PRE-FUNCTIONAL TEST ANNEX FORM FR-06-EMCD-A-EE-001-rev.

0
CONTINUITY TEST FORM (PRE AND POST ENERGIZATION)

1 General Information
a) Area: 2ND FLOOR COMMON AREA d) Brand : SANWA
b) Equipment No. : e) Model/Serial No. : 18010400149
c) Type/ Rating : THHN

2 Test Instruments
a) Multi-meter or Digital test meter b) Calibration Date: MARCH 22, 2021

3 Testing Procedure
a) After the cable and wire pulling for the electrical system:
a.1) Using the multi-meter instrument, set the tester to the ohm setting. By touching the test leads or test probes together,
the tester should indicate a Zero Ohm reading. For a digital test meter, it will likely show 0.00 ohm reading.
b) Before building energization, repeat step a.1) and record result in Pre-enerization Column (B).
b.1) For lighting system with installed fixtures, test continuity for Line-Neutral, Line-Ground and Neutral-Ground.
b.2) For Circuit breaker, test continuity for loadside of the source and line side of the equipment controller.

Actual Reading (Ohm)


Acceptable Pre-Energization (B)
Circuit No. After Wire Result Result
Level (0 Ohm)
Pulling (A) (Pass/Fail) L-N L-G N-G (Pass/Fail)
16-LIGHTING + 1-EXIT0.00 Ohm
LIGHT 0 OHMS PASS 0 0 0 PASS
10-LIGHTING + 1-EXIT0.00 Ohm
LIGHT 0 OHMS PASS 0 0 0 PASS
2-C/O 0.00 Ohm 0 OHMS PASS 0 0 0 PASS
LPP2 0.00 Ohm 0 OHMS PASS 0 0 0 PASS
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm
0.00 Ohm

Page 1 of 2
CONTINUITY TEST FORM (PRE AND POST ENERGIZATION) Revision 001 September 2019
PRE-FUNCTIONAL TEST ANNEX FORM FR-06-EMCD-A-EE-001-rev.0
CONTINUITY TEST FORM (PRE AND POST ENERGIZATION)

c) After building energization:


a.1) Using Voltage Test Pen or Test Light (contact and non contact type), check the presence of electricity or stray voltage within any
conductive / metal materials.
a.2) A test pen/light is simpler and often suffices for checking for the presence of voltage on a conductor. Properly designed test lights
include features to protect the user from accidental electric shock. Non-contact test lights can detect voltage on insulated conductors.
a.3) Ensure that no voltage reading at the locations indicated below. In case there is electricity present at location where it's not supposed to be,
turn off the power supply and rectify the deficiencies immediately.

4 Data Recording
Does the Test Pen/Test Light Glow? (YES/NO)
Acceptable Other Metal Surfaces
Location Hanger Junction Pull Panel Wall boxes Metal Meter
Result
Rods Box Boxes Boards w/ cover Ducts Center

NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO

5 Acceptance / Approvals:
ENGR.PAUL ARON JUNIO 06/08/2021 MAGNAXA
Subcontractor's Representative Date Company

ENGR. ANGELICA CAMPIT ENGR. APRILYN LIBAO 06/08/2021 MDCBP


EMCD Field Engineer / OMCD (QA/QC) Date Company

ENGR. JEFFREN CABRA 06/08/2021 MDCBP


MDC - EMCD Supervisor/Head Date Company

6 Distribution.
c Subcontractor
c MDC Documents Controller
c MDC MEPFS

Page 2 of 2
CONTINUITY TEST FORM (PRE AND POST ENERGIZATION) Revision 001 September 2019