Professional Documents
Culture Documents
I/A Series Remote Terminal Unit (RTU) C50 V.28 Dual Communications Module
I/A Series Remote Terminal Unit (RTU) C50 V.28 Dual Communications Module
PSS 21H-8A2 B4
The C50 V.28 Dual Communications Module provides • Two independent, user configurable channels
two independent communication channels (RS-232).
• Built-in microprocessor that processes signals
Each of the communication channels can be used as and eases the load on the Master Processor
a separate SCADA channels to two Master Stations, Module
or the second channel may be used as a backup to
the master channel. • Supported protocols:
Product Specifications
PSS 21H-8A2 B4
Page 2
ELECTROBUS ADDRESS
INTERFACE DECODER
SHARED RAM
CPU ADDRESS
DECODER
DATA/ADDRESS PROCESSOR
LATCH
EPROM
10 Second 10 Second
Timeout on RTS SERIAL Timeout on RTS
COMMUNICATIONS
CONTROLLER
Module Overview
Figure 1 explains the operational structure of the C50
Dual Communications Board and its relationship to
the Electrobus interface and external modems. V.28 DCB
Communications Subsystem
The communications subsystem of the C50 RTU is RUN/FAIL
based on intelligent communication cards (see the
Dual Communications Module in Figure 2). These
cards contain a microprocessor, with associated RAM
and ROM. The onboard processor is responsible for
sending and receiving messages, as well as control
of the communications protocol. Communication with
the Master Processor Module occurs through shared
memory located on the Dual Communications
CH1
Module.
A serial communications controller (see Figure 3) and
external modem interface circuitry is used to
implement the two independent channels. The user
configures the communications controller during the
initial RTU configuration.
Error detection algorithms appropriate for each
supported communication protocol monitor
communication integrity. A high level of data integrity CH2
is guaranteed by rejecting corrupted messages.
PHYSICAL SPECIFICATIONS
Physical Size Terminations
160 mm x 125 mm 15-pin female connector
ENVIRONMENTAL SPECIFICATIONS
Ambient Temperature Humidity
0°C to 60°C (optional -20°C to 60°C) 10% to 95% RH (non-condensing)
FUNCTIONAL SPECIFICATIONS
Processor Type Interface
Z80180 V.24/RS-232 (V.28) DTE
ORDERING INFORMATION
Part Number Description
0303323 V.28 (RS232) Dual Communications Controller
1050074 Harris 5000/5500 Firmware
1050077 C3000 Conitel Firmware
1050021 C2025 Conitel Firmware
1050021 Baker Firmware
1050076 Indactic 33 Firmware
NOTE
Firmware must be separately ordered and installed.
PSS 21H-8A2 B4
Page 6
PSS 21H-8A2 B4
Page 7
PSS 21H-8A2 B4
Page 8
Foxboro and I/A Series are registered trademarks of The Foxboro Company.
An Invensys company