Professional Documents
Culture Documents
CH - 02 - Water Distribution Systems
CH - 02 - Water Distribution Systems
CH - 02 - Water Distribution Systems
CHAPTER TWO
WATER DISTRIBUTION SYSTEMS IN BUILDIGNS
2.1. INTRODUCTION
At any point within a building, a water distribution system must deliver an adequate water pressure and
volume to operate the fixtures or equipment that it serves, without excessive noise, under all conditions
of normal use.
Mains Connection
After being treated, water is distributed from the Water Supplier to individual buildings and domestic
premises through a network of pipes known as mains. The local mains supply provides the ‘final leg’ for
the supply of water to buildings and domestic dwellings. The Water Supplier is also responsible for the
ferrule connection of a new or replacement supply pipe to the distribution main.
The connection between the main and the consumer’s stop tap is made using a ferrule. The ferrule is
basically a valve that is tapped into the main, with a connection to the supply pipe. The ferrule can be
turned off in order to isolate the supply pipe. Once the ferrule connection is completed, the connection
between the supply pipe and the consumer’s stop valve can take place. Figure below shows the
completed ferrule installation. Note the gooseneck in the service pipe.
DADU Page 1
Architectural Science II (Water & sewage) – ARCH 3232
1 2
Installation of external stop valves
As you can see in Figure above, the supply pipe to the building can be isolated from the main by
installing an external stop valve. This enables the external supply to be isolated for maintenance and
emergency reasons, so easy access to the stop valve is very important. The top of the chamber has a
robust stop valve cover. A stop valve cover is generally made from steel plate or a combination of steel
plate and plastic.
DADU Page 2
Architectural Science II (Water & sewage) – ARCH 3232
1. Direct system
2. Indirect system
The supply then goes on to feed the cold-water storage cistern (CWSC); which is usually found in the
roof space of the building or dwelling. The CWSC is used to supply water to the remaining draw-off
points indirectly
DADU Page 3
Architectural Science II (Water & sewage) – ARCH 3232
A pressure zone is an area of a building (it may be an entire floor, several floors, or the entire building)
supplied with water having a common pressure origin or a common supply. Buildings having more than
one pressure zone are described as having multiple pressure zones.
In low-rise buildings, the water pressure in the public water mains is usually sufficient to distribute the
water to the hydraulically most remote point. When the pressure of the water main is not sufficient for
this purpose, the pressure must be increased or “boosted or pumped,” as described in this chapter and
the one that follows.
Therefore, when planning or designing any water distribution the basic physical laws must be
considered:
1. Water is subject to the force of gravity and will find its own level.
2. To overcome friction within the conveying pipes water which is stored prior to distribution
will require to be under pressure and this is normally achieved by storing the water at a
level above the level of the outlets. The vertical distance between these levels is usually
called the head.
3. Water becomes less dense as its temperature is raised; therefore, warm water will always
displace colder water whether in a closed or open circuit.
DADU Page 4
Architectural Science II (Water & sewage) – ARCH 3232
system is used. In this system, there is a single pressure zone; i.e., all floors in the building are supplied with water
using the pressure in the water main.
pressure in the water main, the requirements of the fixtures, and the applicable plumbing code. Most plumbing
codes place restrictions on the maximum water pressure that may be delivered to a plumbing fixture.
DADU Page 5
Architectural Science II (Water & sewage) – ARCH 3232
(PRV), also called a pressure-reducing valve or pressure regulator, must be used in the water supply
branch to the lower zone.
The water supply system for a high-rise building is a combination of distribution systems. Figure 3.5
shows an 83-story high-rise building in which several water distribution systems are installed. Zone 1
typically is supplied by the pressure from the water main-to the extent permitted by the residual
pressure of the water main; it is an up-feed cold-water system.
DADU Page 6
Architectural Science II (Water & sewage) – ARCH 3232
FIG.: A water supply system in a high-rise building; several water distribution systems are installed; there are
multiple pressure zones.
Zones 2 through 9 are down-feed systems. Zone 10, the top zone, is fed from a tankers pumping system.
The gravity tank is not sufficiently elevated to supply floors 81 through 83.
It is highly desirable that the static pressure in the down-feed gravity main riser not exceed the listed or
maximum working pressure (i.e., the maximum pressure at which piping materials of the “standard” or
“normally used” type may be installed). This is to avoid the necessity of using “extra strength” piping
materials, which may increase the cost.
DADU Page 7
Architectural Science II (Water & sewage) – ARCH 3232
3. For storage of watering during interruption to damage repair etc. of the water mains
4. When the available head is insufficient to supply the water in each story in multi-story buildings
DADU Page 8
Architectural Science II (Water & sewage) – ARCH 3232
7. Screened overflow Pipe: For the exit of water above full supply level.
8. Vent pipes: For free circulation of air
9. Washout pipe: For removing water after cleaning of the reservoir
10. Water level indicator: To know the level of water inside the tank from outside.
In order to reduce the risk of waterborne diseases in water storage systems, it is recommended that the
outlet connection be positioned as near as possible to the bottom of the cistern. This allows any small
particles that may be present to pass through the system, preventing an unhealthy buildup of sediment
at the base of the cistern.
DADU Page 9
Architectural Science II (Water & sewage) – ARCH 3232
The intensity of heat is expressed as temperature, which can be measured using equipment such as a
thermometer or a thermostat. The temperature in a domestic hot water system rarely exceeds 85C.
Centralized system
With this type of system, the heated water can be stored, usually centrally within the building, supplying
a system of pipe work to various draw-off points. Stored means water held in a vessel until required,
with the water temperature usually controlled by a thermostat.
DADU Page 10
Architectural Science II (Water & sewage) – ARCH 3232
Localized system
With this type of system, the water is heated locally to meet the requirements of the consumer, a
typical example being a single point instantaneous water heater sited over a sink. These are often used
in situations where a long distribution pipe-run from a stored system would lead to an unnecessary wait
for hot water to be drawn off. Not only does this save energy and reduces the wastage of water, it also
helps prevent the risk of growth of microorganisms such as Legionella in the system.
Instantaneous supply
Instantaneous, as the name implies, means that there is a readily available (instant) supply of hot water
at the outlet, and only the amount of water drawn off is heated.
DADU Page 11
Architectural Science II (Water & sewage) – ARCH 3232
The immersion heater is inserted directly into the water through a boss fitting at the top of the storage
vessel, or in some cases two small immersion heaters are used at the top and the base of the storage
vessel thus ensuring that the whole of the vessel is heated during peak demand. The temperature is
controlled by a thermostat
DADU Page 12
Architectural Science II (Water & sewage) – ARCH 3232
The storage vessel is fitted with an internal heat exchanger, usually in the form of a coil or an annulus.
The heated water passes through the heat exchanger, heating the stored water within the vessel, and
then returning back to the boiler. This water does not mix with the stored water within the vessel, and
requires an independent feed and expansion cistern to supply it
DADU Page 13
Architectural Science II (Water & sewage) – ARCH 3232
The operation of lifting water or any fluid is called pumping. Pump, a mechanical machine, is used for
lifting water or any fluid to a higher elevation or at higher pressures.
Types of Pumps
Pumps are primarily of three types: centrifugal, reciprocating, and rotary. The most common pump
used in residential and commercial buildings is the centrifugal type. The other types are used in special
industrial applications-for example, reciprocating pumps are used in actuating large forming presses and
rotary pumps in transporting viscous liquids.
A centrifugal pump illustrated in Fig. below, is a continuously acting pump that moves liquid by
accelerating it radially outward in a rotating member (called an impeller) to a surrounding case. The
impeller is essentially a rotating disk with vanes attached to it. Arrows indicate the direction of rotation
and the direction of flow. The vanes on the impeller are curved backward, since this shape provides the
most stable flow characteristics.
DADU Page 14
Architectural Science II (Water & sewage) – ARCH 3232
PUMP CHARACTERISTICS
Capacity
The capacity Q of a pump is the rate of flow of liquid through the impeller expressed in gallons per
minute, gpm (cubic meters per hour, m3/h).
Total Head
Head (h) is the energy per unit weight of a fluid due to
It is commonly expressed as the height of a column of water in feet (or meters) which is necessary to
develop a specific pressure. The total head developed by a pump is equal to the discharge head hd minus
the suction head hs. The discharge head is the energy per unit weight of fluid on the discharge side of
the pump. The suction head is the energy per unit weight on the suction side of the pump. According to
these definitions:
DADU Page 15
Architectural Science II (Water & sewage) – ARCH 3232
Therefore, by definition, the total head H is equal to the difference between the above two equations.
If there is some distance between the points of measurement of the discharge head and the suction
head, there will be a friction loss head hf that must be added to the above equation. Values of hf in pipes
and fittings can be determined from data given in several handbooks.
The static head (Z) is the static elevation measured in feet (meters) at the same point where the
pressure is measured. Note that if a pressure gage is used, the center of the gage is the measurement
point for the static head. The centerline of the pump impeller is usually used as the reference point for
such measurements.
Input Power
The input power or brake horsepower (Pp) required to drive such a pump also varies with capacity, as
shown in Fig. below.
DADU Page 16
Architectural Science II (Water & sewage) – ARCH 3232
Output Power
The pump output power or water horsepower (PW) is given by
Efficiency varies with capacity, as shown in Fig. above, reaching a maximum value at one capacity where
the sum of all losses is a minimum.
DADU Page 17
Architectural Science II (Water & sewage) – ARCH 3232
cavitation within the pump. In multistage pumps, the 3 percent head reduction refers to the first stage
head. As illustrated in Fig. above, the NPSHR increases with capacity.
Speed
Usually a centrifugal pump is driven by a constant-speed electric motor. However, it is more efficient to
control a pump by a variable-speed drive. The extra cost of variable-speed drives can be justified by the
resultant savings in electric power.
Centrifugal pump characteristics vary with speed according to the following relationships.
The total head vs. capacity characteristics for a typical pump at several different speeds are illustrated in
Fig. below.
DADU Page 18
Architectural Science II (Water & sewage) – ARCH 3232
In order to move liquid through any system of pipes, the pump must produce a total head equal to or
greater than the total head required by the system. The system head usually increases with flow rate,
and if plotted vs. capacity, it is called the A system head curve.
The shape of the system head curve is an important consideration in the proper selection of a pump in
building services. The total head required to pump liquid through a system is the sum of the static head
and the head due to friction loss in the system.
DADU Page 19
Architectural Science II (Water & sewage) – ARCH 3232
The pump will operate where the pump curve intersects with the system head curve; at this point the
full flow required will be pumped. Because the pump is subject to wear, the total head output is
reduced. As a result, there is a reduction in flow. However, note that the reduction is greater when there
is a high static head than when the head is due only to friction losses. Hence, it is important that the
system head curve and pump characteristic curve be compared at the time of pump selection to ensure
that a 10 percent reduction in pump output, due to wear, does not result in a significant reduction in
flow rate.
Pump Efficiency
Centrifugal pumps are more efficient at high flow rates and moderate heads than at low flow rates and
high heads.
Booster pumps require no special design features; most of them can be used if properly selected for
head and capacity. On the other hand, the capacity demand on such pumps may vary from a day-time
maximum to a night-time low of practically nothing. Such operation wastes power and causes rapid
wear in pumps. For these reasons, water reserve tanks on the roof of the building or tanks under air
should be used to even out demand. A pressure switch and check valve should be used to shut down the
booster pump automatically when it is not required.
through the piping system and be a source of disturbance in quiet rooms some distance away. To minimize noise
generation, besides implementing other noise control measures, the rotational speed of the pump is often limited
to 1800 rpm. It is also helpful to select a pump that provides wide clearance between the impeller and casing
DADU Page 20
Architectural Science II (Water & sewage) – ARCH 3232
volute tongue, with a minimum value of 15 percent of the impeller radius, since this will minimize hydraulic
pulsations and therefore the generation of noise.
For water circulation systems, an in-line circulator pump is usually used. These pumps are generally operated at
low speeds with a very flexible coupling between the pump and motor and cushioned motor mountings to
minimize the transmission of motor noise to the circulation system.
The circulation of water in high-rise buildings sometimes presents problems because a high-pressure system may
be required to accommodate the height of the vertical pipes. Steel pump casings may be required to withstand the
high system pressure; care must be taken to ensure that mechanical seals also can withstand these pressures,
particularly in hot-water systems. A high-pressure hot-water system is difficult to seal because the hot water turns
to steam between the seal faces, thereby eliminating any lubricating or cooling action. As a result, the seal faces
wear quickly.
Fire Pumps
Fire pumps are designed for connection to automatic sprinkler systems; they are rarely, if ever, used.
However, they are usually turned on periodically for a short time to ensure their proper operation if
needed. For sprinkler systems that use well water as a source of supply, vertical turbine pumps are
available.
Sewage pumps are centrifugal pumps of special design, having impellers that can pump large pieces of solid matter
without clogging. Even the smallest pumps of this type are subject to the requirement that the impeller pass a
sphere 6.4cm in diameter. In addition to wide impellers, hand holes are provided in the pump casing for access to
remove obstacles that may lodge in the pump. Such a pump usually is mounted vertically to save floor space in the
confined area of a sump. This arrangement raises the motor relatively high so that it is protected in the event of
flooding of the sump. Many installations purposely raise the motor even higher with an extended drive shaft.
Other installations include the vertical sump pump of the volute type. If used for handling sanitary sewage, the
impeller of such a pump must have the same solids-handling capability described above. If the pump is used to
remove storm and other runoff water, a more conventional impeller can be used. In either case, the design and
DADU Page 21
Architectural Science II (Water & sewage) – ARCH 3232
lubrication of the lower support bearing is of paramount importance since this bearing is the weakest component
in the structure. A hard shaft sleeve which runs in a wear-resistant material is important. It will prolong the life of
the pump if this bearing is flushed periodically with an independent source of clean water.
Submersible pumps are frequently used in sewage and sump application. A submersible pump is usually of close-
coupled construction with the electric motor protected by a waterproof housing that permits the pump and motor
to be submerged in the liquid to be pumped. Such a pump may be mounted on a slide rail to permit removal from
the sump for service with a minimum of effort. The pressure connection between the casing and the piping is
designed for automatic release when the pump is removed from the sump.
Vertical sump pumps are mounted to the floor above the sump. A rigid floor supporting the pump is extremely
important to avoid vibration problems. The floor should have a natural frequency of vibration well above the
operating speed of the pump.
Pump Installation
The most critical steps in any installation include the following;
Rigidly support the foundation of a pump. This is particularly important with vertically mounted
pumps, which are more likely to vibrate excessively because of resonance with relatively flimsy
supports.
Minimize piping strain where practical. Pumps should not be used as pipe hangers or supports.
Excessive forces on pumps from expanding or heavy pipes should be avoided.
Accurately align the pump and drive shaft to minimize vibration and load on pump and motor
bearings.
Ensure that the inlet piping is relatively straight where it is connected to the pump so that flow
entering the impeller is uniform.
Avoid water hammer (described in Chap. 11) by avoiding control valves or check valves which
quickly stop the flow of water, thereby creating a surge in pressure.
common to replace mechanical seals regularly. In addition, to ensure proper operation of the pump,
DADU Page 22
Architectural Science II (Water & sewage) – ARCH 3232
Operate the pump as closely as possible to its point of highest efficiency. When pumps operate
below 50 percent of this value, re-circulating flow within the impeller can result in cavitation and
excessive forces on the shaft and bearings, causing damage.
Avoid pumping abrasive solids. Most centrifugal pumps are not designed to handle liquid with
abrasive solids. Although this is generally not a problem in building services, sump pumps may
collect dirt with water runoff. Therefore, a settling chamber upstream of the sump pump is
helpful.
Provide sufficient NPSH margin. The value of net positive suction head required by the pump is
indicated by the pump manufacturer. This value is based on a pump test with some cavitation
occurring. Experience shows that to avoid cavitation, about 5 times this value may be required.
However, if the output power of a pump is below 300 hp (400 kw), an NPSH value equal to the
NPSH required by the pump will usually result in satisfactory pump life.
DADU Page 23