VISUALIZATION &
COLOUR
ASTM D1524 & D1500 LIQUID WATER CONTENT
POWER ASTM D1533
FACTOR
ASTM D924
ACIDITY
ASTM D664
Minyak Trafo Sediment, IFT, Furan
INTERFACIAL
TENSION (IFT)
ASTM D971
Minyak Trafo Gravity, Inhibitor, Corrosive, Metal
SPECIFIC GRAVITY
ASTM D4052
INHIBITOR CONTENT
ASTM D2668 CORROSIVE SULPHUR
METALS IN OIL
ASTM D3635
Minyak Trafo Tegangan Tembus
kV
MIXER
KONTROL
220 V
MCB
REGULATOR
100
EPOXY RESIN
d 12,5
r 25
60 70
2,5 2
62
,
5
85
r 25
110
Minyak Trafo DGA
Y N
mengindikasikan
Kondisi Normal
Kondisi 2, 3, 4
Investigasi Lanjut
Pengujian Elektrik Trafo
Konsultasi dengan Ahli
Minyak Trafo DGA
PD Partial discharges
D1 Discharges of low energy
D2 Discharges of high energy
T1 Thermal fault, t< 300 C
T2 Thermal Fault, 300 C < t < 700 C
T3 Thermal Fault, t > 700 C
R1 R3 R4 PD RIV
<0,1 <3 <0.4 Corona
Fault
Not Applicable
Resample
R1 R2 R3 R4 Discarge
0.1-1 >0.75 >0.3 >0.4 Arcing
Fault
Not Applicable
Resample
R1 R2 R3 R4
Discarge
>1 >0.75 >0.3 >0.4 Arcing
Minyak Trafo DGA
Case 3
R5 Low Temperature
1-3 Thermal
Overloading
Case 4
R1 R5 Thermal
>1 1-3
<700 C
Case 5
R5
>3 Thermal
<700 C
Case 1
R2 R1 R2
<0.1
PD
<0.1 <1
Influence Voltage (RIV)
Case 2
R2 R1 R5
1-3 0.1-1 High Energy
>3
Arcing
Minyak Trafo DGA
CO2 CO
Condition 1 Normal 0-2.500 0-350
METODA
INTERPRETASI
H2 Flash Point
Doernenburg ratio
CH 4 Sediment
Rogers ratio
C 2H 4 BDV
Duval
C 2H 6 Water Content
Key Gases
C2 H 2 IFT
CO Nn
IEEE C57 104- 1991 Color
Act Based TDCG
CO2 TDCG Rate(ppm/day)
N2
O2 TDCG
REKOMENDASI
NORMAL
PURIFICATION
BDV
Water Content
TDCG
RECLAMATION
IFT
Nn
Color
MIN
INTERPRETASI CO /CO 2
Status Isolasi Kertas
Furan Test required
Minyak Trafo Minyak Trafo