Professional Documents
Culture Documents
Ultragas (125-1000) : Technical Information Installation Instructions
Ultragas (125-1000) : Technical Information Installation Instructions
Ultragas (125-1000) : Technical Information Installation Instructions
Installation instructions
UltraGas® (125-1000)
Condensing gas heating boilers
for natural gas and liquid gas
for modulating operation
Hoval products must be installed and commissioned The floor standing gas condensing boiler UltraGas®
only by appropriately qualified experts. These instruc- (125-1000) are designed and approved for use as
tions are intended exclusively for the specialist. Electri- heat generators for hot water heating systems with a
cal installations may only be carried out by a qualified permissible flow temperature of up to 90°C1), in accord-
electrician. ance with EN 483 and EN 677. They are designed for
continuously adjustable reduced output operation in
heating systems.
1)
see technical data
2. Important notes
2.1 Acceptance of delivery ........................................................................................................................... 5
2.2 Scope of guarantee.................................................................................................................................. 5
2.3 Instruction manuals................................................................................................................................. 5
2.4 Regulations, official permits................................................................................................................... 5
2.4.1 Germany.................................................................................................................................................... 6
2.4.2 Austria........................................................................................................................................................ 6
2.4.3 Switzerland ................................................................................................................................................ 6
3. Assembly
3.1 Placement................................................................................................................................................. 7
3.2 Mounting of heat insulation.................................................................................................................. 10
3.3 Mounting the casing.............................................................................................................................. 11
3.4 Mounting of base casing....................................................................................................................... 14
3.5 Adjusting the length of the ladder types (850,1000)........................................................................... 15
4. Technical information
4.1 Description of the boiler........................................................................................................................ 16
4.2 Technical data........................................................................................................................................ 17
4.3 Dimensions / Space requirements....................................................................................................... 20
4.3.1 Opening dimension.................................................................................................................................. 21
4.4 Hydraulic resistance.............................................................................................................................. 22
4.5 Brief description of the automatic firing device ................................................................................. 23
5. Installation
5.1 Safety information.................................................................................................................................. 24
5.2 Boiler room requirements..................................................................................................................... 24
5.2.1 Room air dependent installation............................................................................................................... 24
5.2.2 Room air independent installation............................................................................................................ 24
5.3 Flue gas connection and flue................................................................................................................ 25
5.4 Condensate drainage............................................................................................................................. 26
5.4.1 Execution variants.................................................................................................................................... 26
5.5 Gas connection...................................................................................................................................... 27
5.6 Hydraulic connection............................................................................................................................. 27
5.6.1 Customer-side requirements.................................................................................................................... 28
5.6.2 Hydraulic interconnection......................................................................................................................... 28
5.6.3 Cascade control....................................................................................................................................... 28
5.7 Electrical connection ............................................................................................................................ 29
6. Commissioning
6.1 Safety information.................................................................................................................................. 30
6.2 Filling with water.................................................................................................................................... 30
6.3 Water quality........................................................................................................................................... 31
6.4 Bleeding the air from the gas line........................................................................................................ 32
6.5 Switching on the system....................................................................................................................... 32
6.6 Gas inlet pressure.................................................................................................................................. 32
6.7 Setting the gas flow rate CO2(O2) and measurement of NOx/CO content in the flue gas................ 33
6.7.1 Flue gas measurement UltraGas® (125-720)........................................................................................... 33
6.7.2 Flue gas measurement UltraGas® (850,1000)......................................................................................... 34
6.8 Changing over to a different gas type.................................................................................................. 35
6.9 Type (850,1000) Setting for the stabilisation damper (if necessary)................................................. 37
6.10 Handover to the user............................................................................................................................. 38
6.11 Record - Activation of screed function................................................................................................ 39
8. Overview of settings
8.1 Table of parameters............................................................................................................................... 48
8.2 Fault Reporting overview TopTronic®T................................................................................................. 63
8.3 Automatic firing device (Warning, Blocking, Lock-out)...................................................................... 65
i The system shall not be put into operation until all relevant standards and safety
regulations are met.
Tools:
Shows the tools required for the following work.
Instruction:
Prompts you to carry out an action.
Result:
Shows the expected reaction to your action.
i Note:
Provides important information
Safety information:
Indicates an immediate hazard to persons
Warning information
Indicates danger to machines and Installations
Provides important information.
A summary of all the instruction manuals relevant to this system can be found in the
i Hoval System User Guide!
In exceptional cases the instructions are kept with the respective components!
Additional sources of information:
- Hoval catalogue
- Standards and regulations
When installing and operating the system, the standards and regulations specified
in sections 2.4.1 to 2.4.3 must be complied with at all times.
i
2.4.2 Austria §
OENORM 12831 12831Heating systems in buildings - Methods for calculating the design heat load
OENORM 13384 Flue gas systems - Heat and flow calculation methods
OENORM 12828 Heating systems in buildings - Planning of hot water heating systems.
ÖNorm B 8130 Open water heating systems; safety equipment.
ÖNorm B 8131 Closed water heating systems; requirements to safety, construction and testing.
ÖNorm B 8133 Hot water supply systems; safety requirements.
ÖNorm B 8136 Heating systems, space and other building requirements.
ÖNorm M 7515 Dimensioning of chimneys; definitions and calculation procedure.
ÖNorm H 5171 Heating systems - construction requirements for buildings.
ÖVGW TR-Gas
2.4.3 Switzerland §
SN EN 12831 Heating systems in buildings - Methods for calculating the design heat load
SN EN 13384 Flue gas systems - Heat and flow calculation methods
SN EN 12828 Heating systems in buildings - Planning of hot water heating systems.
VKF - Association of Cantonal Fire Insurances.
Fire service regulations.
SVGW Switzerland. Association of the gas and water trade.
SNV 27 10 20 Ventilation requirements for the boiler Installation room.
SWKI BT102-01 Quality of water in installations of building technology.
Technical tank regulations TTV 1990.
and further standards and regulations issued by CEN, CEN ELEC, DIN, VDE, DVGW, TRD and by the
legislator. Regulations from the local building authority, insurance companies and chimney sweeps must
also be complied with. When using gas as fuel, the regulations of the responsible gas board must also
be observed. An official permit may be required.
Fig. 01
UltraGas®
Type A A minimal B C D H H minimum
1
If room height is too small: Reduction of measures possible. See A minimum.
2
Attention! With A minimum the burner is no longer swing-out completely! Cleaning makes more difficult!
3
Boiler foot can be shortened, no base casing possible! Details see next page.
UltraGas®
Type a
cut off
(350 - 500) 1970 - 2030
(575 - 720) 1986 - 2046
(850, 1000) 2039 - 2099
1 Neutralisation box
2 Condensate pump
3 Masonry base
4 Adjustable feed 20-80 mm
UltraGas®
Type a
UltraGas®
Type a
UltraGas® (575-1000)
1b
4 3 6 1a
Fig. 02
Adjustment of the adjustable feet is carried out takes place after installing the neutralisation unit
1c 1
1a
Fig. 03
1b
1. Attach the cable channels (2) left and right to the pins and fix with the hexagon nuts and
washers (3a, fig. 4a) already mounted to the boiler. Turn side wall supports (2b, fig. 4b) laterally
to the outside.
2. Attach the side walls (4) to the boiler and fix with the hexagon nuts and washers (4a, fig. 4a) al-
ready mounted to the boiler. Hook the side wall side onto the screw head on the condensate drip
tray at the bottom. Align the side walls centrally. Adjust the free space for electrical box and rear
wall. Then tighten the hexagon nuts (4a).
3. Fit the rear wall (terminal plate 5, fig. 4c) of the terminal box using 4 screws (4a).
4. Remove stud (6) on the left or right. Hook the terminal box in at the bottom, on the side where the
stud is located. Hold the terminal box in horizontal position and tighten in position with the second
stud on the opposite side.Fold the terminal box shut towards the top and hook it in.
6. Direct the cable for the water pressure sensor (7) downwards, out of the control and plug in at
the bottom of the boiler (cable run according to fig. 4).
Route all other cables to the left or right of the boiler and establish plug connections.
Make sure that the cable does not touch any hot locations!
7. Attach the lower rear wall (8) to the side walls. Mutually attach the rear walls (8a, 8b) and engage
together at the side walls.
8. Fit top side walls (9a, 9b). Position the lower edge of the top side walls (longitudinal bore hole) on
the special screws of the bottom side walls and slide them in. Attach top side walls using 4 self-
tapping screws (9c) ø 3.5 x 10.
9. Attach upper rear walls (10, fig. 4) and mount rosette (10a).
10. Put on cover plates (11). Fit top front cover (11a), place pins in slots and slide towards the rear.
Then secure with carriage bolt (11b, fig. 4). (When removing, lift first one side, then the other side).
11. Hook in the front cover (8) at the bottom (with rail from type 575) and slide shut at the top (attach
with lateral carriage bolt). In the case of a cascade >3, no carriage bolts are fitted on the middle
boilers!
12. The remaining 3 casing walls (15, 15a, 16, fig. 6) are attached after mounting the condensate
boxes.
4a 3a 4a 4 2
Seitenwandstütze 2b
21-UltraGas (850)
Fig. 4a Fig. 4b
5a 7a
6 6a
7b
Fig. 4c 7 Fig. 4e
7c
Fig. 4d
12 Assembly 4 210 267 / 04
Downloaded from www.Manualslib.com manuals search engine
Types (850,1000) two-pieces
11 11b
10a
11a
10
9b
8b 9c
8a 2
3
Burner wiring
Type (125-850);
2 connector plugs
Type (1000);
3 connector plugs
Boiler tempe-
rature sensor
Ignition cable
8
9a
3
8
7
Flue gas sensor Line cord Condensate box Water pressure
(if available) sensor
Fig. 04
1. Mount the siphon (13) delivered loose, incl. double nipple (13a, fig. 5).
2. Position the condensate box (option) under the boiler and make the electrical connection. Create con-
densate outlet, resp. connection line according to separate instructions.
For UltraGas® (575,650,720,850,1000):
Mount condensate outlet pipe (14, fig. 5) (delivered with boiler).
3. Screw mount the right and left side walls (15, 15a, fig. 6) with the already mounted cap nuts.
13a 13 14 Fig. 05
15 16 Fig. 06
If the option with shortened boiler feet is being applied or if the boiler
is put on a concrete base, the ladder supplied must be shortened (cut
away at the notch) resp. lengthened.
The Hoval UltraGas® is a low emission, energy-saving The secondary heating surface is designed so that
condensing gas boiler comprising the Ultraclean part of the water vapour contained in the flue gas is
burner system, a gas fired premix burner with com- condensed and the vaporisation heat it contains is
bustion air fan. The Hoval UltraGas® has a vertically utilised for the heating circuit. The gas burner is in the
disposed combustion chamber of stainless steel as form of a break draught burner, which can easily be
a primary heating surface and a secondary heating swung up for maintenance purposes. The UltraGas®
surface of aluFer® composite tubes (stainless steel is designed to operate with natural and liquid gas. The
on the water side, aluminium on the waste gas side). figure below shows the design principle.
TopTronic®T controller
Trittbrett zur Service-Er-
leichterung (ausklappbar)
1
Data related to Hu. The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWH/m3 operation at a
Wobbe coefficient of 12.0 up to 15.7 kWh/m3 is possible (a readjustment may be necessary).
2
See also notes at „Engineering“.
3
Details for multi-boiler plants (cascade) with common flue gas line: see Hoval UltraGas® (250D-2000D).
1
Data related to Hu. The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWH/m3 operation at a
Wobbe coefficient of 12.0 up to 15.7 kWh/m3 is possible (a readjustment may be necessary).
2
See also notes at „Engineering“.
3
Details for multi-boiler plants (cascade) with common flue gas line: see Hoval UltraGas® (250D-2000D)..
1
Data reladet to Hu. The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWH/m3 operation at a
Wobbe oefficient of 12,0 up to 15,7 kWh/m3 is possible (a readjustment may be necessary).
2
See also notes at „Engineering“.
3
Details for multi-boiler plants (cascade) with common flue gas line: see Hoval UltraGas® (250D-2000D).
* Data unknown at time of printing
Note:
Minimal space see separate page
1 Flow heating 10 Condensate drain with screw joint for plastic tube
2 Low temperature-Return 11 Air inlet connector (Option)
3 Gas connection 12 Boiler foot adjustable up to 80 mm
4 Safety valve 13 Flow fitting pipe (Option)
5 High temperature-Return 14 Return fitting pipe (Option)
6 Electrical connection left or right 15 Expansion 1"
7 Draining (behind the front casing) 16 Pressure limiter ¾”
8 Flue gas connector left or right 17 Safety temperature control ½”
9 Boiler control
Type A B C D D1 D2 E F G H I J K L M N O Q R
(125,150) 1823 633 1336 981 854 324 820 1565 1378 701 677 143 491 287 199 199 200 242 1633
(200-300) 1923 743 1684 1247 1204 321 930 1667 1428 718 710 155 498 287 280 200 186 368 1696
(350) 2070 923 1775 1268 1294 326 1110 1800 1438 808 630 160 528 284 345 205 205 345 1720
(400-500) 2070 923 1775 1268 1294 326 1110 1800 1438 808 630 160 528 284 345 205 205 -12 1829
(575-720) 2086 1103 1928 1438 1480 316 1290 1800 1442 834 608 202 554 284 367 367 110 86 1847
(850,1000) 2139 1363 2243 1703 1790 313 1550 1854 1494 858 636 204 578 294 417 417 218 198 1888
Type S T U V W X Y Z 1,2,5 3 4 8 10 11
(125,150) 351 90 1632 107 207 473 195 138 DN 65 / PN6 / 4 screws* Rp 1" R 1 ½" Ø155/159 DN25 Ø122/125
(200-300) 371 100 1702 108 207 472 217 183 DN 65 / PN6 / 4 screws* Rp 1 ½" R 1 ½" Ø252/256 DN25 Ø197/200
(350) 435 100 1730 100 204 484 267 210 DN 100 / PN6 / 4 screws* Rp 1 ½" R 1 ½" Ø302/306 DN25 Ø197/200
(400-500) 447 100 1812 176 204 484 267 210 DN 100 / PN6 / 4 screws* Rp 2" R 1 ½" Ø302/306 DN25 Ø247/250
(575-720) 513 100 1818 176 204 530 357 218 DN 125 / PN6 / 8 screws* Rp 2" R 2" Ø302/306 DN40 Ø247/250
(850,1000) 624 100 1880 176 214 554 455 243 DN 125 / PN6 / 8 screws* Rp 2" R 2" Ø402/406 DN40 Ø247/250
B
K = x L
T B = Boiler width
L = max. length of boiler
K T = Door width
B K = Corridor width
L
T = x L
B K
< 150
[mbar]
resistance[mbar]
resistance[mbar]
50
20
40
15
Druckverlust
Druckverlust
30
10
20
5 10
Flow
Flow
0 0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 5 10 15 20 25 30
Volumenstrom
Through [m3/h]
put flow rate [m3/h] Volumenstrom
Through [m3/h]
put flow rate [m3/h]
30
[mbar]
[mbar]
resistance [mbar]
25 25
[mbar]
20 20
resistance
Druckverlust
15 15
Druckverlust
10 10
5 5
Flow
Flow
0 0
0 5 10 15 20 25 30 35 40 45 0 5 10 15 20 25 30 35 40 45 50 55 60 65
Volumenstrom
Through [m3/h]
put flow rate [m3/h] Volumenstrom
Through [m3/h]
put flow rate [m3/h]
UltraGas® (850,1000)
60
50
Flow resistance [mbar]
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
Through put flow rate [m3/h]
Fuses:
The BIC 960 is fitted with 3 fuses: 2AT Mains
4AT Pump
4AT Burner fan
Blowing of one of the two 4AT fuses securing the pump or the burner fan, respectively, will prevent the af-
fected device from starting.
A failure of the mains fuse of the automatic firing device is displayed on the TopTronic®T/UG with the error
message „DATABUS ERROR 70-6“.
Caution!
Sharp edges pose a cutting hazard.
Handle the casing parts with care and avoid contact with sharp edges.
§ The boiler room must satisfy the applicable local building regulations.
§ The boiler room ventilation must satisfy the applicable local regulations in this regard.
Boilers may not be installed in rooms containing halogen compounds which can be car-
§ ried into the combustion air (e.g. wash rooms, drying rooms, DIY rooms, hair dresser
rooms).
§ Halogen compunds can originate, for example, from cleaning and degreasing agents,
solvents, glue, and bleaching lyes.
Ensure that the required combustion air can flow unhindered at all times.
This is important for the correct operation of all the boilers installed therein and to protect
the users from an oxygen depleted atmosphere.
An adequate fresh air supply meeting the local regulations must be provided.
i Configuration based on a „connection for direct combustion air supply“ or „air intake valve
motor (optionally):
The following must be observed when laying out the intake pipe:
If the intake opening is installed on the house façace near to a noise-sensitive area (e.g.
bedroom windows, garden seating area, etc.) we recommed installing a noise damper in
the direct fresh air suction line.
The intake opening must be easily accessible.
No chemicals or poisonous substances may be stored close to the intake opening
The intake opening may not be installed beside fume extraction outlets or other venting
outlets.
Ensure that the intake aperture is free from any obstructions at all times (leaves, snow, ...)
A safety grid must be installed on the suction opening on the outside wall.
§ i The flue gas extraction system must comply with the following directives:
DVGW (TRGI)
ÖVGW
SVGW/VKF
Pursuant to the abovementioned regulations, a flue gas temperature limiter must be in-
stalled in the boiler.
i Unhindered backflow of condensate into the boiler can only be ensured if:
i Cross sections and maximum lengths are calculated on the basis of graphs or tables.
The tables can be obtained from the chimney or flue system manufacturer.
The calculation values can be obtained from the table in chapter 4.2.
The flue gas conduit cross sections and lengths are calculated following the technical data
for the boiler.
i The condensate drainage pipes on the boiler must be made of corrosion resistant
material.
The following materials are suitable for condensate drainage:
PVC
PE
PP
ABS
The local regulations regarding condensate drainage must be observed.
UltraGas® (575-1000)
The siphon is filled with water
through the cleaning aperture.
1 Neutralisation box
2 Condensate pump: Art. Nr. 6015159
3 Base bricked
Hazard!
Explosion hazard due to leaky gas connection.
Check the gas connection for gas tightness after completing the boiler installation.
The boiler comprises the following safety equipment, in accordance with EN 12828:2003:
- Minimum pressure limiter DBmin
- Safety maximum pressure limiter DBmax
- Hydraulic pressure monitor DBmax + 50%
- Thermostat
- Temperature monitor TBmax + 20%
- Safety temperature limiter
i To achieve an optimal efficiency, ensure that the return pipe is properly connected.
Example:
AF
UltraGas® (125-1000) 1 HT NT
Gas heating boiler with
TopTronic T
- water heating, VF1 VF2 B1
Notice:
- This hydraulic schematic is a principle
KW
schematic. It does not contain all details for
installation. The installation must be done ac-
cording to local conditions, dimensioning and
regulations
- For underfloor heating, a flow temperature
RS-T Room station MK1 Pump mixing circuit 1
monitor must be built-in.
MK2 Pump mixing circuit 2
- Shut-off devices to the safety valve (pressur-
AF Outside sensor SLP Calorifier - loading pump
ized expansion tank, safety valve, etc.) are to
VF1 Flow sensor 1 YK1 Actuator mixer 1
safe against unintended closing!
VF2 Flow sensor 2 YK2 Actuator mixer 2
- Anti thermal siphon dip has to be installed.
SF Calorifier sensor
- An automatic air vent (AAV) must be fitted
B1 Flow temperature monitor HT High temperature
on the top boiler connection and before
(on demand) NT low temperature
any isolation valve. This is not provided
SV Safety valve
by Hoval.
AAV Automatic air vent
Before putting the boiler into operation, the siphon and neutralisation tank needs
to be filled with water.
When starting up the system for the first time, the correct operation of all the
safety and control devices must be verified.
The operation and maintenance of the system must be explained to the user in
detail.
The combustion air needs to be filtered in very dusty environments.
The gas flow pressure and the CO2 value must be checked imperatively and set
correctly.
Caution!
Sharp edges pose a cutting hazard.
Handle the casing parts with care and avoid contact with sharp edges.
Caution!
Danger of injury for unqualified personnel.
Maintenance and cleaning work may only be performed by trained personnel or
by the HOVAL Customer Service.
i Caution!
Danger of damaging the system by filling it with incorrect liquids.
Water filled into the system must have drinking quality.
The European Standard EN 14868 and the Directive VDI 2035 must be ob-
served (see chapter 6.3).
i Use only chemical additives with suppliers’ confirmation of their safe usage. If
frost protection agent is being used, please contact the Hoval company to ask
for the separate engineering sheet.
i The gas flow may only be adjusted and the heating system therefore started
up, if the minimum flow pressure values are achieved (see section 6.7 Adjusting
the gas flow).
The minimum flow pressure in the connector pipe must reach the following
values:
Natural Gas 18 to 80 mbar
Liquid gas 37 to 57 mbar
B D
C A
B C D A
i To set the flow on the valve, both flue gas values need to be controlled. e.g.: Set
upper value - control lower value - value incorrect - set lower value - control up-
per value - ...
If the limiting values prescribed by the regulations are exceeded, the boiler must
be put out of operation and the corresponding measures for repair work must be
initiated.
Ensure that the liquid gas line is free of any air. Any air in the liquid gas line can have
a negative influence on the flue gas values.
aperture
7. Set the CO2(O2) content as described under 6.7 at rated output and minimum
output to CO2 = 9,9 - 10,2 (O2 = 5,9 - 5,5) vol-% (dry).
The stabilisation damper reduces the outlet cross-section of the fan during the start-
up phase. This optimises the start-up characteristics of the boiler! Factory setting for
the stroke: 20 mm.
This is the optimum setting under normal flue conditions.
If lower compression is required, the stroke can be lowered, e.g. to 18 mm, using
the setscrew.
m
m
20
ke
ro
St
Setscrew
Heating circuit selection for screed function and necessary parameter settings
Mixing circuit 1 Mixing circuit 1
MC1/MC2 level
Start
Parameters 13,16
PRESS
Activate Installer level > 3 sec: Select / Confirm Set Confirm End / Exit
(Code entry) Access to
level
Direct heating circuit (possible only with H-Gen without minimum H-Gen temperature - e.g. condensing boiler)
Start HC level
Parameters 13,16
H-GEN level
PRESS Parameter 4
Characteristic Activate Installer level > 3 sec: Select / Confirm Set Confirm End / Exit
heating curve (Code entry) Access to
Enable HC level
In alternation with the basic display of the controller, the activated screed heating is displayed giving some information
about the remaining term in days „screed - 18“.
Record
Screed heating activated by: ............................................
Screed heating activated on: ............................................ ..........................................................................................
Screed heating ends on: .................................................. Date and signature
Example:
Maximum flow temperature 40°C
1 Function heating
Starting day + 7 days
T VLSol [°C]
55°C maximum
maximal set level!
55°C einstellbar!
55
55
45
45
35
35
25
25
1=Funktionsheizen
1 = Function heating
Funktionsheizen
START 1
START 1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 9
9 10
10 11
11 12
12 13
13 14
14 15
15 16
16 17
17 18
18 19
19 20
20 21
21 22
22 23
23 24
24 25 26 DAYS
25 26 tTAGE]
[TAGE]
• On the starting day and for the three following days at 25°C constantly
• Subsequently for 4 days at the set flow maximum temp., but limited to a maximum of 55°C
2 Surface-ready heating
Starting day + 18 days
T VLSol [°C]
55
55
45
45
35
35
25
25
2=Belegreifheizen
2 = Surface-ready heating
Belegreifheizen
START 11 22 33 44 55 66 77 88 99 10
START
START 10 11
11 12
12 13
1314
14 15
15 16
16 17
17 18
18 19
19 20
20 21
21 22
22 23
23 24
24 25 26 DAYS
25 26 t[TAGE]
[TAGE]
• On the starting day and on the 1st day constantly at 25°C, on each further day the demand value rises by 5°C until the maximum
flow temperature is reached. Subsequently the temperature is lowered again in the same gradations until the low point of 25°C
is reached.
Example: Set flow maximum temp.: 40°C
Starting day + 1st day: 25°C 5th - 15th day: constant heating with the max. flow temperature
2nd day: 30°C 16th day: 35°C
3rd day: 35°C 17th day: 30°C
4th day: 40°C 18th day: 25°C
55
55
45
45
35
35
25
25
= Function heating andund
3=Funktionsheizen
3
Funktionsheizen Belegreifheizen
surface-ready
und heating
Belegreifheizen
START 1
START 1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 9
9 10
10 11
11 12
12 13
13 14
14 15
15 16
16 17
17 18
18 19
19 20
20 21
21 22
22 23
23 24
24 25
25 26 tDAYS
26 [TAGE]
[TAGE]
7.2 Bleeding
Open all radiator valves.
Heat up the system for at least half a day with a high flow temperature.
Turn off the boiler and wait 5 minutes.
Bleed all the air from the system.
i The systems warns when the water pressure falls below 1 bar and the boiler out-
put is reduced to 50%. If the water pressure falls below 0.5 bar, the boiler is set
automatically to a fault state.
The system must be refilled with water when the pressure falls below the mini-
mum system pressure:
Connect the filling hose to the water supply.
Remove the air from the filling hose.
Connect the filling hose to the filling and draining cock.
Top up with water (see point 6.2).
All other control elements of the control unit are described in the operating instructions.
The emission monitor key can also be used to change over to manual operating mode.
Emissions metering
Immediate end
%%
PRESS Output reference / actual value
SHORTLY Modulation display
Manual operation
Immediate end
PRESS
> 5 seconds
i The boiler may only be cleaned by an authorised technician or by the HOVAL Cus-
tomer Service.
i The HOVAL gas heating boiler should be cleaned and maintained once every
year.
If the HOVAL gas heating boiler was in operation during the building phase, it will be
necessary to carry out a check for cleanliness. If the boiler is dirty, clean it.
4
2
1
Fig. 07 Fig. 08 Fig. 09 Fig. 10
Warning!
Chemical burn hazard through cleaning agents.
Safety gloves and eye protection must be worn when using cleaning agents.
Observe the information on the original packaging.
Caution!
The system can be damaged when using incorrect cleaning agents.
Use only cleaning agents approved for gas boilers with aluminium components.
Preparation: 1. Set the main switch on the boiler control unit to “0”.
2. Close the main gas valve.
3. Remove the sound insulation cover.
4. Disconnect all the burner connector plugs.
5. Remove the front casing.
Warning!
If a gas pressure spring is weakened, the boiler door is lowered. There is an
increased danger of injury when reopening the boiler door.
Note!
Both gas pressure springs must be replaced..
Fig. 11
Fig. 12
Fig. 13
Preparation Set the main system switch of the boiler control to “0”.
Procedure to readjust:
Heat the ignition electrode at the kink with the blowtorch until it glows red.
Bend the ignition electrode with the long-nosed pliers until the required distance is
set.
Ignition electrode
Ignition and ionisation electrode
10 ± 2 mm
4 mm
m
m
4
Fig. 14 Fig. 15
535,8
Reassembly: Replace the gasket at the gas connection.
Reassemble the burner in reverse order.
Check for leaks
( 214,5 )
7.5.4 Cleaning the gas filter HFVR050 (only applicable for UltraGas® (450-720)) (if fitted)
Gas valve
( 116 )
Gas filter
Ersatz fuer:
zweiten Gewindegang begonnen werden
in :
3
Aktiengesellschaft Art.Nr. 6 034 324K-3 00
46 Maintenance 4 210 267 / 04
Downloaded from www.Manualslib.com manuals search engine
7.6 Setting the gas flow rate CO2(O2) and measurement of NOx/CO content in the flue
gas
(according to point 6.7)
Caution: poisoning!
21-UltraGas (850)
If siphonSifon
is not filled with water or if it is contaminated or obstructed by contami-
nation, leaking flue gas may put people in danger of life.
• Before reinserting the siphon, it must be filled with water.
Type of device:
DHW:
SW:
Address:
Surface operation Key :
Heating curve HC OFF OFF, 0,20 .... 3,5
Heating curve MC1 1,0 OFF, 0,20 .... 3,5
Heating curve MC2 1,0 OFF, 0,20 .... 3,5
Daytime target temperature HC *) 20°C 5 .... 30°C *)
Daytime target temperature MC1 *) 20°C 5 .... 30°C *)
Daytime target temperature MC2 *) 20°C 5 .... 30°C *)
Night-time target temperature HC *) 16°C 5 .... 30°C *)
Night-time target temperature MC1 *) 16°C 5 .... 30°C *)
Night-time target temperature MC2 *) 16°C 5 .... 30°C *)
DHW target temperature 50°C 5 ... DHW-Max.
*) Depending on the setting of system parameters 03 OPERATING MODE
DHW circuit
Time program P1 Time program P2 Time program P3
Tag Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3
from to from to from to from to from to from to from to from to from to
Mo
Tu
We
Th
Fr
Sa
Su
Direct circuit
Time program P1 Time program P2 Time program P3
Tag Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3
from to from to from to from to from to from to from to from to from to
Mo
Tu
We
Th
Fr
Sa
Su
Mixer Circuit 1
Time program P1 Time program P2 Time program P3
Tag Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3
from to from to from to from to from to from to from to from to from to
Mo
Tu
We
Th
Fr
Sa
Su
Mixer Circuit 2
Time program P1 Time program P2 Time program P3
Tag Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3 Cycle 1 Cycle 2 Cycle 3
from to from to from to from to from to from to from to from to from to
Mo
Tu
We
Th
Fr
Sa
Su
SYSTEM
Par. Designation Factory 10 20 30 40 50 Lev.
LANGUAGE Selection of the style-language EN BE
2 Number of cleared switching time programs P1 HF
3 Clearing for separate operating mode 1 HF
4 Limit temperature for summer disconnection 22 °C HF
5 System frost protection 3 °C HF
6 Demand contact module for VE1 1 HF
7 Demand contact module for VE2 1 HF
8 Demand contact module for VE3 1 HF
9 Air conditioning zone -12 °C HF
10 Building type 2 HF
Automatic reversion time (surface end user level, except
11 5 min HF
info. level)
12 Pump and mixer compulsory operation ON HF
13 Logical fault signal OFF HF
Automatic SET function
14 ON/ OFF HF
(after 24:00, is automatically set to OFF)
15 Blocking code for heating Installer OEM
18 Release cycle temperature OFF HF
19 Frost protection mode 30 min HF
21 RTC adjustment 0 HF
23 Blocking code operator level OFF HF
24 Temperature display in Fahrenheit OFF OEM
26 First commissioning date (after 24:00) - OEM
27 Fault report (only TTT/UG) 2 HF
28 Fault stack 2 ON HF
29 Characteristic curve emergency operation 0 °C HF
30 Thermostat function sensor allocation AF HF
31 Thermostat function reference value 1 °C HF
32 Thermostat function switching difference 3K HF
33 Thermostat function anti-blocking protection ON HF
Top: ArtNo - HW Index
----- OEM
Bottom: Code:REV - Software version
RESET Reset parameter values BE
UNMIXED CIRC
Par. Designation Factory 10 20 30 40 50 Lev.
1 Type of reduced operation ECO/ ABS HF
2 Heating system (exponent) DK= 1,30 HF
3 Room override (in connection with room sensor) 3 HF
4 Room factor OFF HF
5 Adaptation heating curve OFF HF
6 Switch-on optimisation 1 HF
7 Heating limit 0,5 OEM
8 Room frost protection limit 10 °C HF
9 Room thermostat function OFF HF
10 Outside temperature allocation 0 HF
11 Constant temperature reference value 20 °C HF
12 Minimum temperature limit 10 °C HF
13 Maximum temperature limit 55/ 75 °C HF
14 Temperature elevation Heating circuit DK=0 HF
15 Pump follow-on 5 min HF
16 Screed function OFF HF
23 Room control K-factor 8 HF
24 Room control Tn-factor 35 min HF
25 Vacation mode STBY HF
36 Minimum value override OFF HF
Name heating circuit (max. 5 letters) XXXXX HF
UltraGas® (125)
UltraGas® (150)
UltraGas® (200)
UltraGas® (250)
UltraGas® (300)
Plant settings
Parameter
Level
Unit
30-
30-
30-
30-
30-
Designation
1 2AA Blocking temperature °C OEM 95 95 95 95 95
2 2AC Maximum setpoint °C BE 80 80 80 80 80
3 2AD Switch-off hysteresis via setpoint °C OEM 10 10 10 10 10
4 2AE Switching difference to switch-off point °C HF 10 10 10 10 10
5 2AF Proportional range °C OEM 40 40 40 40 40
6 2AG Integral part sec OEM 100 100 100 100 100
7 2AH Differential part sec OEM 25 25 25 25 25
8 2AI Setpoint for bus interrupt °C HF 75 75 75 75 75
9 2AJ Maximum temperature rise for low flow temperature °C/s OEM 1 1 1 1 1
10 2AK Maximum temperature rise for high flow temperature °C/s OEM 0.5 0.5 0.5 0.5 0.5
11 2AL “low” flow temperature °C OEM 60 60 60 60 60
12 2AM “high” flow temperature °C OEM 80 80 80 80 80
13 2BC Flue gas temperature lock °C OEM 110 110 110 110 110
14 2BD Flue gas temperature block °C OEM 100 100 100 100 100
15 2CA Gas pressure switch available OEM ON ON ON ON ON
16 2DA Hydrau. pressure sensor available OEM ON ON ON ON ON
17 2DB Pressure warning bar OEM 1 1 1 1 1
18 2DC Pressure warning hysteresis bar OEM 0.2 0.2 0.2 0.2 0.2
19 2DD Blocking pressure min bar OEM 0.5 0.5 0.5 0.5 0.5
20 2DE Blocking pressure min - hysteresis bar OEM 0.2 0.2 0.2 0.2 0.2
21 2DF Blocking pressure max bar OEM 4.8 4.8 4.8 4.8 4.8
22 2DG Blocking pressure max - hysteresis bar OEM 0.2 0.2 0.2 0.2 0.2
23 2DH Lock-out pressure max bar OEM 5 5 5 5 5
24 2DI Max boiler output for pressure warning % OEM 50 50 50 50 50
25 2EC Ionisation warning µA OEM 3 3 3 3 3
26 2FA Number of Hall pulses per rotation OEM 3 3 3 3 3
27 2FF Fan speed first phase pre-vent min–1 OEM 4800 5700 3900 4800 5700
28 2FG Start rpm min–1 OEM 1600 1900 1300 1600 1900
29 2FH Maximum fan speed min–1 OEM 4800 5700 3900 4800 5700
30 2FI Minimum fan speed min–1 OEM 1100 1200 900 1000 1100
31 2FJ Fan ramp-up during purge min /s OEM
–1
500 500 500 500 500
32 2FK Fan ramp-down during purge min–1/s OEM 200 200 200 200 200
33 2FL Fan ramp-up during operation min–1/s OEM 100 100 100 100 100
34 2FM Fan ramp-down during operation min /s OEM
–1
100 100 100 100 100
35 2FN Fan follow-on time after a lock-out sec OEM 180 180 180 180 180
36 2FO Fan speed after shut-down during normal operation or lock-out min –1
OEM 1100 1200 900 1000 1100
37 2FR Fan follow-on time after operation or block min OEM 3 3 3 3 3
38 2FU Fan speed for boiler operation in frost protection mode min–1 OEM 1500 1500 1500 1500 1500
39 2GA Waiting period after opening of main gas valve or activation min OEM 0 0 0 0 0
of boiler room fan
40 2GB External main gas valve / boiler room fan available OEM ON ON ON ON ON
41 2HA Follow-on time for heating pump or shut-off device after heat demand min HF 5 5 5 5 5
42 2HD Summer operation (“summer kick”) sec OEM 10 10 10 10 10
UltraGas® (125)
UltraGas® (150)
UltraGas® (200)
UltraGas® (250)
UltraGas® (300)
Plant settings
Parameter
Level
Unit
30-
30-
30-
30-
30-
Designation
43 2IA Ignition (0-> internal, 1-> internal + external, 2-> external) OEM 2 2 2 2 2
44 2KM Stepped modulation (0-> off, 1-> rising, 2-> rising and falling) HF 1 1 1 1 1
45 2LA Action mode fault relays HF 2 2 2 2 2
46 2NA ADC/4 value at 0 bar OEM 25 25 25 25 25
47 2NB *ADC/4-value at 6/10 bar (V3) OEM 145/ 145/ 145/ 145/ 145/
225 225 225 225 225
48 2IB Extended external ignition time sek OEM 8 8 8 8 8
49 2QA Reserve % OEM 70 70 70 70 70
i *With automatic firing device: BIC960_V2 parameter 47: must be 145 (6bar)
With automatic firing device: BIC960_V3 parameter 47: must be 225 (10bar)
Liquid gas adaptations
27 2FF Fan speed first phase pre-vent min–1 OEM 4700 5500 3700 4600 5400
28 2FG Start rpm min–1 OEM 2800 3300 2200 2700 3200
29 2FH Maximum fan speed min –1
OEM 4700 5500 3700 4600 5400
30 2FI Minimum fan speed min–1 OEM 1400 1600 1300 1400 1400
36 2FO Fan speed after shut-down during normal operation or lock-out min–1 OEM 1400 1600 1300 1400 1400
UltraGas® (350)
UltraGas® (400)
UltraGas® (450)
UltraGas® (500)
UltraGas® (575)
Plant settings
Parameter
Level
Unit
30-
30-
30-
30-
30-
Designation
1 2AA Blocking temperature °C OEM 95 95 95 95 95
UltraGas® (350)
UltraGas® (400)
UltraGas® (450)
UltraGas® (500)
UltraGas® (575)
Plant settings
Parameter
Level
Unit
30-
30-
30-
30-
30-
Designation
22 2DG Blocking pressure max - hysteresis bar OEM 0.2 0.2 0.2 0.2 0.2
23 2DH Lock-out pressure max bar OEM 6 6 6 6 6
24 2DI Max boiler output for pressure warning % OEM 50 50 50 50 50
25 2EC Ionisation warning µA OEM 3 3 3 3 3
26 2FA Number of Hall pulses per rotation OEM 3 3 3 3 3
27 2FF Fan speed first phase pre-vent min–1 OEM 5600 3600 4000 4400 4200
28 2FG Start rpm min–1 OEM 1900 1200 1300 1400 1400
29 2FH Maximum fan speed min–1 OEM 5600 3600 4000 4400 4200
30 2FI Minimum fan speed min–1 OEM 1000 900 900 900 1000
31 2FJ Fan ramp-up during purge min OEM 500 500 500 500 500
–1
/s
32 2FK Fan ramp-down during purge min OEM 200 200 200 200 200
–1
/s
33 2FL Fan ramp-up during operation min OEM 100 100 100 100 100
–1
/s
34 2FM Fan ramp-down during operation min OEM 100 100 100 100 100
–1
/s
35 2FN Fan follow-on time after a lock-out sec OEM 180 180 180 180 180
36 2FO Fan speed after shut-down during normal operation or lock-out min –1
OEM 1000 900 900 900 1000
37 2FR Fan follow-on time after operation or block min OEM 3 3 3 3 3
38 2FU Fan speed for boiler operation in frost protection mode min–1 OEM 1500 1500 1500 1500 1500
39 2GA Waiting period after opening of main gas valve or activation of boiler room fan min OEM 0 0 0 0 0
40 2GB External main gas valve / boiler room fan available OEM ON ON ON ON ON
41 2HA Follow-on time for heating pump or shut-off device after heat demand min HF 5 5 5 5 5
42 2HD Summer operation (“summer kick”) sec OEM 10 10 10 10 10
43 2IA Ignition (0-> internal, 1-> internal + external, 2-> external) OEM 2 2 2 2 2
44 2KM Stepped modulation (0-> off, 1-> rising, 2-> rising and falling) HF 1 1 1 1 1
45 2LA Action mode fault relays HF 2 2 2 2 2
46 2NA ADC/4 value at 0 bar OEM 25 25 25 25 25
47 2NB *ADC/4-value at 6/10 bar (V3) OEM 145/ 145/ 145/ 145/ 145/
225 225 225 225 225
48 2IB Extended external ignition time sek OEM 8 8 8 8 8
49 2QA Reserve % OEM 70 70 70 70 70
i *With automatic firing device: BIC960_V2 parameter 47: must be 145 (6bar)
With automatic firing device: BIC960_V3 parameter 47: must be 225 (10bar)
Liquid gas adaptations
27 2FF Fan speed first phase pre-vent min–1 OEM 5300 3300 3700 4100 3900
28 2FG Start rpm min–1 OEM 3100 1600 1700 1800 1800
29 2FH Maximum fan speed min –1
OEM 5300 3300 3700 4100 3900
30 2FI Minimum fan speed min–1 OEM 1300 1300 1300 1300 1400
36 2FO Fan speed after shut-down during normal operation or lock-out min–1 OEM 1300 1300 1300 1300 1400
UltraGas® (1000)
UltraGas® (650)
UltraGas® (720)
UltraGas® (850)
Plant settings
Parameter
Level
Unit
30-
30-
30-
30-
Designation
1 2AA Blocking temperature °C OEM 95 95 95 95
2 2AC Maximum setpoint °C BE 80 80 80 80
3 2AD Switch-off hysteresis via setpoint °C OEM 10 10 10 10
4 2AE Switching difference to switch-off point °C HF 10 10 10 10
5 2AF Proportional range °C OEM 40 40 40 40
6 2AG Integral part sec OEM 100 100 100 100
7 2AH Differential part sec OEM 25 25 25 25
8 2AI Setpoint for bus interrupt °C HF 75 75 75 75
9 2AJ Maximum temperature rise for low flow temperature °C/s OEM 1 1 1 1
10 2AK Maximum temperature rise for high flow temperature °C/s OEM 0.5 0.5 0.5 0.5
11 2AL “low” flow temperature °C OEM 60 60 60 60
12 2AM “high” flow temperature °C OEM 80 80 80 80
13 2BC Flue gas temperature lock °C OEM 110 110 110 110
14 2BD Flue gas temperature block °C OEM 100 100 100 100
15 2CA Gas pressure switch available OEM ON ON ON ON
16 2DA Hydrau. pressure sensor available OEM ON ON ON ON
17 2DB Pressure warning bar OEM 1 1 1 1
18 2DC Pressure warning hysteresis bar OEM 0.2 0.2 0.2 0.2
19 2DD Blocking pressure min bar OEM 0.5 0.5 0.5 0.5
20 2DE Blocking pressure min - hysteresis bar OEM 0.2 0.2 0.2 0.2
21 2DF Blocking pressure max bar OEM 4.8 5.8 5.8 5.8
22 2DG Blocking pressure max - hysteresis bar OEM 0.2 0.2 0.2 0.2
23 2DH Lock-out pressure max bar OEM 5 5 6 6
24 2DI Max boiler output for pressure warning % OEM 50 50 50 50
25 2EC Ionisation warning µA OEM 3 3 3 3
26 2FA Number of Hall pulses per rotation OEM 3 3 3 4 (5) *
UltraGas® (1000)
UltraGas® (650)
UltraGas® (720)
UltraGas® (850)
Plant settings
Parameter
Level
Unit
30-
30-
30-
30-
Designation
27 2FF Fan speed first phase pre-vent min–1 OEM 4800 4800 4700 5600
28 2FG Start rpm min–1 OEM 1600 1600 1700 1700
29 2FH Maximum fan speed min–1 OEM 4800 4800 4700 5600
30 2FI Minimum fan speed min –1
OEM 1000 1000 900 1200
31 2FJ Fan ramp-up during purge min–1/s OEM 500 500 500 500
32 2FK Fan ramp-down during purge min –1/s OEM 200 200 200 200
33 2FL Fan ramp-up during operation min /s OEM
–1
100 100 100 100
34 2FM Fan ramp-down during operation min–1/s OEM 100 100 100 100
35 2FN Fan follow-on time after a lock-out sec OEM 180 180 180 180
36 2FO Fan speed after shut-down during normal operation or lock-out min–1 OEM 1000 1000 900 1200
37 2FR Fan follow-on time after operation or block min OEM 3 3 3 3
38 2FU Fan speed for boiler operation in frost protection mode min–1 OEM 1500 1500 1500 1500
39 2GA Waiting period after opening of main gas valve or activation of boiler room fan min OEM 0 0 0 0
40 2GB External main gas valve / boiler room fan available OEM ON ON ON ON
41 2HA Follow-on time for heating pump or shut-off device after heat demand min HF 5 5 5 5
42 2HD Summer operation (“summer kick”) sec OEM 10 10 10 10
43 2IA Ignition (0-> internal, 1-> internal + external, 2-> external) OEM 2 2 2 2
44 2KM Stepped modulation (0-> off, 1-> rising, 2-> rising and falling) HF 1 1 1 1
45 2LA Action mode fault relays HF 2 2 2 2
46 2NA ADC/4 value at 0 bar OEM 25 25 25 25
47 2NB *ADC/4-value at 6/10 bar (V3) OEM 145/ 145/ 145/ 145/
225 225 225 225
48 2IB Extended external ignition time sek OEM 8 8 8 8
49 2QA Reserve % OEM 70 70 70 70
i *With automatic firing device: BIC960_V2 parameter 47: must be 145 (6bar)
With automatic firing device: BIC960_V3 parameter 47: must be 225 (10bar)
Liquid gas adaptations
27 2FF Fan speed first phase pre-vent min–1 OEM 4400 4200 4200 5200
28 2FG Start rpm min –1
OEM 1800 2000 1700 1700
29 2FH Maximum fan speed min–1 OEM 4400 4200 4200 5200
30 2FI Minimum fan speed min–1 OEM 1400 1500 1300 1500
36 2FO Fan speed after shut-down during normal operation or lock-out min–1 OEM 1400 1500 1300 1500
SOLAR
Par. Designation Factory 10 20 30 40 50 Lev.
1 Switch-on difference 10 K HF
2 Switch-off difference 5K HF
3 Minimum running time SOP 3 min HF
4 Solar collector maximum temperature 100 °C HF
5 Solar tank maximum limit (KSPF) 65 °C HF
6 Solar mode of operation 2 HF
7 Heat generator cycle lock (only when parameter 06=1,3,4) 0,5 h HF
8 Solar priority parallel changeover 10 K HF
9 Solar heat balance OFF HF
SOLAR
Reset heat balance HF
RESET
0,0 l/ min
11 Volumetric flow rate HF
0,0 l/ IMP
12 Density, medium 1,05 kg/ l HF
13 Specific thermal capacity, medium 3,6 KJ/ kgK HF
14 Final switching-off temperature 120 °C HF
15 Test cycle solar charging switch-over 10 min HF
16 Switch-over temperature (SLVF) 60 °C HF
17 Solar minimum temperature OFF HF
SOLID FUEL
Par. Designation Factory 10 20 30 40 50 Lev.
1 Minimum temperature 60 °C HF
2 Maximum temperature 95 °C HF
3 Switch-on difference 10 K HF
4 Switch-off difference 5K HF
5 Clock block, heat generator 15 HF
MAIN SUPPLY
Par. Designation Factory 10 Lev.
1 PI-amplification factor, P-portion Xp 0 %/ K HF
2 PI-scanning time Ta 20 s HF
3 PI -reset time Tn 600 s/ °C HF
CASCADE
Par. Designation Factory 10 Lev.
1 Switch-off difference 3K OEM
2 Connecting delay 20 OEM
3 Switch-off delay 5 OEM
4 Switching output stage sequence 65 OEM
5 Stage reversal OFF OEM
6 Control stage 1 BE
7 Peak load stage OFF OEM
8 Group switch-over OFF OEM
9 DHW fast activation OFF OEM
10 Peak load elevation 10 K OEM
BUS
Par. Designation Factory 10 20 30 40 50 Lev.
1 Bus address central device 10 HF
2 Bus right RS direct circuit 1 HF
3 Bus right RS mixer circuit 1 1 HF
4 Bus right RS mixer circuit 2 1 HF
ALARM 1
Par. Designation 10 20 30 40 50 Lev.
1 Alarm 1 OEM
2 Alarm 2 OEM
3 Alarm 3 OEM
4 Alarm 4 OEM
5 ... 20 Alarm 5 - 20 OEM
21 Reset fault signals OEM
SENSOR ALLOC.
Par. Designation Factory 10 20 30 40 50 Lev.
1 Balancing external sensor 0 OEM
RS-T Balancing room sensor (only adjustable with RS-T) 0 HF
2 Balancing heat generator 0 OEM
3 Balancing tank sensor 0 OEM
4 Balancing flow sensor 1 0 OEM
5 Balancing flow sensor 2 0 OEM
6 Balancing solar collector sensor 0 OEM
7 Balancing solar buffer sensor 0 OEM
8 Balancing variable input 1 0 OEM
9 Balancing variable input 2 0 OEM
10 Balancing variable input 3 0 OEM
Confirmation
Serial number:
Year of manufacture:
Place, Date:
Confirmation
Serial number:
Year of manufacture:
Place, Date: