0.30m
[1']
[8'-6"]
2.60m
PB-2
PB-2
PB-2
B
PB-3
0.30m
[1']
[2'-5"]
0.72m
C
0.60m
0.30m
PB-1 [1']
[2'-9"]
0.85m
[5'-1"]
1.56m
PB-2
PB-3
PB-3
[8'-6"]
2.60m
PB-2
PB-2 PB-2
PB-2
[42'-8"]
13.00m
1.46m
C'
[4'-9"]
PB-2 PB-2
PB-3
2.40m
PB-2
[7'-10"]
1.71m
[5'-7"]
D
PB-2 PB-2
3.40m
[11'-2"]
PB-1 ( 10"x12" )
PB-3 ( 10"x16" )
PB-2 ( 10"x14" )
0.46m
Note: Plinth Beam
[1'-6"]
PB-3
E
1
[2'-5"]
0.72m
[1'-7"]
[1'-7"]
0.48m
0.48m
Detail Section-X1
1.20m
[3'-11"]
GROUND FLOOR BEAM PLAN
SCALE 1:20
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
[6'-7"]
2.00m
B
[2']
0.60m
0.30m
[1']
[8'-6"]
2.60m
B
0.30m
[1']
[2']
[2'-6"]
0.75m
C
0.60m
0.30m
[1']
[8'-6"]
2.60m
[42'-8"]
13.00m
C'
3.40m
[11'-2"]
0.46m
1
0.46m [1'-6"]
[1'-6"] PB-3
E
0.72m
0.72m
[1'-7"]
[1'-7"]
0.48m
0.48m
1.20m 1.20m
8" Thk Cantilever Suspended Slab
[3'-11"] [3'-11"]
SCALE 1:50
GROUND FLOOR SLAB ( ON GRADE ) PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
[6'-7"]
2.00m
B
[8'-6"]
2.60m
B
[8'-6"]
2.60m
[42'-8"]
13.00m
Note:
3.40m
[11'-2"]
LB- ( 10"x10" )
1
E
SCALE 1:20
LINTEL BEAM WITH CANTILEVER SLAB PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
[1']
[6"]
0.30m
0.15m
A
LB LB
LB
LB
[6'-7"]
2.00m
B
0.15m
[6"]
[3'-3"]
0.98m
LB
0.30m
[8'-6"]
2.60m
B
[1']
C
[8'-6"]
2.60m
[42'-8"]
13.00m
0.30m
[1']
LB
C'
LB
Note:
LB
LB
3.40m
[11'-2"]
LB- ( 10"x10" )
1
4" Thk Cantilever Slab
LB
E
[1'-1"]
0.32m
Detail Section-X2
SCALE 1:20
LINTEL BEAM WITH CANTILEVER SLAB PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
FB-2
FB-2
FB-2
FB-2
FB-1 FB-2
B
FB-3
[8'-6"]
2.60m
FB-2
B
FB-2
FB-2
[8'-6"]
2.60m
FB-3
FB-3
FB-2
FB-2
FB-2
[4'-6"]
C'
1.19m
FB-2 FB-2 FB-2 [3'-11"] FB-2
2.40m
[7'-10"]
FB-2
FB-1
1.78m
2.93m
[5'-10"]
FB-3
FB-3
D
[9'-8"]
D
FB-2
FB-2
FB-2
FB-1 ( 10"x12" )
FB-3 ( 10"x16" )
FB-2 ( 10"x14" )
FB-4 ( 10"X18" )
Note: Floor Beam
FB-4 FB-4
E
1
SCALE 1:20
FIRST FLOOR BEAM PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
[1']
[6"]
0.30m
0.15m
A
[6'-7"]
2.00m
0.15m
[6"]
B
0.30m
[1']
[8'-6"]
2.60m
B
[8'-6"]
2.60m
[8'-6"]
2.60m
0.00m
C'
[0"]
2.05m 0.30m
[6'-9"] [1']
2.40m
[7'-10"]
D
0.30m
[1']
D
5.78m
[18'-11"]
3.40m
[11'-2"]
[1'-1"]
0.33m
Detail Section-X3
1
SCALE 1:20
FIRST FLOOR SLAB PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
[6'-7"]
2.00m
B
[8'-6"]
2.60m
B
[8'-6"]
2.60m
[42'-8"]
13.00m
Note:
3.40m
[11'-2"]
LB- ( 10"x10" )
1
E
SCALE 1:20
LINTEL BEAM WITH CANTILEVER SLAB PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
FB-1
FB-1
FB-1
FB-2 FB-1
B
[8'-6"]
2.60m
FB-1
FB-1
B
FB-2 FB-1
C
[8'-6"]
2.60m
FB-2
FB-2
FB-1
FB-1 FB-1
C'
FB-1
FB-2
FB-2
2.40m
[7'-10"]
FB-1
D
FB-1 FB-1
D
3.40m
[11'-2"]
FB-1
FB-1
FB-1 ( 10"x14" )
FB-2 ( 10"x16" )
Note: Floor Beam
FB-2
E
1
SCALE 1:20
ROOF DECK BEAM PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
[1']
[6"]
0.30m
0.15m
A
[6'-7"]
2.00m
B
[2'-9"]
0.83m
[8'-6"]
2.60m
B
0.30m
[1']
[2'-5"]
0.75m
C
[8'-6"]
2.60m
0.30m
[1']
2.40m
[7'-10"]
D
0.30m
[1']
D
3.40m
[11'-2"]
[1'-6"]
0.45m
1
SCALE 1:20
ROOF DECK SLAB PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
RB-2
RB-2
RB-2
B
RB-2 RB-1
[8'-6"]
2.60m
B
RB-2
RB-2
RB-2
C
RB-3 RB-3
[8'-6"]
2.60m
2.40m
[7'-10"]
D
3.40m
[11'-2"]
RB-1 ( 10"x14" )
RB-2 ( 10"x16" )
Note: Roof Beam
RB-3 ( 12"X24" )
E
1
SCALE 1:20
ROOF BEAM PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
[1']
0.30m
A
[6'-7"]
2.00m
B
0.30m 0.30m
[1'] [1']
[8'-6"]
2.60m
B
1.18m
[3'-10"]
Detail Section-X4
[8'-6"]
2.60m
2.40m
[7'-10"]
D
3.40m
[11'-2"]
1
SCALE 1:20
ROOF SLAB PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
[6'-7"]
2.00m
1.45m
[4'-9"]
B
[8'-6"]
2.60m
B
LB-(10"X16")
C
1.00m
[3'-3"]
[8'-6"]
2.60m
[42'-8"]
13.00m
C'
3.40m
[11'-2"]
1
SCALE 1:20
LANDING BEAM & SLAB PLAN
C
A
9.30m
[30'-6"]
2.35m 2.85m 4.10m
[7'-8"] [9'-4"] [13'-5"]
A
[6'-7"]
2.00m
1.40m
[4'-7"]
B
[8'-6"]
2.60m
B
LB-(10"X20")
C
0.45m
[1'-6"]
[8'-6"]
2.60m
[42'-8"]
13.00m
C'
3.40m
[11'-2"]
1
SCALE 1:20
LANDING BEAM & SLAB PLAN
0.30m
[1']
SPIRAL ARCHITECTS.
ROOF BEAM SCHEDULE
Top Reinforcement ( No. & Size ) Bottom Reinforcement Stirrups
Torsion Steel
Type Size Remark
0.50m Right Right ( No. & Size ) Support Mid Span
Left Mid Left Mid
[1'-8"]
RB-1 10"x14" 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ - 10mmØ @ 4" c/c 10mmØ @ 6" c/c
C-2 10" x 20" Foundation To Roof Deck Level 10-16mmØ 2-10mmØ @ 6" c/c
0.25m
-
[10"]
RB-2 10"x16" 4-18mmØ 4-18mmØ 4-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 10mmØ @ 4" c/c 10mmØ @ 6" c/c
RB-3 12"x24" 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 2-16mmØ 10mmØ @ 4" c/c 10mmØ @ 6" c/c
Remark:
FOOTING SCHEDULE
Size Top Reinforcement Bottom Reinforcement
Depth From N.G.L
Type L ( ft-in ) B ( ft-in ) H ( ft-in ) Remark
28 MAY 2021
Longer Direction Shorter Direction Longer Direction Shorter Direction ( footing bottom level )
1 July 2021
F-1 4'-0" 4'-0" 14" - - 16mmØ Bar@6"c/c 16mmØ Bar@6"c/c -8'-0" Square Footing
LANDING BEAM SCHEDULE
-
F-2 5'-0" 5'-0" 14" - - 16mmØ Bar@6"c/c 16mmØ Bar@6"c/c -8'-0" Square Footing
Top Reinforcement ( No. & Size ) Bottom Reinforcement Stirrups
Torsion Steel
Issue / Date:
Revision/ Date:
Plot Date:
Type
Approved by:
16mmØ Bar@6"c/c 16mmØ Bar@6"c/c Square Footing
Checked by:
F-3 5''-6" 5'-6" 14" - - -8'-0" Size ( No. & Size ) Remark
Left Mid Right Left Mid Right Support Mid Span
F-4 6'-6" 6'-6" 14" - - 16mmØ Bar@6"c/c 16mmØ Bar@6"c/c -8'-0" Square Footing
LB-1 10"x16" 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ - 10mmØ @ 4" c/c 10mmØ @ 6" c/c
F-5 7'-6" 7'-6" 14" - - 16mmØ Bar@6"c/c 16mmØ Bar@6"c/c -8'-0" Square Footing LB-2 10"x20" 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 2-16mmØ 10mmØ @ 4" c/c 10mmØ @ 6" c/c
F-6 7'-0" 5'-0" 14" - - 16mmØ Bar@6"c/c 16mmØ Bar@6"c/c -8'-0" Rectangular Footing
Top Reinforcement ( No. & Size ) Bottom Reinforcement Stirrups Reinforcement Remark
Torsion Steel
Type Size Remark
Type-1-Structural Drawing
Right Right ( No. & Size ) Support Mid Span Type Thickness Layer Short Direction Short Direction
Left Mid Left Mid
Cont: Edge Mid Span Discont: Edge Cont: Edge Mid Span Discont: Edge
- 10mmØ @ 4" c/c 10mmØ @ 6" c/c
PB-1 10"x12" 3-16mmØ 3-16mmØ 3-16mmØ 3-16mmØ 3-16mmØ 3-16mmØ
File Name :
FLOOR BEAM SCHEDULE
Drawn by: TK
FB-1 10"x12" 3-16mmØ 3-16mmØ 3-16mmØ 3-16mmØ 3-16mmØ 3-16mmØ 10mmØ @ 4" c/c 10mmØ @ 6" c/c
FB-2 10"x14" 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ - 10mmØ @ 4" c/c 10mmØ @ 6" c/c
Type Thickness Main Bar Distribution Bar Remark
SCHEDULE
FB-3 10"x16" 4-18mmØ 4-18mmØ 4-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ - 10mmØ @ 4" c/c 10mmØ @ 6" c/c
U MYINTTAR
FB-4 10"x18" 4-18mmØ 4-16mmØ 4-18mmØ 3-18mmØ 3-18mmØ 3-18mmØ 2-16mmØ 10mmØ @ 4" c/c 10mmØ @ 6" c/c Stair 5" 12mmØ @ 6" c/c 12mmØ @ 6" c/c 10mmØ @ 6" c/c 10mmØ @ 6" c/c
LB (Lintel Beam) 10"x10" 2-16mmØ 2-16mmØ 2-16mmØ 2-16mmØ 2-16mmØ 2-16mmØ 8mmØ @ 4" c/c 8mmØ @ 6" c/c
Project Owner :
Drawing Title :
Project Title :
1:20
Scale:
C:\Users\Engr. Myo Aung\Downloads
STR-17
Drawing No. :
1 SCHEDULE
SCALE 1:20
Plinth Beam Sectional Detail
8" Thk Cantilever Wall Supporting Slab
10mm Ø Bar @ 4"c/c (Main Top)
10mm Ø Bar @ 8"c/c (Main Bottom) 10"x10" Lintel Beam
0.25m 0.25m 0.25m 0.25m 10mm Ø Bar @6: c/c Distribution
4" Thk Cantilever Wall Supporting Slab
[10"] [10"] [10"] [10"] 10"x20" R.C Column 12"x12" R.C Column 10mm Ø Bar @ 4"c/c (Main Top)
10mm Ø Bar @6: c/c Distribution
3-16mmØ ( Top Bar ) 3-16mmØ ( Top Bar ) 3-18mmØ ( Top Bar ) 3-18mmØ ( Top Bar )
0.30m
0.30m
0.35m
0.35m
[1'-2"]
[1'-2"]
[1']
[1']
10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c 10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c
3-16mmØ ( Bottom Bar ) 3-16mmØ ( Bottom Bar )
3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar ) 10"x16" Plinth Beam 0.30m
Support Mid 0.48m
[1']
PB-1 ( 10"x12" ) PB-1 ( 10"x12" ) Support Mid [1'-7"]
PB-2 ( 10"x14" ) PB-2 ( 10"x14" )
0.40m
[1'-4"]
[1'-4"]
10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c
Mid
SPIRAL ARCHITECTS.
PB-3 ( 10"x16" ) PB-3 ( 10"x16" )
0.60m
0.25m 0.25m
[2']
0.25m 0.25m
0.20m
[8"]
[10"] [10"] [10"] [10"]
Remark:
5"Thk Floor Slab
3-16mmØ ( Top Bar ) 3-16mmØ ( Top Bar ) 3-18mmØ ( Top Bar ) 3-18mmØ ( Top Bar ) 0.32m
1.18m
10"x18" Floor Beam
0.30m
0.30m
0.35m
0.35m
[1'-2"]
[1'-2"]
[1']
[1']
[1']
10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c 10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c [3'-10"]
3-16mmØ ( Bottom Bar ) 3-16mmØ ( Bottom Bar )
3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar )
0.30m
Support Mid
Detail Section-X3 [1']
FB-1 ( 10"x12" ) FB-1 ( 10"x12" ) Support Mid
FB-2 ( 10"x14" ) FB-2 ( 10"x14" ) Detail Section-X4
0.25m 0.25m
28 MAY 2021
0.25m 0.25m
1 July 2021
[10"] [10"]
[10"] [10"]
4-18mmØ ( Top Bar ) 4-18mmØ ( Top Bar )
4-18mmØ ( Top Bar ) 4-18mmØ ( Top Bar ) 2-16mmØ ( Torsion Bar ) 2-16mmØ ( Torsion Bar )
0.45m
0.45m
[1'-6"]
[1'-6"]
0.40m
0.40m
[1'-4"]
[1'-4"]
10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c 10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c
-
3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar )
Issue / Date:
Revision/ Date:
Support Mid Support Mid
Plot Date:
Approved by:
Checked by:
FB-3 ( 10"x16" ) FB-3 ( 10"x16" ) FB-4 ( 10"x18" ) FB-4 ( 10"x18" )
0.60m 0.47m
[1'-7"]
GROUND LEVEL
[2']
REF LEVEL+0.4m 9" Thk: Brick Wall
0.40m
[1'-4"]
[1'-4"]
0.35m
0.35m
[1'-2"]
[1'-2"]
Type-1-Structural Drawing
3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar )
0.45m
Support Mid Support Mid
RB-1 ( 10"x14" ) RB-1 ( 10"x14" ) RB-2 ( 10"x16" ) RB-2 ( 10"x16" )
[1'-6"]
File Name :
2-16mmØ ( Torsion Bar ) 2-16mmØ ( Torsion Bar )
0.62m
0.62m
[2']
[2']
0.47m
[1'-7"]
GROUND LEVEL
Drawn by: TK
Landing Beam Sectional Detail
FFL±0.00m
Well Compacted Sandfilling
REF LEVEL+0.4m
0.93m
[3']
U MYINTTAR
0.25m 0.25m
0.25m
[10"]
0.25m
[10"]
9" Thk: Brick Wall
[10"] [10"] 3-18mmØ ( Top Bar ) 3-18mmØ ( Top Bar )
0.50m
[1'-8"]
[1'-8"]
0.40m
0.40m
[1'-4"]
[1'-4"]
10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c 10mmØ Stirrups@ 4" c/c 10mmØ Stirrups@ 6" c/c
Project Owner :
3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar ) 3-18mmØ ( Bottom Bar )
Drawing Title :
Project Title :
1:30
Support
LB-1 ( 10"x16" )
Mid
LB-1 ( 10"x16" )
Support
LB-2 ( 10"x20" ) 0.25m
[10"]
Mid
LB-2 ( 10"x20" ) 0.45m
[1'-6"]
Scale:
LB-2 ( 10"x20" ) Landing
10mmØ Bar@6"c/c
Beam with 6" Thk:
Lintel/Sun Shade Slab
Exterior Retaining Wall Detail
10mmØ Bar@6"c/c
STR-18
Drawing No. :
1 BEAM SECTIONAL DETAIL & RETAINING WALL DETAIL
SCALE 1:30
A B C C' D E
2.00m 2.60m 2.60m 2.40m 3.40m
[6'-7"] [8'-6"] [8'-6"] [7'-10"] [11'-2"]
13.00m
[42'-8"]
0.24m
[10"]
SPIRAL ARCHITECTS.
[3'-10"]
0.21m
[8"]
RB-1 RB-2
RB-3 8" Thick Cantilever Slab
[9'-10"]
3.00m
2.65m
[8'-8"]
Remark:
ROOF DECK LEVEL 10"x16" Roof Beam
0.10m
[4"]
5" Thick Floor Slab 5" Thick Floor Slab
FFL +7.77m 5"Thick Cantilever Slab
28 MAY 2021
1 July 2021
FB-1 FB-2 FB-2 FB-1 FB-1 0.75m
FB-2
[2'-6"]
-
Issue / Date:
Revision/ Date:
Plot Date:
Approved by:
Checked by:
[11'-6"]
3.50m
[2'-6"]
[2'-10"]
0.87m
5" Thick Floor Slab 5" Thick Floor Slab 0.46m
8"Thick Cantilever Slab
FFL +4.27m [1'-6"]
[2'-11"]
0.88m
FB-2 FB-1 FB-2 FB-2 FB-2 FB-4
Type-1-Structural Drawing
0.46m 4"Thick Cantilever Slab
File Name :
2.92m
[9'-7"]
0.47m
[1'-7"]
[1'-7"]
Drawn by: TK
GROUND LEVEL PB-2 PB-3
U MYINTTAR
REF LEVEL+0.4m
2.44m
[8']
Project Owner :
Drawing Title :
Project Title :
1:20
Scale:
CROSS SECTION A-A
SPIRAL ARCHITECTS.
RB-2 RB-2 RB-2
[9'-10"]
3.00m
6"Thk Lintel/Sun shade Slab
Remark:
10"x10" Lintel Beam
28 MAY 2021
1 July 2021
6"Thk Lintel/Sun shade Slab
FB-1 FB-1
10"x10" Lintel Beam
-
5" Thick Landing Slab
8" Thk Cantilever Slab
Issue / Date:
Revision/ Date:
Plot Date:
Approved by:
Checked by:
[11'-6"]
3.50m
To Support Cantilever Brick Wall RISER =160mm
THREAD=250mm
10"x20" Landing Beam with
10.77m
[35'-4"]
6"Thk Lintel/Sun shade Slab
[2'-11"]
0.88m
6"Thk Lintel/Sun shade Slab FB-2 FB-2 FB-3 FB-2
Type-1-Structural Drawing
10"x10" Lintel Beam
[12'-6"]
RISER =160mm
3.80m
THREAD=250mm
File Name :
10"x16" Landing Beam
1.90m
[6'-3"]
Drawn by: TK
GROUND LEVEL
U MYINTTAR
REF LEVEL+0.4m
2.44m
[8']
Project Owner :
Drawing Title :
Project Title :
1:20
Scale:
C:\Users\Engr. Myo Aung\Downloads
STR-20
CROSS SECTION B - B
Drawing No. :
1 CROSS SECTION B-B
SCALE 1:20
A B C C' D E
2.00m 2.60m 2.60m 2.40m 3.40m
[6'-7"] [8'-6"] [8'-6"] [7'-10"] [11'-2"]
13.00m
[42'-8"]
0.25m
SPIRAL ARCHITECTS.
0.20m
[8"]
RB-1 RB-2
RB-3 8" Thick Cantilever Slab
[9'-10"]
3.00m
2.64m
[8'-8"]
Remark:
ROOF DECK LEVEL
0.30m 5" Thick Floor Slab 5" Thick Floor Slab
FFL +7.77m [1']
28 MAY 2021
FB-1
1 July 2021
FB-2 FB-2 FB-1
-
[11'-6"]
3.50m
Issue / Date:
Revision/ Date:
Plot Date:
Approved by:
Checked by:
10.77m
[35'-4"]
0.30m
4"Thk Lintel/Sun shade Slab [1'] FB-2 FB-2 FB-2
Type-1-Structural Drawing
10"x10" Lintel Beam
10"x10" Lintel Beam with 4" Thk
File Name :
GROUND FLOOR LEVEL
5" Thick Slab On Grade
GROUND LEVEL
Drawn by: TK
FFL±0.00m Well Compacted Sandfilling
REF LEVEL+0.4m
U MYINTTAR
2.44m
[8']
Project Owner :
Drawing Title :
Project Title :
1:20
Scale:
C:\Users\Engr. Myo Aung\Downloads
CROSS SECTION C - C
STR-21
Drawing No. :
1 CROSS SECTION C-C
SCALE 1:20
FFL±0.00m
FFL +0.47m
FFL +4.27m
FFL +7.77m
FFL +10.77m
GROUND LEVEL
REF LEVEL+0.4m
ROOF TOP LEVEL
0.10m
[4"]
FB-3
RB-2
PB-3
[5'-6"]
1.68m
0.15m
[6"]
PB-2
4.10m
[13'-5"]
FB-1
0.05m
[2"]
2.41m
[7'-11"]
[3'-9"]
1.14m
3
RB-2
PB-3
FB-3
9.30m
[30'-6"]
CROSS SECTION D - D
[9'-4"]
2.85m
FB-2
PB-2
[1']
[1']
0.30m
0.30m
RB-1
0.88m
[2'-11"]
[7'-8"]
2.35m
1.75m
[5'-9"]
[5'-9"]
SPIRAL ARCHITECTS.
12mmØ Bar@6"c/c (Top & Bottom) 10mmØ Bar@6"c/c (Top & Bottom)
RISER =160mm RISER =160mm
THREAD=250mm THREAD=250mm
10"x20" Landing Beam with WAIST =130mm 10"x20" Landing Beam with WAIST =130mm
6"Thk Lintel/Sun shade Slab 6"Thk Lintel/Sun shade Slab
LB-2 LB-2
FIRST FLOOR LEVEL FIRST FLOOR LEVEL
10mmØ Bar@6"c/c (Top & Bottom)
FFL +4.27m 3.65m FFL +4.27m
3.65m
[12']
[12']
12mmØ Bar@6"c/c (Top & Bottom)
Remark:
FB-2 FB-2 FB-2
Add 12mmØ @ 6"c/c (Extra Bar) Add 12mmØ @ 6"c/c (Extra Bar)
12mmØ Bar@6"c/c (Top & Bottom) RISER =160mm 10mmØ Bar@6"c/c (Top & Bottom) RISER =160mm
THREAD=250mm THREAD=250mm
WAIST =130mm WAIST =130mm
28 MAY 2021
1 July 2021
LB-1
1.90m
1.90m
[6'-3"]
[6'-3"]
10mmØ Bar@6"c/c (Top & Bottom)
GROUND FLOOR LEVEL GROUND FLOOR LEVEL
5" Thick Slab On Grade 5" Thick Slab On Grade
-
FFL +0.47m PB-2 PB-2 FFL +0.47m PB-2 PB-2
Issue / Date:
Revision/ Date:
Plot Date:
Approved by:
Checked by:
GROUND LEVEL GROUND LEVEL
Type-1-Structural Drawing
Project No. : SPIRAL -
GROUND FLOOR LEVEL GROUND FLOOR LEVEL
PB-2
FFL +0.47m FFL +0.47m
0.47m
[1'-7"]
0.47m
[1'-7"]
GROUND LEVEL
C C'
GROUND LEVEL
C-1 ( 12"X12" ) C-2 ( 10"X20" )
File Name :
2.60m
FFL±0.00m 8-16mmØ Main Bar FFL±0.00m 10-16mmØ Main Bar
2-10mmØ Stirrups@6"c/c 2-10mmØ Stirrups@6"c/c [8'-6"]
REF LEVEL+0.4m REF LEVEL+0.4m
2.44m
[8']
GROUND LEVEL
WAIST =130mm
H
3" Thk: ( 1:3:6: ) Lean Concrete 3" Thk: ( 1:3:6: ) Lean Concrete
Drawn by: TK
FFL±0.00m Well Compacted Sandfilling
9" Thk: Hardcore & Sanfilling 9" Thk: Hardcore & Sanfilling 10mmØ Bar@6"c/c (Top & Bottom)
( L )( B ) 1.52m REF LEVEL+0.4m
[5']
Section
Section
U MYINTTAR
C-1 ( 12"X12" )
8-16mmØ Main Bar C-2 ( 10"X20" )
2-10mmØ Stirrups@6"c/c 10-16mmØ Main Bar
2-10mmØ Stirrups@6"c/c
B
2.13m
Project Owner :
[7']
Drawing Title :
Project Title :
1:15
16mmØ Bar@6" c/c
MESH ( Bottom Layer )
16mmØ Bar@6" c/c
L MESH ( Bottom Layer )
ENTRANCE STAIR DETAIL
Scale:
Plan
1.52m
Typical Footing Detail For Square Footing
[5']
Plan
Drawing No. :
1 STAIR & FOOTING DETAIL
SCALE 1:15