Job Safety Analysis Sheet: Facility

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Job Safety Analysis Sheet

JOB DESCRIPTION: Functional Testing of H2S Detectors JSA Ref. No. JSA / KOC / 13

Facility: Work Area / Equipment: Permit No.


Date:

PERSONAL PROTECTIVE EQUIPMENT & TOOLS: Hard Hat, Safety Shoes, Hand Gloves, Coverall, Portable Radio, Escape Mask
SEQUENCE OF Yes /
POTENTIAL HAZARDS PRECAUTIONS
BASIC JOB STEPS No

 Refer HSEMS Procedure - Doc. No. SA.KOC.004 “Permit to


Non – compliance of HSE MS Work”.
Procedures
 Take a Cold Work Permit from Asset Owner.

 Ensure test bottle (containing H2S Gas of 10 ppm


concentration) & accessories are free from defect & not
Defective Tool & Equipment leaking.
 Refer manufacturer instruction for refilling of test gas bottle.
Planning
 Assess the risk & Override the H2S detector to be function
Unintended Shutdown of Facility / tested.
Equipment
 Do not remove override prior to resetting the alarm in the
panel.

 Maintain a radio communication between worker at Gas


Lack of Communication Detector site and the person stationed near F & G panel /
Control Room.

Wrong Identity of Gas Detector  Ensure the identity of detector before charging the gas into it.

 Apply only the required amount of gas as needed to actuate


Excessive Charging of H2S to the detector sensor.
Detector  Refer manufactures instruction for functional testing &
calibration of detector.

Toxic Gas Leak  Keep the Test Bottle valve closed when not in use.

Functional Testing  Do not bring any naked flame or spark generating equipment
Fire & Explosion near the test gas bottle.
 Do not dismantle or puncture the test gas bottle even if empty.

 Confirm the alarm on gas charging through radio


Fault Alarm
communication.

 Keep the test bottle in safe and secured location.


Unsafe Storage / Disposal of Test  Do not dispose the empty bottle unsafely.
Bottle
 Refer manufacturer instruction for safe disposal / transportation
of empty bottle.

 Ensure proper wind up & housekeeping at worksite.


Windup &
Scattered Material  Remove the gas detector override after resetting the alarm in
Housekeeping
the panel.

Additional Hazards
(Other than indicated
above)

Name: Designation:
KOC / ID. No. Company:
JSA Done By
Controlling Team: Contract No.(If Applicable):
Signature: Date: