DIESEL GENERATOR SET

STANDBY
600 ekW 749 kVA
60 Hz 1800 rpm 240 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.

FEATURES
FUEL/EMISSIONS STRATEGY CAT® C18 ATAAC DIESEL ENGINE
• Low fuel consumption • Reliable, rugged, durable design
• Field-proven in thousands of applications
DESIGN CRITERIA worldwide
• The generator set accepts 100% rated load in one • Four-stroke-cycle diesel engine combines
step per NFPA 110 and meets ISO 8528-5 transient consistent performance and excellent fuel
response. economy with minimum weight
• Electronic controlled governor
UL 2200
• UL 2200 listed packages available. Certain CAT GENERATOR
restrictions may apply. Consult with your • Matched to the performance and output
Caterpillar Dealer. characteristics of Caterpillar engines
• Load adjustment module provides engine relief
FULL RANGE OF ATTACHMENTS
upon load impact and improves load acceptance
• Wide range of bolt-on system expansion
and recovery time
attachments, factory designed and tested
• UL 1446 Recognized Class H insulation
• Flexible packaging options for easy and cost
effective installation CAT EMCP 3 SERIES CONTROL PANELS
• Simple user friendly interface and navigation
SINGLE-SOURCE SUPPLIER
• Scalable system to meet a wide range of
• Fully prototype tested with certified torsional
customer needs
vibration analysis available
• Integrated Control System and Communications
WORLDWIDE PRODUCT SUPPORT Gateway
• Caterpillar® dealers provide extensive post sale
support including maintenance and repair
agreements
• Caterpillar dealers have over 1,600 dealer branch
stores operating in 200 countries
• The Cat® S•O•SSM program cost effectively detects
internal engine component condition, even the
presence of unwanted fluids and combustion
by-products

SS-006248.pdf: Secured on 04/17/2009 00:29


®

STANDBY 600 ekW 749 kVA


60 Hz 1800 rpm 240 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System Standard Optional


Air Inlet • Light Duty Air Cleaner • Single element canister type air cleaner
• Service indicator • Dual element air cleaner
• Heavy-duty air cleaner with precleaner
• Air inlet shutoff
Cooling • Radiator with guard sized for 50º C • Radiator duct flange
• Coolant level sight window • Low Coolant Level Sensor
• Coolant drain line with valve • Radiator removal
• Fan and belt guards
• Caterpillar® Extended Life Coolant
Exhaust • Stainless steel exhaust flex and ANSI weld flange • Industrial, residential and
• Turbo outlet elbow critical mufflers
• 35 dBA muffler
• Engine mounted muffler
• Mounting and through-wall installation kits
• Manifold and turbocharger guards
Fuel • Primary fuel filter with integral water separtor • Dual Wall Integral Fuel Tanks
• Secondary fuel filters • Dual Wall Sub-base Fuel Tanks
• Fuel cooler • Manual Fuel Fill Pump
• Fuel priming pump • Automatic Fuel Fill Options
• Fuel pressure gauge
• Flexible fuel lines
Generator • Class H insulation • Oversize and premium generators
• Class H Temperature Rise • Three phase sensing
• R448 Voltage Regulator • Quadrature droop kit
• Power terminal strip connections • Digital voltage Regulator
• IP23 Protection • Space heaters
• Power Center • RFI filter
• 80% & 100% UL Breakers
• IEC compliant 3 or 4-pole
• Floor standing circuit breakers with auxiliary contacts
& cabling kits
Control Panels • EMCP 3.1 (package mounted) • EMCP 3.2
• EMCP 3.3
• Local alarm and remote annunciator modules
• Protective devices
Lube • Lubricating oil and filter • Oil temperature sensor
• Oil drain line with valves • Manual sump pump
• Fumes disposal
• Lube oil level indicator
Mounting • Formed steel narrow base frame • Formed steel wide base frame
• Linear vibration isolators between base and engine • Oil field skid base
generator
Starting/Charging • 45 amp charging alternator • Jacket water heater
• 24 volt starting motor(s) • Block heater
• Batteries with rack and cables • Ether starting aid
• Battery disconnect switch
• Battery charger(5A, 10A)
• Oversized batteries
• Battery removal

SS-006248.pdf: Secured on 04/17/2009 00:29 2 April 16 2009 11:25 AM


®

STANDBY 600 ekW 749 kVA


60 Hz 1800 rpm 240 Volts

SPECIFICATIONS

CAT GENERATOR CAT CONTROL PANEL


Frame size.................................................................LC7024F EMCP 3 Series Controls
Excitation...................................................... Internal Excited 24 Volt DC Control
Pitch.............................................................................. 0.6667 EMCP 3.1 (Standard)
Number of poles...................................................................4 • UL/CSA/CE
Number of bearings...................................... Single Bearing NEMA 1, IP22 enclosure
Number of leads................................................................. 12 • Run/Auto/Stop control
Insulation....................... UL 1446 Recognized Class H with Lockable hinged door (option)
tropicalization and antiabrasion • True RMS metering, 3-phase
- Consult your Caterpillar dealer for available voltages • Speed Adjust
IP rating..........................................................Drip Proof IP23 Voltage adjust (optional)
Alignment.............................................................. Pilot Shaft • Digital Indication for:
Overspeed capability...................................... 125% of rated - RPM
Wave form deviation (Line to Line)................................. 2% -Operating hours
Paralleling kit droop transformer.......................... Standard - Oil Pressure
Voltage regulator.3 Phase sensing with selectible volts/Hz -Coolant temperature
Voltage Regulator............. Single phase sensing with load - System DC volts
adjustable module - L-L volts, L-N volts, phase amps, Hz
Voltage Regulation...........Less than +/- 1/2% (steady state)
-ekW, kVA, kVAR,kW-hr, %kW, PF (*)
Less than +/- 1/2% (w/ 3% speed change)
Telephone Influence Factor.............................. Less than 50 • Shutdowns
Harmonic distortion......................................... Less than 5% -Low oil pressure
-High coolant temperature
CAT ENGINE -Overspeed
C18 ATAAC, I-6, 4-stroke watercooled diesel -Emergency stop
Bore - mm.............................................. 145.00 mm (5.71 in) -Failure to start (overcrank)
Stroke - mm............................................. 183.00 mm (7.2 in) • Programmable protective relaying functions: (*)
Displacement - L................................... 18.13 L (1106.36 in3) -Under and over voltage
Compression ratio........................................................ 14.5:1 -Under and over frequency
Aspiration........................................... Air-to-Air Aftercooled - Reverse power
Fuel system..................................... Electronic unit injection -Overcurrent
Governor type................. Caterpillar ADEM control system • MODUS isolated data link (RS-485 half-duplex) supports
serial communication at data rate up to 115.2 kbaud (*)
(*) Available on EMCP 3.2 & EMCP 3.3
Single location customer connector point
Consult your Caterpillar dealer for available voltages.

SS-006248.pdf: Secured on 04/17/2009 00:29 3 April 16 2009 11:25 AM


®

STANDBY 600 ekW 749 kVA


60 Hz 1800 rpm 240 Volts

TECHNICAL DATA

Open Generator Set - - 1800 rpm/60 Hz/240 Volts DM7548


Low Fuel Consumption

Generator Set Package Performance


Genset Power rating @ 0.8 pf 750 kVA
Genset Power rating with fan 600 ekW
Coolant to aftercooler
Coolant to aftercooler temp max 49 º C 120 º F
Fuel Consumption
100% load with fan 162.8 L/hr 43.0 Gal/hr
75% load with fan 120.2 L/hr 31.8 Gal/hr
50% load with fan 84.4 L/hr 22.3 Gal/hr
Cooling System1
Air flow restriction (system) 0.12 kPa 0.48 in. water
Air flow (max @ rated speed for radiator arrangement) 804 m³/min 28393 cfm
Engine Coolant capacity with radiator/exp. tank 81.8 L 21.6 gal
Engine coolant capacity 20.8 L 5.5 gal
Radiator coolant capacity 61.0 L 16.1 gal
Inlet Air
Combustion air inlet flow rate 48.4 m³/min 1709.2 cfm
Exhaust System
Exhaust stack gas temperature 553.2 º C 1027.8 º F
Exhaust gas flow rate 141.4 m³/min 4993.5 cfm
Exhaust flange size (internal diameter) 203 mm 8 in
Exhaust system backpressure (maximum allowable) 10.0 kPa 40.2 in. water
Heat Rejection
Heat rejection to coolant (total) 183 kW 10407 Btu/min
Heat rejection to exhaust (total) 641 kW 36454 Btu/min
Heat rejection to aftercooler 145 kW 8246 Btu/min
Heat rejection to atmosphere from engine 107 kW 6085 Btu/min
Heat rejection to atmosphere from generator 41.0 kW 2331.7 Btu/min
Alternator2
Motor starting capability @ 30% voltage dip 1633 skVA
Frame LC7024F
Temperature Rise 150 º C 270 º F
Lube System
Sump refill with filter 38.0 L 10.0 gal
Emissions (Nominal) 3

NOx g/hp-hr 5.61 g/hp-hr


CO g/hp-hr .47 g/hp-hr
HC g/hp-hr .01 g/hp-hr
PM g/hp-hr .038 g/hp-hr
1
For ambient and altitude capabilities consult your Caterpillar dealer. Air flow restriction (system) is added to existing restriction from
factory.
2
Generator temperature rise is based on a 40º C (104º F) ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuel
with 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.

SS-006248.pdf: Secured on 04/17/2009 00:29 4 April 16 2009 11:25 AM


®

STANDBY 600 ekW 749 kVA


60 Hz 1800 rpm 240 Volts

RATING DEFINITIONS AND CONDITIONS

Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, These ratings also apply at ISO3046 standard conditions.
NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC, Fuel rates are based on fuel oil of 35º API [16º C (60º F)]
2004/108/EC gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
Standby - Output available with varying load for the when used at 29º C (85º F) and weighing 838.9 g/liter
duration of the interruption of the normal source power. (7.001 lbs/U.S. gal.). Additional ratings may be available
Average power output is 70% of the standby power for specific customer requirements, contact your
rating. Typical operation is 200 hours per year, with Caterpillar representative for details. For information
maximum expected usage of 500 hours per year. regarding Low Sulfur fuel and Biodiesel capability,
Standby power in accordance with ISO8528. Fuel stop please consult your Caterpillar dealer.
power in accordance with ISO3046. Standby ambients
shown indicate ambient temperature at 100% load which
results in a coolant top tank temperature just below the
shutdown temperature.

SS-006248.pdf: Secured on 04/17/2009 00:29 5 April 16 2009 11:25 AM


®

STANDBY 600 ekW 749 kVA


60 Hz 1800 rpm 240 Volts

DIMENSIONS

Package Dimensions
NOTE: For reference only - do not use for
Length 3936.9 mm 155 in installation design. Please contact
Width 1536.0 mm 60.47 in your local dealer for exact weight
and dimensions. (General
Height 2165.8 mm 85.27 in Dimension Drawing #2996192).
Weight 4001 kg 8,821 lb

www.CAT-ElectricPower.com
Performance No.: DM7548
© 2009 Caterpillar
All rights reserved.
Feature Code: C18DE39
Materials and specifications are subject to change without notice.
Gen. Arr. Number: 2476127 The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, SAFETY.CAT.COM their respective logos, "Caterpillar
Source: U.S. Sourced Yellow," and the POWER EDGE trade dress, as well as corporate and
product identity used herein, are trademarks of Caterpillar and may not
be used without permission.
April 16 2009 14165053