VLC–853C3

Programmable VisualLogic ® Controller

Features & Application Highlights


• Capable Eight 10-bit inputs, five binary
outputs, and three 8-bit analog outputs.

• Interoperable Fully BACnet-compliant on


MS/TP LAN at up to 76.8 Kbps.

• Versatile Fully programmable for central plant


systems, air handling units, other control and
process equipment.

• Reliable Extensive onboard filtering, with all


program data backed up in nonvolatile
EEPROM.

• Fast Internal logic loop of 100 msec.

The Alerton ® BACtalk ® VLC–853C3 ™ is a high- control strategies. A single VLC–853C3 can contain
performance, fully programmable logic controller numerous algorithm loops that control various parts or
designed for control of central plant systems, air multiple pieces of equipment. Non-volatile EEPROM
handling units, large terminal units and similar control stores all program data.
and process equipment. The VLC–853C3 is part of
Alerton's complete BACtalk product line in total The VLC–853C3 is built for high-speed processing,
compliance with ANSI/ASHRAE Standard 135–1995, with an internal logical loop time of 100 msec.
BACnet. As a native BACnet controller, it requires no Programmable timers also maintain a resolution of 100
proprietary chip sets to integrate seamlessly with your msec.
BACnet system.
High-resolution, 10-bit analog inputs are field-
The VLC–853C3 communicates using the standard adjustable for thermistor/dry contact, 0–5 VDC/4–20 mA
BACnet protocol on a BACnet MS/TP LAN, which or 0–10 VDC. Analog outputs are switch-selectable for
operates at up to 76.8 Kbps. An onboard LED indicates 4–20 mA or 0–10 VDC. An onboard LED for each binary
the status of BACnet communications. The VLC–853C3 output indicates ON/OFF status.
can also operate as a stand-alone controller. Its design
includes support for Alerton’s BACtalk Microset™, an CMOS circuitry, a four layer circuit board with
intelligent wall sensor unit offering convenient data separate ground plane, and extensive hardware,
display and setpoint adjustment. software, and power-supply filtering ensure reliable and
stable operation. The CMOS processor uses an internal
All VLC–853C3 control logic is programmed with watchdog, and power supply voltage is monitored to
Alerton's easy-to-learn graphical programming language, provide automatic shutdown and data backup.
VisualLogic. This self-documenting software’s complete Product Number
function library enables you to implement entirely flexible
VLC-853C3
LTBT-VLC-853C3
8/99

VLC–853C3 SPECIFICATIONS

Power 24 VAC @ 10 VA min., plus binary output loads (80 VA max). Utilizes a half-wave rectifier, which
allows multiple VLCs to be powered from a single transformer. One leg of 24 VAC connects to
earth (panel) ground.

Inputs 8 inputs with 10-bit resolution. Input 0 can be used for a BACtalk® Microset™. Inputs 1–7 are
jumper-selectable for thermistor/dry contact, 0–5 VDC/4–20 mA or 0–10 VDC signals.

Binary Outputs 5 outputs, each rated at 24 VAC, 0.5 A. The outputs utilize hot-switched triacs, which have a
common connection to the fused 24 VAC supply.

Analog Outputs 3 outputs with 8-bit resolution. Each is switch-selectable for 0–10 VDC or 4–20 mA. 4–20 mA
outputs are sourced by the VLC. Connected loads must return to the VLC ground. 4–20 mA max.
load resistance is 1,000Ω. 0–10 VDC min. load resistance is 500Ω.

24VDC Outputs Two terminals provide up to 250 mA (total) of 24 VDC to power transducers or other devices.

Processor Motorola CMOS processor with ROM and RAM.

EEPROM Provides non-volatile program and data storage.

Max. Dimensions 4.9" (125mm) H X 5.4" (136mm) W X 1.4" (36mm) D.

Terminations Removable header-type screw terminals accept 14–24 AWG wire.

Environmental 32–158°F (0–70°C). 0–95% RH, non-condensing.

Communications BACnet MS/TP LAN up to 76.8 Kbps.

BACnet
Conformance Conformance Class 3. See Protocol Implementation Conformance Statement (PICS).

Ratings • Listed Underwriters Laboratory for Open Energy Management Equipment (PAZX) under
the UL Standard for Safety 916. Listing includes U.S. and Canadian certification.

• EMC Directive 89/336/EEC (European CE Mark).

• FCC Part 15, Subpart J, Class A.

Specifications subject to change without notice.