Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PLANS AND CALCULATIONS 13–225

Table 22.4.3.1.1 Equivalent Schedule 40 Steel Pipe Length Chart

Fittings and Valves Expressed in Equivalent Feet (Meters) of Pipe

⁄ in.
12 ⁄ in.
34 1 in. 1 ⁄ in.
14 1 ⁄ in.
12 2 in. 21⁄2 in. 3 in. 31⁄2 in. 4 in. 5 in. 6 in. 8 in. 10 in. 12 in.
Fittings and
Valves (15 mm) (20 mm) (25 mm) (32 mm) (40 mm) (50 mm) (65 mm) (80 mm) (90 mm) (100 mm) (125 mm) (150 mm) (200 mm) (250 mm) (300 mm)

45° elbow — 1 1 1 2 2 3 3 3 4 5 7 9 11 13
(0.3) (0.3) (0.3) (0.6) (0.6) (0.9) (0.9) (0.9) (1.2) (1.5) (2.1) (2.7) (3.4) (4)

90° standard 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27
elbow (0.3) (0.6) (0.6) (0.9) (1.2) (1.5) (1.8) (2.1) (2.4) (3) (3.7) (4.3) (5.5) (6.7) (8.2)

90° long-turn 0.5 1 2 2 2 3 4 5 5 6 8 9 13 16 18


elbow (0.2) (0.3) (0.6) (0.6) (0.6) (0.9) (1.2) (1.5) (1.5) (1.8) (2.4) (2.7) (4) (4.9) (5.5)

Tee or cross (flow 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60


turned 90°) (0.9) (1.2) (1.5) (1.8) (2.4) (3) (3.7) (4.6) (5.2) (6.1) (7.6) (9.1) (10.7) (15.2) (18.3)

Butterfly valve — — — — — 6 7 10 — 12 9 10 12 19 21
(1.8) (2.1) (3) (3.7) (2.7) (3) (3.7) (5.8) (6.4)

Gate valve — — — — — 1 1 1 1 2 2 3 4 5 6
(0.3) (0.3) (0.3) (0.3) (0.6) (0.6) (0.9) (1.2) (1.5) (1.8)

Swing check* — — 5 7 9 11 14 16 19 22 27 32 45 55 65
(1.5) (2.1) (2.7) (3.4) (4.3) (4.9) (5.8) (6.7) (8.2) (9.3) (13.7) (16.8) (20)

For SI units, 1 in. = 25.4 mm; 1 ft = 0.3048 m.


Note: Information on 1⁄2 in. pipe is included in this table only because it is allowed under 8.15.19.4 and 8.15.19.5.
*
Due to the variation in design of swing check valves, the pipe equivalents indicated in this table are considered average.

22.4.4.4.2 A minimum of two additional sets of calculations


Table 22.4.3.2.1 C Value Multiplier shall be submitted to demonstrate peaking of demand area
friction loss when compared to areas immediately adjacent on
Value of C 100 130 140 150 either side along the same branch lines, unless the require-
Multiplying factor 0.713 1.16 1.33 1.51 ments of 22.4.4.4.3 are met.
Note: These factors are based upon the friction loss through the fit- 22.4.4.4.3 Computer programs that show the peaking of the
ting being independent of the C factor available to the piping. demand area friction loss shall be acceptable based on a single
set of calculations.
22.4.4.5 Design Densities.
22.4.4.1.1.3 In systems having branch lines with an insuffi- 22.4.4.5.1* For antifreeze systems greater than 40 gal (151 L)
cient number of sprinklers to fulfill the 1.2 requirement, the in size, the friction loss shall also be calculated using the
design area shall be extended to include sprinklers on adja- Darcy–Weisbach equation shown in 22.4.2.1.3 using a Moody
cent branch lines supplied by the same cross main. diagram, ε-factors that are representative of aged pipe, and
adjusted K-factors for fluid properties. The discharge from in-
22.4.4.1.2 Room Design Method. Where the design is based
dividual sprinklers shall be based on adjusted K-factors for
on the room design method, the calculation shall be based on
fluid properties and shall be determined on the basis of the
the room and communicating space, if any, that is hydrauli-
following formula:
cally the most demanding. (See 11.2.3.3.)
22.4.4.2 CMSA Sprinkler Method. K a = 7.94K w (1/ γa )
22.4.4.2.1 For CMSA sprinklers, the design area shall be a
rectangular area having a dimension parallel to the branch where:
lines at least 1.2 times the square root of the area protected by Ka = K-factor adjusted for fluid properties
the number of sprinklers to be included in the design area. Kw = K-factor used when calculating with water
γa = specific weight of the fluid (density in lb/ft3)
22.4.4.2.2 Any fractional sprinkler shall be carried to the
next higher whole sprinkler. 22.4.4.5.2* System piping shall be hydraulically designed us-
ing design densities and areas of operation in accordance with
22.4.4.3 ESFR Sprinkler Method. For ESFR sprinklers, the de- 11.2.3.2 or Chapter 12 as required for the occupancies or haz-
sign area shall consist of the most hydraulically demanding ards involved.
area of 12 sprinklers, consisting of four sprinklers on each of
three branch lines, unless other specific numbers of design 22.4.4.5.3* The density shall be calculated on the basis of floor
sprinklers are required in other sections of this standard. area of sprinkler operation. Where sprinklers are installed un-
der a sloped ceiling, the area used for this calculation shall be
22.4.4.4* Gridded Systems. the horizontal plane below the sprinklers.
22.4.4.4.1 For gridded systems, the designer shall verify that 22.4.4.5.4 The area covered by any sprinkler used in hydrau-
the hydraulically most demanding area is being used. lic design and calculations shall be the horizontal distances

2010 Edition

( EXHIBIT # 48 )

You might also like