Professional Documents
Culture Documents
System Descr MAB Modules
System Descr MAB Modules
System Description
&
Operating Instructions
Printed 3/29/2005
Document n° 53555432
Revision 0
File 53555432.doc
1 Scope
This description is valid for the following separator module system:
2 System Overview
In the separation process, heated lubricating oil is fed through the separator to
clean the oil by removing any solid particles and water.
A MAB/MMB system comprises:
• Separator.
• Ancillary equipment including a control panel.
• Oil feed pump.
• Oil heating system.
The MAB/MMB separator module operates normally as clarifier. The cleaned oil
is discharged continuously, while the solid particles are collected in the
separator and have to be removed manually.
Cleaned oil leaves the separator through the oil outlet while separated particles
and sludge accumulates at the periphery of the separator bowl and separated
water goes out from the outlet.
The control panel supervises the entire operation of the separation system and
performs control and alarm functions.
Water is used in the separation process and a specified amount of processing
water is added manually by the operator into the bowl to form a water seal.
page 2
3 System Description and Layout
The drawing numbers of the modules are according to the below table:
Refer to the appropriate flow chart diagram. Oil to be treated (201) flows to the
module, it is drawn by the built-on pump installed on the module and it is
heated up at the temperature suitable for its treatment. An electric heater
assures the heating function (for total power installed refers to the table below)
and a programmable electronic temperature controller regulates the correct
working oil temperature.
During start up, electric 3-way valve MV1 re-circulates oil, diverting flow back to
the tank whilst the heater raises the oil temperature to the set point value.
For proper and correct unit performance refer to temperature/oil capacity table
below.
Treated oil outlet (220) and the recirculation oil (209) must be connected
directly back to the oil tank. Pressure switch arrangement PS42 detect that no
water seal breakage happens. The regulating valve RV4 creates the suitable oil
page 3
operating back pressure that must be adjusted about to 100-150 kPa. The free
separated water is discharged through the outlet (221).
5 Start Up Operations
• Open all manual valves (oil in/out, press switch, drain etc.).
• Close oil drain valves V3 of electric heater and water seal V6.
• On Control panel the alarms, heater and 3-way valve switches must be in
“Off” position.
• Switch “On” the Main Power selector switch.
• All alarms lamps must be “On”.
• Turn the reset alarm selector switch, the alarm signals will disappear.
• Start separator by pushing the start button.
• Start feeding pump by start button. In this phase the oil is recirculating, out
(209) to the storage tank. (Not applicable on MAB103).
• IMPORTANT: Air must be completely removed from electric heater by
opening the safety valve SV1 or by proper vent ball valve on the top of
the heater.
• Check the absence of leakage on pipes and heater.
• Wait until the separator has reached the full speed.
WATER SEAL
• Open slowly the water seal valve V6 to torn the water seal in the bowl.
• When water visibly flows out the bowl from open funnel or sight glass, close
water seal valve V6.
HEATING
• Turn the heater section switch to “On” position.
page 4
• Wait until the oil temperature reaches the set point (approx. 60 °C). Thermo-
regulation function is performed automatically. It is possible to change the oil
temperature set point by pushing the buttons “Up” and “Down” on
temperature controller.
⊗ Note (only for MAB 103 Module): Valve V7 must always be left opened in
order to feed “full pump flow” to separator. Closing valve V7 the oil is diverted
back to feed pump by opening the relief valve.
6 Stopping Operation
• Turn 3-way valve selector switch to “Off” position. The oil flow then
recirculates.
• Turn heater section switch to “Off” position.
• Push feed pump stop button.
• Push separator stop button.
• Wait for separator to completely stop (use the brake in order to reduce the
stopping time).
• Close oil valves.
• Turn Main power selector switch to “Off”.
7 General Remarks
7.1 Heater
IMPORTANT
Long storage can decrease the electric insulation value of the coils.
Generally, the continuous working brings up again the insulation to normal
values.
If the value is lower than 1 MΩ, energize the coils in open air for 3 - 4 hours
with half rated voltage or leave them in an oven for 1 hour at a temperature of
max. 80 °C (completely el. disconnected in this case).
page 5
Coil Cleaning
• for non water soluble deposits, circulate a cleaning solution inside the
section;
• for other kind of deposits, apply a specific cleaning product as recommended
by the maker.
Always ascertain that the products used are compatible with the material
circulating inside the heat exchanger.
In some special cases, also using brushes can assist cleaning.
In this case, utmost care must be taken to prevent deterioration of the external
surface of the heating element.
Frequent cleaning makes the de-scaling process easier.
During disassembly, special care should be taken not to damage the coils and
the gasket seats.
page 6
MAB/MMB Separation System
page 7
Low Oil Pressure (PS 42)
Too low back pressure Increase the back pressure with the
regulating valve RV4 to correct back
pressure (about 100-150 kPa)
* In order to reset this alarm the operator should switch off the three-way valve in “0” position.
Emergency stop button has been 1. Remedy the cause for the
pushed emergency stop.
2. Reset the alarm by switching the
power off and on.
3. Restart the separator.
4. Restart the process.
page 8
Low Flow (FS)
page 9
Motor Overload
Separator and feed pump electric 1. Check if the thermal switch is set to
motors overload the correct amperage according
with the maximum electric motor
consumption.
2. Check electric motors and
mechanical motion parts.
3. Check if the voltage supplied is in
accordance with the control panel
label.
* In order to reset this alarm the operator should reset the circuit breaker by opening the door of
the control panel and pushing the reset button inside.
page 10