RECOMMENDED WATER QUALITY

CONSTITUENTS EVAPORATOR CONDENSER COOLING WATER


CHILLED WATER
(CIRCULATING)
(CIRCULATING) (MAKE UP) (5)

PH (25oC) 6.5 − 8.5 6.5 − 8.5 6.5 − 8.5


Electric Conductivity (MIC S/CM), (25oC) < 500 < 800 <200
(1)
M ALKALINITY (ppm) < 100 < 100 < 50
(2)
CHLORIDE ION CI (mg CI/I) < 100 < 200 < 50
(3)
SULPHURIC ACID ION SO (mg SO/I) < 100 < 200 < 50
TOTAL HARDNESS (mg CaCO3/I) < 100 < 200 < 50
TOTAL IRON FE (mg Fe/I) < 1.0 < 1.0 0.3
SULPHUR ION S (mg S/I) Non-Detectable Non-Detectable Non-Detectable
(4)
AMMONIUM ION NH (mg NH/I) < 0.5 < 1.0 < 0.2
SILICA IN ION STATE SIO (mg SIO/I) < 50 < 50 < 30
FREE CARBONIC ACID (mg HCO3/I) 10 − −
TOTAL DISSOLVED SOLIDS (ppm) < 150 < 600 < 150

NOTES
1) Increased M Alkalinity causes excessive fouling of tubes and reduction in output of the
equipment.
2) Higher chloride level than specified in circulation causes tubes failure.
3) Higher sulphate level (Sulphuric acid ion) than specified in circulation causes tubes failure.
4) Ammonium ion exceeding the recommended level is detrimental to copper tubes.

5) Blow down of the cooling water in circulation must be carried out to maintain the cycle
concentration. We strongly recommend cooling water treatment if your water quality is not
meeting the recommended standard.