CIRCUIT DESIGN STANDARD - TYPICAL SIGNALLING & CONTROL SYSTEMS CIRCUITS - T HR SC 00001 ST

ASA STANDARD DRAWINGS


TYPICAL SIGNALLING & CONTROL SYSTEMS CIRCUITS

This drawing and the related information have been prepared by, or at the request of, TfNSW for a specific
purpose and may not be used for any purpose other than the purpose intended by TfNSW. TfNSW does CIRCUIT BOOK No: 00001
not provide any warranties and accepts no liability arising out of the use of this drawing or any of the related
information for any purpose other than the intended purpose. This drawing is protected by copyright and
no part of this drawing may be reproduced in any form without the express written permission of TfNSW.
T HR SC 00001 ST
STATUS: STANDARD DRAWINGS
DRAWN C. Turnbull 31/08/2018
BOOK: 1 OF 1 C
DESIGNED D. Oakes 31/08/2018
PART: 1 OF 1 A3
D.O. 31/08/18 D.M. 31/08/18 P.M. 31/08/18 REVIEWED D. Oakes 31/08/2018
A0 COMPLETE ISSUE DRG No.
CSTD0A00.DGN 0
ACCEPTED BY ASA VERIFIED D. Martin 31/08/2018
DESCRIPTION REVIEWED VERIFIED APPROVED EDMS No.
AMD P. McGregor 31/08/2018
SIGN./DATE SIGN./DATE SIGN./DATE PJM 31/08/2018 APPROVED SG0602002 A
DF 385*275
MAINTENANCE CONTROL SHEET Date: 31/08/2018

Control Sheet No: 1 of 2 Note - Medium: C = CAD; X = Excel File


Circuit Book No: 00001 Name: ASA STANDARD DRAWINGS_TYP. SIGNALLING & CONTROL SYS. CCTS Book: 1 of 1
List of Effective Pages List of Effective Pages List of Effective Pages List of Effective Pages
Page (from) Page (to) Med Date Page (from) Page (to) Med Date Page (from) Page (to) Med Date Page (from) Page (to) Med Date
A00 C 31/08/18 A131_2 C 31/08/18 T024 C 31/08/18 W062 C 31/08/18
CP1_1 X 31/08/18 A132_1 C 31/08/18 T030 C 31/08/18 W063 C 31/08/18
CP1_2 X 31/08/18 A132_2 C 31/08/18 T031 C 31/08/18 W075 C 31/08/18
AS X 31/08/18 A139 C 31/08/18 T032 C 31/08/18 W076 C 31/08/18
A01 C 31/08/18 A140 C 31/08/18 T035 C 31/08/18 W078 C 31/08/18
A101 C 31/08/18 N056 C 31/08/18 T036 C 31/08/18 W079 C 31/08/18
A102 C 31/08/18 P004 C 31/08/18 T041 C 31/08/18 W080 C 31/08/18
A103 C 31/08/18 P005 C 31/08/18 T042 C 31/08/18 W085 C 31/08/18
A104 C 31/08/18 Q001 C 31/08/18 U103 C 31/08/18 W086 C 31/08/18
A105 C 31/08/18 Q002 C 31/08/18 U104 C 31/08/18 W087 C 31/08/18
A106 C 31/08/18 R003 C 31/08/18 U105 C 31/08/18 W088 C 31/08/18
A107 C 31/08/18 R004 C 31/08/18 U107 C 31/08/18 W089_1 C 31/08/18
A108 C 31/08/18 R005 C 31/08/18 U109 C 31/08/18 W089_2 C 31/08/18
A109 C 31/08/18 R006 C 31/08/18 U115 C 31/08/18 W090 C 31/08/18
A110 C 31/08/18 R007 C 31/08/18 U116 C 31/08/18 W091 C 31/08/18
A112 C 31/08/18 R008 C 31/08/18 U117 C 31/08/18 W093 C 31/08/18
A115 C 31/08/18 R009 C 31/08/18 U118 C 31/08/18 W094 C 31/08/18
A116 C 31/08/18 R010 C 31/08/18 V001 C 31/08/18 W095 C 31/08/18
A117 C 31/08/18 R011 C 31/08/18 V002 C 31/08/18 W097 C 31/08/18
A118 C 31/08/18 T005 C 31/08/18 V060 C 31/08/18 W098 C 31/08/18
A119 C 31/08/18 T006 C 31/08/18 V061 C 31/08/18 W099 C 31/08/18
A120 C 31/08/18 T010 C 31/08/18 V070 C 31/08/18 W100 C 31/08/18
A121 C 31/08/18 T011 C 31/08/18 V071 C 31/08/18 W101 C 31/08/18
A122 C 31/08/18 T012 C 31/08/18 V072 C 31/08/18 W102 C 31/08/18
A123 C 31/08/18 T015 C 31/08/18 V073 C 31/08/18 W103 C 31/08/18
A124 C 31/08/18 T016 C 31/08/18 W008 C 31/08/18 W112 C 31/08/18
A125 C 31/08/18 T017 C 31/08/18 W010 C 31/08/18 W113 C 31/08/18
A130_1 C 31/08/18 T021 C 31/08/18 W011 C 31/08/18 W114 C 31/08/18
A130_2 C 31/08/18 T022 C 31/08/18 W060 C 31/08/18 W119 C 31/08/18
A131_1 C 31/08/18 T023 C 31/08/18 W061 C 31/08/18 W120 C 31/08/18

Version: 1.0 CSTD0CP1_1


MAINTENANCE CONTROL SHEET Date: 31/08/2018

Control Sheet No: 2 of 2 Note - Medium: C = CAD; X = Excel File


Circuit Book No: 00001 Name: ASA STANDARD DRAWINGS_TYP. SIGNALLING & CONTROL SYS. CCTS Book: 1 of 1
List of Effective Pages List of Effective Pages List of Effective Pages List of Effective Pages
Page (from) Page (to) Med Date Page (from) Page (to) Med Date Page (from) Page (to) Med Date Page (from) Page (to) Med Date
W121 C 31/08/18 X100 C 31/08/18
W122 C 31/08/18 X101 C 31/08/18
W123 C 31/08/18 X102_1 C 31/08/18
W124 C 31/08/18 X102_2 C 31/08/18
X001 C 31/08/18 X103-1 C 31/08/18
X003 C 31/08/18 X103-2 C 31/08/18
X005 C 31/08/18 X104_1 C 31/08/18
X006 C 31/08/18 X104_2 C 31/08/18
X007 C 31/08/18 X105 C 31/08/18
X014 C 31/08/18 X106 C 31/08/18
X015 C 31/08/18 X121_1 C 31/08/18
X023 C 31/08/18 X121_2 C 31/08/18
X024 C 31/08/18 X122 C 31/08/18
X025 C 31/08/18 X123 C 31/08/18
X026 C 31/08/18 Y001 C 31/08/18
X029 C 31/08/18 Y002 C 31/08/18
X030 C 31/08/18 Y003 C 31/08/18
X031 C 31/08/18 Z001 C 31/08/18
X039 C 31/08/18 Z002 C 31/08/18
X041 C 31/08/18
X042 C 31/08/18
X045 C 31/08/18
X051 C 31/08/18
X052 C 31/08/18
X053 C 31/08/18
X054 C 31/08/18
X055_1 C 31/08/18
X055_2 C 31/08/18
X056 C 31/08/18
X060 C 31/08/18

Version: 1.0 CSTD0CP1_2


31/08/2018 CSTD00AS AMENDMENT SHEET Pt 1 of 3 CB: 00001

Change History ASA Name: Typical S & CS Circuits CB: 00001


Revision No Version Date Job/Modification Details Company Name Amended Pages/Additional Pages/Removed Pages/Replaced Pages
Converted to RailCorp format from Specification No New sheets: A001, A140, A141, X051
1.1 08/07/2008 SC001400SP- Standard Signalling Circuits - Version RailCorp Split sheets: X053 to X052 & X053
3.3 of 26 May 2008 Amended sheets: W008, X026, X030, X031, X041, X052, X054
1.2 14/10/2008 UCR coil labelled 1, AT in TDR amended to TDR RailCorp Amended sheet: X105
1.3 03/11/2008 POJR Straps amended RailCorp Amended sheet: U103
1.4 25/11/2008 RailCorp New sheet: Q010
Withdrawn sheet: Index drawing
Wire size & N-RI contacts. Amended sheet: W008(V6)
1.5 12/01/2009 WTJR contacts. RailCorp Amended sheet: W101(V6)
#4 - Latch delays set to 10". Amended sheet: X031
#4 - Contact 6 on Up side. Amended sheet: X054
Formatting of HDFR times. Amended sheet: A131_2(V1)
Amended polarity of Load Supply Avail relay. Amended sheet: U109(V6)
LOC terms added to detection. Amended sheet: W119, W120, W121, W122
1.6 09/03/2009 Labels of detector contacts in N/RKR amended. RailCorp Amended sheet: W120
Notes 6 & 7 added, Amended sheets:X015(V3)
Split and formed. Amended sheet: X023
Change of name for emergency switches. Amended sheets: X024, X029(V4)
Amendments made to Base arrgts & Mech terminals, Amended sheet: X006(V4)
XNR layout between Bases amended.
Current monitor - Fastron deleted. Amended sheet: X025(V9)
1.7 17/08/2009 Sheet deleted & layout for type 3593B moved to RailCorp Withdrawn sheet: X038
Obsolete.
Layout for 3590 inserted & layout for 3590B moved to Amended sheet: X039(V1)
Obsolete
31/08/2018 CSTD00AS AMENDMENT SHEET Pt 2 of 3 CB: 00001

Change History ASA Name: Typical S & CS Circuits CB: 00001


Revision No Version Date Job/Modification Details Company Name Amended Pages/Additional Pages/Removed Pages/Replaced Pages
Moved to Obsolete. Withdrawn sheets: A102(V9), A104(V4), A111
New dwg to replace A111. New sheet: A112(V1)
Link 9 in trainstop added, contacts for VR in V cct Amended sheet: A122(V3)
corrected, VNR/VRR cct moved to V002.
VNR & VRR added - note added wrt trainstops. Amended sheets: R006(V5), R007(V5)
Note added when TX & RX on same freq to use Amended sheet: T004(V5)
separate PSUs.
Link 9 in trainstop added, contacts for VR in V cct Amended sheets: U115(V1), U116(V1), U117(V1), U118(V1), V001(V6)
corrected, VNR/VRR cct moved to V002.
Cct controller without RSA studs moved to new dwg Amended sheet: V002(V6)
V003 in Obsolete.
101 RLR in 101 RKR changed to 101 RWR. Amended sheet: W101
1.8 27/04/2010 W115 replaces W117 and brake cct added. RailCorp New sheet: W115(V1)
Moved to Obsolete. Replaced sheet: W117
W116 replaces W118 and brake cct added. New sheet: W116(V1)
Moved to Obsolete. Replaced sheet: W118
Adjustments to LXMON B15. Amended sheet: X006(V4)
SS& CS Gate ZK. Amended Sheet: X014(V)
Emergency Switches. Amended Sheet: X020(V3)
Supplies to Battery Low ZK interface. Amended Sheet: X026(V5)
Master Emergency Switch. Amended Sheet: X029(V4)
Timer set to 12" . Amended Sheet: X042(V4)
Alt. config for vital PED XNR. Amended Sheet: X054(V5)

Application of TMA 400 format,


As Built To RailCorp format. Amended sheet: A001
New cover sheet for construction. New sheet: A002
1.9 13/09/2011 RailCorp Amended sheet: A118
VRR shown rather than VNR for R1 R3 coil.
105B to be SLAVE. Amended sheet: W078
No break supply note. Amended sheet: W088

1.11
19/06/2012 As built & construction cover sheets RailCorp Amended sheets: A001, A002
(skip 1.10)

New sheets: T021, T022, T023, T024, V060, V061, W076, W097, W098, W099, W100,
W123, W124, X106
Amended sheets: A000, A100, A101, A107, A108, A109, A115, A118, A119, A121, A122,
A125, A130-2/2, A131-2/2, A141, T004, T010, T011, T030, T031, T035, U109, U116, U117,
1.12 19/04/2013 RailCorp U118, V002, W008, W060, W061, W062, W063, W075, W078, W079, W080, W085, W088,
W090, W091, W093, W094, W095 (page changed from W097), W101, W115, W116, W119,
W120, W121, W122, X003, X006, X007, X014, X015, X020, X023, X025, X026, X029, X030,
X031, X042, X045, X051, X052, X055-1/2, X055-2/2, X101, X102-1/2, X102-2/2, X103-1/2,
X103-2/2, X104-1/2, X104-2/2, X105, X121
31/08/2018 CSTD00AS AMENDMENT SHEET Pt 3 of 3 CB: 00001

Change History ASA Name: Typical S & CS Circuits CB: 00001


Revision No Version Date Job/Modification Details Company Name Amended Pages/Additional Pages/Removed Pages/Replaced Pages
Note: Previous changes up to this point were carried out under the former rail
authority RailCorp. All change control revisions from this point shall follow the ASA
standard drawings process.
ASA document template and numbering applied.
New sheets: Nil
1.0 25/06/2015 ASA
Amended sheets: Nil
TfNSW Logo Change Withdrawn sheets: A000, A001, A002

New sheets:

A00, A132_1, A132_2, A139, T012, T015, T016, T017, V070, V071, V072, V073, W102,
W103, W112, W113, W114, X121_2

Amended sheets:

A01, A101, A102, A103, A104, A105, A106, A107, A108, A109, A110, A112, A115, A116,
A117, A118, A119, A120, A121, A122, A123, A124, A125, A130_1, A130_2, A131_1,
A131_2, A140, N056, P004, P005, Q001, Q002, R003, R004, R005, R006, R007, R008,
R009, R010, R011, T005, T006, T010, T011, T021, T022, T023, T024, T030, T031, T032,
T035, T036, T041, T042, U103, U104, U105, U107, U109, U115, U116, U117, U118, V001,
ASA standard drawing format release, complete issue - V002, V060, V061, W008, W010, W011, W060, W061, W062, W063, W075, W076, W078,
Revision A W079, W080, W085, W086, W087, W088, W089_1, W089_2, W090, W091, W093, W094,
A 31/08/2018 ASA
(refer to T HR SC 00001 ST - Circuit Design Standard: W095, W097, W098, W099, W100, W101, W119, W120, W121, W122, W123, W124, X001,
Typical Circuits - Release Note) X003, X005, X006, X007, X014, X015, X023, X024, X025, X026, X029, X030, X031, X039,
X041, X042, X045, X051, X052, X053, X054, X055_1, X055_2, X056, X060, X100, X101,
X102_1, X102_2, X103_1, X103_2, X104_1, X104_2, X105, X106, X121_1,
X122_X123_Y001, Y002, Y003, Z001, Z002

Renumbered sheets:

A01 (previously A100), T006 (previously T120), X121_1 (previously X121)

Withdrawn sheets, moved to Legacy Circuits (Obsolete):

A141, Q010, T039, T040, W115, W116, X020, Z003


VERSION: 31/08/18 14:32 DRG No: CSTD0A01 SHEET TITLE: ASA STANDARD DRAWING INDEX EDMS No: SG0602002 SHEET No: A01 CIRCUIT BOOK No: 00001

CIRCUIT DESCRIPTION SHEET BOOK CIRCUIT DESCRIPTION SHEET BOOK

COVER SHEET A00 SIGNALS

CONTROL & OPERATING A101-A141

INDEX A01

TELEMETRY

DUPLINE FIELDBUS R003-R011

ALARMS

EARTH LEAKAGE Y003

FILAMENT AND LAMP FAILURE Y001 TRACKS

WARNINGS AND ALARMS Y002 TRACK CIRCUITS & INDICATIONS T005-T041

EMBANKMENT SLIP DETECTORS TRAIN STOPS

CONTROL, DETECTION & INDICATIONS V070-V073 CONTROL, OPERATING & DETECTION V001-V004

MISCELLANEOUS WARNING LIGHTS

AXLE COUNTER T042 CONTROL, OPERATING & PROVING V060-V061

CIRCUIT NOMENCLATURE Z001, Z002

LOCATION OF EARTHING Q001

MISC. - MONITORING APPLICATIONS Q002

SOLAR POWERED BUFFER STOPS Q010

ROUTE SETTING N056

LEVEL CROSSING

CONTROLS, OPERATING AND LIGHTING X001-X123

POINTS

CONTROLS, OPERATION & DETECTION W008-W124

POWER

DISTRIBUTION, CHANGEOVER & INDICATIONS U103-U118

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:34 DRG No: CSTDA101 SHEET TITLE: SIGNAL OPERATING - AUTO SIGNALLING - SINGLE LIGHT - WITHOUT TRAINSTOP EDMS No: SG0602002 SHEET No: A101 CIRCUIT BOOK No: 00001

153.1 154.3 155.5


151.9BT 153.1AT 153.1BT 154.3AT 154.3BT 155.5AT

+ R + R + R + R + R
151.9 153.1

153.1
153.1
153.1 LPM ECR
SIGNAL OPERATING 153.1
DR LOC SB SB LOC LOC
G B50 1 (5) 3
1B 1W
1 1 2 2 f 4A R1 R2

A1 A2 #

N50 2 (6) 4
(LOC)
153.1A 153.1 153.1 t

PSU LOC PR HR HR PSU


BX120 Y NX120
2B 2W (LOC)
f 4A A6 A5 3 3 4 4 1 2 t

A3 A4
A1 A2 A3 A4
ADJUST LPM TO DROP ECR RELAY
WHEN LAMP UNIT IS OUT

LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY


#
R WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4
3B 3W
A6 A5 5 5 6 6

LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY


WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6

LAMPS: LED
A6 A5
MAKE & MODEL:

153.1
ECR

PSU LOC LOC SB SB LOC PSU


BX120 R NX120
4B 4W (LOC)
f 4A A6 A5 7 1 2 8 t

153.1
HR

D6 D5

HR 153.1
HR
153.1A
PSU LOC 154.3A 154.3 153.1B 153.1B 153.1B 153.1 PR
B
153.1 153.1
TRACK STICK 153.1A f 4A R1 R2
HR DR PR B1 B2 B1 B2 B1 B2

PSU LOC 153.1A PSU PSU


B N N
f 4A D6 D5 D6 D5 R1 R2 t (LOC) (LOC) t

A1 A2 B4 B3 B4 B3

DR 153.1
DR
154.3 154.3 153.1
PSU LOC ECR HR 154.3 153.1 HR
B
A1 A2
f 4A R1 R2

A1 A2
B1 B2 C1 C2

PSU
N
(LOC) t

A4 A3
B4 B3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:34 DRG No: CSTDA102 SHEET TITLE: SIGNAL CONTROLS - AUTOMATIC (METROPOLITAN) - RELAY EDMS No: SG0602002 SHEET No: A102 CIRCUIT BOOK No: 00001

7.35 7.87 8.39

6.83 7.35
7.35AT 7.35BT 7.87AT 7.87BT 8.39AT

RX TX RX TX RX TX RX TX RX
NOTE : VR NOT REQUIRED FOR EP TRAIN STOPS

7.35 7.35
HR VR
7.87 7.35
LOC VCSR 7.87A 7.87 7.35B 7.35B 7.35B 7.35 7.35A LOC HR 7.35A
B B N
f 4A R1 R2 f 4A R1 R2 t (LOC)

A3 A4 A3 A4 A3 A4 A3 A4 B1 B2
B1 B2

N
(LOC) t

B4 B3 B4 B3 B4 B3

7.35
7.35
HDR C1 C3 C5 C7
7.87 7.87 7.35 7.35 7.35
LOC VRR HR 7.87 7.35 HR LOC VR 7.35 7.35 VR
B BX M NX
#1 #1 (LOC)
f 4A R1 R2 f 4A C2 C4 9 10 C6 C8 t

A1 A2 A3 A4 A1 A2

N
(LOC) t
#1 DENOTES 7/0.85mm

B2 B1 B4 B3 7.35
DR
7.87 7.35
FOR VNR/VRR CIRCUIT, SEE SHEET V002.
HDR HDR

R1 R2

A3 A4 A1 A2

B4 B3

# BACK PROVING REQUIRED OF ALL


# SIGNAL CONTROL RELAYS
EACH HDR TO BE INCLUDED FOR
CONTROLLED SIGNAL ROUTES WHERE SPLIT
7.35 7.35 7.35 7.35 7.87
HR HDR DR VCSR 7.35A VCSR
7.87
LOC 7.87A VNR 2 4
B N
B6 B5 B6 B5 B6 B5 D6 D5 R1 R2 f 4A 1 R1 R2 t (LOC)
1N4007
C1 C2 C1 C2

100W 1000mF
7.35A
EX RECEIVER 7.87 160V
10W
HR

A1 A2
3

C1 C2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:40 DRG No: CSTDA103 SHEET TITLE: SIGNAL OPERATING - AUTOMATIC (METROPOLITAN) DOUBLE LIGHT EDMS No: SG0602002 SHEET No: A103 CIRCUIT BOOK No: 00001

LAMPS: LED
SIGNAL OPERATING MAKE & MODEL:
7.35

7.35 7.35
PSU LOC VRR HR LOC SB SB LOC PSU
BX G NX
1B 1W 1 (LOC)
f 4A 1 1 2 2 t

D1 D2 D1 D2

R
3B 3W 3
D6 D5 5 5 6 6

D6 D5

7.35
DR LOC SB SB LOC
G
4B 4W 4
7 1 2 8

D1 D2

7.35
HDR
Y
5B 5W 5
D6 D5 9 3 4 10

D1 D2

R
6B 6W 6
D6 D5 11 5 6 12

D8 D7

PSU LOC
BX
f 4A D8 D7

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:42 DRG No: CSTDA104 SHEET TITLE: SIGNAL CONTROLS - AUTOMATIC (CITY) - RELAY EDMS No: SG0602002 SHEET No: A104 CIRCUIT BOOK No: 00001

2.13 2.29 2.41 2.45

1.97AT 1.97BT 2.13AT 2.13BT 2.29AT 2.41AT 2.45AT 2.45BT

2.13 L Sp 2.29 L Sp(COND) 2.41 L Sp(COND)


ALL RELAYS IN LOCATION AT STATION
1.97 CAUT 2.29 L Sp
CIRCUITS BETWEEN STATIONS DOUBLE SWITCHED
1.97B 1.97B 2.13 CAUT

DPU DPU 1.97 MED


LOW SPEED (LSpR) INCL
1.97 TRACK RELAYS
JR(1) JR(2) LSpR
2.13 DPU 1.97B
PSU LOC VCSR 2.13A 1.97B 1.97A PSU DPU
B N
f 4A D6 D5 D6 D5 R1 R2 t (LOC)

A3 A4 A3 A4 A3 A4 A3 A4
R1 R2

2.13B 2.13B 2.13B 2.13 EX RECEIVER


INCL JR(1) JR(2) JR(3) LSpR
2.29 DPU
PSU LOC VCSR 2.29A 2.13B 2.13A PSU
B N
f 4A D6 D5 D6 D5 D6 D5 R1 R2 t (LOC) 1.97B

A3 A4 A3 A4 A3 A4 A3 A4

R1 R2
2.29A 2.29A 2.29A
DPU DPU DPU EX RECEIVER A1 A2
2.29
JR(1) JR(2) JR(3) INCL
LSpR
2.41 DPU
PSU LOC VCSR 2.45A 2.41A 2.29A PSU
B N
(LOC) #
f 4A D6 D5 D6 D5 D6 D5 R1 R2 t

A3 A4 A3 A4 A3 A4 A3 A4

2.13B 2.13 2.13 2.13 2.13 2.13


# BACK PROVING REQUIRED OF ALL
JR(3) SIGNAL CONTROL RELAYS LSpR HR HDR DR VCSR 2.13A

CAUTION (HR) C1 C2 2.13 D6 D5 D6 D5 D6 D5 D6 D5 D6 D5 R1 R2

HR 2.13A
2.29 2.13
PSU LOC LSpR LSpR PSU EX RECEIVER
B N
(LOC) A1 A2
f 4A R1 R2 t

A1 A2 A1 A2 2.13
HDR
2.29 2.13
HR HR 2.13B
L.YELLOW (HDR)
R1 R2

A1 A2 A1 A2 2.13 R1 R2

DR EX RECEIVER
2.29 2.29 2.13
HDR VRR HDR
L.GREEN (DR)
R1 R2

A1 A2 A1 A2 A1 A2

2.13V
TRAIN STOP (V)
2.13 2.13 2.13 2.13
PSU LOC HDR LSpR 2.13A LOC LOC 2.13A LSpR HDR PSU
B N
f 4A 9 10 t (LOC)
EP
B1 B2 B3 B4
B1 B2 B1 B2 B3 B4 B3 B4
1.97B 1.97B
DPU 2.13 2.13 DPU
JR(1) HR HR JR(1)

FOR VNR/VRR CIRCUIT, SEE SHEET V002.

C1 C2 B1 B2 B3 B4 C3 C4

1.97B 1.97B
DPU DPU
JR(2) JR(2)

C1 C2 C3 C4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:42 DRG No: CSTDA105 SHEET TITLE: SIGNAL OPERATING - AUTOMATIC (CITY) - DOUBLE LIGHT EDMS No: SG0602002 SHEET No: A105 CIRCUIT BOOK No: 00001

SIGNAL OPERATING
2.13

2.13 2.13
PSU LOC LSpR HR LOC SB SB LOC PSU
BX G NX
1B 1W 1 (LOC)
f 4A 1 1 2 2 t

A3 A4 A3 A4

R
3B 3W 3
A6 A5 5 5 6 6

A6 A5

2.13
DR
2.13 2.13
HDR VRR LOC SB SB LOC
Y
4B 4W 4
A8 A7 7 7 8 8

A3 A4 A3 A4

R
5B 5W 5
A8 A7 9 9 10 10

G
6B 6W 6
A8 A7 11 11 12 12

A3 A4

PSU LOC
LAMPS: LED
BX
MAKE & MODEL:
f 4A A8 A7

2.13
LOC SB SB LOC LSpR PSU
G NX
7B 7W (LOC)
D6 D7 13 13 14 14 t

A1 A2

1.97B
1.97B
TIME LIMITS (JR) DPU
DPU
JR(1)
PSU LOC PSU
B R1 R2 N
f 4A D6 D5 t (LOC)

TIMER
SETTINGS XX"

QTD5

1.97B
DPU
JR(2)

R1 R2

TIMER
SETTINGS XX"

QTD5

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:34 DRG No: CSTDA106 SHEET TITLE: SIGNAL CONTROLS - AUTOMATIC (CITY) - CONDITIONAL CLEARING EDMS No: SG0602002 SHEET No: A106 CIRCUIT BOOK No: 00001

RX TX
2BT RX TX
2AT RX TX
3BT RX TX
3AT RX TX
4BT RX TX
4AT RX TX

3 3 COND. 4 5

1 2 3 4

3BT 3
JR HR
2 2BT
PSU LOC VCSR 2AT 2 3B 3BT 3B 3 3AT PR
B
f 4A D6 D5 R1 R2

C1 C2 C1 C2 C1 C2 C1 C2 C1 C2

4BT
JR

C1 C2

PSU
N
(LOC) t D7 D8

C4 C3 C4 C3 C4 C3

THIS RELAY IS TO BE USED FOR


DIAGRAM INDICATIONS IF PROVIDED 2BT
IN LIEU OF 2BT TRACK RELAY PR

PSU LOC 2BT 2B 2 3B 3B 3


B
f 4A R1 R2

D1 D2

PSU
N
(LOC) t

D4 D3

2BT
PPR
2BT
PSU LOC PR 3 3B 2 2B 1 RR
B
f 4A R1 R2

D1 D2

PSU
N
(LOC) t
IF 2BT IS REQUIRED FOR APPROACH LOCKING/DIAGRAM AT
D4 D3 AN INTERLOCKING AHEAD, CIRCUIT IS TO COME OFF CONDITIONAL
RES

CLEARING PR TO PROVIDE DIAGRAM SUPERVISION OF


OTHERWISE UNPROVED RELAYS

4BT
4BT 4BT
JR
PSU LOC 4B 3 3 4B PSU
B R1 R2 N
f 4A A8 A7 A8 A7 t (LOC)

TIMER
SETTINGS XX"

QTD5

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:34 DRG No: CSTDA107 SHEET TITLE: SIGNAL CONTROLS - INSUFFICIENT BRAKING DISTANCE - WITHOUT TRAINSTOP EDMS No: SG0602002 SHEET No: A107 CIRCUIT BOOK No: 00001

'P'
1 3 155.5
151.9BT 1AT + R
1BT R 3AT + R
3BT 155.5AT

+ R 151.9 + 1 + R

R
3XT

CLEAR (1 DR) 1
DR
3 3(M)A 1
PSU LOC ECR HR 3 1 HR
B
f 4A R1 R2

A1 A2
B1 B2 C1 C2

PSU
N
(LOC) t

A4 A3
B4 B3

1
MEDIUM (1 HDR) HDR
3(M)B 3(M)B 1
ECR HR 3 1 HR

R1 R2

A1 A2 B1 B2 C3 C4

A4 A3 B4 B3

MEDIUM (1 HDR)
(LESS THAN SERVICE BRAKING DISTANCE
1
BETWEEN SIGNALS 3 AND 155.5)
HDR
3 3(M)A 1
PSU LOC ECR HR 3 1 HR
B
f 4A R1 R2

D1 D2
C1 C2 C3 C4

3(M)B 3(M)B
ECR HR

A1 A2 B1 B2

3 3(M)A
PSU ECR HR
N
(LOC) t

D4 D3
C4 C3

3(M)B 3(M)B
ECR HR

A2 A1 B4 B3
CLEAR (1 DR)
(LESS THAN SERVICE BRAKING DISTANCE
1
BETWEEN SIGNALS 3 AND 155.5)
DR
3(M)A 1
PSU LOC HDR 3 1 HDR
B
f 4A R1 R2

B1 B2 C1 C2

PSU
N
(LOC) t

B4 B3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:34 DRG No: CSTDA108 SHEET TITLE: SIGNAL OPERATING - SINGLE LIGHT - MEDIUM ASPECT EDMS No: SG0602002 SHEET No: A108 CIRCUIT BOOK No: 00001

1
1
1 LPM ECR
SIGNAL OPERATING 1
DR LOC SB SB LOC LOC
G B50 1 (5) 3
1B 1W
1 1 2 2 f 4A R1 R2

A1 A2 #
1
N50 2 (6) 4
HDR
(LOC)
1AT 1 1 t

PSU LOC PR HR HR PSU


BX120 Y NX120
2B 2W (LOC)
f 4A A6 A5 A6 A5 3 3 4 4 1 2 t

A3 A4 1
A1 A2 A3 A4
#2 FOLLOWING TIMER
HDFR ADJUST LPM TO DROP ECR RELAY
FAILURE, SIGNAL
WHEN LAMP UNIT IS OUT
ASPECT MAINTAINED
AT CAUTION #2
(STEADY YELLOW)
4 1
R QSR3 SLOW RELEASE 330 ms
3B 3W
A6 A5 5 5 6 6
MEDIUM ASPECT 200 ms LAMP OFF

LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY


#
LAMPS: LED WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4
MAKE & MODEL:
A6 A5 5 8
LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY
1
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6
HR

PSU LOC LOC SB SB LOC PSU


BX120 R NX120
4B 4W (LOC)
f 4A A8 A7 7 1 2 8 t

1
ECR

A6 A5

#1 PROVIDED TO EXTEND UNESSESARY TIMER OPERATION AND FOR ISOLATION

1 #1 1
DR HDFR
1
PSU LOC HDR T OFF = 640 ms
BX120 2 T ON = 200 ms
f 4A D6 D5
OMRON
C1 C2 COVER TYPE - Y92A - 48B
H3CR-F8
BASE - PLUG-IN TYPE P2CF-08
PSU
NX120 7 RESISTOR - 800 OHM 30w
(LOC) t D7 D8 PULSE RATE REQUIRED - 70 FLASHES PER MINUTE

C4 C3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:34 DRG No: CSTDA109 SHEET TITLE: SIGNAL OPERATING - SINGLE LIGHT (COUNTRY) - BAND OF LIGHTS (PULSATING) EDMS No: SG0602002 SHEET No: A109 CIRCUIT BOOK No: 00001

'P'

1 3 155.5
151.9BT 1AT + R
1BT R
3AT + R
3BT 155.5AT

+ R 151.9 + 1 + R

R
3XT

3
3 3 LPM ECR

LOC
3(M)A
B50 1 (5) 3
DR LOC SB SB LOC
f 4A R1 R2
G
1B 1W
SIGNAL OPERATING 1 1 2 2 #
A1 A2
N50 2 (6) 4
(LOC)
3AT 3(M)A 3(M)A t

PSU LOC PR HR HR PSU


BX120 Y NX120
2B 2W (LOC)
f 4A A6 A5 3 3 4 4 1 2 t

A3 A4
A1 A2 A3 A4

ADJUST LPM TO DROP ECR RELAY


WHEN LAMP UNIT IS OUT

R
3B 3W
A6 A5 5 5 6 6

LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY


#
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4

LAMPS: LED
A6 A5 MAKE & MODEL: LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6
3(M)B
HR

PSU LOC LOC SB SB LOC PSU


BX120 R NX120
3(M)B 4B 4W (LOC)
f 4A A8 A7 A8 A7 7 7 8 8 t
HDR
3 3(M)B 3AT
ECR HR PR PSU
Y NX120
5B 5W (LOC)
A6 A5 11 9 10 12 1 2 t

3(M)B D3 D4 PSU LOC


A6 A5 D3 D4
HDFR Y B50 1 (5) 3
15 3 4 16 f 4A 3(M)B
#
PSU LOC
#2 *2 ECR
BX120 Y
*1 PSU
f 4A 4 1 17 11 12 18
N50 2 (6) 4
D1 D2 (LOC)
D1 D2 t R2 R1
#2 FOLLOWING TIMER
FAILURE, TURNOUT 3(M)B
ASPECT MAINTAINED
5 8 AT CAUTION TURNOUT LPM
(STEADY BOL)

*2 LPM SHOULD BE ADJUSTED


#1 FOLLOWING LAMP FAILURE, SIGNAL *1 ONE OF THE DROP CONTACTS OF H3CR-F8 RELAY SUCH THAT ECR IS DE-ENERGISED
MAINTAINED AT THE MOST MAY BE ALLOCATED TO DRIVE CO-ACTING ONLY WHEN ALL LAMPS ARE OUT
RESTRICTIVE ASPECT SIGNAL WHERE NECESSARY

3(M)B
#1 HDFR
3 3(M)B INITIAL SETTING
PSU LOC ECR HDR T OFF = 640 ms SIGNAL AHEAD
BX120 2
T ON = 200 ms
f 4A 3(M)B
PULSE RATE REQUIRED 68 - 72 PER MIN
OMRON
D3 D4
C1 C2
HDR
3(M)B
H3CR-F8
PSU COVER TYPE - Y92A - 48B PSU LOC HR ECR LOC LOC HR
NX120 7 BASE - PLUG-IN TYPE P2CF-08 B50
(LOC) t f 4A R1 R2
RESISTOR - 800 OHM 70w
B1 B2
C4 C3 B1 B2 B1 B2

PSU
N50
(LOC) t

B4 B3
B4 B3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:34 DRG No: CSTDA110 SHEET TITLE: SIGNAL OPERATING - SHUNT SIGNAL EDMS No: SG0602002 SHEET No: A110 CIRCUIT BOOK No: 00001

SIGNAL OPERATING

'X' SHUNT UG

A 'DM' SUGE
PSU LOC HR LOC SH SH LOC NX PSU
BX120 W NX120
4B 4W 1 (LOC)
f 4A 7 8 t

D3 D4

B 'DR'
HR
W
5B 5W 2
9 10

D3 D4

LAMPS: LED
MAKE & MODEL:

A B 'X' SHUNT
HR HR
SGE
PSU LOC LOC SH SH LOC NX PSU
BX120 R NX120
1B 1W 1 (LOC)
f 4A D6 D5 D6 D5 1 2 t

Y
2B 2W 2
3 4

D1 D2

D1 D2

PSU LOC
BX120 R
3B 3W 3
f 4A D8 D7 D8 D7 5 6

LAMPS: LED
MAKE & MODEL:

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA112 SHEET TITLE: SIGNAL OPERATING - DOUBLE LIGHT EDMS No: SG0602002 SHEET No: A112 CIRCUIT BOOK No: 00001

29 29(M)B
CD CD VRR HR
BX120
SIG LTS f 4A

A3 A4 D1 D2

29(M)C
HR

29
D1 D2 29(M)A 29(M)C
HR HR
29(M)A
HR LOC SB SB LOC PSU
G NX120
1B 1W 1 (LOC)
B8 B7 B8 B7 1 1 2 2 t

D1 D2 29(M)B
HR

Y
2B 2W 2
B8 B7 3 3 4 4

R
3B 3W 3
D8 D7 D8 D7 D8 D7 5 5 6 6

A6 A5 LAMPS: LED
MAKE & MODEL:

29
DR LOC SB SB LOC
G
4B 4W 4
7 1 2 8

D1 D2

29
HDR
Y
5B 5W 5
D6 D5 9 3 4 10

D1 D2

R
6B 6W 6
D6 D5 11 5 6 12

29(M)A 29(M)B 29(M)C


HR HR HR

D6 D5 D6 D5 D6 D5

CD CD
BX120
SIG LTS f 4A A8 A7

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA115 SHEET TITLE: SIGNAL OPERATING - DOUBLE LIGHT - PRELIMINARY MEDIUM ASPECT EDMS No: SG0602002 SHEET No: A115 CIRCUIT BOOK No: 00001

SIGNAL OPERATING
LAMPS: LED
MAKE & MODEL:
1

1 1
PSU LOC VRR HR LOC SB SB LOC PSU
BX G NX
1B 1W 1 (LOC)
f 4A 1 1 2 2 t

D1 D2 D1 D2

R
3B 3W 3
D6 D5 5 5 6 6

D6 D5

1
DR LOC SB SB LOC
G
4B 4W 4
7 1 2 8

D1 D2

1
PHDR
1
HDR
Y
5B 5W 5
D6 D5 A6 A5 9 3 4 10

D1 D2 1
HDFR

4 1

R
6B 6W 6
D6 D5 11 5 6 12

5 8

D8 D7

PSU LOC
BX
f 4A D8 D7

1 1
DR HDFR
1
PSU LOC PHDR T OFF = 640 ms
BX120 2 T ON = 200 ms
f 4A A6 A5
OMRON
C1 C2 COVER TYPE - Y92A - 48B
H3CR-F8
BASE - PLUG-IN TYPE P2CF-08
PSU
NX120 7 RESISTOR - 800 OHM 30w
(LOC) t A7 A8 PULSE RATE REQUIRED - 70 FLASHES PER MINUTE

C4 C3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA116 SHEET TITLE: INTERMEDIATE T.STOPS - TRAINSTOP CONTROL - APPROACHING CATCHPOINTS EDMS No: SG0602002 SHEET No: A116 CIRCUIT BOOK No: 00001

DISTANCES
8
6AT G

A A- BRAKING DISTANCE GE52A @ 35Km/hr (80m LEVEL)


51B
B- BRAKING DISTANCE GE52A @ 20Km/hr (30m LEVEL)
DPU(2) DPU(1)
51A TX 10BT RX 10AT 18CT
X- 33m (20Km/hr, 6sec)

20
10
6 10 Y- 17m (10Km/hr, 6sec)
G ITS(2) ITS(1) G

B Y X

10BT 10BT 10BT


ITS(1) 10BT 10BT
DPU1 DPU2
VR DPU1 DPU2
10BT JR JR
PSU LOC HR DPU2 PSU PSU LOC PSU PSU LOC PSU
B50 N50 B50 R1 R2 N50 B50 R1 R2 N50
f 4A R1 R2 t (LOC) f 4A A6 A5 t (LOC) f 4A A6 A5 t (LOC)
A1 A1
C1 C2
C1 C2
B7 B7
6(S)
B8 B8
HR 5" 5"
A8 A8

C5 C6 C5 C6
C1 C2 10BT
10BT PR QTD5 QTD5
10BT
DPU(1)
JPR(2)
JR
D6 D5

C1 C2
C1 C2

10BT
ITS(1)
VR

C1 C2

NOTE: 10BT JR(1) WOULD BE USR TIMER

10BT
ITS(2) 10BT 10BT
VR JR (2) JPR(2)
6(M)
PSU LOC HR 6AT PSU PSU LOC
B50 N50 B12 1 3 R1 R3
f 4A R1 R2 t (LOC) f 4A R1 R2

C3 C4 PSU
C3 C4
N12 2 4 R2 R4
(LOC)
6(S) 51* t
RETURNS ITS TO NORMAL IF
HR NKR 12V REGULATOR 10BT DOWN AND 6 SIGNAL
NORMAL 120 sec OR MORE

10BT
C3 C4 10BT D1 D2 PR
D3 D5
10BT PR
DPU(2)
10BT *THIS QUALIFICATION ONLY
REQUIRED IF 51 POINTS LOCAL TRACK
A7 A8

JPR(2) D1 D2
JR IS OCCUPIED BY ANOTHER
D4 D6
SIGNALLED MOVEMENT VIA
D8 D7 6
51 POINTS NORMAL
C3 C4
NGPR
C3 C4
A1 D1 STRAPPING FOR
10BT
50V RELAY
ITS(2) A2 D2
A6 A5
VR A3 D7

A7 D8
120"
C3 C4

QTD4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA117 SHEET TITLE: ROUTE/SIGNAL CONTROLS-INTERMEDIATE T.STOPS-TRAIN APPROACH CATCHPOINT EDMS No: SG0602002 SHEET No: A117 CIRCUIT BOOK No: 00001

10
10 10BT LSp
TZR JR(1) UCR
10 10AT 10BT 10
PSU LOC SR 1PR 1PR 6AT RUR PSU
B50 N50
f 4A A6 A5 D6 D5 R1 R2 t (LOC)

B1 B2 B1 B2 B1 B2 B1 B2
A1 A2

51 10 LSp UCR UP STARTS SIGNAL


10BT 10 REPEATER FLASHING GREEN
NWKR CAUTION OVERLAP UCR
ITS 6(M) LSp UNTIL RGKR ENERGISES TO
VRR UCR UCR GIVE STEADY GREEN REPEATER

B1 B2
R1 R2

B1 B2 B1 B2 A1 A2

6(S)
UCR

B1 B2

10BT 10BT
10 10 10 10 DPU(1) DPU(2) 10
NGPR ALSR ALSJR USR 10BT 10 JR JR LSpR
18CT ITS LSp
PSU LOC JR VNR UCR LOC LOC LOC LOC
B50(EXT)
f 4A D6 D5 A6 A5 D6 D5 D6 D5 D6 D5 D6 D5 R1 R2

C1 C2 B1 B2 A1 A2

6(M)
UCR

B1 B2

6(S)
UCR

B1 B2

10BT
ITS 18CT
PSU VNR JR
N50(EXT)
(LOC) t D7 D8 D7 D8 D7 D8 D7 D8 D7 D8 D7 D8

B4 B3 C4 C3

6(M)
UCR

B3 B3

6(S)
UCR

B4 B3 10
HR
10 10
UCR LOC LOC LSpR

R1 R2

A1 A2 A1 A2

A4 A3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA118 SHEET TITLE: INTERMEDIATE TRAINSTOP DETECTION - APPROACH CATCHPOINTS EDMS No: SG0602002 SHEET No: A118 CIRCUIT BOOK No: 00001

10BT ITS(1) CIRCUIT 10BT ITS(2) CIRCUIT


CONTROLLER CONTROLLER

SW1 SW2 SW1 SW2 10BT ITS 10BT ITS


VRR VNR

PSU LOC LOC RSA RSA LOC LOC RSA RSA LOC PSU
N-RI N N-RI N
B50(EXT) N50(EXT)
f 4A 1 7 8 1 2 2 1 7 8 1 2 2 A8 A7 R2 R4 t (LOC)

N-RI N N-RI N

3 3 4 5 6 4 3 3 4 5 6 4

10BT ITS 10BT ITS


VNR VRR
R R-NI R R-NI

5 6 3 4 5 6 3 4
6 5 6 5 D8 D7 R1 R3

R R-NI R R-NI

1 2 7 8 1 2 7 8
8 7 8 7

(ENCAPSULATED)

V CIRCUIT CONTROLLERS

(WITH RSA STUDS)

DRAWN WITH ARM IN THE NORMAL RAISED POSITION

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:41 DRG No: CSTDA119 SHEET TITLE: SIGNAL OPERATING - DOUBLE LIGHT (TRI-COLOUR) - TURNOUT ROUTE EDMS No: SG0602002 SHEET No: A119 CIRCUIT BOOK No: 00001

10(M)A 10(M)A
HR HR
10 10(M)A 10(M)A 10
PSU LOC VRR HR LOC SB 10 SB LOC HR VRR
BX120
f 4A D6 D5
1B 1 2
1W C8 C7

A1 A2 D1 D2 D3 D4 A3 A4

10(M)B 10(M)B
1 2
HR G HR
10(M)B 10(M)B
Y
HR HR
R
D6 D5
2B 3 3 4 4
2W C8 C7

D1 D2 D3 D4

5 6

3B 3W
D8 D7 D8 D7 5 * 6

A6 A5

10 10
DR LOC SB SB LOC DR

4B 7 8
4W

D1 D2 D3 D4

1 2
G
10(M) 10(M)
Y
HDR HDR
R
D6 D5
5B 9 3 4 10
5W D8 D7

D1 D2 D3 D4 PSU
NX120
t (LOC)
5 6

6B 6W
D6 D5 11 * 12

10(M)A 10(M)B
HR HR

* FOR ALSTOM THE LINK BAR FITTED


C6 C5 C6 C5 BETWEEN TERMINALS 4.5 AND 6 TO BE REMOVED.

10
VRR

PSU LOC
BX120
f 4A A8 A7

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA120 SHEET TITLE: SIGNAL OPERATING - DOUBLE LIGHT (TRI-COLOUR) EDMS No: SG0602002 SHEET No: A120 CIRCUIT BOOK No: 00001

PSU LOC VRR HR LOC SB XX SB LOC HR VRR


BX120
f 4A
1B 1 2
1W

A3 A4 D1 D2 D3 D4 A3 A4

1 2
G
Y

5 6

D6 D5
3B 5 * 6
3W

D6 D5

DR LOC SB SB LOC DR

4B 7 8
4W

A3 A4 D1 D2

1 2
G
Y
HDR HDR
R
A6 A5
5B 9 3 4 10
5W D6 D5

D1 D2 D3 D4 PSU
NX120
t (LOC)
5 6

6B 6W
D6 D5 11 * 12

* FOR ALSTOM THE LINK BAR FITTED


D8 D7 BETWEEN TERMINALS 4, 5 AND 6 TO BE REMOVED.

PSU LOC
BX120
f 4A D8 D7

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA121 SHEET TITLE: SIGNAL OPERATING - SINGLE LIGHT (TRI-COLOUR) - DOUBLE SWITCHED EDMS No: SG0602002 SHEET No: A121 CIRCUIT BOOK No: 00001

LPM ECR
FULL DOUBLE SWITCHED
DR LOC SB XX SB LOC DR LOC
B50 1 (5) 3
1B 1 2
1W f 4A R1 R2

A1 A2 A3 A4 #

1 2
N50 2 (6) 4
G (LOC) t
Y
VRR HR HR VRR PSU
R NX120
A6 A5
2B 3 3 4 4
2W A8 A7 1 2 t (LOC)

D1 D2 D1 D2 D3 D4 D3 D4

5 6

D6 D5
*

HR

PSU LOC
BX120
f 4A D6 D5
3B 5 6
3W

LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY


#
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4
* FOR ALSTOM THE LINK BAR FITTED
BETWEEN TERMINALS 4, 5 AND 6 TO BE REMOVED.
LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6

LPM ECR

PARTIAL DOUBLE SWITCHED DR LOC SB XX SB LOC


B50 1 (5) 3
1B 1 2
1W f 4A R1 R2

A1 A2 #

1 2
N50 2 (6) 4
G (LOC) t
Y
VRR HR LOC HR VRR PSU
R NX120
A6 A5
2B 3 3 4 4
2W 1 2 t (LOC)

D1 D2 D1 D2 D3 D4 D3 D4

5 6

D6 D5
*

HR

PSU LOC
BX120
f 4A D6 D5
3B 5 6
3W

* FOR ALSTOM THE LINK BAR FITTED


BETWEEN TERMINALS 4, 5 AND 6 TO BE REMOVED.

N.B. THE PARTIAL DOUBLE SWITCHED ARRANGEMENT IS ONLY TO BE USED


IN EXISTING SIGNALS WHERE CABLE CORES DO NOT PERMIT FULL
DOUBLE SWITCHING

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA122 SHEET TITLE: SIGNAL CONTROLS - AUTOMATIC - WORKSITE PROTECTION EDMS No: SG0602002 SHEET No: A122 CIRCUIT BOOK No: 00001

METROPOLITAN/COUNTRY

RX TX
2BT RX TX
2AT RX TX
3BT RX TX
3AT RX TX
4BT RX TX
4AT RX TX
5BT

3 3 COND. 4 4 COND.

1 2 3 4
#SKS

3 #SKS - DENOTES SIGNAL KEY SWITCH

SKS OPERATIONAL SAFEWORKING USE OF SKS IS TO BE DETERMINED


BY THE PROTECTION OFFICER USING NETWORK RULES
3 KEY WARDINGS, INSCRIPTIONS AND SKS BOX SIGNAGE

GZR WORDING TO BE SHOWN ON SIGNALLING PLAN

PSU LOC LOC LOC


B50(EXT)
f 4A R1 R2

PSU
N50(EXT)
(LOC) t #1 ONLY PROVIDED WHERE ADDITIONAL SIGNAL
PROTECTION REQUIRED

4BT 4
JR HR
3 3BT 3
PSU LOC VCSR 3AT LOC LOC 4BT LOC LOC 4AT PR GZR
B50
#1 #1
f 4A D6 D5 R1 R2

C1 C2 C1 C2 C1 C2 B1 B2 C1 C2 A3 A4 #1
5BT
JR

C1 C2

PSU
N50
(LOC) t D7 D8

C4 C3 C4 C3 C4 C3

3BT 3
JR HR
2 2BT 3
PSU LOC VCSR 2AT LOC LOC 3BT LOC LOC 3AT PR GZR
B50
f 4A D6 D5 R1 R2

C1 C2 C1 C2 C1 C2 B1 B2 C1 C2 A1 A2
4BT
JR

C1 C2

PSU
N50
(LOC) t D7 D8

C4 C3 C4 C3 C4 C3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA123 SHEET TITLE: SIGNAL CONTROLS - AUTOMATIC - WORKSITE PROTECTION EDMS No: SG0602002 SHEET No: A123 CIRCUIT BOOK No: 00001

CITY UNDERGROUND

STATION A #SKS STATION B


2.13 A 2.29 A 2.41 A 2.45 A

1.97AT 1.97BT 2.13AT 2.13BT 2.29AT 2.41AT 2.45AT 2.45BT

1.97 LSp 2.13 LSp 2.29 LSp(COND) 2.41 LSp(COND)


ALL RELAYS IN LOCATION AT STATION.
1.97 CAUT 2.29 LSp
CIRCUITS BETWEEN STATIONS DOUBLE SWITCHED

2.13B 2.13B 2.13B 2.13


INCL JR(1) JR(2) JR(3) LSpR
2.29 DPU 2.13
PSU LOC VCSR 2.29A 2.13A 2.13B GZR PSU
B50 INCL N50
f 4A D8 D7 D8 D7 D8 D7 R1 R2 t (LOC)

B1 B2 B1 B2 A3 A4 A3 A4 A1 A2

2.13
SKS

2.13
GZR

PSU LOC LOC LOC PSU LOC GZR IASS (IF PROVIDED)
B50(EXT) B50
f 4A R1 R2 f 4A

A1 A2

PSU
N50(EXT)
(LOC) t
#SKS - DENOTES SIGNAL KEY SWITCH
OPERATIONAL SAFEWORKING USE OF SKS IS TO BE DETERMINED
BY THE PROTECTION OFFICER USING NETWORK RULES
KEY WARDINGS, INSCRIPTIONS AND SKS BOX SIGNAGE
WORDING TO BE SHOWN ON SIGNALLING PLAN
COUNTRY - CODED TRACKS

#SKS
167.3 170.1 173.6
167.3AT SKS 170.1AT 173.6AT

CS CM CS CM CS CM CS

OVERLAP

2.13
SKS

PSU LOC LOC LOC


B50(EXT)
f 4A

MICROLOK
INPUT

PSU
N50(EXT)
(LOC) t

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA124 SHEET TITLE: SIGNAL OPERATING - AUTOMATIC (CITY) - CO-ACTING LED EDMS No: SG0602002 SHEET No: A124 CIRCUIT BOOK No: 00001

LAMPS: LED
XX
SIGNAL OPERATING MAKE & MODEL:

PSU LOC LSpR HR LOC JB # # # JB PSU


BX120 G NX120
1 1B 1W 2 (LOC)
f 4A 1 2 t

1B 1W
A3 A4 A3 A4

R
5 3B 3W 6
5 6

3B 3W
A6 A5

DR
A6 A5

HDR VRR
Y
7 4B 4W 8
A8 A7 7 8

4B 4W
A3 A4 A3 A4

R
9 5B 5W 10
A8 A7 9 10

5B 5W

G
11 6B 6W 12
A8 A7 11 12

PSU LOC 6B 6W
A3 A4
BX120
f 4A A8 A7

LOC LSpR PSU


G NX120
13 7B 7W 14 (LOC)
D6 D5 13 14 t

7B 7W
A1 A2

CO-ACTING

#
G
1 2

DEPENDENT ON MANUFACTURER / SUPPLIER,


R #
TERMINALS MAY BE PROVIDED INSIDE THE
5 6
SIGNAL HEAD IN LIEU OF A SIGNAL BASE/
JUNCTION BOX

Y
7 8

R
9 10

G
11 12

G
13 14

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA125 SHEET TITLE: SIGNAL OPERATING - SINGLE LIGHT (METROPOLITAN) - OUTER JCT SIGNAL EDMS No: SG0602002 SHEET No: A125 CIRCUIT BOOK No: 00001

'P'
1 3 155.5
151.9BT 1AT + R
1BT R
3AT + R
3BT 155.5AT

+ R + + R
151.9 1

R
3XT

1
1
1 LPM ECR
1
DR LOC SB SB LOC LOC
G B50 1 (5) 3
1B 1W
SIGNAL OPERATING 1 1 2 2 f 4A R1 R2

A1 A2 #
1
N50 2 (6) 4
HDR
(LOC) t
1 1 1
PSU LOC VRR HR HR PSU
BX120 Y NX120
2B 2W (LOC)
f 4A A6 A5 A6 A5 3 3 4 4 1 2 t

A3 A4 A1 A2 1 A3 A4
HDFR ADJUST LPM TO DROP ECR RELAY
WHEN LAMP UNIT IS OUT

4 1
LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY
R #
3B 3W WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4
A6 A5 5 5 6 6

LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY


5 8 WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6
LAMPS: LED

A6 A5 MAKE & MODEL:

1
HR

PSU LOC LOC SB SB LOC PSU


BX120 R NX120
4B 4B (LOC)
f 4A D8 D7 7 1 2 8 t

1
ECR

A6 A5

1
VRR

A8 A7

1 HDFR 1 1
DR HDFR
1
PSU LOC HDR T OFF = 640 ms
BX120 2 T ON = 200 ms
f 4A D6 D5
OMRON
C1 C2 COVER TYPE - Y92A - 48B
H3CR-F8
BASE - PLUG-IN TYPE P2CF-08
PSU
NX120 7 RESISTOR - 800 OHM 30w
(LOC) t D7 D8 PULSE RATE REQUIRED - 70 FLASHES PER MINUTE

C4 C3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA130_1 SHEET TITLE: SIGNAL CONTROLS - TURNOUT REPEATER - CONTROL RELAYS EDMS No: SG0602002 SHEET No: A130_1 CIRCUIT BOOK No: 00001

SUFFICIENT DISTANCE TO REDUCE


FROM LINE SPEED TO TURNOUT SPEED 155.5

3
3AT 1 3BT 155.5AT
151.9 1
R2 R + R

151.9AT 151.9BT 1AT 151.9 1BT 1 3XT

+ R + R + R + R + + R1 R + R

MEDIUM (1 HDR) 1
HDR
1JP 1(3A)
PSU LOC ECR HDR PSU
B50 N50
f 4A R1 R2 t (LOC)

C1 C2 C1 C2

1(3B)
NOTE:
HDR
# MAY ALSO BE REQUIRED FOR ETCS INTERFACE,
TURNOUT ROUTE CONTROL RELAYS OR
SIGNAL INFORMATION IN ADVANCE, SHALL
BE USED AS APPLICABLE
C1 C2 NAMING CONVENTION SHALL FOLLOW LOGIC
IDENTIFIED IN ESG 100.1
MEDIUM 1 (3A) HDR 1(3A)
HDR #
3 3(M)A 1(M) 3(M)A 3
PSU LOC VRR HR LOC LOC HR LOC LOC HR VRR PSU
B50 N50
f 4A R1 R2 t (LOC)

A1 A2 A1 A2 C3 C4 A3 A4 A3 A4

1(3B)
HDR #
3(M)B 1(M) 3(M)B
HR HR HR
MEDIUM 1 (3B) HDR
R1 R2

A1 A2 C1 C2 A3 A4

1
DR
3 1 3
CLEAR (1 DR) HDR HDR HDR

R1 R2

A1 A2 C1 C2 A3 A4

MEDIUM (151.9 HDR) 151.9


HDR
1 1(M) 151.9 1(M) 1
PSU LOC VRR HR LOC LOC HR LOC LOC HR VRR PSU
B50 N50
f 4A R1 R2 t (LOC)

A1 A2 A1 A2 C1 C2 A3 A4 A3 A4

151.9(3B)
CLEAR (WITH STRAIGHT 1 1(3B) 151.9
DR #
1(3B) 1
HDR HDR HDR HDR HDR
ROUTE SET) 151.9(3B) DR
R1 R2

A1 A2 A1 A2 C1 C2 A3 A4 A3 A4

151.9(3A) 151.9
CLEAR (WITH TURNOUT DR # DR
1(3A) 151.9 1(3A) 151.9(3A)
ROUTE SET) 151.9B (3A) DR HDR HDR HDR PSU LOC DR PSU
B50 N50
R1 R2 f 4A R1 R2 t (LOC)

A1 A2 C3 C4 A3 A4 A1 A2

151.9(3B)
NOTE:
DR
REFER TO ETCS STANDARD DRAWINGS FOR MORE DETAIL
ON SPLITTING AND NAMING RELAYS

A1 A2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:35 DRG No: CSTDA130_2 SHEET TITLE: SIGNAL OPERATING - DOUBLE LIGHT- TURNOUT REPEATER EDMS No: SG0602002 SHEET No: A130_2 CIRCUIT BOOK No: 00001

SIGNAL OPERATING
1(3A) 1
PSU LOC 1AT HDR VRR
BX120
f 4A

C1 C2
D1 D2 C1 C2

1JP 1JP
LPM ECR

PSU LOC
B50 1 (5) 3
f 4A R1 R2

# 1 JP

PSU LOC SB
N50 2 (6) 4
(LOC) t 33 1

PSU
MAKE & MODEL:
NX120
(LOC) t 1 2 34 2

C4 C3
D4 D3 C4 C3
LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY
#
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4

LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY


WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6

1 1(M)
PSU LOC VRR HR LOC SB SB LOC PSU
BX120 G NX120
1B 1W 1 (LOC)
f 4A 1 1 2 2 t

D1 D2 D1 D2

R
3B 3W 3
D6 D5 5 5 6 6

D6 D5

1
DR LOC SB SB LOC
G
4B 4W 4
7 1 2 8

D1 D2

1
HDR
Y
5B 5W 5
D6 D5 9 3 4 10

D1 D2

R
6B 6W 6
D6 D5 11 5 6 12

LAMPS: LED
D8 D7 MAKE & MODEL:

PSU LOC
BX120
f 4A D8 D7

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDA131_1 SHEET TITLE: SIGNAL CONTROLS - TURNOUT REPEATER (PRELIMINARY MEDIUM) EDMS No: SG0602002 SHEET No: A131_1 CIRCUIT BOOK No: 00001

INSUFFICIENT DISTANCE TO REDUCE FROM


LINE SPEED TO TURNOUT SPEED

'P'
151.9 1 3
5
151.9AT 151.9BT 1AT 1BT 3AT 1 3BT 5AT

+ R + R + R + R R1 R + R
+ +

1JP 1(3B)
ECR HDR 1 3XT
R2 R + R

MEDIUM 1 HDR C1 C2 C1 C2 1
HDR
1(3A)
PSU LOC HDR PSU
B50 N50
f 4A R1 R2 NOTE: t (LOC)
MAY ALSO BE REQUIRED FOR ETCS INTERFACE,
#
C1 C2 TURNOUT ROUTE CONTROL RELAYS OR
SIGNAL INFORMATION IN ADVANCE, SHALL

MEDIUM 1 (3B) HDR 1(3B) BE USED AS APPLICABLE

HDR # NAMING CONVENTION SHALL FOLLOW LOGIC


3 3(M)B 1(M) IDENTIFIED IN ESG 100.1 3(M)B 3
PSU LOC VRR HR LOC LOC HR LOC LOC HR VRR PSU
B50 N50
f 4A R1 R2 t (LOC)

A1 A2 A1 A2 C3 C4 A3 A4 A3 A4

1(3A)
HDR #
3(M)A 1(M) 3(M)A
MEDIUM 1 (3A) HDR HR HR HR

R1 R2

A1 A2 C1 C2 A3 A4

1
DR
3 1 3
CLEAR 1 DR HDR HDR HDR

R1 R2

A1 A2 C1 C2 A3 A4

MEDIUM 151.9 HDR 151.9(3A)


HDR #
1 1(M) 151.9 1(M) 1
PSU LOC VRR HR LOC LOC HR LOC LOC HR VRR PSU
B50 N50
f 4A R1 R2 t (LOC)

A1 A2 A1 A2 C1 C2 A3 A4 A3 A4

MEDIUM 151.9(3B) HDR 151.9(3B)


HDR #
1 1 1(3B) 151.9 1(3B) 1 1
PSU LOC VRR HDR HDR LOC LOC HR LOC LOC HDR HDR VRR PSU
B50 N50
f 4A R1 R2 t (LOC)

B1 B2 B1 B2 B1 B2 C3 C4 B3 B4 B3 B4 B3 B4

PRELIMINARY
151.9 151.9
MEDIUM 151.9 PHDR 151.9(3B) 151.9JP
PHDR
151.9(3A)
HDR

WHERE 1 (3A) HDR NOT PROVIDED, HDR ECR PSU LOC HDR PSU
USE 3(M) HR & 1 HDR CONTACTS B50 N50
R1 R2 f 4A R1 R2 t (LOC)

C1 C2 C1 C2 A1 A2

CLEAR 151.9 DR 151.9 151.9(3B)


DR HDR
1(3A) 151.9 1(3A)
HDR HDR HDR

R1 R2 A1 A2

B1 B2 C1 C2 B3 B4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDA131_2 SHEET TITLE: SIGNAL OPERATING - DOUBLE LIGHT - TURNOUT REPEATER (PRELIM MED.) EDMS No: SG0602002 SHEET No: A131_2 CIRCUIT BOOK No: 00001

SIGNAL OPERATING
151.9(3B) 151.9
PSU LOC 151.9AT HDR VRR
BX120
f 4A

C1 C2
D1 D2 C1 C2

151.9JP 151.9JP
LPM ECR

PSU LOC
B50 1 5
f 4A R1 R2

151.9 JP
#
PSU LOC SB
N50 2 6
(LOC) t 33 1

PSU
MAKE & MODEL:
NX120
(LOC) t 1 2 34 2

C4 C3
D4 D3 C4 C3
LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY
#
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4

LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY


LAMPS: LED
WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6
MAKE & MODEL:

151.9 151.9
PSU LOC VRR HR LOC SB SB LOC PSU
BX120 G NX120
1B 1W 1 (LOC)
f 4A 1 1 2 2 t

D1 D2 D1 D2

R
3B 3W 3
D6 D5 5 5 6 6

D6 D5

151.9
DR LOC SB SB LOC
G
4B 4W 4
7 1 2 8

D1 D2 151.9
PHDR
151.9
HDR
Y
5B 5W 5
D6 D5 D6 D5 9 3 4 10

D1 D2

R
6B 6W 6
D6 D5 11 5 6 12

151.9
HDFR

D8 D7 151.9
151.9
DR
4 1 151.9 HDFR
T OFF = 640 ms
PSU LOC PSU LOC PHDR
T ON = 200 ms
BX120 BX120 2
f 4A D8 D7 f 4A A6 A5
OMRON COVER TYPE - Y92A - 48B
5 8 A1 A2 H3CR-F8 BASE - PLUG-IN TYPE P2CF-08
PSU RESISTOR - 800 OHM 30w
NX120 7
PULSE RATE REQUIRED - 70 FLASHES
(LOC) t
PER MINUTE
A4 A3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDA132_1 SHEET TITLE: SIGNAL OPERATING - DOUBLE LIGHT - MAIN LINE ROUTE INDICATOR EDMS No: SG0602002 SHEET No: A132_1 CIRCUIT BOOK No: 00001

26CT 19(M)A 19(M)B


PSU LOC PR HR HR
BX120
f 4A

B1 B2
C1 C2 C2 C1
19 MLRI

19(M)C
HR

MAKE & MODEL:

C2 C1

SIG
LOC SB SB LOC BUS PSU
G NX120
1B 1W 1 (LOC)
C8 C7 C8 C7 1 1 2 2 t

Y
2B 2W 2
C8 C7 3 3 4 4

R
3B 3W 3
B8 B7 B8 B7 B8 B7 5 5 6 6

B8 B7

19
HDR
Y
5B 5W 5
9 3 4 10

C1 C2

R
6B 6W 6
C8 C7 11 5 6 12

LAMPS: LED
MAKE & MODEL:

C6 C5 C6 C5 C6 C5

PSU LOC
BX120
B6 B5 ALL INTERNAL WIRING ETFE TEFLON
f 4A
COATED 1.23mm SQ, 19/29AWG 600V GRADE
UNLESS SHOWN OTHERWISE

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDA132_2 SHEET TITLE: SIGNAL OPERATING - MAIN LINE ROUTE INDICATOR LED EDMS No: SG0602002 SHEET No: A132_2 CIRCUIT BOOK No: 00001

19
MLRI

TERMINAL
BLOCK
26CT 19(M)A
PSU LOC PR HR LOC SB
BX120
f 4A 27 1
'B'
C1 C2
C3 C4 COM

28 2

19(M)B
HR

29 3
'D'
C3 C4 COM
MLRI
BUS
4

2L 2 30

PSU
NX120
(LOC) t

LAMPS: LED
MAKE & MODEL:

ALL INTERNAL WIRING ETFE TEFLON


COATED 1.23mm SQ, 19/29AWG 600V GRADE
UNLESS SHOWN OTHERWISE

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDA139 SHEET TITLE: SIG OPERATING - SINGLE LIGHT JCT SIG (WITH CO-ACTING) - ECR ARRGT. EDMS No: SG0602002 SHEET No: A139 CIRCUIT BOOK No: 00001

'P' 'P'

1 3 155.5
151.9BT 1AT + R
1BT 3AT 3BT 155.5AT

+ R 151.9 R1 R + R
+ +

3XT
MEDIUM PROVIDED
'P'
FOR TURNOUT ROUTE R2 R
ON 3 ONLY 3 CO-ACT
3
3 ## 3 LPM ## ECR##

LOC
3(M)A
B50 1 (5) 3
DR LOC SB SB LOC
3 SIGNAL AND 3 CO-ACTING G
f 4A R1 R2

1W
1B 1 1 2 2 #
SIGNAL OPERATING
A1 A2
(A3) (A4) N50 2 (6) 4
(LOC) t
3 3(M)A 3(M)A
PSU LOC VRR HR HR PSU
BX120 Y NX120
2W (LOC)
f 4A A6 A5 2B 3 3 4 4 1 2 t
(A8) (A7)
A1 A2 A1 A2 A3 A4
(A3) (A4) (B1) (B2) (B3) (B4) ADJUST LPM TO DROP ECR RELAY
WHEN LAMP UNIT IS OUT

R
3W
A6 A5 3B 5 5 6 6 LPM VERSION 1.0 REQUIRES A FILTERED 50V DC SUPPLY
#
(B6) (B5) WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 3 & 4

LAMPS: LED LPM VERSION 1.1 DOES NOT REQUIRE A FILTERED 50V DC SUPPLY
MAKE & MODEL: WITH INPUT TERMINALS 1 & 2, OUTPUT TERMINALS 5 & 6
A6 A5 3(M)B
(B6) (B5) HR

PSU LOC LOC SB SB LOC PSU


BX120 R NX120
3(M)B 4B 4W (LOC)
f 4A A8 A7 A8 A7 7 7 8 8 t
(B8) (B7) (B8) (B7) HDR
3 CO-ACT 3 3(M)B 3
ECR ECR HR VRR PSU
Y NX120
5B 5W (LOC)
A6 A5 11 9 10 12 1 2 t
(B6) (B5)
PSU LOC
A6 A5 A6 A5 A3 A4 B3 B4
(B6) (B5) (B6) (B5) Y (B3) (B4) (C3) (C4) B50 1 (5) 3
3 3(M)B 15 3 4 16 f 4A 3(M)B
VRR HDFR # ECR ##
Y *2
17 11 12 18 PSU
N50 2 (6) 4
A8 A7 4 1 (LOC) t R2 R1
(B8) (B7) (5) (8)
PSU LOC
A1 A2 3(M)B ##
BX120 (B1) (B2)
f 4A LPM
1
3(M)B
HDR
B1 B2 3 3(M)B CO-ACT 3(M)B 3 1
1
(C1) (C2) *2 LPM SHOULD BE ADJUSTED
3 LOC VRPR ECR ECR HR LOC LOC HR
SUCH THAT ECR IS DE-ENERGISED
B50
ONLY WHEN ALL LAMPS ARE OUT
f 4A R1 R2

C1 C2 C1 C2
C1 C2 C1 C2 C1 C2

N50 3 3(M)B
(3 LOC) HDFR
t CO-ACT 3 3(M)B
C4 C3
C4 C3 C4 C3
C4 C3 PSU LOC ECR ECR HDR
1
3 3 BX120 2
DR
3(M)A 3 CO-ACT 3 3 CO-ACT 3(M)A 3 1
f 4A
OMRON
3 LOC HR ECR ECR VRPR 3 ECR ECR HR LOC LOC D3 D4 D3 D4
C1 C2
B50 RGKR H3CR-F8
f 4A t R1 R2 PSU
NX120 7
D1 D2 D1 D2 C1 C2 C1 C2 (LOC)
D1 D2 D1 D2 C1 C2 C3 C4 t

C4 C3
3(M)B INITIAL SETTING
3(M)B 3(M)B CO-ACT T OFF = 640 ms
HR ECR ECR C4 C3 C4 C3
C4 C3 T ON = 200 ms
PULSE RATE REQUIRED 68 - 72 PER MIN

NOTE: 3 SIGNAL AND 3 CO-ACTING SIGNAL MUST USE CONTACTS OF THE SAME RELAYS
D1 D2 D1 D2
D1 D2 IN THE OPERATING CIRCUIT. COVER TYPE - Y92A - 48B

CONTACT NUMBERS IN BRACKETS ARE FOR CO-ACTING SIGNAL OPERATING. BASE - PLUG-IN TYPE P2CF-08
RESISTOR - 800 OHM 70w
## FOR CO-ACTING CIRCUITS NAME TO INCLUDE CO-ACTING (SIGNAL / LPM/ ECR)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDA140 SHEET TITLE: SIGNAL OPERATING - CO-ACTING SIGNAL EDMS No: SG0602002 SHEET No: A140 CIRCUIT BOOK No: 00001

31 31
CO-ACTING CO-ACTING
MAY BE VRR
LPM ECR
(DEPENDS ON APPLICATION) LOC
B50 1 (5) 3
f 4A R1 R2

31 #
CO-ACTING
N50 2 (6) 4
(LOC)
36AT 31(M)A 31 31(M)A t

CD CD PR HPR DR LOC SB SH SH SB LOC HR CD


SIG LTS G SIG LTS
BX120 1B 1W NX120
f 4A 1 1 2 2 1 2 t
(CD)
B3 B4
D3 D4 31(M)B D3 D4 D1 D2

HPR
31(M)B
HR

D3 D4
# LPMVERSION 1.0 REQUIRES A FILTERED 50V DC
31(M)C SUPPLY WITH INPUT TERMINALS 1 & 2, OUPUT
HPR TERMINALS 3 & 4
D1 D2
Y
2B 2W
C8 C7 3 3 4 4 31(M)C
D3 D4
HR
LAMPS: LED
MAKE & MODEL:

D1 D2

R
3B 3W
C8 C7 C8 C7 C8 C7 5 5 6 6

A6 A5

31(S)A 31(S)A
CD CD HR HR CD
SIG LTS Y SIG LTS
BX120 4B 4W NX120
f 4A 7 7 8 8 t
(CD)
B5 B6 B7 B8

31(S)B LAMP: LED 31(S)B


HR MAKE & MODEL: HR

B5 B6 B7 B8

31(S)C NOTE: ORDER OF LIGHTS COULD BE 31(S)C


HR G/R/Y/SMALL Y TO IMPROVE HR
VISIBILITY OF SHUNT WITH
RED LIGHT

B5 B6 B7 B8

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDN056 SHEET TITLE: ENTRANCE EXIT ROUTE SET (WITHOUT A RING CIRCUIT) EDMS No: SG0602002 SHEET No: N056 CIRCUIT BOOK No: 00001

3(S)A
1 3(M)B
4 DOWN MAIN

UP MAIN

6 8
PREVENTS CeR ENERGISING IF
BUTTON IS ENABLED AS A FINISH
ALSO CROSSPROVE (S)&(M) CeR FOR
SAME SIGNAL
PUSH BUTTON TABLE

COLUMN D FOR
A B C D
X IN COLUMN C
COMMENCE POSSIBLE FINISH POSSIBLE
BUTTON FINISH BUTTON BUTTON COMMENCE BUTTON
X CER X FnR CeR CeR X CeR 1 3M 3M 1
X (FM) R X (F)R 3M DM 4 3S
3S 4 DM 3M
COLUMN B FOR X IN COLUMN A R1 R2
4 UM UM 4,6

FnR FnR 6 UM 6 8
8 6

RESETS COMMENCE
AFTER FINISH ACTIONED

MICROLOK ASSIGNMENT
3FMR*((3MBFR*~3FNR*~3SACER*~1CER)+(~DMFNR*3MBCER)) TO 3MBCER

ALL VALID COMMENCE FOR Y,


EXCEPT ITSELF

COLUMN D FOR Y
COLUMN B FOR Y IN COLUMN A
IN COLUMN C

Y FNR FnR FnR Y FnR

Y (F)R CeR

R1 R2

WHERE MULTIPLE FINISHES ARE POSIBLE FROM A SINGLE COMMENCE,


CeR
ENSURE ONLY THE FINISH OPERATED DEFINES THE ROUTE TO BE SET
(NONE SHOWN IN THIS EXAMPLE)

etc
Y FnR

MICROLOK ASSIGNMENT
3MBFR*(1CER+3FNR)*~DMFNR TO 3FNR

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDP004 SHEET TITLE: AUTONORMALISING & APPROACH LOCKING EXAMPLES - MICROLOK OCS EDMS No: SG0602002 SHEET No: P004 CIRCUIT BOOK No: 00001

CASE 1: PLAIN TRACK CASE 2: ONE TRACK BETWEEN SIGNALS CASE 3: FACING JUNCTION & SUBSIDIARY SHUNTS

27 31 35 102 37
27AT 27BT 31AT 35AT 37AT 37BT

105

37XT

27 31 37(S)A 37(S)B 37
27AT TZR 31AT TZR RUR RUR 37AT TZR
105
27BT 35AT 37BT NLR

R1 R2

27BT 35AT
27 31 105
TZR TZR 37XT RLR

37BT
ASSIGN ~27AT * 27BT + 27_TZR * ~27BT TO 27 TZR ASSIGN ~31AT * 35AT + 31_TZR * ~35AT TO 31 TZR 37 105
TZR NLR

37XT
# NOTE: THESE CIRCUITS OPTIMISED FOR USE AS MICROLOK LOGIC. 105
RELAY INSTALLATIONS REQUIRE DIFFERENT CIRCUITS TO ACHIEVE SAME FUNCTIONALITY. RLR
REFER TO SHEET P005 FOR RELAY CIRCUITS.

ASSIGN 37SA_RUR * 37SB_RUR *

(~37AT * ((37BT * 105_NLR) + (37XT * 105_RLR)) +

37_TZR * ((~37BT * 105_NLR) + (~37XT * 105_RLR))) TO 37 TZR

27 31 37
ALSR ALSR ALSR
27 31 37
NGPR APPROACH NGPR APPROACH NGPR APPROACH
TRACKS AND TRACKS AND TRACKS AND
SELECTION SELECTION SELECTION

27 31 37
TZR 27AT POJR TZR 31AT POJR TZR 37AT POJR

31AT
JR(P)

TO ALSJR TO ALSJR

ASSIGN 27_NGPR * ((27_ALSR + 27M_ALSJR) + ASSIGN 31_NGPR * ((31_ALSR + 31M_ALSJR) + TO ALSJR ASSIGN 37_NGPR * ((37_ALSR +

(APPROACH TRACKS AND SELECTION) + (APPROACH TRACKS AND SELECTION) + (37M_ALSJR + 37MA_NLR + 37MB_NLR) * 37S_ALSJR) +

(27_TZR * 27AT * POJR))) TO 27 ALSR (31_TZR * (31AT + 31AT_JRP) * POJR))) TO 31 ALSR (APPROACH TRACKS AND SELECTION) +

(37_TZR * 37AT * POJR))) TO 37 ALSR

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDP005 SHEET TITLE: AUTONORMALISING & APPROACH LOCKING EXAMPLES - RELAY OCS EDMS No: SG0602002 SHEET No: P005 CIRCUIT BOOK No: 00001

CASE 1: PLAIN TRACK CASE 2: ONE TRACK BETWEEN SIGNALS CASE 3: FACING JUNCTION & SUBSIDIARY SHUNTS

27 31 35 102 37
27AT 27BT 31AT 35AT 37AT 37BT

105

37XT

27 31 37(S)A 37(S)B 37
27AT TZR 31AT TZR RUR RUR 37AT TZR
105
27BT 35AT NLR 37BT

R1 R2 R1 R2 R1 R2

27BT 35AT 37BT

105
RLR 37XT

37XT

37
TZR

27 31 37
ALSR ALSR ALSR
27 31 37
NGPR APPROACH TRACKS NGPR APPROACH TRACKS NGPR APPROACH TRACKS
AND SELECTION R1 R2 AND SELECTION R1 R2 AND SELECTION R1 R2

27BT 35AT 37BT


27 31 37 105
TZR 27AT POJR TZR 31AT POJR TZR 37AT NLR POJR

37XT
31AT 105
JR(P) RLR

TO ALSJR

TO ALSJR TO ALSJR

NOTE: THESE CIRCUITS ARE FOR USE IN RELAY INSTALLATIONS.


REFER TO SHEET P004 FOR LOGIC OPTIMISED FOR USE IN MICROLOK DATA.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDQ001 SHEET TITLE: EARTHING - LOCATION WIRING EDMS No: SG0602002 SHEET No: Q001 CIRCUIT BOOK No: 00001

TEST EARTH

EARTH BAR
1
***
2

TEST
***
3 ELD TEST EARTHS
***
4
COMMUNICATIONS 1

EARTH #3
***
2

RACK 1 EARTH BAR


***
3
CABLE/SHEATH/
#1 4 ARRESTORS EARTHS
***
1 5

***
2 NORMAL & EMERGENCY SUPPLY
*** ***
3 SURGE PROTECTION EARTHS 6

*** ***
4 7 TRACK CIRCUITS
#2 8 EARTHS
#1
5 9
POTENTIAL #1
EQUALISATION 6
CLAMP 10
(PEC100)

7
#1 IMPORTANT
1
#1 ALL EARTH WIRING TO BE AS SHORT AND

TERM INATION RACK EARTH BAR


8

M AIN EARTH BAR


DIRECT AS PRACTICAL.
9
AVOID "COILING" OR "LOOPING" EARTH WIRES.
***
2
OUTGOING MAINS
***
TRENCH EARTH 3
SURGE PROTECTION IF OTHER EARTH SYSTEM'S EARTH ARE WITHIN
10 4 EARTHS 8 METRES OF EARTH GRID THEN THE MATTER

11 5
IS TO BE REFERRED TO ASSET STANDARDS
LOCATION EARTH IS TO BE LESS AUTHORITY FOR ADVICE.
12
THAN 5V IF ELECTRONIC EQUIPMENT
IS INSTALLED IN LOCATION, ***
13 6
OTHERWISE LESS THAN 10V
*** CABLE/SHEATH/ 1
14 7
ARRESTORS EARTHS
***

RACK 2 EARTH BAR


15 8 2

***
TRENCH EARTH 9 3
EQUIPMENT
4 EARTHS

16 5 NOTES:

10 ***-NAME OF SUPPLY OR
CIRCUIT CONNECTED
***
6
ONE EARTH BUS PER RACK-FUNCTION
*** CAN BE COMBINED AS NECESSARY.
7
EQUIPMENT
8 EARTHS CABLE SIZES IN ACCORDANCE WITH
POTENTIAL CONSTRUCTION SPECIFICATION
#1
EQUALISATION 18 9 SC00170000SP LIGHTNING SURGE
CLAMP #1 PROTECTION.
19
(PEC100)
10 ALL TERMINALS RECORDED ON CIRCUIT
(TYPICAL NUMBERING SHOWN).

#1 16mm2 GREEN/YELLOW WIRE.


IF THE DISTANCE IS GREATER
THAN 10m, THEN THE MATTER IS
TO BE REFERRED TO ASSET STANDARDS
AUTHORITY FOR ADVICE.

#2 MAY BE DIRECT BONDED IF EARTH IS


#1 PURELY USED FOR COMMUNICATION
SYSTEMS AND NOT ALSO USED FOR
POWER SYSTEMS.

#3 ALL TEST EARTH WIRING TO BE VIOLET

RAILWAY POWER EARTH


OR POWER POLE EARTH

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDQ002 SHEET TITLE: MONITORING APPLICATIONS - MISCELLANEOUS EDMS No: SG0602002 SHEET No: Q002 CIRCUIT BOOK No: 00001

1. VIO (OPTO ISOLATOR)


1 1 1 1 1
NGPR ALSR ALSJR USR HR
1
PSU LOC UCR RR 1
B50(EXT)
f 4A R1 R2

PSU
N50(EXT)
(LOC) t

TYPICAL APPLICATION - SIGNAL CONTROL RELAY (HR)

B24(NV)
BUSBAR
VIO(50V)

3 1

4 2
N OR NX
(SAME SUPPLY AS CCT)

NOTE: SEE SPG 1033 FOR


MORE EXAMPLES

OUTPUT
(TO TELEMETRY)

2. VAI (ANALOGUE INTERFACE)

JOINTLESS TRACK
1 VRMS 2600 Hz
CIRCUIT RECEIVER B50 N50
R1 R2

3 3
CHART RECORDER OR CHART RECORDER OR
4 4
ANALOGUE DATA LOGGER ANALOGUE DATA LOGGER
1 5 1 5
VAI VAI
2 6 2 6

7 7
120V AC 120V AC
9 9

TYPICAL APPLICATION - UNATTENDED MONITORING OF TRACK VOLTAGES TYPICAL APPLICATION - UNATTENDED DETAILED MONITORING OF POINTS DETECTION

NOTES:

1. FOR TYPICAL APPLICATIONS OF LAMP MONITORING


DEVICES REFER TO SHEET NO. A03.

2. FOR TYPICAL APPLICATIONS OF CURRENT SENSING


DEVICES REFER TO SHEET NO. X17.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDR003 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELD BUS - INPUT ASSIGNMENT EDMS No: SG0602002 SHEET No: R003 CIRCUIT BOOK No: 00001

(TRACK LAYOUT EXAMPLE)

12.3
LOC 12.6
LOC
TO STATION A 10.9B LOC 12.6B LOC 13.4B LOC

10.9 12.3 A

Rx 10.9AT Tx Tx 10.9BT Rx Rx 10.9CT Tx Tx 10.9DT Rx Rx 12.3AT Tx Rx 12.3BT

Tx 11.6BT Rx Tx 11.6AT Rx Rx 12.6BT Tx Tx 12.6AT Rx Rx 13.4BT

11.6 12.6

10.9 10.9C LOC 11.6 A


LOC LOC

A
13.7

Tx Tx 12.3CT Rx Rx 13.7AT Tx Tx

STATION B

Tx Tx 13.4AT Rx Rx 13.8BT Tx Tx 13.8AT Rx Rx

FRAME C FRAME D
13.4
FRAME B
13.8
A FRAME A
REL REL
SW A SW B

R13.4
13.7B

13.4 13.7 LOC

LOC LOC

16.4
16.4 LOC 15.7C LOC 16.9B LOC
LOC
15.7 16.9

Rx Rx 15.7AT Tx Tx 15.7BT Rx Rx 15.7CT Tx Tx 15.7DT Rx Rx 16.9AT Tx

STATION C

Tx Rx 16.4BT Tx Tx 16.4AT Rx Rx 17.0BT Tx Tx 17.0AT Rx Rx 17.6DT Tx

16.4 17.0 TO STATION D

15.7 17.0B
LOC LOC

16.9 17.0
LOC LOC

NOT TO SCALE

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDR004 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELDBUS - TX INPUT WIRING (EXAMPLE) EDMS No: SG0602002 SHEET No: R004 CIRCUIT BOOK No: 00001

10.9 10.9C
COMMON COMMON
PAIR 10 PAIR 10
SIGNAL SIGNAL

No.1 INPUT UNIT No.1 INPUT UNIT

RED RED RED RED


L1 E1 1 L1 E1 1
CRITEC CRITEC
UTB-18 UTB-18
GREY GREY GREY GREY
L2 E2 2 L2 E2 2

3 3

4 4

10.9AT A4 10.9BT B2
5 5

D1 D2 D1 D2

10.9
HR A5 10.9CT B3
6 6

D1 D2
D1 D2

A6 11.6BT B4
7 7
D6 D5
INTERNAL WIRE INTERNAL WIRE
D1 D2
10.9
ECR A7 B5
8 8

D1 D2

PSU 10.9 PSU 10.9C


BX120 L1 E1 21 BX120 L1 E1 21
3 4 3 4
f 4A f 4A
CRITEC CRITEC
5 5
DSF-6A DSF-6A
PSU 150V PSU 150V
NX120 L2 E2 22 NX120 L2 E2 22
(10.9) 7 8 (10.9C) 7 8
t t

23 23

24 24

A8 25 25

10.9
*IF SIGNAL KEY SWITCH
IS PROVIDED * GZR B1
26 26

D1 D2

P5 27 27

NOTE: REFER TO DUPLINE FIELDBUS CHANNEL


ALLOCATION FOR FUNCTION ANALYSIS

28 28

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDR005 SHEET TITLE: TELEMETRY SYSTEM - CHANNEL GENERATOR & PRIVATE LINE MODEM WIRING EDMS No: SG0602002 SHEET No: R005 CIRCUIT BOOK No: 00001

13.7B

COMMON
PAIR 10
SIGNAL

CHANNEL
GENERATOR PRIVATE
LINE MODEM PRIVATE

RED RED
LINE MODEM
L1 E1 1
RED
CRITEC 1
RED
UTB-18 1
SE
GREY GREY
L2 E2 2
GREY
2
GREY
2

3
4 3

5 4

6 5

7 6

8 7

8
13.4 13.7B
BX120 L1 E1 21 8
3 4
f 4A
CRITEC 21
5
DSF-6A
21
13.4 150V
NX120 L2 E2 22
(13.7B) 7 8
t
22

23 22

23

23

24

24

25 24

25

26 25

26

27 26
RED RED
L1 E1 27
3 4
RED RED
CRITEC L1 E1 27
5 3 4
UBT-18 CRITEC
28
5
GREY GREY UBT-18
L2 E2 28
7 8
GREY GREY
L2 E2 28
D34900000115 7 8

G34910040115

G34910040115

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:36 DRG No: CSTDR006 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELDBUS TX INPUT WIRING (EXAMPLE) EDMS No: SG0602002 SHEET No: R006 CIRCUIT BOOK No: 00001

13.4
COMMON
PAIR 10
SIGNAL

No.1 INPUT UNIT


No.2 INPUT UNIT
RED RED
L1 E1 1
RED
CRITEC 1
UTB-18

GREY GREY
L2 E2 2
GREY
2

3 3

4 4

13.4AT E8
5 F8 5

D1 D2
INTERNAL WIRE
13.4BT F1
6 6
G1

D1 D2

13.4 13.4 # FRAME CD


HR VRR F2 NR G2
7 7

D1 D2
D1 D2 D1 D2

13.4 # REL.SW.A
INTERNAL WIRE
VNR F3 N G3
8 8
D6 D5

D1 D2 D1 D2

PSU 13.4
BX120 L1 E1 21 21
3
f 4A CRITEC 4

5
DSF-6A

PSU 150V
NX120 L2 E2 22 22
(13.4) 7
t 8

23 23

13.4 13.4
24 24
120V 120V 13.4 13.4
13.4 NORM EMERG 50V 50V
ECR F4 PWR PSI PSI PWR CH1 CH2 G4
25 25
1 3 1 3 1 2 3 1 3 1

D1 D2

F5 26 26

F6 27 27

F7 28 28
NOTE: REFER TO DUPLINE FIELDBUS CHANNEL
ALLOCATION FOR FUNCTION ANALYSIS

WHERE TRAINSTOPS ARE PROVIDED


#

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDR007 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELDBUS TX INPUT WIRING (EXAMPLE) EDMS No: SG0602002 SHEET No: R007 CIRCUIT BOOK No: 00001

17.0
COMMON
PAIR 10
SIGNAL

No.1 INPUT UNIT

RED RED
L1 E1 1
CRITEC

UTB-18

GREY GREY
L2 E2 2

17.0AT O6
5

D1 D2

17.0 17.0 #
HR VRR O7
6

D1 D2 D1 D2

17.0 #
VNR O8
7
D6 D5
INTERNAL WIRE
D1 D2
17.0
ECR P1
8

D1 D2

PSU 17.0
BX120 L1 E1 21
3 4
f 4A CRITEC
5
DSF-6A

PSU 150V
NX129 L2 E2 22
(17.0) 7 8
t

23

24

17.6D P2
25

D1 D2

P3 26

NOTE: REFER TO DUPLINE FIELDBUS CHANNEL


P4 27
ALLOCATION FOR FUNCTION ANALYSIS NOTE: WHERE TRAINSTOPS ARE PROVIDED
#

28

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDR008 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELDBUS - SCHEMATIC DIAGRAM (EXAMPLE) EDMS No: SG0602002 SHEET No: R008 CIRCUIT BOOK No: 00001

10.9 LOC 10.9C LOC 11.6 LOC 12.3 LOC 12.6 LOC 13.4 LOC 13.7 LOC

DT 1
01
2

CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC

UNIT 1 UNIT 1 UNIT 1 UNIT 1 UNIT 1 UNIT 2 UNIT 1 UNIT 2 UNIT 1

CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC

120V AC 120V AC 120V AC 120V AC 120V AC 120V AC 120V AC

13.7B LOC 13.8 LOC 15.2C LOC 14.5 LOC 15.2 LOC 15.7 LOC 16.4 LOC 16.9 LOC 17.0 LOC

1 DT

01
2

CRITEC
CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC

PRIVATE PRIVATE
CHANNEL
LINE LINE UNIT 1 UNIT 1 UNIT 1 UNIT 1 UNIT 2 UNIT 1 UNIT 2 UNIT 1 UNIT 2 UNIT 1 UNIT 1
GENERATOR
MODEM MODEM

CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC CRITEC

CRITEC
TO TO 120V AC 120V AC 120V AC 120V AC 120V AC 120V AC 120V AC 120V AC
STATION A STATION D
120V AC

FOR WIRING DETAILS SEE:

LOCATION PAGE

10.9 R004

10.9C R004

11.6

12.3

13.4 R006

13.7B R005

15.7

17.0 R007

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDR009 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELDBUS - CHANNEL ALLOCATIONS (EXAMPLE) EDMS No: SG0602002 SHEET No: R009 CIRCUIT BOOK No: 00001

STATION A TO STATION B
SYSTEM 1 (10.9 LOCATION TO 17.0 LOCATION)

INPUT CONNECTIONS INPUT CONNECTIONS

LOCATION FUNCTION CHANNEL MODULE LOCATION FUNCTION CHANNEL MODULE

TERMINAL INPUT TERMINAL INPUT

SPARE SPARE A1 1 12.3 10.9DT 5-4 5 C6 1


SPARE A2 12.3AT 6-4 6 C7
SPARE A3 12.3 RGKR 7-4 7 C8

12.3 NGKR 8-4 8 D1

12.3 ECR 25-24 1 D2

12.3 50V WARNING 26-24 2 D3

SPARE 27-24 3 D4

SPARE 28-24 4 D5

10.9 10.9AT 5-4 5 A4 1 12.6 12.6AT 5-4 5 D6 1

10.9 RGKR 6-4 6 A5 12.3BT 6-4 6 D7

10.9 NGKR 7-4 7 A6 13.4BT 7-4 7 D8

10.9 ECR 8-4 8 A7 8-4 8

SPARE 25-24 1 A8
12.6 RGKR 25-24 1 E1
26-24 2 B1
*10.9 GZR 12.6 NGKR 26-24 2 E2
SPARE 27-24 3 P5
27-24 3
28-24 4
28-24 4
12.6 ECR 5-4 5 E3

10.9BT 5-4 5 B2 1 12.6 50V WARNING 6-4 6 E4 2


10.9C
10.9CT 6-4 6 B3 DIRECT INPUT 7-4 7 E5

11.6BT 7-4 7 B4 SPARE 8-4 8 E6

DIRECT INPUT 8-4 8 B5 SPARE 25-24 1 E7

SPARE 25-24 1 26-24 2


SPARE 26-24 2 27-24 3

SPARE 27-24 3 28-24 4


SPARE 28-24 4

CHANNEL
11.6 11.6AT 5-4 5 B6 1 13.7B GENERATOR
12.6BT 6-4 6 B7 AND PRIVATE
11.6 RGKR 7-4 7 B8 LINE MODEMS
11.6 NGKR 8-4 8 C1

11.6 ECR 25-24 1 C2

11.6 50V WARNING 26-24 2 C3

SPARE 27-24 3 C4

SPARE 28-24 4 C5

* IF SIGNAL KEY SWITCH PROVIDED

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDR010 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELDBUS - CHANNEL ALLOCATIONS (EXAMPLE) EDMS No: SG0602002 SHEET No: R010 CIRCUIT BOOK No: 00001

STATION A TO STATION B

SYSTEM 1 (10.9 LOCATION TO 67.0 LOCATION)

INPUT CONNECTIONS INPUT CONNECTIONS

LOCATION FUNCTION CHANNEL MODULE LOCATION FUNCTION CHANNEL MODULE

TERMINAL INPUT TERMINAL INPUT

13.4 13.4AT 5-4 5 E8 1 13.8 13.8AT 5-4 5 I1 1


13.4BT 6-4 6 F1 15.2CT 6-4 6 I2
13.4 RGKR 7-4 7 F2 13.8 RGKR 7-4 7 I3
13.4 NGKR 8-4 8 F3 13.8 NGKR 8-4 8 I4
13.4 ECR 25-24 1 F4 13.8 ECR 25-24 1 I5
SPARE 26-24 2 F5 13.8 50V WARNING 26-24 2 I6
SPARE 27-24 3 F6 SPARE 27-24 3 I7
SPARE 28-24 4 F7 SPARE 28-24 4 I8
SPARE 5-4 5 F8 2
DIRECT INPUT 6-4 6 G1
FRAME CD NR 7-4 7 G2 15.2C 13.7BT 5-4 5 J1 1
REL SW A N 8-4 8 G3 15.2BT 6-4 6 J2
13.4 120V&50V WARNING 25-24 1 G4 DIRECT INPUT 7-4 7 J3
SPARE 26-24 2 G5 8-4 8
SPARE 27-24 3 G6 25-24 1

28-24 4 26-24 2
27-24 3
28-24 4

13.7 12.3CT 5-4 5 G7 1 14.5 13.7CT 5-4 5 J4 1


13.7AT 6-4 6 G8 14.5AT 6-4 6 J5
13.7 RGKR 7-4 7 H1 14.5 RGKR 7-4 7 J6
13.7 NGKR 8-4 8 H2 14.5 NGKR 8-4 8 J7
13.7 ECR 25-24 1 H3 14.5 ECR 25-24 1 J8
13.7 50V WARNING 26-24 2 H4 14.5 50V WARNING 26-24 2 K1
SPARE 27-24 3 H5 SPARE 27-24 3 K2
SPARE 28-24 4 H6 SPARE 28-24 4 K3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDR011 SHEET TITLE: TELEMETRY SYSTEM - DUPLINE FIELDBUS - CHANNEL ALLOCATIONS (EXAMPLE) EDMS No: SG0602002 SHEET No: R011 CIRCUIT BOOK No: 00001

STATION A TO STATION B

SYSTEM 1 (10.9 LOCATION TO 17.0 LOCATION)

INPUT CONNECTIONS INPUT CONNECTIONS

LOCATION FUNCTION CHANNEL MODULE LOCATION FUNCTION CHANNEL MODULE

TERMINAL INPUT TERMINAL INPUT

15.2 14.5BT 5-4 5 K4 1 16.4 16.4AT 5-4 5 M8 1


15.2AT 6-4 6 K5 15.7BT 6-4 6 N1
16.4CT 7-4 7 K6 15.7CT 7-4 7 N2
8-4 8 17.0BT 8-4 8 N3
15.2 RGKR 25-24 1 K7 16.4 RGKR 25-24 1 N4
15.2 NGKR 26-24 2 K8 16.4 NGKR 26-24 2 N5
27-24 3 27-24 3
28-24 4 28-24 4
15.2 ECR 5-4 5 L1 2 16.4 ECR 5-4 5 N6 2
12.5 50V WARNING 6-4 6 L2 16.4 50V WARNING 6-4 6 N7
DIRECT INPUT 7-4 7 L3 DIRECT INPUT 7-4 7 N8
SPARE 8-4 8 L4 8-4 8
SPARE 25-24 1 L5 SPARE 25-24 1 O1
26-24 2 SPARE 26-24 2 O2
27-24 3 27-24 3
28-24 4 28-24 4

15.7 14.5CT 5-4 5 L6 1 16.9 15.7DT 5-4 5 O3 1


15.7AT 6-4 6 L7 16.9AT 6-4 6 O4
16.4BT 7-4 7 L8 DIRECT INPUT 7-4 7 O5
8-4 8 8-4 8
15.7 RGKR 25-24 1 M1 25-24 1
15.7 NGKR 26-24 2 M2 26-24 2
27-24 3 27-24 3
28-24 4 28-24 4
15.7 ECR 5-4 5 M3 2
15.7 120V&50V WARNING 6-4 6 M4
17.0 17.0AT 5-4 5 O6 1
DIRECT INPUT 7-4 7 M5
M6 17.0 RGKR 6-4 6 O7
SPARE 8-4 8
17.0 NGKR 7-4 7 O8
SPARE 25-24 1 M7
17.0 ECR 8-4 8 P1
26-24 2
17.6DT 25-24 1 P2
27-24 3
SPARE 26-24 2 P3
28-24 4
SPARE 27-24 3 P4
28-24 4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT005 SHEET TITLE: TRACK CIRCUITS - UM71 CSEE - FEED & RELAY EDMS No: SG0602002 SHEET No: T005 CIRCUIT BOOK No: 00001

OUTPUT CONNECTIONS FOR

OTHER FREQUENCIES
Q1 FEED Q1 Q1 TX
SEE FREQ/KEM CHART
TX ARR Q1 TX

PSU LOC
BLACK #3
B24 A+ V2 3 2 E1
f 4A
M1

#1 @ TMU *1
1700Hz E *2 TO TRACK
PSU 1700Hz
N24 A- M3
(LOC) SE
t WHITE #3
V7 4 1 E2
V3 V4 V5 V6 V1 1 V2 4

SHEATH
#2

PSU LOC SE 7/0.50mm


B24 SHIELDED PAIR

Q1 RELAY f 4A

PSU
N24
(LOC) t Q1 Q1 RX
Q1 RX ARR Q1 RX
Q1 A- A+
BLACK #3
L+ V1 3 2 9
R2 R1
C
A2 A1
#1 @ TMU *1
C2 1700Hz E *2 TO TRACK
1700Hz
L-
SE
WHITE #3
V2 4 1 10
R1 R2 V1 1 V2 4

SHEATH
#2

SE 7/0.50mm
SHIELDED PAIR
SEE KRV TABLE
##
COMMON PSU OUTPUT CONNECTIONS FOR

OTHER FREQUENCIES
Q1 FEED Q1 TX
Q1
SEE FREQ/KEM CHART
P.S.U. TX ARR Q1 TX
B24
LOC
BLACK #3
BX120 S1 A+ A+ V2 3 2 E1
f 4A f1 4A
S2 M1

#1 @ TMU *1
1700Hz E *2 TO TRACK
f2 4A 1700Hz
NX120 S3 M3
N24
(LOC) SE
t WHITE #3
S4 A- A- V7 4 1 E2
t1 V3 V4 V5 V6 V1 1 V2 4

SHEATH
TRANSMITTERS AND RECEIVERS ON COMMON #2

FREQUENCIES MUST USE SEPARATE SE 7/0.50mm


t2
SHIELDED PAIR
POWER SUPPLIES
Q2 RELAY

Q2 RX
Q2
Q2 RX ARR Q2 RX
Q2 A- A+
BLACK #3
L+ V1 3 2 9
R2 R1
C
A2 A1
2300Hz #1 @ TMU *1
C2 E *2 TO TRACK
2300Hz
L-
SE
WHITE #3
V2 4 1 10
R1 R2 V1 1 V2 4

SHEATH
#2
## SE 7/0.50mm
SHIELDED PAIR
SEE KRV TABLE ALL INTERNAL WIRING TO BE ETFE TEFLON COATED 1.23mm2
19/29 AWG 600V GRADE UNLESS SHOWN OTHERWISE
NOTES:

#1 ELSAFE 290V ARRESTOR MODULE #2 ARRESTOR EARTHED MECHANICALLY VIA #3 494/0.50mm ALUMINIUM HYPALON HD-90-CPE YELLOW *1 7/0.85mm GREEN/YELLOW CABLE
MODULE AND BASE PART Nos. THE ATTACHMENT SCREW TO THE MOUNTING
## TYPICAL TRACK STICK CIRCUIT BASE - 216600 RAIL. MOUNTING RAIL ELECTRICALLY @ CABLE SCREEN SHOULD NOT BE EARTHED AT TMU *2 TMU SURGE MODULE PART No. E14094
SHOWN ON SHEET A102 MODULE - 216680 (GRAPHITE) CONNECTED TO MAIN EARTH APPLY HEAT SHRINK TUBING

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT006 SHEET TITLE: TRACK CIRCUITS - CSEE (WITH DPU & INTERMEDIATE AMP) T1 EDMS No: SG0602002 SHEET No: T006 CIRCUIT BOOK No: 00001

COMMON PSU
DPU DPU RX
PSU IRX ARR
B24 DPU
PSU LOC JB
BLACK *2
B24 120V B24 R1 A1 3 2
f1
f 4A 4A 1
f2 D1
4A
DPU
#1
AMP SCREEN ABCHz
E

THRU LINK
D2
N24
PSU MODULE
WHITE *2
N24 0V N24 R3 A2 4 (GREY) 1
(LOC) t1
t @ 2
t2
2C 7/0.50mm
A5 A6

SE #2
DPU RELAY
DPU
RX DPU

V1 V2
A+ L+
R1 R2

A- L-
ABCHz

R1 C
SEE
KRV
TABLE
R2 C2

NOTE 1: #1 ELSAFE 290V RMS ARRESTOR #2 ARRESTOR EARTHED MECHANICALLY *2 7/0.85mm @ CABLE SCREEN SHOULD
TX AND RX WITH A COMMON FREQUENCY MUST MODULE & BASE PART No: TO THE MOUNTING RAIL NOT BE EARTHED AT DPU.
NOT BE FED FROM THE SAME POWER SUPPLY BASE - 216600 MOUNTING RAIL ELECTRICALLY APPLY A HEAT SHRINK TUBING.
MODULE - 216620 (GREY) CONNECTED TO MAIN EARTH
MODULE - 216680 (GRAPHITE)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT010 SHEET TITLE: TRACK CIRCUITS - ML JOINTLESS - FEED & RELAY EDMS No: SG0602002 SHEET No: T010 CIRCUIT BOOK No: 00001

Q1
Q1 FEED PSU TX
B24
*2
T125 B24 B24 O/P1 1 T1
PSU LOC f1 4A #
BX120 T115 * 2
TO
f 4A f2 4A
ABC
T105 3 TU TRACK
N24 HZ
T0 N24 N24 * 4 Q1
SE
PSU t1
NX120 T5 E O/P2 5 T2
(LOC) t2
t
TAP MOD E
COM 0-2A 2-4.4A

NOTE 1:
** SE SE
Q2 SCREEN @
SE
SE

B3 B4

Q2
RX
## N24 B24 T1
1 T1
Q2
Q2 RELAY 1 Ohm * 2
FROM
R+ 3 TU TRACK
R2 R1
DEF Q2
9L
SE * 4
HZ #
9H 5 T2
T2
R- 3L
E 1H 1L 3H

NOTE 1:

SCREEN @
SE SE
SE

Q3 FEED WITH MATCHING UNIT Q3


PSU TX
B24
*2
T125 B24 B24 O/P1 1 7 7 1 1 T1
PSU LOC f1 4A #
BX120 T115 * 2 2
TO
f 4A f2 4A
ABC
T105 MTU MTU 3 TU TRACK
N24 HZ
T0 N24 N24 * 4 Q3
SE
PSU t1
NX120 T5 E O/P2 2 8 8 5 T2
(LOC) t2
t
TAP MOD E
COM 0-2A 2-4.4A

NOTE 1: SCREEN @
** SE SE SE SE
Q4
NOTE:
M.T.U'S. INSTALLED WHERE
DICTATED BY COMBINATION B3 B4
OF TRACK CIRCUIT LENGTH
AND CABLE LENGTH.
Q4
SEE MANUAL FOR DETAILS
RX
## N24 B24 T1
1 7 7 1 1 T1
Q4
1 Ohm * 2 2
FROM
Q4 RELAY R+ MTU MTU 3 TU TRACK
R2 R1
DEF Q4
9L
SE * 4
HZ #
9H 2 8 8 5 T2
T2
R- 3L
E 1H 1L 3H

Q2 & Q4 50V DC RELAYS NOTE 1: NOTE 1: SCREEN @


TX AND RX WITH A COMMON FREQUENCY MUST SE SE
** SUPPLY SETTING NOT BE FED FROM THE SAME POWER SUPPLY SE
TO SUIT TX, RX LOAD M.T.U. = MATCHING TRANSFORMER UNIT

## TYPICAL TRACK STICK # SEE TRACK CIRCUIT MANUAL * 7/0.85mm @ CABLE SCREEN SHOULD
3Y20-290GT.
CIRCUIT SHOWN ON (TO SUIT TRACK LENGTH & CONDITION) NOT TO EXCEED NOT BE EARTHED AT M.T.U. OR T.U.
PAGE A102 150mm IN LENGTH. APPLY A HEAT SHRINK TUBING.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT011 SHEET TITLE: TRACK CIRCUITS - ML JOINTLESS (WITH DPU) - FEED & RELAY EDMS No: SG0602002 SHEET No: T011 CIRCUIT BOOK No: 00001

Q1
Q1 FEED PSU TX
B24
B24 B24 O/P1 1 T1
f1 4A #
T125 * 2
TO
LOC f2 4A
PSU
ABC
BX120 T115 3 TU TRACK
f3 4A
f 4A HZ
T105 * 4 Q1
f4 SE
4A
T0 O/P2 5 T2
PSU N24
NX120 T5 N24 N24
t1
(LOC) t
TAP E MOD E
t2
COM 0-2A 2-4.4A

t3
NOTE 1: SCREEN @
t4 SE SE
SE
SE

Q2 Q2
DPU IRX
RX AMP
Q2 DPU
N24 B24 N24 B24
Q2 T1 T1
O/P1 I/P2
DPU
1R *
R+ DEF DEF
R2 R1 HZ HZ
9L
SE *
#
9H O/P2 I/P2
T2
D.P.U. (A) D.P.U. (B)
R- 3L COM E
E 1H 1L 3H T2 1 2 3 4 5 6 7

NOTE 1: #
SCREEN @
NOTE 1: SE
SE

SE

Q2

B3 B4

Q2
Q2 RELAY RX
N24 B24
## T1
1 T1
Q2
1R * 2
FROM
R+ DEF 3 TU TRACK
R2 R1 HZ
9L * 4 Q2
SE
#
9H 5 T2
T2
R- 3L
E 1H 1L 3H

NOTE 1:

SCREEN
@
SE SE
SE

NOTE 1:
TX AND RX WITH A COMMON FREQUENCY MUST
NOT BE FED FROM THE SAME POWER SUPPLY 3Y20-290GT

Q2 & Q2 DPU ARE 50V DC RELAYS

## TYPICAL TRACK STICK


# GAIN STRAPPINGS TO * 7/0.85mm @ CABLE SCREEN SHOULD
CIRCUIT SHOWN ON SUIT TRACK LENGTH NOT TO EXCEED NOT BE EARTHED AT TU.
** SUPPLY SETTING
PAGE A102 AND CONDITION 150mm IN LENGTH APPLY A HEAT SHRINK TUBINNG
TO SUIT TX, RX LOAD

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT012 SHEET TITLE: EBI TRACK 200 TI21 (ET200) AUDIO FREQUENCY TRACK CIRCUIT ( DIGITAL) EDMS No: SG0602002 SHEET No: T012 CIRCUIT BOOK No: 00001

2AT 2AT TX
2AT FEED P.S.U. TX LIGHTLY ARR 2AT
TWISTED
B24
B BLACK
B24 B24 O/P1 3 2 1 T1
PSU LOC f1
4A
BX120 120V(+/-) * 2
#1 TU
f 4A f2 4A SCREEN @
TO
REGULATED ABCD E 3 ABCD *1
N24 TRACK
SUPPLY
N24 N24
Hz 4
Hz
PSU t1 ** WHITE
NX120 COM E O/P2 4 1 5 T2
t2 W
(LOC) t
MOD
#3
#4 E #2 SHEATH #5
#4

#4 #4
SE

SE SE TU E

* TO 4 AND 5 FOR NORMAL POWER


** TRANSMITTERS AND RECEIVERS OF THE TO 1 AND 2 FOR LOW POWER
SAME FREQUENCY MUST USE SEPARATE SEE TRACK CIRCUIT MANUAL
POWER SUPPLIES (TO SUIT TRACK LENGTH AND CONDITION)
2BT 2BT RX
2BT RX LIGHTLY
ARR 2BT
TWISTED
2BT N24 B24
2BT RELAY RL+ IP1
B
3 2
BLACK
1 T1
R2 R1
ABCD 2
TU
#1
KEY SCREEN @
FROM
#
E 3 ABCD *1
TRACK
## (Hz) Hz
4
**
WHITE
RL- IPC 4 1 5 T2
W

#3
E TP1 #2 SHEATH #5
#4

#4 #4
SE

SE # FREQUENCY CONFIGURATION KEY WHEN INSERTED SETS THE TU E


RX FREQUENCY. ENSURE THE CORRECT FREQUENCY KEY IS
INSERTED TO MATCH THE TX FREQUENCY OF THE TRACK TO
BE CONFIGURED
2CT FEED WITH LINE MATCHING UNITS 2CT 2CT TX
P.S.U. TX LIGHTLY LIGHTLY ARR 2CT
TWISTED TWISTED
B24
B B BLACK
B24 B24 O/P1 9 4 3 2 TX TU 1 T1
PSU LOC f1
4A *
BX120 120V(+/-) 2
TU
f 4A f2 4A LMU SCREEN @ LMU
REGULATED ABCD #1 E 3 ABCD *1 TO
N24 (TX) (TU) TRACK
SUPPLY
Hz Hz
N24 N24 4
PSU t1 ** WHITE
NX120 COM E O/P2 7 2 4 1 TX TU 5 T2
t2 W W
(LOC) t E
MOD
#4 E #4 #2 SHEATH #5
SE #3 #4

#4 #4 #4
SE
NOTE:
KEY FREQUENCY SE SE LMU'S INSTALLED WHERE TU E
DICTATES BY COMBINATION
A 1700 HZ OF TRACK CIRCUIT LENGTH * TO 4 AND 5 FOR NORMAL POWER
AND CABLE LENGTH. TO 1 AND 2 FOR LOW POWER
B 2300 HZ SEE MANUAL FOR DETAILS SEE TRACK CIRCUIT MANUAL
(TO SUIT TRACK LENGTH AND CONDITION)
C 2000 HZ 2DT 2DT RX
D 2600 HZ 2DT RX LIGHTLY ARR 2DT
TWISTED
2DT N24 B24
B BLACK
RL+ IP1 3 2 1 T1

2DT RELAY R2 R1
ABCD 2
#1 ETU FROM
KEY SCREEN @
# E 3 ABCD *1 IMPEDANCE
## (Hz) Hz
BOND
4
**
WHITE
RL- IPC 4 1 5 T2
W

#3
#2 SHEATH #5
E TP1 #4

#4
#4 SE
2BT & 2DT ARE 50VDC QN1 RELAYS

TU E
SE

## TYPICAL TRACK STICK #1 ELSAFE ARRESTOR MODULE


CIRCUIT SHOWN ON MODULE AND BASE PART Nos. #2 ARRESTOR EARTHED MECHANICALLY VIA
#3 7/0.50mm SHIELDED PAIR TWIN TWISTED
PAGE A102 BASE - 216600A THE ATTACHMENT SCREW TO THE MOUNTING @ CABLE SCREEN SHOULD NOT BE
MODULE - 216680 (290VDC GRAPHITE) FOR TX AND RX #4 GREEN/YELLOW CABLE 7/0.85mm
RAIL. MOUNTING RAIL ELECTRICALLY EARTHED AT TU OR LMU(TU)
MODULE - 216690 (700VDC BROWN) FOR LMU(TX) CONNECTED TO MAIN EARTH #5 494/0.5mm ALUMINIUM/HD-90-CPE (YELLOW) APPLY A HEAT SHRINK TUBING

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT015 SHEET TITLE: EBI TRACK 200 TI21 (ET200) AUDIO FREQUENCY TRACK CIRCUITS EDMS No: SG0602002 SHEET No: T015 CIRCUIT BOOK No: 00001

MIN 50m TO MAX 1100m

20m 20m

(NOTE) (NOTE) (NOTE) (NOTE)

1 1 1 1

TU TU TU TU
T1 T2 T1 T2 T1 T2 T1 T2
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

TO 4 AND 5 FOR NORMAL POWER MODE


TO 1 AND 2 FOR LOW POWER MODE
(REFER TO POWER SETTING TABLE)

TU TU

LMU(TU)
TX TX

POWER SETTING TABLE

TRACK LENGTH TRACK POWER TRANSMITTER TO TRANSMITTER TO


SETTING TUNING UNIT MAX TUNING UNIT MAX
METRES CABLE LENGTH - No CABLE LENGTH WITH
(SET IN TX TU LMU REQUIRED LMU
2 TX CABLE TO TU
2
TERMINALS) METRES: LOOP OHMS METRES

50-250 LOW (TU 1 & 2) <200m OR 5 OHMS 2000


ELSAFE ELSAFE
ARRESTOR MODULE 200-500 NORMAL (TU 4 & 5) <60m OR 1.5 OHMS 2000 ARRESTOR MODULE

500-1100 NORMAL (TU 4 & 5) <30m OR 0.75 OHMS 1000

NOTE: No. OF IMPEDANCE BONDS ON TRACK TO BE CUT TRACK


CONSIDERED FOR POWER SETTING CONTACT TO BE
CONNECTED HERE
4 (WHERE APPLICABLE) 4

TRACK STICK CIRCUIT


TO BE CONNECTED HERE
WHERE APPLICBLE

TP1
TR

QN1,50V
IPC RL+ O/P1

Rx I/P
EBI TRACK 200 R1 R2 EBI TRACK 200
TI-21 RECEIVER TI - 21 TRANSMITTER
IP1 RL- O/P2

3
E E
B24 N24 MOD B24 N24

B24 5 B24 5
f 4A f 4A

N24 N24
t t

3 3

1 494/0.5mm ALUMINIUM / HD-90-CPE (YELLOW)

2 7/0.5mm WHT, BLK PVC TWIN TWISTED / (AL SHIELD + DRAIN WIRE) / BLK PVC/NYL
(NOTE):RAIL TO TU/ETU, TIED AND RUN
CABLES TOGETHER WHEN POSSIBLE 3 7/0.4mm PLAIN COPPER / WHT PVC/BLK NYL

TU = TUNING UNIT 4 LIGHTLY TWISTED


* FOR SURGE PROTECTION
GREEN/YELLOW CABLE 7/0.85mm SEE SPG 0712
5

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT016 SHEET TITLE: EBI TRACK 200 TI21 (ET200) AUDIO FREQUENCY TRACK CIRCUITS EDMS No: SG0602002 SHEET No: T016 CIRCUIT BOOK No: 00001

MIN 50m TO MAX 970m

20m 20m

(NOTE) (NOTE) (NOTE) (NOTE)

1 1 1 1

TU TU TU TU
T1 T2 T1 T2 T1 T2 T1 T2
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

TO 4 AND 5 FOR NORMAL POWER MODE


TO 1 AND 2 FOR LOW POWER MODE
(REFER TO POWER SETTING TABLE)

TU TU

LMU(TU)
TX TX

POWER SETTING TABLE

TRACK LENGTH TRACK POWER TRANSMITTER TO TRANSMITTER TO


SETTING TUNING UNIT MAX TUNING UNIT MAX
METRES CABLE LENGTH - No CABLE LENGTH WITH
(SET IN TX TU LMU REQUIRED LMU
2 TX CABLE TO TU
2
TERMINALS) METRES: LOOP OHMS METRES

50-250 LOW (TU 1 & 2) <200m OR 5 OHMS 2000


ELSAFE ELSAFE
ARRESTOR MODULE 200-500 NORMAL (TU 4 & 5) <60m OR 1.5 OHMS 2000 ARRESTOR MODULE

500-1100 NORMAL (TU 4 & 5) <30m OR 0.75 OHMS 1000

NOTE: No. OF IMPEDANCE BONDS ON TRACK TO BE CUT TRACK


CONSIDERED FOR POWER SETTING CONTACT TO BE
CONNECTED HERE
4 (WHERE APPLICABLE) 4

TRACK STICK CIRCUIT


TO BE CONNECTED HERE
WHERE APPLICBLE

4(TU) 2(TU)
TP1
TR

QN1,50V
IPC RL+ O/P1 9(TX)

Rx I/P
EBI TRACK 200 R1 R2 EBI TRACK 200
LMU(TX)
TI-21 RECEIVER TI-21 TRANSMITTER
IP1 RL- O/P2 7(TX)

3 4
E E
B24 N24 MOD B24 N24 E

B24 5 B24 5 5
f 4A f 4A

N24 N24
t t

3 3

1 494/0.5mm ALUMINIUM / HD-90-CPE (YELLOW)

(NOTE):RAIL TO TU/ETU, TIED AND RUN 2 7/0.5mm WHT, BLK PVC TWIN TWISTED / (AL SHIELD + DRAIN WIRE) / BLK PVC/NYL

CABLES TOGETHER WHEN POSSIBLE


3 7/0.4mm PLAIN COPPER / WHT PVC/BLK NYL

TU = TUNING UNIT 4 LIGHTLY TWISTED


* FOR SURGE PROTECTION
LMU = LINE MATCHING UNIT GREEN/YELLOW CABLE 7/0.85mm SEE SPG 0712
5

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT017 SHEET TITLE: EBI TRACK 200 TI21 (ET200) AUDIO FREQUENCY TRACK CIRCUITS EDMS No: SG0602002 SHEET No: T017 CIRCUIT BOOK No: 00001

MIN 50m TO MAX 1035m

20m

6 IRJ 6

(NOTE) (NOTE)

1 1 1
IB IB
NOTE(A)
TU TU TU
T1 T2 T1 T2 T1 T2
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

TO 4 AND 5 FOR NORMAL POWER MODE


TO 1 AND 2 FOR LOW POWER MODE
(REFER TO POWER SETTING TABLE)

POWER SETTING TABLE

TRACK LENGTH TRACK POWER TRANSMITTER TO TRANSMITTER TO


SETTING TUNING UNIT MAX TUNING UNIT MAX
METRES CABLE LENGTH - No CABLE LENGTH WITH
(SET IN TX TU LMU REQUIRED LMU
2 TX CABLE TO TU
2
TERMINALS) METRES: LOOP OHMS METRES

50-250 LOW (TU 1 & 2) <200m OR 5 OHMS 2000


ELSAFE ELSAFE
ARRESTOR MODULE 200-500 NORMAL (TU 4 & 5) <60m OR 1.5 OHMS 2000 ARRESTOR MODULE

500-1100 NORMAL (TU 4 & 5) <30m OR 0.75 OHMS 1000

NOTE: No. OF IMPEDANCE BONDS ON TRACK TO BE CUT TRACK


CONSIDERED FOR POWER SETTING CONTACT TO BE
CONNECTED HERE
4 (WHERE APPLICABLE) 4

TRACK STICK CIRCUIT


TO BE CONNECTED HERE
WHERE APPLICBLE

TP1
TR

QN1,50V
IPC RL+ O/P1

Rx I/P
EBI TRACK 200 R1 R2 EBI TRACK 200
TI-21 RECEIVER TI - 21 TRANSMITTER
IP1 RL- O/P2

3
E E
B24 N24 MOD B24 N24

B24 5 B24 5
f 4A f 4A

N24 N24
t t

3 3
1 494/0.5mm ALUMINIUM / HD-90-CPE (YELLOW)

2 7/0.5mm WHT, BLK PVC TWIN TWISTED / (AL SHIELD + DRAIN WIRE) / BLK PVC/NYL

3 7/0.4mm PLAIN COPPER / WHT PVC/BLK NYL


(NOTE):RAIL TO TU/ETU, TIED AND RUN IB = IMPEDANCE BOND
CABLES TOGETHER WHEN POSSIBLE 4 LIGHTLY TWISTED
IRJ = INSULATED RAIL JOINT
5 GREEN/YELLOW CABLE 7/0.85mm
NOTE(A): IMPEDANCE BOND TO ETU, TIED AND TU = TUNING UNIT
* FOR SURGE PROTECTION
RUN CABLES TOGETHER WHEN POSSIBLE 2x962/0.5mm ALUMINIUM
6 ETU = END TUNING UNIT SEE SPG 0712

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:37 DRG No: CSTDT021 SHEET TITLE: TRACK CIRCUIT - UM71 T1 - GENERAL ARRANGEMENT EDMS No: SG0602002 SHEET No: T021 CIRCUIT BOOK No: 00001

MAX 650m

23m 23m

11.5m ± 0.2 11.5m ± 0.2 11.5m ± 0.2 11.5m ± 0.2

DPU

(NOTE) (NOTE) (NOTE) (NOTE)

1 1 DISTANCE FROM 1 1
RAIL MIN. 65mm

TU TU TU TU
V1 V2 V1 ACI V2 V1 V2 V1 V2 V1 ACI V2 V1 V2
1 2 3 4 1 2 3 4 2 1 2 3 4 1 2 3 4

LOW GAIN: NO BRIDGE


HIGH GAIN: BRIDGE D1-D2

2 2

D1 D2 A1 A2

DPU
INTERMEDIATE ALWAYS BRIDGE
AMPLIFIER R1-R2 WHEN
9 10 11 12 13 14 V1 V2 9 10 11 12 13 14 V1 V2
RESISTOR PROVIDED

3 R1 R1
R1 R3 A6 A5

MU MU
LOC
R2 B24 R2

f 4A
3
2
E1 E2 L3 L4 5 6 7 8 E1 E2 L3 L4 5 6 7 8
N24
(LOC) t 2
ALWAYS BRIDGE
3
R1-R2 WHEN
RESISTOR PROVIDED
2
3

RECEIVER SENSTIVITY: REFER TO KRVTABLE RECEIVER SENSTIVITY: REFER TO KRVTABLE


FOR CONNECTION FOR CONNECTION
FOR TRANSMITTER CONNECTION
AND BRIDGES AND BRIDGES
AND BRIDGES REFER TO KEMTABLE
3 TRACK STICK CIRCUIT OF RELEVANT FREQUENCY FOR T1
TO BE CONNECTED
HERE WHERE
APPLICABLE

R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 V1 V2 V3 V4 V5 V6 V7 V8
TR TR 3
M1

QN1,24V QN1,24V MODULATION


M2
V1 L+ V1 L+
M1-M3 LINK
Rx I/P
R1 R2
Rx I/P
DPU R1 R2
M3
RECEIVER (Rx) TRANSMITTER (Tx)
RECEIVER (Rx)
V2 L- V2 L- M4

M5
3 3
A+ A- C C1 C2 A+ A- C C1 C2 A+ A-

TRANSMITTER POWER:
LOC LOC LOC LOW: NO BRIDGES
B24 3 B24 3 B24 HIGH: BRIDGE M2-M4,
f 4A PICKUP DELAY f 4A PICKUP DELAY f 4A AND M2-M5
(SHORT BRIDGES)

N24 N24 N24


(LOC) t (LOC) t (LOC) t

3 3 3
TU = TUNING UNIT
1 494/0.5mm ALUMINIUM / HD-90-CPE (YELLOW)
MU = MATCHING UNIT
2 7/0.5mm WHT, BLK PVC / (AL SHIELD +DRAIN WIRE) / BLK PVC/NYL
DPU = DATA PICKUP UNIT * FOR SURGE PROTECTION
(NOTE): RAIL TO ACI/TU/TMU, TIED AND
RUN CABLES TOGETHER WHEN POSSIBLE 7/0.4mm PLAIN COPPER /WHT PVC/BLK NYL SEE SPG 0712
3 ACI = AIR CORE INDUCTOR

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT022 SHEET TITLE: TRACK CIRCUIT - UM71 T1 - COMBINED TUNING & MATCHING UNIT (TMU) EDMS No: SG0602002 SHEET No: T022 CIRCUIT BOOK No: 00001

MAX 650m

23m 23m

11.5m ? 0.2 11.5m ? 0.2 11.5m ? 0.2 11.5m ? 0.2

(NOTE) (NOTE) (NOTE) (NOTE) (NOTE) (NOTE)

1 1 1 1 1 1

TU SURGE SURGE TU
V1 V2 V1 ACI V2 MODULE TMU EARTH POST TMU EARTH POST MODULE V1 ACI V2 V1 V2
1 2 3 4 1 2 3 4

V1 V2 V1 V2

1 4 1 4

TMU TMU
E1 8 E1 8
E2 9 E2 9
5 10 5 10
6 11 6 11
7 12 7 12

2 2

RECEIVER SENSTIVITY: REFER TO KRVTABLE


FOR CONNECTION
FOR TRANSMITTER CONNECTION
AND BRIDGES
AND BRIDGES REFER TO KEMTABLE
3 TRACK STICK CIRCUIT OF RELEVANT FREQUENCY FOR T1
EM

TO BE CONNECTED
HERE WHERE
APPLICABLE

R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 V1 V2 V3 V4 V5 V6 V7 V8
TR 3
M1

QN1,24V MODULATION
M2
V1 L+
M1-M3 LINK
R1 R2
Rx I/P RECEIVER (Rx) TRANSMITTER (Tx) M3

V2 L- M4

M5
3
A+ A- C C1 C2 A+ A-

TRANSMITTER POWER:
LOC LOC LOW: NO BRIDGES
B24 3 TU = TUNING UNIT B24 HIGH: BRIDGE M2-M4,
f 4A TMU = COMBINED TUNINGMATCHING UNIT f 4A AND M2-M5
PICKUP DELAY (SHORT BRIDGES)
ACI = AIR CORE INDUCTOR
N24 N24
(LOC) t (LOC) t

3 3
1 494/0.5mm ALUMINIUM / HD-90-CPE (YELLOW)

2 7/0.5mm WHT, BLK PVC / (AL SHIELD +DRAIN WIRE) / BLK PVC/NYL
(NOTE): RAIL TO ACI/TU/TMU, TIED AND
RUN CABLES TOGETHER WHEN POSSIBLE 3 7/0.4mm PLAIN COPPER /WHT PVC/BLK NYL * FOR SURGE PROTECTION SEE SPG 0712

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT023 SHEET TITLE: TRACK CIRCUIT - UM71 - CIRCUIT END TERMINATION ARRANGEMENT EDMS No: SG0602002 SHEET No: T023 CIRCUIT BOOK No: 00001

COMBINED TUNING MATCHING UNIT (TMU) AND ACI UNIT ARRANGEMENT TUNING UNIT AND ACI UNIT ARRANGEMENT

UM71 TRACK CIRCUIT IRJ UM71 TRACK CIRCUIT IRJ

1 1
IB IB IB IB
NOTE (A) NOTE (A)
ACI ACI
NOTE (B)
1 NOTE (B)
1
SURGE TU
MODULE
1 2 3 4

V1 V2

1 4

TMU
E1 8 2
E2 9
5 10
V1 V2 9 10 11 12 13 14
6 11
7 12
R1

MU
R2
3

E1 E2 L3 L4 5 6 7 8

2
3

RECEIVER SENSTIVITY: REFER TO KRVTABLE


FOR CONNECTION
FOR TRANSMITTER CONNECTION
AND BRIDGES
AND BRIDGES REFER TO KEMTABLE
3 TRACK STICK CIRCUIT OF RELEVANT FREQUENCY FOR T1
TO BE CONNECTED
HERE WHERE
APPLICABLE

R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 V1 V2 V3 V4 V5 V6 V7 V8
TR 3
M1

QN1,24V MODULATION
M2
V1 L+
M1-M3 LINK
R1 R2
Rx I/P RECEIVER (Rx) TRANSMITTER (Tx) M3

V2 L- M4

M5
3 ACI = AIR CORE INDUCTOR
A+ A- C C1 C2 A+ A-
IB = IMPEDANCE BOND

IRJ = INSULATED RAIL JOINT


TRANSMITTER POWER:
MU = MATCHING UNIT
LOC LOC LOW: NO BRIDGES
B24 3 TMU = COMBINED TUNING MATCHING UNIT B24 HIGH: BRIDGE M2-M4,
f 4A f 4A AND M2-M5
TU = TUNING UNIT
PICKUP DELAY (SHORT BRIDGES)

N24 N24
(LOC) t (LOC) t

3 3
1 494/0.5mm ALUMINIUM / HD-90-CPE (YELLOW)
NOTE(A) : IMPEDANCE BOND TO ACI, TIED AND
RUN CABLES TOGETHER WHEN POSSIBLE 2 7/0.5mm WHT, BLK PVC / (AL SHIELD +DRAIN WIRE) / BLK PVC/NYL

NOTE(B) : ACI TO TU/TMU, 400mm LONG EACH SIDE 3 7/0.4mm PLAIN COPPER /WHT PVC/BLK NYL * FOR SURGE PROTECTION SEE SPG 0712

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT024 SHEET TITLE: TRACK CIRCUIT - UM71 T2 - GENERAL ARRANGEMENT EDMS No: SG0602002 SHEET No: T024 CIRCUIT BOOK No: 00001

19m MAX 300m 19m

DPU

(NOTE) (NOTE)

1 1
DISTANCE FROM
RAIL MIN. 65mm

TU TU TU TU
V1 V2 V1 V2 4 V1 V2 V1 V2
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

2 2

ALWAYS BRIDGE ALWAYS BRIDGE


R1-R2 WHEN R1-R2 WHEN
RESISTOR PROVIDED RESISTOR PROVIDED

ALWAYS BRIDGE
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 R1-R2 WHEN 9 10 11 12 13 14 15 16
RESISTOR PROVIDED

R1 R1 R1
ADJUST MU CONNECTIONS
AND BRIDGES ACCORDING TO MU MU MU
ADJUST MU CONNECTIONS
MATCHING UNIT ADJUSTMENT R2 R2 R2
AND BRIDGES ACCORDING TO
TABLE TO GIVE 18 TO
MATCHING UNIT ADJUSTMENT
23 V TO RX
3 TABLE TO GIVE 280-300 mV
8 7 6 5 4 3 E2 E1 8 7 6 5 4 3 E2 E1 8 7 6 5 4 3 E2 E1
AT RX M1,M2 3

3
3
2

FINE ADJUSTMENT
2 FOR TRANSMITTER CONNECTION
AND BRIDGES REFER TO KEMTABLE
TRACK STICK CIRCUIT
OF RELEVANT FREQUENCY FOR T2
TO BE CONNECTED
HERE WHERE
APPLICABLE

DPU
3 P5 P4 P3 P2 P1 P0 3 P5 P4 P3 P2 P1 P0 V1 V2 V3 V4 V5 V6 V7 V8
C
TR C
R 3
2 M1
C1 C1
QN1,50V QN1,50V MODULATION
M2
C2 TR+ C2 DPU TR+
M1-M3 LINK
RECEIVER (Rx) R1 R2 R1 R2
LOC RECEIVER TRANSMITTER (Tx) M3
B24 F+ T2 B24 F+
f 4A
TR-
f 4A
T2 TR- M4

N24 F- N24 F- M5
(LOC) 3 3
t t
M1 M2 S0 S1 S2 S3 S4 S5 M1 M2 S0 S1 S2 S3 S4 S5 A+ A-
3 3

TEST TRANSMITTER POWER:


COARSE ADJUSTMENT LOC LOW: NO BRIDGES
TERMINALS
B24 HIGH: BRIDGE M2-M4,
f 4A AND M2-M5
(SHORT BRIDGES)

N24
(LOC) t

1 494/0.5mm ALUMINIUM / HD-90-CPE (YELLOW) 3

2 7/0.5mm WHT, BLK PVC / (AL SHIELD +DRAIN WIRE) / BLK PVC/NYL
TU = TUNING UNIT
(NOTE) : RAIL TO TU, TIED AND RUN CABLES 3 7/0.4mm PLAIN COPPER /WHT PVC/BLK NYL
MU = MATCHING UNIT
TOGETHER WHEN POSSIBLE
4 7/0.85 RED PVC/BLK PVC/NYL DPU = DATA PICKUP UNIT *FOR SURGE PROTECTION SEE SPG 0712

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT030 SHEET TITLE: TRACK CIRCUIT - JEUMONT SCHNEIDER - SINGLE RAIL (WITH TV TH D2) EDMS No: SG0602002 SHEET No: T030 CIRCUIT BOOK No: 00001

SUMMARY OF CONNECTIONS FOR SINGLE RAIL JEUMONT SCHNEIDER TRACKS


USING TV TH D2 MATCHING TRANSFORMERS
ADJACENT TRACKS TO BE (NON ELECTRIFIED) ADJACENT TRACKS TO BE
ALTERNATE POLARITIES ALTERNATE POLARITIES

+ +

#1 #1
- #1 #1
CONNECTED TO RAIL CONNECTED TO RAIL TOTAL LOOP RES.
TOTAL LOOP RESISTANCE NOT TO EXCEED
WITH CHANNEL PIN WITH CHANNEL PIN
NOT TO EXCEED 0.2 OHM 0.2 OHM

#2 #2 #2 #2

#2 #2 #2 #2

V V V VA VC VB
A B C
MOUNTED MOUNTED
MATCHING TRANSFORMER NEAR NEAR
MATCHING TRANSFORMER

TV TH D2 TRACK TRACK TV TH D2
A B C A B C

FOR CONNECTIONS
TOTAL LINE LOOP RESISTANCE
#3 #3 SEE TABLE 2 BELOW
MAXIMUM LINE RESISTANCE
ADJUSTED TO 20 OHMS
60 OHMS PER LOOP
AS PER TABLE 1 BELOW

#4 #4

6 5 4 3 2 1 C+ C- C+ C1-

PSU LOC
BX120 AP2 TRANSMITTER RECEIVER
f 4A
AP1 NCO EGT 600 NCO RVT 600

P1 P2 D1 D2 S1 S2 V1+ V V2+ 2
SUPPLY VOLTAGE

103V TO 127V TRACK STICK CIRCUIT


#4 #4 TO BE CONNECTED HERE #4
WHERE APPLICABLE

P1 P2 D1 D2 S1 S2 TABLE 1 V1+ V1- V2+ V2-

SETTING OF LOOP RESISTANCE


AP POWER SUPPLY RELAY
PSU TO 20 OHMS USING INTERNAL RESISTORS
NX120 AN NCO EAT 115CA NCO CV TH 2 404
(LOC) t ACTUAL LOOP
BRIDGES TO BE MADE TO ACHIEVE
RESISTANCE OF
TOTAL LOOP RESISTANCE OF 20 OHMS
WIRE A/C+, C-/C

NOTE: WIRE/CABLE SIZES


0 TO 2 C+ TO 6
#1 7/19/0.26mm STEEL HYPALON
2 TO 4 C+ TO 5
#2 7/0.85mm
4 TO 5.5 C+ TO 5, 2 TO 3
#3 7/0.5mm TWIN SHIELDED
5.5 TO 7 C+ TO 6, 3 TO 4
#4 7/0.4mm
7 TO 9 C+ TO 4

9 TO 10.5 C+ TO 4, 2 TO 3
TABLE 2
10.5 TO 12 C+ TO 6, 3 TO 5

12 TO 14 C+ TO 3 RECEIVER MU CONNECTIONS

14 TO 16 C+ TO 2 CONNECT
TRACK LENGTH (m)
C- TO
16 TO 17 C+ TO 6, 1 TO 3, 3 TO 5

17 TO 19 18 TO 600 B
C+ TO 6, 1 TO 5

19 TO 20 600 TO 1500 C
C+ TO 1

3 TERMINAL ARRESTOR

3Y20 700GT

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT031 SHEET TITLE: TRACK CIRCUIT - JEUMONT SCHNEIDER - SINGLE RAIL (WITH TV TH 1) EDMS No: SG0602002 SHEET No: T031 CIRCUIT BOOK No: 00001

SUMMARY OF CONNECTIONS FOR SINGLE RAIL DC ELECTRIFIED OR NON-ELECTRIFIED


JEUMONT SCHNEIDER TRACKS
ADJACENT TRACKS TO BE ADJACENT TRACKS TO BE
ALTERNATE POLARITIES
USING TV TH 1 MATCHING TRANSFORMERS ALTERNATE POLARITIES

+ +
- -

#1 #1 #1 #1
CONNECTED TO RAIL CONNECTED TO RAIL
TOTAL LOOP RESISTANCE WITH CHANNEL PIN WITH CHANNEL PIN TOTAL LOOP RESISTANCE
NOT TO EXCEED 0.2 OHM NOT TO EXCEED 0.2 OHM

#2 #2 #2 #2

#2 #2

#5 ENDCAP #5 ENDCAP

* *
SHORT *ER2-2 RESISTOR REQUIRED FOR ELECTRIFIED AREAS, SHORT

LEAD LONG LEAD OR LOOP BETWEEN R AND V- LEAD LONG LEAD


REQUIRED FOR NON-ELECTRIFIED AREAS
V+ R V- V+ R V-

MOUNTED MOUNTED
MATCHING TRANSFORMER NEAR NEAR
MATCHING TRANSFORMER
TV TH 1 TRACK TRACK TV TH 1
A B C A B C

TOTAL LINE LOOP RESISTANCE


#3 #3
MAXIMUM LINE LOOP
ADJUSTED TO 20 OHMS
RESISTANCE 60 OHMS
AS PER TABLE BELOW

#4 #4

6 5 4 3 2 1 C+ C- C+ C1-

PSU LOC
BX120 AP2 TRANSMITTER RECEIVER
f 4A
AP1 NCO EGT 600 NCO RVT 600

P1 P2 D1 D2 S1 S2 V1+ V V2+ 2
SUPPLY VOLTAGE

103V TO 127V
#4 #4 TRACK STICK CIRCUIT #4
TO BE CONNECTED HERE
SETTING OF TRANSMITTER LOOP RESISTANCE WHERE APPLICABLE

P1 P2 D1 D2 S1 S2 TO 20 OHMS USING INTERNAL RESISTORS V1+ V1- V2+ V2-

ACTUAL LOOP
AP POWER SUPPLY BRIDGES TO BE MADE TO ACHIEVE RELAY
PSU RESISTANCE OF
NX120 AN NCO EAT 115CA TOTAL LOOP RESISTANCE OF 20 OHMS NCO CV TH 2 404
(LOC) WIRE A/C+, C-/B
t

0 TO 2 C+ TO 6

2 TO 4 C+ TO 5

4 TO 5.5 C+ TO 5, 2 TO 3

5.5 TO 7 C+ TO 6, 3 TO 4

7 TO 9 NOTE: WIRE/CABLE SIZES


C+ TO 4

9 TO 10.5 #1 7/19/0.26mm STEEL HYPALON


C+ TO 4, 2 TO 3

10.5 TO 12 #2 7/0.85mm
C+ TO 6, 3 TO 5

12 TO 14 #3 7/0.5mm TWIN SHIELDED


C+ TO 3

14 TO 16 #4 7/0.4mm
C+ TO 2

16 TO 17 C+ TO 6, 1 TO 2, 3 TO 5 #5 GREEN/YELLOW WIRE TO BE ISOLATED WITH


AN INSULATED END CAP
17 TO 19 C+ TO 6, 1 TO 5

19 TO 21 C+ TO 1
3 TERMINAL ARRESTOR

3Y20 700GT

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT032 SHEET TITLE: TRACK CIRCUIT - JEUMONT SCHNEIDER - SINGLE RAIL (DC ELEC CAP FED) EDMS No: SG0602002 SHEET No: T032 CIRCUIT BOOK No: 00001

SUMMARY OF CONNECTIONS FOR SINGLE RAIL DC ELECTRIFIED CAPACITOR FED


ADJACENT TRACKS TO BE
JEUMONT SCHNEIDER TRACKS ADJACENT TRACKS TO BE
ALTERNATE POLARITIES USING TV TH D2 SAR MATCHING TRANSFORMERS ALTERNATE POLARITIES

+ +

- -

#1 #1 #1 #1
CONNECTED TO RAIL CONNECTED TO RAIL
TOTAL LOOP RESISTANCE
WITH CHANNEL PIN WITH CHANNEL PIN
NOT TO EXCEED 0.5 OHM

#2 #2 #2 #2

#2
#2 #2 #2

10A
2000mF
TO SECOND TRACK
63V RK2

TOTAL LOOP RESISTANCE

ADJUSTED TO 2 OHMS

BT1 BT2 NT BT1 BT2 NT BT1 BT2 NT


MOUNTED MOUNTED
MATCHING TRANSFORMER NEAR
MATCHING TRANSFORMER NEAR
MATCHING TRANSFORMER

TV TH D2 SAR TRACK TV TH D2 SAR TRACK TV TH D2 SAR


BHV NHV BHV NHV BHV NHV

TOTAL LINE LOOP RESISTANCE


MAXIMUM LINE RESISTANCE
ADJUSTED TO 60 OHMS RF20 RF20 #2
#2 #2
60 OHMS PER LOOP

RK40 RK40

#3 #3 #3

#4
#4 #4

1 C+ C- C+ C1-

PSU LOC
BX120 AP2 TRANSMITTER RECEIVER
f 4A
AP1 NCO EGT 600 NCO RVT 600

P1 P2 D1 D2 S1 S2 V1+ V V2+ 2
SUPPLY VOLTAGE

103V TO 127V TRACK STICK CIRCUIT


#4 #4 NOTE: WIRE/CABLE SIZES #4
TO BE CONNECTED HERE
WHERE APPLICABLE
#1 7/19/0.26mm STEEL HYPALON

P1 P2 D1 D2 S1 S2 #2 7/0.85mm V1+ V1- V2+ V2-

#3 7/0.5mm TWIN SHIELDED


AP POWER SUPPLY RELAY
#4 7/0.4mm
PSU
NX120 AN NCO EAT 115CA NCO CV TH 2 404
(LOC) t
3 TERMINAL ARRESTOR

3Y20 700GT

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT035 SHEET TITLE: TRACK CIRCUIT - JEUMONT SCHNEIDER - SINGLE RAIL 2 WIRE RECEIVER EDMS No: SG0602002 SHEET No: T035 CIRCUIT BOOK No: 00001

SINGLE RAIL JEUMONT SCHNEIDER TRACKS


TYPICAL 2-WIRE RECEIVER WITH TRACK STICK

LOC LOC
BX120
f1 4A
MAX LINE RES. TOTAL LOOP RESISTANCE TOTAL LOOP RESISTANCE MAX LINE RES.
#4 TRACK
60 OHMS NOT TO EXCEED 0.2 OHM NOT TO EXCEED 0.2 OHM 60 OHMS
RELAY

LOC TB RB LOC #4
AP AP1 AP2 C+ A V+ V+ A C+ V2+

NCO CV TH 2 404
#4 #4 X #2 #2 #1 #1 #2 #2 X #4 V2+ V2-
S1 S1
#4
SHORT SHORT
S2 S2 R R B V1+
#5 #5
V1+ V1-
PSU D1 D1 TX #3 MTU TO RAILS MTU #3 RX

2
ER2.

ER2.
D2 D2 * * 2

P1 P1 LONG LONG
LOC #4 #2 #2 #1 TN RN #1 #2 #2 #4 #4
NX120 AN P2 P2 C- B V- V- C C1- V
(LOC) t1 Y Y

NCO EAT 115CA NCO EGT 600 NCO RVT 600 M3 T3


TV TH 1 TV TH 1
MOUNTED NEAR TRACK MOUNTED NEAR TRACK

*ER2-2 RESISTOR REQUIRED FOR ELECTRIFIED AREAS, **


OR LOOP BETWEEN R AND V-
REQUIRED FOR NON-ELECTRIFIED AREAS

NOTE: WIRE/CABLE SIZES

#1 7/19/0.26mm STEEL HYPALON

#2 7/0.85mm

#3 7/0.5mm TWIN SHIELDED

#4 7/0.4mm

#5 GREEN/YELLOW WIRE TO BE ISOLATED


WITH AN INSULATED END CAP

** TYPICAL TRACK STICK


CIRCUIT SHOWN ON
PAGE A102

3 TERMINAL ARRESTOR

3Y20 700GT

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT036 SHEET TITLE: TRACK CIRCUIT - JEUMONT SCHNEIDER - DOUBLE RAIL ELECTRIFIED EDMS No: SG0602002 SHEET No: T036 CIRCUIT BOOK No: 00001

SUMMARY OF CONNECTIONS FOR DOUBLE RAIL ELECTRIFIED


JEUMONT SCHNEIDER TRACKS UP TO 600m
ADJACENT TRACKS TO BE ADJACENT TRACKS TO BE
ALTERNATE POLARITIES
USING DC IMPEDANCE BONDS AND NCO. RVT. 600, 2 WIRE RECEIVER ALTERNATE POLARITIES

+ +

+ +

- _

#3 #3 #3 #3

TRACTION NEUTRAL TRACTION NEUTRAL


TO ADJACENT TRACK CIRCUIT TO ADJACENT TRACK CIRCUIT

V V V V V V
A N B A N B

DC IMPEDANCE BOND DC IMPEDANCE BOND

CIT 1400 CT1 OR 2000P CIT 1400 CT1 OR 2000P


I/J G H F NOTE 2 A B C D E F G H I/J K L M
NOTE 2

#1 FOR CONNECTIONS
SEE TABLE IN MANUAL

#4 NOTE 3

TOTAL LINE LOOP RESISTANCE


#1
ADJUSTED TO 20 OHMS
AS PER TABLE 1 BELOW MAXIMUM LOOP RESISTANCE
60 OHMS
#4 NOTE 3

#2 TABLE 1
#2 #2
6 5 4 3 2 1 C+ C- SETTING OF LOOP RESISTANCE

PSU LOC TO 20 OHMS USING INTERNAL RESISTORS C+ C2-


BX120 AP2 TRANSMITTER 1
f 4A ACTUAL LOOP
AP1 NCO EGT 600 BRIDGES TO BE MADE TO ACHIEVE RECEIVER 2
RESISTANCE OF
TOTAL LOOP RESISTANCE OF 20 OHMS NCO RVT 600 3
P1 P2 D1 D2 S1 S2 WIRE C+/F, C-/I
4 FOR CONNECTIONS
SUPPLY VOLTAGE
0 TO 2 C+ TO 6 V1+ V2+ V SEE TABLE IN MANUAL
103V TO 127V
#2 #2 2 TO 4 C+ TO 5
#2
4 TO 5.5 C+ TO 5, 2 TO 3
MAXIMUM LOOP RESISTANCE MAXIMUM LOOP RESISTANCE
P1 P2 D1 D2 S1 S2 5.5 TO 7 C+ TO 6, 3 TO 4 120 OHMS 20 OHMS
(1500 METRES MAX.)
7 TO 9 C+ TO 4 + -
EV2
AP POWER SUPPLY
PSU 9 TO 10.5 C+ TO 4, 2 TO 3
NX120 AN NCO EAT 115CA #2
NCO VDR
(LOC) t 10.5 TO 12 C+ TO 6, 3 TO 5
SV2
12 TO 14 + -
C+ TO 3
TRACK STICK CIRCUIT
14 TO 16 C+ TO 2 TO BE CONNECTED HERE
WHERE APPLICABLE MAXIMUM LOOP RESISTANCE
#2
16 TO 17 C+ TO 6, 1 TO 3, 3 TO 5 120 OHMS
(1500 METRES MAX.)
17 TO 19 C+ TO 6, 1 TO 5 V1+ V1- V2+ V2-

19 TO 20 C+ TO 1
RELAY

NCO CV.TH 2.404


NOTE 1: WIRE/CABLE SIZES NOTE 2: ON 2000P BOND TERMINAL "I"
IS LABELLED AS "J"
#1 7/0.5mm TWIN SHIELDED

#2 7/0.4mm NOTE 3: WIRE ENDS TO BE LABELLED SAME AS


CORRESPONDING RX, TX OR IB TERMINALS
#3 TRACTION SIDE LEADS

#4 ELSAFE 700V RMS ARRESTOR 3 TERMINAL ARRESTOR


MODULE AND BASE 3Y20 700GT

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT041 SHEET TITLE: TRACK CIRCUIT - DC - TRACK FEED EDMS No: SG0602002 SHEET No: T041 CIRCUIT BOOK No: 00001

-
+
ADJACENT TRACKS TO BE

ALTERNATE POLARITIES

LOC

+
"HIGH BALLAST"

PSU LOC 3Y20-290GT


BX120
f 4A
SE

LOC
PSU
NX120
(LOC) t "LOW BALLAST"

3Y20-290GT

TR
SE
TR17 TRACK FEED UNIT

-
R2 R1

+
-
QT1 4R

-
+
ADJACENT TRACKS TO BE

ALTERNATE POLARITIES

LOC

+
T+
4R
PSU LOC #1 3Y20-290GT
BX120
f 4A 1V
SE

3V
T-
LOC
PSU 2V
NX120
(LOC) t

#1 TAPPINGS AS REQUIRED FOR 3Y20-290GT


TRACK CIRCUIT ADJUSTMENTS
TR
SE
STORE 72
R2 R1

+
-
QT1 4R

-
+
CHARGE TRACK ADJACENT TRACKS TO BE
ADJUST ADJUST
ALTERNATE POLARITIES

#2 #3 LOC

T+ 4A
4R 4R
PSU LOC #1 3Y20-290GT
BX120
f 4A 1V
SE

-
3V
T-
Ni/Cad 135 AH
LOC
PSU 2V 1 OR 2 Cells
NX120 * 7/0.85mm
(LOC) t NOT TO EXCEED
150mm IN LENGTH
3Y20-290GT
#2 ADJUST VOLTAGE FOR TRICKLE TR
CHARGE AS APPROPRIATE
SE
STORE 72

-
(NEW DESIGN)
#3 WIRES MUST BE R2 R1

+
-
TERMINATED ON THE BATTERY QT1 4R

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDT042 SHEET TITLE: AXLE COUNTER - TIFFENBACH EDMS No: SG0602002 SHEET No: T042 CIRCUIT BOOK No: 00001

TAZ DSS1

BK
N1 N2 N3 N4 N5
4
YE S1

AXLE COUNTER RESET


5

BUFFER AM PLIFIER
WHEEL SENSORS

COUNTER M ODULE
VOLTAGE SUPPLY
TIFFENBACH TYPE

RELAY BOARD
GN 2 N59-1R-600-40
6
WT S11

BOARD
7

STAR QUAD SIGNAL CABLE OR EQUIVALENT


BUFFER (MAX RESISTANCE 200 OHMS)

AMPLIFIER
DSS2
N2
BN
8
YE S1
9
WHEEL SENSORS
CARD LAYOUT
TIFFENBACH TYPE
GN 2 N59-1R-600-40
10
WT S11
11

STAR QUAD SIGNAL CABLE OR EQUIVALENT


12 (MAX RESISTANCE 200 OHMS)

13
DSS3
14 (IF REQUIRED)

15
NOTE: RESISTORS ARE TO BE INSERTED WHEN SENSORS ARE NOT USED

16 FOR DSS4, ONE RESISTOR BETWEEN 16 AND 17 TERMINALS

AND ONE RESISTOR BETWEEN 18 AND 19 TERMINALS


17
DSS4
RESISTOR VALUE 1k5, 0.25 OR 0.5 WATT, 1% OR 2%
18 (IF REQUIRED)

19
BTR

PSU LOC BTR UP WITH BLOCK CLEAR BCR PSU


B50 20 21 N50
(NO BREAK) f 4A R1 R2 t (NO BREAK)
(LOC)
A1 A2

BTR BCR
RELAY

BOARD
D1 D2
R1 R2
N4

BCR UP WITH BLOCK OCCUPIED


22 23
1 2 3 4
IN4007 100R 10W mF160V
1000
#
REMOTE
AT BT RESET SLOW RELEASE MODULE
26

IN4007 - RS PART No:261-980


#
A1 A2
RESET

RESET BOARD R
N5 ##

28 ELECTRICIAN KEYLOCKED
##
SPRING LOADED SWITCH

PSU LOC
B50 1 WHEN AXLE COUNTER IS USED IN A
(NO BREAK) f 4A VOLTAGE SUPPLY REDUNDANT MODE IN CONJUNCTION
WITH COMPLETE TRACK CIRCUIT
PSU N1 REMOTE AX
N50 2 OVER BLOCK
3
BCR RESET TPR
(NO BREAK) t
(LOC)
RESET
PSU LOC BTR PSU
B50 N N50
f 4A A6 A5 A6 A5 R1 R2 t (LOC)

A1 A2 ##

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDU103 SHEET TITLE: POWER SUPPLIES - POWER SUPPLY LOCAL INDICATIONS EDMS No: SG0602002 SHEET No: U103 CIRCUIT BOOK No: 00001

A B C
XCX XCX
XCX

NORM SUPPLY
PSKR
CONT'R
A A EMERG N
BX120
f 4A 2 10

HH23 PSKR'S DETECT A SINGLE


PW-T CHANNEL FAILURE
120v AC
A
NX120
(A) t

'A'
# RESISTOR TO BE PROVIDED IF THE DISTANCE 120V
BETWEEN LOC CASE A AND C IS GREATER THAN 200m PSR

A A A B C
BX120
f 4A

3K9 10W
#
A
NX120
(A) t
'B'
120V
PSR
USE PSR'S DIRECT IN POJR/POR CIRCUIT
B B B C
BX120
f 4A

PSR'S NOT REQUIRED WHEN THE SUPPLY


B INVOLVES AUTOMATIC SIGNALLING ONLY
NX120
(B) t
'C'
120V PSR'S DETECT A TOTAL SUPPLY FAILURE
PSR
RR POR
C C C
RR
'A' 'B' 'C' BX120 NX120
POR (C)
120V 120V 120V RR f 4A t

C XING PSR PSR PSR POR C


B50(INT) N50(INT)
f 4A 4 1 4 1 4 1 R1 R2 t (XING)
50V
D1 D2
INT
RR PSR
RR
POJR
RR POJR POJR C C C
B50(INT) N50(INT)
f 4A t (C)
R1 R2
D6 D5
A1 50V
EXT
A7
PSR
B8
30" C
C C
B7 B50(EXT) N50(EXT)
f 4A t (C)

24V
RR DC
POJPR PSR
RR RR
RR POJPR POR POJR C C C
B24 N24
R1 R2 DIAG f 4A t DIAG
(C)
B1 B2 C1 C2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDU104 SHEET TITLE: POWER SUPPLY INDICATIONS EDMS No: SG0602002 SHEET No: U104 CIRCUIT BOOK No: 00001

##
WARN
50V 50V 50V 50V LXING
PSKR
A-C 24V 24V INT INT EXT EXT NO CHARGE
PSU LOC PSKR CH1 CH2 CH1 CH2 CH1 CH2 WARN KR PSU
B24 N24
f 4A 4 1 4 1 4 1 4 1 4 1 4 1 4 1 6 3 10 2 t (LOC)

INDICATES A SINGLE
LXING
CHANNEL FAILURE
BATTERY
TEST R

FAIL
A B C 50V 50V
A3 A4
PSKR
120V 120V 120V 24V INT EXT
PSU LOC PSR PSR PSR PSR PSR PSR PSU
B24 N24
f 4A 4 1 4 1 4 1 4 1 4 1 4 1 10 2 t (LOC)

INDICATES A TOTAL
FAILURE OF BOTH
CHANNELS OF A SUPPLY

PSU
FAIL WARN
NORMAL
PSU LOC PSR PSKR PSU
B24 G N24
f 4A 1 4 1 4 t (LOC)

PSU
5 5
WARN
Y

PSU
FAIL
R

MOUNTED IN DIAGRAM

## REQUIRED FOR STORE 74 BATTERY CHARGERS


WITHIN CIRCUIT BOUNDARY.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDU105 SHEET TITLE: POWER DISTRIBUTION - 415V (APPROVED LOCATIONS ONLY) EDMS No: SG0602002 SHEET No: U105 CIRCUIT BOOK No: 00001

BX NX
LOC "A" LOC "B"
120 120 CB
MAINS EXT. 120/415V MAINS EAST

BX 415 BX 415

120V 415V
CB
CB
10A IVAP *
100A 15A NX 415 NX 415

10KVA

# # #

ELD

415V 415V
IVAP * IVAP *
15A 15A

SE

415V 415V

120V 120V
TEST E
SE SE

BX 120 BX 120

NX 120 NX 120

LOC "C" LOC "D"

MAINS WEST

BX 415 BX 120

415V
CB
10A IVAP
15A
*
NX 415 NX 120

415V 120V 120V


IVAP * IVAP * IVAP *
15A 15A 15A
SE SE

*IVAP FOR LOCATIONS WITH ELECTRONIC EQUIPMENT BX 120


VAP FOR LOCATIONS WITHOUT ELECTRONIC EQUIPMENT
NX 120
415V
# ISOLATING SWITCH-HEINEMANN CF2 NON-AUTO CIRCUIT BREAKER CB
120V 15A
SE
EARTHED METAL ENCLOSURE WITH "CAUTION 415V"

BX 120

NX 120

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:38 DRG No: CSTDU107 SHEET TITLE: POWER SUPPLY ARRANGEMENT - 240V (LOC. XXX) EDMS No: SG0602002 SHEET No: U107 CIRCUIT BOOK No: 00001

POWER SUPPLY 240V


METER BOX 240V LOAD CENTRE

DSF
63A CB 32A CB ACTIVE 6A CB
SIGNALLING
L1 E1
GPO
MAIN
SWITCH

240V
GPO
240V
MAINS
* *
NOTE 3 NOTE 3

NEUTRAL

L2 E2
EARTH

NEUTRAL
LINK

MEN
NOTE 2 MEN

EARTH EARTH

20A/30mA RCD

GPO

10A/30mA RCD 240V


GPO
FLUORESCENT
LIGHT

CE

NOTE 1: ALL WIRING TO COMPLY WITH AS3000 WIRING RULES

CE

NOTE 2: WHERE THE EARTH CABLE BETWEEN THE METER BOX


AND LOAD CENTRE IS NOT INSTALLED DUE TO AS3000
WIRING RULES, A MEN LINK AND COUNCIL EARTH IS TO SE
BE PROVIDED AT THE LOAD CENTRE.

NOTE 3: THE PREFERRED ARRANGEMENT IS TO HAVE 240V MAINS


SURGE PROTECTION COMPONENT LIST
DIVERTER LOCATED IN THE METER BOX. IF HOWEVER THE
DISTANCE BETWEEN THE METER BOX AND THE LOAD CENTRE
EXCEEDS 20 METRES, THE 240V MAINS DIVERTER IS TO BE
LEGEND DESCRIPTION MAKER PART No.
LOCATED AT THE LOAD CENTRE. PLEASE INDICATE ON
THE COC THE ARRANGEMENT USED.
THE INCOMING & OUTGOING WIRING TO THE DIVERTER 240V MAINS SURGE TDS-MT-277 or
IS TO BE PHYSICALLY SEPARATED. * DIVERTER
ERICO
EQUIVALENT

DSF DINLINE SURGE FILTER ERICO DSF-6A-275V

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDU109 SHEET TITLE: EMERGENCY CHANGEOVER CONTACTOR (HS) 25 - 200A EDMS No: SG0602002 SHEET No: U109 CIRCUIT BOOK No: 00001

BX

LOAD SUPPLY

120V AC THE HIGH SPEED ECO MUST COMPLY WITH THE REQUIREMENTS FROM

EQUIPMENT SPECIFICATION - SPG 1755 'EMERGENCY


NX
CHANGEOVER CONTACTOR PANEL'

# HIGH TEMPERATURE RATED WIRE


R1 R3 1 3 A2 RESISTOR MOUNTED ON SUITABLE HEATSINK
NON SOLDERED MECHANICAL CONNECTIONS

ECO COIL *1
*1 SELECT REQUIRED ECO CONTACTOR FROM
TABLE BELOW:
R2 R4 2 4 A1

RATING ECO CONTACTOR


25A LC1-D25008F5 with LA1-DN40
R
1 2 65A LC1-D65008F5 with LA1-DN40
BX
EMERGENCY SUPPLY
80A LC1-D80008F5 with LA1-DN40
*2
NX 100A CV1-GB with 2 AUX CONTACTS
# #
NRJR
150A CV1-HB with 2 AUX CONTACTS

BX 200A CV1-JB with 2 AUX CONTACTS


NORMAL SUPPLY
1 4

NX
NCR

6 3 *2 RESISTOR VALUE POWER RATING TO


f1 f2 f3
EMERG LOAD
SUIT CONTACTOR COIL.
SUPPLY 4A 4A SUPPLY
4A THE RESISTOR MUST MEET THE SPECIFICATION.
AVAIL AVAIL
165R 100W HAS BEEN TESTED FOR 25 - 80A
NORMAL
30R 400W HAS BEEN TESTED FOR 100 - 200A
SUPPLY
2 10 VSR/Timer 2 10

A1 A2
VOLTAGE SENSING RELAY (VSR)
EMERG
500V ADJUSTMENTS: (PILZ SI UM)
SUPPLY

W 11 PICK UP VOLTS = 115V


4 1 RELEASE VOLTS = 100V
L1 Y1
14
TIME DELAY = 7 Seconds
Y2
SWITCH SETTINGS: S1 - 0.5
NRJR
ECO S2 - 1
AUX 2 NCR

63 64 9 11 2 7
NCR

15" MATERIALS

1 6 3 2 10 FUSES f1,f2,f3 SAKS1, 4A (KLIPPON)

SUPPLY TERMINALS ENTRELEC M35/16


W
2 NORMAL IND'R TERMINALS SAKC10 (KLIPPON)
L2
SUPPLY
RESISTOR TERMINALS SAK6N (KLIPPON)
ECO
AUX 1 RELAYS HH23 PW-T 110V

3 53 54 4 1 LED INDICATOR (L1,L2) 10-16mm GREEN (90-135V AC)

CONTACTOR TELEMECANIQUE

4 OMRON H3CR-A8

NORMAL SUPPLY
TIMERS
VSR/TIMER
5 6 3 PILZ SI UM
500V AC/DC

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDU115 SHEET TITLE: POWER SUPPLY ARRANGEMENT - 415V GENERAL SCHEMATIC EDMS No: SG0602002 SHEET No: U115 CIRCUIT BOOK No: 00001

GENERAL 415V POWER ARRANGEMENTS

FOR SIGNALLING

RAILWAY COUNCIL
NORMAL EMERGENCY
11KV/240V/415V 415V/240V

AUTOMATIC TRANSFER SWITCH 1 ALARMS

AUTO SELECTED

NORMAL SUPPLY AVAILABLE AND ON LINE

EMERGENCY SUPPLY AVAILABLE


ATS 1
ESSENTIAL SWITCHBOARD 1 SUPPLY AVAILABLE

NON-ESSENTIAL BUS

UPS ALARMS

UPS HEALTHY UPS


UPS ON BYPASS

UPS ON STANDBY BATTERY

ATS 2
NOTE: ALL ALARMS INDICATED NOTE: #1

INTO SIGNALLING SYSTEM OR

REMOTE MONITORING SYSTEM.


ELECTRICAL RESPONSIBILITY

3 PHASE UPS PREFERRED


HOWEVER SINGLE PHASE ACCEPTABLE ECO 1 ALARMS
FOR SMALL LOADINGS. ESSENTIAL SWITCHBOARD
UPS SUPPLY AVAILABLE AND ON LINE

BYPASS SUPPLY AVAILABLE

ESSENTIAL SWITCHBOARD 2 SUPPLY AVAILABLE

#2 #2 #2

SIGNALLING RESPONSIBILITY NORTH MAINS #3 LOCAL#3 SOUTH MAINS #3

SIGNALLING SUPPLIES

NOTE:

FOR COMPLETE POWER SUPPLY DETAILS, REFER TO SHEETS U116, U117 AND U118

NOTES:

#1 - ECO 1 TO HAVE CHANGEOVER IN LESS THAN 200mS

#2 - ISOLATION TRANSFORMERS TO EP17 00 00 11 SP

#3 - IT DISTRIBUTION MAINS LIMITED TO 4km LENGTH

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDU116 SHEET TITLE: POWER SUPPLY ARRANGEMENT - 415V EDMS No: SG0602002 SHEET No: U116 CIRCUIT BOOK No: 00001

ESSENTIAL SWITCHBOARD
(ELECTRICAL) ELECTRICAL POWER ROOM TO BE READ WITH
INCOMING
SHEET U117 #B
SIGNALLING SWITCHBOARD
415V SURGE
100A 6kA 0.67s
PROTECTION EARTHED METAL ENCLOSURE WITH LABEL "CAUTION 415V"
R W BU N E PANEL 4mm2
INTERNAL EXTERNAL
SIGNALLING ROOM
CABLE CABLE

#A #A TRF1 #A #A #2
CB1 CB1
240/415V
3
SAK35N
#A

#3 #1 415V TO LOC NORTH


f1 4A

#A #A
415V

f2 4A LOC
#2
BX BX120
BUS1 (110V AC) 1
4A f

NX NX120
CASE BUS2 2 (LOC)
(0V AC) t
2.5mm2
MRD ELD
AC/DC
AUTO-110
F

3
TEST DET ELD ALARM
A
E E
4

INTERNAL EXTERNAL
VIOLET
CABLE CABLE
#A #A TRF2 #A #A #2
CB2 CB2
240/415V
2
SAK35N
#A

#3 #1 415V TO LOC SOUTH


f1 4A

#A #A
415V

f2 4A LOC
#2
BX BX120
BUS1 (110V AC) 1
4A f

NX NX120
CASE BUS2 2 (LOC)
(0V AC) t
2.5mm2
MRD ELD
AC/DC
AUTO-110
F

3
TEST DET ELD ALARM
A
ELECTRICAL SIGNALLING E E
REFER TO 4
SHEET U117 #B
RESPONSIBILITY RESPONSIBILITY

TEST
ELD EARTH TERM
SAKG28
4mm2 VIOLET 4mm2 VIOLET

SIGNALLING

16mm 2 16mm 2 TO EARTH BUS


POTENTIAL
COMMS ENCLOSURE EQUALISATION
COMMS EARTH TERM CLAMP
16mm 2 SAK35N SAK35N 16mm 2
SAKG28

POWER EARTH SIGNALLING


NOTES: EARTH

#1 - ISOLATION TRANSFORMER.
NOTES FOR STANDARD DRAWING ONLY ALL EARTH CONDUCTORS TO
PRIMARY 240V 1ph 50Hz 2
EARTHBAR 7/1.70mm UNLESS 2.5mm - 1/1.78mm
2
SHOWN OTHERWISE 4mm - 7/0.85mm
#2 - SCREEN CONNECTED TO SIGNALLING EARTH BUS #A - RATING AND SIZE TO SUIT SPECIFIC DESIGN
2
6mm - 7/1.04mm
AT SUPPLY END ONLY
2
#B - SHOW SHEET REFERENCES THAT APPLY TO APPLICATION ALL INTERNAL WIRING 10mm - 7/1.35mm
2
#3 - SD-125S VNOM - 275V AC IS 7/0.40mm UNLESS 16mm - 7/1.70mm
KVM 25kA VMAX. 275V AC SHOWN OTHERWISE 2
50mm - 19/1.78mm

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDU117 SHEET TITLE: POWER SUPPLY ARRANGEMENT - 415V (POWER LOCATION) EDMS No: SG0602002 SHEET No: U117 CIRCUIT BOOK No: 00001

ESSENTIAL SWITCHBOARD ELECTRICAL POWER ROOM


(ELECTRICAL) TO BE READ WITH

SHEET U116 #B

REFER TO SHEET U116 #B

415V SURGE SIGNALLING SWITCHBOARD


100A 6kA 0.67s
PROTECTION
R W BU N E
EARTHED METAL ENCLOSURE WITH LABEL "CAUTION 415V" SIGNALLING ROOM
PANEL

#3
BX120
#A #A TRF3 #A #A
CB1 CB1
240/120V
1 LOCAL
#A VAR(1)
SIOVB32K150 SIGNALLING
#3 #1

NX120
#A #A

#2
WBX120
#A
CB2
LOCAL
VAR(2)
CASE SIOVB32K150
POINTS
2.5mm 2

WNX120
CASE #A
2.5mm2

2.5mm 2 LABEL 'TEST INSTRUMENTS ONLY' LABEL 'TEST INSTRUMENTS ONLY'


CB2 CB3
#C #C

#A #A 2.5mm2
2c+E

2c+E

POWER ROOM LIGHTS SIGNALLING ROOM LIGHTS

LIGHT SW 36W FLUORESCENT LIGHT SW 36W FLUORESCENT


FITTING FITTING

CB4

1.5mm 2

#A

EARTH TERMINAL 1.5mm 2 EARTH TERMINAL


2c+E

POWER EARTH

2c+E

NOTES: NOTES FOR STANDARD DRAWING ONLY

#1 - ISOLATION TRANSFORMER. RELAY ROOM LIGHTS, RELAY ROOM SPO'S,


PRIMARY 240V 1ph 50Hz RATING AND SIZE TO SUIT SPECIFIC DESIGN POWER ROOM LIGHTS, POWER ROOM SPO'S
#A -
ARE WIRED FROM THE NON-ESSENTIAL SWITCHBOARD.
#2 - SCREEN CONNECTED TO POWER EARTH #B - SHOW SHEET REFERENCES THAT APPLY TO APPLICATION
HOWEVER, WHERE THIS IS NOT POSSIBLE, WIRE FROM THE ALL EARTH CONDUCTORS TO 2
2.5mm - 1/1.78mm
#3 - SD-125S VNOM - 275V AC #C - TEST INSTRUMENT OUTLETS ARE NOT FOR GENERAL USAGE ESSENTIAL SWITHCBOARD AS SHOWN HERE. LOAD LIMIT EARTHBAR 7/1.70mm UNLESS 2
4mm - 7/0.85mm
KVM 25kA VMAX. 275V AC SPO TO BE COLOURED RED BY CIRCUIT BREAKER, IF NECESSARY. SHOWN OTHERWISE 2
6mm - 7/1.04mm

ONE SPO PER ITEM OF EQUIPMENT (EG MODEM ETC) 10mm


2
- 7/1.35mm
#4 - RCD- 2 POLE 10A 30mA Trip
ALL INTERNAL WIRING 16mm
2
- 7/1.70mm
2
IS 7/0.40mm UNLESS 50mm - 19/1.78mm
SHOWN OTHERWISE

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDU118 SHEET TITLE: POWER SUPPLY ARRANGEMENT - 415V (THROUGH LOCATION) EDMS No: SG0602002 SHEET No: U118 CIRCUIT BOOK No: 00001

SIGNALLING
415V SWITCHBOARD (SIGNALS) 120V SWITCHBOARD POWER ROOM SIGNALLING ROOM

#1
RACK 1
#A BX415 BX415 #A 6mm 2 6mm2 16mm 2
CB1 415/120V CB #5
NX415
BX415 4KVA
BX120
FROM 120V
UPSTREAM #4 SURGE
LOCATION NX415 PANEL VAR

#A #A SIOVB32K150
#2 #6 #6
ISOLATING NX415
SWITCH NX120
CASE CASE
2.5mm 2 2.5mm2 2.5mm 2

16mm2
SIGNALLING SUBSIDIARY EARTH BAR TO
100A 240V SWITCHBOARD PRIMARY
16mm 2
NON-AUTO EARTH BAR
CASE
2.5mm 2 BX240 NX240
2.5mm 2
LABEL 'LIGHT LOADS ONLY' LABEL 'LIGHT LOADS ONLY'
CB1

#A

2.5mm 2
2c+E

415/240V
#A 6mm 2 6mm 2
CB2 1000VA RCD
#1 #2

2c+E

#A #3 POWER ROOM LIGHT


CB2

LIGHT SW 36W FLUORESCENT


#A FITTING

UNPROTECTED 1.5mm2
NEUTRAL BAR

PROTECTED
SIGNALLING ROOM LIGHTS

M EN LINK 6mm 2
NEUTRAL BAR
LIGHT SW 36W FLUORESCENT
EARTH TERMINAL FITTING
2c+E

1.5mm 2
CASE
ISOLATING 2.5mm 2 2.5mm 2

SWITCH

CASE
2.5mm 2

EARTH TERMINAL
2c+E

100A
NON-AUTO

MAIN POWER EARTH


#A NOTES:
BX415 #1 - ISOLATING TRANSFORMER TO EP17 00 00 11 SP

TO
#4 #2 - SHIELD CONNECTED TO SIGNALLING EARTH
DOWNSTREAM
LOCATION NX415
NOTE FOR STANDARD DRAWING ONLY #3 - 30MA TRIP RCD

#A - RATING AND SIZE TO SUIT SPECIFIC DESIGN


7/0.85mm - 4mm 2
#4 - CABLE BETWEEN LOCATIONS. CABLE IS
7/1.70mm - 16mm 2
IDENTIFIED AS 415V AT EACH END.
19/1.78mm - 50mm 2
37/2.52mm - 185mm 2
MAIN POWER EARTH #5 - SURGE PROTECTOR. EACH LEG
TO EARTH AND LINE TO LINE. ALL EARTH CONDUCTORS TO
EARTHBAR 7/1.70mm UNLESS
#6 - CABLE TIED TOGETHER FOR SHOWN OTHERWISE
SURGE PROTECTION REASONS.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV001 SHEET TITLE: TRAIN STOP SUPPRESSION - TYPICAL ARRANGEMENTS EDMS No: SG0602002 SHEET No: V001 CIRCUIT BOOK No: 00001

1
1AT 1BT

*1

Y
R
Y
R
2 3

2
2 VR
VR
2
PSU LOC HR 1AT PSU
B50 N50
f 4A R1 R2 t (LOC)

B1 B2
B1 B2
2 2
VSnR VSnR

B1 B2 B3 B4
2
2
2 VSnR 2 V
VSnR C1 C3 C5 C7
1 2 2
PSU LOC HR PSU PSU LOC VR LOC LOC VR PSU
B50 N50 BX120 M NX120
(LOC) # # (LOC)
f 4A R1 R2 t f 4A C2 C4 9 10 C6 C8 t

B1 B2
1AT
2 # DENOTES 7/0.85mm

VSnR
2 VNR/VRR
B1 B2 2
2 VSnJR VSnJR
FOR VNR/VRR CIRCUIT, SEE SHEET V002.
2 A1 A2

VSnR

R1 R2

A3 A4

2 2 2 2
VNR VSnR VSnJR HR
2
2 HR
VSnJR

A6 A5 A6 A5 A6 A5 R1 R2

A1 A2

2 2
2 NGPR 2
HR UCR NGPR
2
PSU LOC VNR 2 2 3
B50
VSnR VSnJR HR
f 4A D6 D5 A6 A5 R1 R2
3 HR 2
B1 B2 VCSR
2
VSnJR D6 D5 D6 D5 R1 R2

B1 B2

B1 B2
2
VSnR *2 D7 D8 D7 D8

B4 B3

PROVING: THE SUPPRESSION IS PROVED NORMAL BEFORE ALLOWING A TRAIN


C1 C2
UP TO THE SIGNAL IN THE FACING DIRECTION
2
PSU VNR 1AT
N50
(LOC) t D7 D8 A7 A8
1AT

B4 B3
R1 R2
2 *1 TRAINSTOP IS NOT TO BE PROVED
A1 1 A2 1 1 1 2 2
VSnJR SUPPRESSED IN SIGNAL 1 BUT
SHOULD BE PROVED IN HIGHER
EX RECEIVER HR HDR DR VCSR HR HDR
2
ASPECTS.
B4 B3
VNR
2 *2 REQUIRED WHEN TRAINSTOP

VSnR CONTACTOR IS NOT PROVIDED


*2 A6 A5 A6 A5 A6 A5 A6 A5 A6 A5 A6 A5

NOTE 1: IF SIGNAL 3 DOES NOT EXIST, NOTE 2: IF LAYOUT IS AS SHOWN, AND VCSR IS NOT PROVIDED C1 C2
2
THERE IS NO NEED TO PROVIDE ON SIGNAL 2, FOR SIGNAL 3. THEN 1AT TRACK STICK
C4 C3 VSnJR
TRACK STICK ON 1AT AND WILL HAVE TO BE AS SHOWN, OTHERWISE FOR A
SIGNAL 2 'SUPPRESSED' TRAIN MOVEMENT FOR SIGNAL 1, TRACK 1AT
WILL NOT ENERGISE.
C1 A2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV002 SHEET TITLE: TRAINSTOP DETECTION (WITH SEALED CIRCUIT CONTROLLER) EDMS No: SG0602002 SHEET No: V002 CIRCUIT BOOK No: 00001

VNR/VRR

SW1 SW2
VRR VNR

PSU LOC LOC RSA RSA LOC PSU


N-RI N
B50(EXT) N50(EXT)
f 4A 1 7 8 1 2 2 A8 A7 R2 R4 t (LOC)

N-RI N

3 3 4 5 6 4

VNR VRR
R R-NI
LOC

5 6 3 4
6 5 D8 D7 R1 R3

R R-NI

1 2 7 8
8 7

(ENCAPSULATED)

V CIRCUIT CONTROLLER

(WITH RSA STUDS)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV060 SHEET TITLE: WARNING LIGHTS - CONTROL & OPERATING - RELAY & MICROLOK EDMS No: SG0602002 SHEET No: V060 CIRCUIT BOOK No: 00001

1152 1152
A SIDE B SIDE 23.063 (UP)
8B WLR
23.063 (UP)
WLR + 1152
N12
O/P8 C6
R1 R2 t48 (1152)
23.063 (UP) #1
WLR +
O/P8 C6 1 2

8A 1N4007

STANDARD VITAL STANDARD VITAL


OUTPUT PCB (2) OUTPUT PCB (2)
MKII SLOT 6 MKII SLOT 6

UP ILLAWARRA
23.063 (UP) WLE
23.063 (UP) 1152 23.063 (UP)
1152 1152 WLR LOC
BLACK
WL
BX120
f31 4A 1 1

A1 A2
23.063 KM
W WE

23.063 (UP)
1152 WL
WHITE
LAMP TYPE : LED
NX120
(1152) t27 2 2

B2 B1

(ALTERNATIVE WHERE
RELAY DRIVEN)
16BT 16CT 1160AT 1160BT 1160CT
SD11 SD11 1158 1158 1152 1152
BX120
f38 4A

B1 B2 B1 B2 B1 B2 B1 B2 B1 B2
23.063 KM
W WE

LAMP TYPE : LED


NX120
(SD11) t38

B4 B3 B4 B3 B4 B3 B4 B3 B4 B3

1152
TUNNEL TYPE
NOTE:
ALL INTERNAL WIRING #1 WEIDMULLER PARTS
ALSO USED IN CITY WHERE 120V
ETFE TEFLON COATED 1N4007 DIODES SIGNIFICANT WHITE BACKGROUND 2 WAY YELLOW
1.23mm SQ, 19/29AWG LIGHT OCCURS Y Y
ZAP/TW2 PARTITIONS TUNNEL TYPE
600V GRADE UNLESS LED UNITS
ZTR2.5/D DIODE DISCONECTORS
SHOWN OTHERWISE
ZQV2.5/2 CROSS CONNECT

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV061 SHEET TITLE: WARNING LIGHTS - PROVING - RELAY & MICROLOK EDMS No: SG0602002 SHEET No: V061 CIRCUIT BOOK No: 00001

UM PSU(2)
UM B24(2)
1152 1152
BX120 120V B24
f1 4A
f 4A 1160CT RX
1160CT RX
f2 4A ARR
f3 R1 R2
4A
RACK 2 BLACK
*2
A+ V1 3 2 9 V1 1 V1
f4 4A

UM N24(2) 1 2
1152 1 C #1 2
SEE 5 TUNING
NX120 0V N24 R1
t1 KRV 2600Hz SCREEN MATCHING TO
(1152) KRV SE **
t
TEST E UNIT TRACK
t2
TABLE R2 UNIT *1
STORE 93 POINT C2 4 3 3 2600Hz
THRU LINK
##
t3 MODULE
2
WHITE
*2
A- V2 4 1 10 V2 4 V2
t4
@
L- L+
1160CT RELAY 1160CT
2c 7/0.5mm 2c 7/0.5mm
#2 SE

R1 R2

#4
1 2

1N4007

1160CT

A4 A3

23.063(UP)
WLR

B5 B6 1152 1152
ALTERNATIVE PROVING
A SIDE B SIDE

23.063(UP)
WLR

1152 1152
B50 I/P3+
B B B
f 4A B6 B5 #3 A2

23.063(UP)
WLC

1152 W W W
NX120 I/P3-
(1152) t B7 B8 #3 A4

I/P3+
B
A2
NOTE: 23.063(UP)
THIS CIRCUIT ONLY REQUIRED
WLC
WHERE PROVING OF WARNING LIGHT
RELAY IS NEEDED IN DATA AS
W
LOCAL TRACK RELAY NOT AVAILABLE
I/P3-
A4

VITAL VITAL
## OCTAL BASE LOOPS INPUT PCB (3) INPUT PCB (3)
MKII SLOT 10 MKII SLOT 10

#1 ELSAFE 290V RMS ARRESTOR


3 2
MODULE AND BASE PART Nos.
BASE - 216600 4 1 *1 7/0.85mm GREEN/YELLOW
MODULE - 216620 (GREY) SCREEN *2 37/1.78mm PVC
5 8

#2 ARRESTOR EARTHED MECHANICALLY TO THE MOUNTING RAIL


6 7 1
MOUNTING RAIL ELECTRICALLY CONNECTED TO MAIN EARTH ALL INTERNAL WIRING
**
TERMINALS 2 & 3 MUST 5
NOT BE EXTERNALLY CONNECTED ETFE TEFLON COATED
#3 WEIDMULLER PARTS ZTR 2.5 1.23mm SQ, 19/29AWG
@ CABLE SCREEN SHOULD NOT 4
BE EARTHED AT M.U. 600V GRADE UNLESS
3Y20-290GT
1-2, 3-4, 5-6-7-8
#4 DIODE TO BE MOUNTED DIRECTLY BEHIND RELAY APPLY A HEAT SHRINK TUBING SHOWN OTHERWISE
GREEN/YELLOW 7/0.85mm

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV070 SHEET TITLE: EMBANKMENT SLIP DETECTORS EDMS No: SG0602002 SHEET No: V070 CIRCUIT BOOK No: 00001

58.6A
LED

58.6A DETR NR 58.6A


DETR
NR
58.6A SLIP 58.6A SLIP
LOC LOC 58.6A DETECTOR 58.6A LOC LOC 58.6A DETECTOR 58.6A LOC N50
B50 (EXT)
(EXT) N N (LOC)
f 4A R2 R4 t

2 5

58.6B
LED

58.6B DETR NR 58.6B


DETR
NR
58.6B SLIP 58.6B SLIP
LOC LOC 58.6B DETECTOR 58.6B LOC LOC 58.6B DETECTOR 58.6B LOC N50
B50 (EXT)
(EXT) N N (LOC)
f 4A R1 R3 t

2 5

58.6 EMERG. SWITCH R 58.6


58.6 58.6
EMERG. SW
EMERGENCY R EMERGENCY
LOC
SWITCH LOC LOC
SWITCH
N50
B50 (EXT)
(EXT) f 4A R1 R2 t (LOC)

58.6 SLIP NR
58.6 EMERG 58.6 SLIP 58.6
SW R ALARM R SLIP NR
58.6A DETR 58.6B DETR
LOC NR NR LOC RR
B50
(EXT) f 4A A6 A5 D8 D7 R1 R3

C1 C2 A1 A2

58.6 58.6 SLIP


SLIP NR ALARM R
58.6 SLIP ALARM R
58.6 EMERG A2 A1
SW R
58.6B DETR 58.6A DETR A7 A8 R4 R2

N50 NR NR
(EXT)
(LOC) t A7 A8

A4 A3 C4 C3

58.6 SLIP DETECTORS


SIGNAL PROTECTING SLIP SITE 58.6
660(M)B SLIP NORMAL N24

UCR RR NR CP DIAG
58.6 660(M)B A3 A4
B24 G
SLIP NR RUR f 4A

A3 A4
R1 R2
58.6
A1 A2 SLIP
B1 B2
58.6 ALARM R
EMERG ALARM
SW R
R
B8 B7 C8 C7

B1 B2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV071 SHEET TITLE: SLIP DETECTOR AND RAINFALL DATA LOGGER EDMS No: SG0602002 SHEET No: V071 CIRCUIT BOOK No: 00001

SLIP DETECTORS, WATER


LEVEL DETECTORS AND DATA LOGGER
WIND SPEED AND INPUT TERMINALS
DIRECTION INPUTS
(SEE SHT 365D_2)

16

D GND
17

RAINFALL MON
15MIN WARN

8 11
D1
18

RAINFALL MON
15MIN ALARM

8 11
D2
19

RAINFALL MON
8HR WARN

8 11
D3
20

RAINFALL MON
8HR ALARM

8 11
D4
21

PLC
11
HSC
22

23

INCLINOMETER
PRESSURE TRANSDUCERS
(SEE SHT 365D_2)

27
DATA LOGGER
ISOLATION TX
120V/120V

CC CC
BX120
Af5 4A 29

CC
NX120
(CC) At5 30

200VA

COAL CLIFF DATA LOGGER

DATA TAKER DTB0

DATA TAKER CEM20

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV072 SHEET TITLE: SLIP DETECTOR AND RAINFALL DATA LOGGER EDMS No: SG0602002 SHEET No: V072 CIRCUIT BOOK No: 00001

WG633 WG633 C21 CCRR MOUNTED ON THE


PIEZO
WATER LEVEL 2 ##
WG637 WG645 WG645A WG651
ROOF OF COAL CLIFF RR.
2 15 15 B18 B28 12
1
STONEY CREEK
1 1 24 11
59.6C 3
59.6C SD WG645 LOGGER
B17 B27
SLIP DETECTOR ##
3 3 3 5 10
TRANSDUCER 16
1 WIND DIRECTION
TO BE INSTALLED 6 6 6

15
59.6B 2
59.6B SD
B16 B26
SLIP DETECTOR ##
3 3 3 6 9
TRANSDUCER 14
1
WIND SPEED
TO BE INSTALLED 6 6 6

13
59.6A 1
59.6A SD
B15 B25
SLIP DETECTOR ##
3 3 3 7 8
TRANSDUCER 1
TO BE INSTALLED 6 6 6
GEO 3 COALCLIFF DATA LOGGER
GEOTECH TECH WG665 WG665 WG661 CCRR
46 A46
PRESSURE ##
9 9 9 25
TRANSDUCER 2 I/P
TERM
FUNCTION
DN SIDE 10 10 10

1 57.7A SLIP DETECTOR N


4
GEOTECH 31 B31 2 57.7A WATER LEVEL DETECTOR N
INCLINOMETER ##
7 7 7 27 3 57.7B SLIP DETECTOR N
TRANSDUCER 32 B32
2
8 8 8 26 4 57.7C - 58.6A SLIP DET./RFM +VE
5
45 A45 5 57.7C SLIP DETECTOR N

11 ##
11 11 23 6 58.6B SLIP DETECTOR N
2 INPUTS TO
12 12 12 7 58.6A SLIP DETECTOR N
COALCLIFF
DATA LOGGER 8 59.6A SLIP DETECTOR N
58.6B 6
SD
(SEE SHT 365D_1)
44 A44 9 59.6B SLIP DETECTOR N
PRESSURE
11 ##
TRANSDUCER 11 11 24 10 59.6C SLIP DETECTOR N
2 58.6A
UP SIDE 1
12 12 12 SD WG665 WG665 CCRR 11 STONEY CREEK RFM/59.6A - 59.6C SLIP DET. +VE
A19
58.6A
9 ##
SLIP DETECTOR 9 9 7 12 STONEY CREEK WATER LEVEL DETECTOR N
2
TRANSDUCER
10 10 10 13 WIND SPEED +VE

14 WIND SPEED N
58.6B 2
SD 15 WIND DIRECTION +VE
A29
58.6B
9 ##
SLIP DETECTOR 9 9 6 16 WIND DIRECTION N
2
TRANSDUCER
10 10 10 17 PLC/RFM (15MIN/8HR) GND
57.7C 1
SD WG673 WG673 WG661 18 RFM 15MIN WARN
38 48 B48
57.7C
9 ##
SLIP DETECTOR 9 9 37 47 B47 5 19 RFM 15MIN ALARM
2
TRANSDUCER
10 10 10 4 20 RFM 8HR WARN

21 RFM 8HR ALARM


57.7B 2
SD 22 PLC RAINFALL COUNT/TIPS
39 49 B49
57.7B
9 ##
SLIP DETECTOR 9 9 3 23 INCLINOMETER
2
TRANSDUCER
10 10 10 24 PRESSURE TRANSDUCER UP SIDE

25 PRESSURE TRANSDUCER DN SIDE


3
B16 26 NEGATIVE SUPPLY INCLINOMETER N24
57.7A
11 ##
WATER LEVEL 11 11 2 27 POSITIVE SUPPLY INCLINOMETER B24
2
DETECTOR
12 11 12 28 SPARE

29 BX120 DATA LOGGER ISOL. TX


57.7A 4
SD 30 NX120 DATA LOGGER ISOL. TX
B15
57.7A
9 ##
SLIP DETECTOR 9 9 1
2
TRANSDUCER
10 10 10 ##1 UTB-15

##2 RTB-30-S3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:39 DRG No: CSTDV073 SHEET TITLE: SLIP DETECTOR AND RAINFALL DATA LOGGER EDMS No: SG0602002 SHEET No: V073 CIRCUIT BOOK No: 00001

DATA LOGGER ISOLATION TX


120V/120V, 200VA

SH SH
1
BX120
Bf9 4A

SH
NX120
(SH) 2
Bt9

WG627 WG622 SCARBOROUGH RR


61.658 SD B21 B21 t3
61.658
SLIP DETECTOR
TRANSDUCER
B22 B22 t4

61.715 SD
61.715
SLIP DETECTOR t5
TRANSDUCER
B23 B23

WG622
*
62.4 SD 10
10 b1 b
62.4
SLIP DETECTOR 10 # t6
TRANSDUCER
9 a1 a B20
9 9

WG612 SCARBOROUGH RR
*
63.6A SD 63.6 63.6
6 b1 b
63.6A
SLIP DETECTOR 6 6 #
TRANSDUCER
3 a1 a SCARBOROUGH
3 3
DATA LOGGER
A31

* ENCLOSURE
63.6B SD C1 t7
6 b1 b
63.6B
SLIP DETECTOR 6 6 #
TRANSDUCER
3 a1 a
3 3

A32

* t8
64.4 SD 64.4 C2
10 b1 b 64.4
64.4 WG609
SLIP DETECTOR 10 10 #
TRANSDUCER
9 a1 a A2 B11 B10 t9
9 9

609CT 609CT
*
65.4A SD 15 15 A11 A11 A11 A11 A11
b1 b t10
65.4A
SLIP DETECTOR 15 #
TRANSDUCER
14 a1 a B5 B5 B5 t11
14 14

t12(DGND)
SCARBOROUGH
RAINFALL
GAUGE
t13

1
t14

SCARBOROUGH
WIND t15
2
SPEED
AND 3
t16
DIRECTION

t17
4

* SD TRANSDUCER SURGE PROTECTION

UTB-15
#

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW008 SHEET TITLE: POINTS OPERATION - SIEMENS M3A MK2 - SINGLE END EDMS No: SG0602002 SHEET No: W008 CIRCUIT BOOK No: 00001

N-RI
SINGLE LEFT HAND

1 5
7/0.85 LOC MOTOR/CAPACITOR

2 6 2 6-2 6-1 3-3


C1 C3 C1 C3

3 IR NWR 7
4 8
C2 C4 C2 C4

R-NI M

7/0.85
9

85
7-1 7-2

7/0.
10 3 3-2
C1 C3

RWR 11
PSU LOC 7/0.85
12
WBX120
C2 C4
f 20A

20A DP

PSU 7/0.85
WNX120
(LOC) t CUT
OFF

7/0.85 7/0.85
17 13

18 14 1 5-1 5-2 5
C7 C5

19 IR 15
20 16
C8 C6

SINGLE RIGHT HAND


R-NI

7/0.85
1 5

2 6 2 6-2 6-1 3-3


MOTOR/CAPACITOR
C1 C3 C1 C3

3 IR NWR 7
4 8
C2 C4 C2 C4

N-RI M

7/0.85
9
85

7-1 7-2
7/0.

10 3 3-2
C1 C3

RWR 11
PSU LOC 7/0.85 12
WBX120
C2 C4
f 20A

20A DP

PSU 7/0.85
WNX120
(LOC) t CUT
OFF

7/0.85 17 13 7/0.85

18 14 1 5-1 5-2 5
C7 C5

19 IR 15
20 16
C8 C6
ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW010 SHEET TITLE: POINTS DETECTION (LOCAL) - SIEMENS M3A MK2 - DOUBLE END EDMS No: SG0602002 SHEET No: W010 CIRCUIT BOOK No: 00001

DOUBLE LEFT HAND

101 101
A END B END
RKR NKR
101
PSU LOC LOC 7-8 7-7 9-5 9-6 8-3 8-4 LOC 7-8 7-7 9-5 9-6 8-3 8-4 LOC NWR
B50
f 4A 10 12 16 22 10 12 16 22 A6 A5 R2 R4

A1 A2
N N N-RI N N N-RI
101 101
NKR RKR
101
R R R-NI R R R-NI
RWR

D5 D6 R3 R1

6-8 6-7 8-6 8-5 9-4 9-3 6-8 6-7 8-6 8-5 9-4 9-3
9 11 15 21 9 11 15 21 A2 A1

6-5 6-6 9-2 9-1 6-5 6-6 9-2 9-1

4 7 19 17 4 7 19 17

N-RI N N-RI N

R-NI R R-NI R

PSU
N50
(LOC) 7-6 7-5 8-1 8-2 7-6 7-5 8-1 8-2
t 6 8 20 18 6 8 20 18

DOUBLE RIGHT HAND

101 101
A END B END
RKR NKR
101
PSU LOC LOC 7-8 7-7 9-5 9-6 8-3 8-4 LOC 7-8 7-7 9-5 9-6 8-3 8-4 LOC NWR
B50
f 4A 10 12 16 22 10 12 16 22 A6 A5 R2 R4

A1 A2
R R R-NI R R R-NI
101 101
NKR RKR
101
N N N-RI N N N-RI
RWR

D5 D6 R3 R1

6-8 6-7 8-6 8-5 9-4 9-3 6-8 6-7 8-6 8-5 9-4 9-3
9 11 15 21 9 11 15 21 A2 A1

6-5 6-6 9-2 9-1 6-5 6-6 9-2 9-1

4 7 19 17 4 7 19 17

R-NI R R-NI R

N-RI N N-RI N

PSU
N50
(LOC) 7-6 7-5 8-1 8-2 7-6 7-5 8-1 8-2 NOTE: QBA1 RELAYS MAY ALSO BE USED
t 6 8 20 18 6 8 20 18

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW011 SHEET TITLE: POINTS DETECTION (LOCAL) - SIEMENS M3A MK2 - SINGLE END EDMS No: SG0602002 SHEET No: W011 CIRCUIT BOOK No: 00001

SINGLE LEFT HAND


101 101
RKR NKR
101
PSU LOC LOC 7-8 7-7 9-5 9-6 8-3 8-4 LOC NWR
B50
f 4A 10 12 16 22 A6 A5 R2 R4

A1 A2
N N N-RI
101 101
NKR RKR
101
R R R-NI
RWR

D5 D6 R3 R1

6-8 6-7 8-6 8-5 9-4 9-3


9 11 15 21 A2 A1

6-5 6-6 9-2 9-1

4 7 19 17

N-RI N

R-NI R

PSU
N50
(LOC) 7-6 7-5 8-1 8-2
t 6 8 20 18

SINGLE RIGHT HAND


101 101
RKR NKR
101
PSU LOC LOC 7-8 7-7 9-5 9-6 8-3 8-4 LOC NWR
B50
f 4A 10 12 16 22 A6 A5 R2 R4

A1 A2
R R R-NI
101 101
NKR RKR
101
N N N-RI
RWR

D5 D6 R3 R1

6-8 6-7 8-6 8-5 9-4 9-3


9 11 15 21 A2 A1

6-5 6-6 9-2 9-1

4 7 19 17

R-NI R

N-RI N

PSU
N50
(LOC) 7-6 7-5 8-1 8-2
t 6 8 20 18

NOTE: QBA1 RELAYS MAY ALSO BE USED

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW060 SHEET TITLE: POINTS DETECTION (LOCAL) - EP CATCHPOINTS - LH 'A' VALVE EDMS No: SG0602002 SHEET No: W060 CIRCUIT BOOK No: 00001

101 101 101


MASTER 'A' VALVE 101 MASTER 'A' VALVE 101 MASTER 'A' VALVE
LOC UNIT & EOL DETECTOR UNIT & EOL OPERATING BAR UNIT & EOL LOC

PRESSURE 101 101 101


SWITCHES LHCB RHCB LHCB RHCB RWR RKR NKR
101
3 8 7 2 1 8 7 2 1 NWR

1B 4B 4B 2B 4B
B5 B3 C7 C1 A1 D6 D5 A6 A5 R2 R4

PSU LOC 1 D3 D4
B50(EXT) R R-NI R R-NI
3B 101 101
f 4A A16 101
2
NWR NKR RKR
6 5 4 3 6 5 4 3

1W 3B 3B 1B
B6 B1 C5 C3 A3

N C5 C6 D5 D6 R3 R1
N-RI N N-RI N
D4 D3

3 2 1 8 7 2 1 8 7

2B 3W 3W
B7 B2 C6 1W C4 A4

PSU 1
N50(EXT) N-RI N N-RI N
(LOC) 3W
t A19

Pt 12pr 2 4 3 6 5 4 3 6 5
CABLE
2W 4W 4W 2W 4W
101 WM B8 B4 C8 C2 A2

R Pt 8pr Pt 8pr Pt 8pr Pt 8pr Pt 12pr


CABLE R R-NI CABLE CABLE R R-NI CABLE CABLE
101 WD 101 WD 101 WOB 101 WOB 101 WM

NOTE: QBA1 RELAYS MAY ALSO BE USED ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW061 SHEET TITLE: POINTS DETECTION (LOCAL) - EP CATCHPOINTS RH ('A' VALVE) EDMS No: SG0602002 SHEET No: W061 CIRCUIT BOOK No: 00001

101 101 101


MASTER 'A' VALVE 101 MASTER 'A' VALVE 101 MASTER 'A' VALVE
LOC UNIT & EOL DETECTOR UNIT & EOL OPERATING BAR UNIT & EOL LOC

PRESSURE 101 101 101


SWITCHES LHCB RHCB LHCB RHCB RWR RKR NKR
101
3 8 7 2 1 8 7 2 1 NWR

1B 3B 3B 1B 4B
B5 B1 C5 C1 A1 D6 D5 A6 A5 R2 R4

PSU LOC 1 D3 D4
B50(EXT) N N-RI N N-RI
3B 101 101
f 4A A16 101
2
NWR NKR RKR
6 5 4 3 6 5 4 3

1W 4B 4B 2B
B6 B3 C7 C3 A3

N C5 C6 D5 D6 R3 R1
R-NI R R-NI R
D4 D3

3 2 1 8 7 2 1 8 7

2B 4W 4W 2W
B7 B4 C8 C4 A4

PSU 1
N50(EXT) R-NI R R-NI R
(LOC) 3W
t A19

Pt 12pr 2 4 3 6 5 4 3 6 5
CABLE
2W 3W 3W 1W 4W
101 WM B8 B2 C6 C2 A2

R Pt 8pr Pt 8pr Pt 8pr Pt 8pr Pt 12pr


CABLE N N-RI CABLE CABLE N N-RI CABLE CABLE
101 WD 101 WD 101 WOB 101 WOB 101 WM

NOTE: QBA1 RELAYS MAY ALSO BE USED ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW062 SHEET TITLE: POINTS DETECTION (LOCAL) - EP SINGLE END - LH 'A' VALVE EDMS No: SG0602002 SHEET No: W062 CIRCUIT BOOK No: 00001

101 101
MASTER 'A' VALVE 101 MASTER 'A' VALVE
LOC UNIT & EOL DETECTOR UNIT & EOL LOC

PRESSURE 101 101 101


SWITCHES LHCB RHCB RWR RKR NKR
101
3 8 7 2 1 NWR

1B 4B 4B
B5 B1 A1 D6 D5 A6 A5 R2 R4

PSU LOC 1 D3 D4
B50(EXT) R R-NI
3B 101
f 4A A16 101
2
NKR RKR
6 5 4 3

1W 3B
B6 B3 A3

N C5 C6 D5 D6 R3 R1
N-RI N
D4 D3

3 2 1 8 7

2B 3W
B7 B4 A4

PSU 1
N50(EXT) N-RI N
(LOC) 3W
t A19

Pt 12pr 2 4 3 6 5
CABLE
2W 4W 4W
101 WM B8 B2 A2

R Pt 8pr Pt 8pr Pt 12pr


CABLE R R-NI CABLE CABLE
101 WD 101 WD 101 WM

NOTE: QBA1 RELAYS MAY ALSO BE USED ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW063 SHEET TITLE: POINTS DETECTION (LOCAL) - EP SINGLE END - RH 'A' VALVE EDMS No: SG0602002 SHEET No: W063 CIRCUIT BOOK No: 00001

101 101
MASTER 'A' VALVE 101 MASTER 'A' VALVE
LOC UNIT & EOL DETECTOR UNIT & EOL LOC

PRESSURE 101 101 101


SWITCHES LHCB RHCB RWR RKR NKR
101
3 8 7 2 1 NWR

1B 3B 4B
B5 B1 A1 D6 D5 A6 A5 R2 R4

PSU LOC 1 D3 D4
B50(EXT) N N-RI
3B 101
f 4A A16 101
2
NKR RKR
6 5 4 3

1W 4B
B6 B3 A3

N C5 C6 D5 D6 R3 R1
R-NI R
D4 D3

3 2 1 8 7

2B 4W
B7 B4 A4

PSU 1
N50(EXT) R-NI R
(LOC) 3W
t A19

Pt 12pr 2 4 3 6 5
CABLE
2W 3W 4W
101 WM B8 B2 A2

R Pt 8pr Pt 8pr Pt 12pr


CABLE N N-RI CABLE CABLE
101 WD 101 WD 101 WM

NOTE: QBA1 RELAYS MAY ALSO BE USED ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW075 SHEET TITLE: POINTS CONTROL & DETECTION - THROUGH CIRCUITS EDMS No: SG0602002 SHEET No: W075 CIRCUIT BOOK No: 00001

RR LOC

101 101 101 101 101


RLR EOLJPR NKR RCR NCR
101 50AT 60AT 50 101 50AT
PSU RR NLR PR PR ALSR RR LOC EOLR
B50(EXT)
f 4A D6 D5 B6 B5 C6 C5 B6 B5 R2 R4

B5 B6 B1 B2 B5 B6 B1 B2 D1 D2 T5 M5

101 101 101 101


NLR RKR NCR RCR
101
RLR B1 B2

D6 D5 B5 B6 D5 D6 R3 R1

B5 B6

PSU
N50(EXT)
(RR) t D7 D8 B7 B8
NOTE: QBA1 RELAYS MAY ALSO BE USED
C6 C5 C2 C1 B8 B7 B4 B3 D4 D3 M7 T7

101 101N
OPTIONAL ARRANGEMENT
NLR WHEN INSUFFICIENT CABLE CORES EXIST PBR
101
RLR

D7 D8 101 101 C5 C6
NWKR RWKR
C6 C5 101R
PSU RR RR LOC PBR
B50(EXT)
f 4A D6 D5 D6 D5

B5 B6

101N
PBR

C8 C7 B4 B3

101R
PSU PBR
N50(EXT)
(RR) t D7 D8 D7 D8

B8 B7
LOC RR

101 101 101 101


NCR RCR RWKR NWKR
101 101 101
PSU LOC EOLR NKR LOC RR NLR
B50(EXT)
f 4A C6 C5 A6 A5 A8 A7 R1 R2

B1 B2 D1 D2 B1 B2

101 101 101


RKR NWKR RWKR
101
RLR

A1 A2 A7 A8 R2 R1

101 B2 B1

PSU NKR
N50(EXT)
(LOC) t C7 C8 A7 A8

B4 B3 D4 D3

101 ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED


RKR

A4 A3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW076 SHEET TITLE: POINTS CONTROL & DETECTION - EP (THREE ENDS) - THROUGH CIRCUITS EDMS No: SG0602002 SHEET No: W076 CIRCUIT BOOK No: 00001

RR LOC

101 101 101A/B 101 101


RLR EOLJPR NKR RCR NCR
101 50AT 60AT 50 101 50AT
PSU RR NLR PR PR ALSR RR LOC EOLR
B50(EXT)
f 4A D6 D5 B6 B5 C6 C5 B6 B5 R2 R4

B5 B6 B1 B2 B5 B6 B1 B2 D1 D2 T5 M5

101 101C
NLR NKR
101
RLR B1 B2

D6 D5 C6 C5

B5 B6

101A/B 101 101


RKR NCR RCR

PSU
N50(EXT)
(RR) t D7 D8 B7 B8 B5 B6 D5 D6 R3 R1

C6 C5 C2 C1 B8 B7 B4 B3 D4 D3 M7 T7

101 101N 101C


OPTIONAL ARRANGEMENT
NLR WHEN INSUFFICIENT CABLE CORES EXIST PBR RKR
101
RLR

D7 D8 101 101 C5 C6 B5 B6
NWKR RWKR
C6 C5 101R
PSU RR RR LOC PBR NOTE: QBA1 RELAYS MAY ALSO BE USED
B50(EXT)
f 4A D6 D5 D6 D5

B5 B6

101N
PBR

C8 C7 B4 B3

101R
PSU PBR
N50(EXT)
(RR) t D7 D8 D7 D8

B8 B7
LOC RR

101 101 101 101


NCR RCR RWKR NWKR
101 101A/B 101C 101
PSU LOC EOLR NKR NKR LOC RR NLR
B50(EXT)
f 4A C6 C5 A6 A5 A8 A7 R1 R2

B1 B2 D1 D2 D1 D2 B1 B2

101A/B 101C 101 101


RKR RKR NWKR RWKR
101
RLR

A1 A2 A1 A2 A7 A8 R2 R1

101A/B 101C B2 B1

PSU NKR NKR


N50(EXT)
(LOC) t C7 C8 A7 A8

B4 B3 D4 D3 D4 D3

101A/B 101C
RKR RKR

A4 A3 A4 A3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW078 SHEET TITLE: POINTS CONTROL & OPERATION - EP 'A' VALVE EDMS No: SG0602002 SHEET No: W078 CIRCUIT BOOK No: 00001

101A
MASTER 'A' VALVE UNIT AND EOL

NW
101
PSU LOC NWR LOC
BX120
1B
f 4A 1 A8

C1 C2

PSU
NX120
(LOC) 1W
t 2 A9

C4 C3

RW
101
RWR
2B
3 A10

A1 A2

2W
4 A11

A4 A3 Pt 12pr
CABLE
101A WM

101 101 101 101 101B


NWR RWR RKR RCR SLAVE 'A' VALVE UNIT
101
PSU LOC NCR PSU
B50 B50
(NO BRK) f 4A R2 R4 B8 B7 B8 B7 B8 B7 t (NO BRK) NW
(LOC)
QNN1 LOC
C1 C2
4/4
1B
101 1 A8

NWR

D1 D2

2 1W A9

101 101 101 101


RWR NWR NKR NCR RW
101
PSU LOC RCR PSU
B50 B50
(NO BRK) f 4A R1 R3 D8 D7 D8 D7 D8 D7 t (NO BRK) 3 2B A10
(LOC)
A1 A2 QNN1
4/4

101
RWR
2W
4 A11

B1 B2 Pt 8pr
CABLE
101B WS
TO 101C SLAVE

NOTE: MASTER CAN BE ON "A" OR "B" END

(ARRANGEMENT SHOWN FOR


THREE ENDED POINTS - WHERE INSTALLED)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW079 SHEET TITLE: POINTS DETECTION (LOCAL) - EP DOUBLE END - LH 'A' VALVE EDMS No: SG0602002 SHEET No: W079 CIRCUIT BOOK No: 00001

101A 101A
MASTER 'A' VALVE 101A MASTER 'A' VALVE
LOC UNIT & EOL DETECTOR UNIT & EOL LOC

PRESSURE
SWITCHES LHCB RHCB

3 8 7 2 1

1B 4B 5B
B5 B3 A3

PSU LOC 1
B50(EXT) R R-NI
3B
f 4A A16

2 6 5 4 3

1W 3B 4B
B6 B1 A1

N
N-RI N

3 2 1 8 7

2B 3W 4W
B7 B2 A2

PSU 1
N50(EXT) N-RI N
(LOC) 3W
t A19

Pt 12pr 2 4 3 6 5
CABLE
2W 4W 5W
101A WM B8 B4 A4

R Pt 8pr Pt 8pr Pt 12pr


CABLE R R-NI CABLE CABLE
101A WD 101A WD 101A WM

101B 101B
SLAVE 'A' VALVE 101B SLAVE 'A' VALVE
LOC UNIT DETECTOR UNIT

PRESSURE
SWITCHES LHCB RHCB

101 101 3 8 7 2 1
101
NKR RKR RWR 1B 4B 5B
101 B5 B3 A3

NWR 1
R R-NI
3B
R4 R2 A5 A6 D5 D6 A16

D4 D3 2 6 5 4 3

101 101 1W 3B 4B
101 B6 B1 A1

RKR NKR NWR


N
N-RI N

3 2 1 8 7
R1 R3 D6 D5 C6 C5

2B 3W 4W
D3 D4 B7 B2 A2

1
N-RI N
3W
A19

Pt 8pr 2 4 3 6 5
CABLE
2W 4W 5W
101B WS B8 B4 A4

R Pt 8pr Pt 8pr Pt 8pr


CABLE R R-NI CABLE CABLE
101B WD 101B WD 101B WS

NOTE: QBA1 RELAYS MAY ALSO BE USED ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW080 SHEET TITLE: POINTS DETECTION (LOCAL) - EP DOUBLE END - RH 'A' VALVE EDMS No: SG0602002 SHEET No: W080 CIRCUIT BOOK No: 00001

101A 101A
MASTER 'A' VALVE 101A MASTER 'A' VALVE
LOC UNIT & EOL DETECTOR UNIT & EOL LOC

'A' PRESSURE
SWITCHES LHCB RHCB

3 8 7 2 1

1B 3B 4B
B5 B1 A1

PSU LOC 1
B50(EXT) N N-RI
3B
f 4A A16

2 6 5 4 3

1W 4B 5B
B6 B3 A3

N
R-NI R

3 2 1 8 7

2B 4W 5W
B7 B4 A4

PSU 1
N50(EXT) R-NI R
(LOC) 3W
t A19

Pt 12pr 2 4 3 6 5
CABLE
2W 3W 4W
101A WM B8 B2 A2

R Pt 8pr Pt 8pr Pt 12pr


CABLE N N-RI CABLE CABLE
101A WD 101A WD 101A WM

101B 101B
SLAVE 'A' VALVE 101B SLAVE 'A' VALVE
LOC UNIT DETECTOR UNIT

'A' PRESSURE
SWITCHES LHCB RHCB

101 101 3 8 7 2 1
101
NKR RKR RWR 1B 3B 4B
101 B5 B1 A1

NWR 1
N N-RI
3B
R4 R2 A5 A6 D5 D6 A16

D4 D3 2 6 5 4 3

101 101 1W 4W 5W
101 B6 B4 A4

RKR NKR NWR


N
R-NI R

3 2 1 8 7
R1 R3 D6 D5 C6 C5

2B 4B 5B
D3 D4 B7 B3 A3

1
R-NI R
3W
A19

Pt 8pr 2 4 3 6 5
CABLE
2W 3W 4W
101B WS B8 B2 A2

R Pt 8pr Pt 8pr Pt 8pr


CABLE N N-RI CABLE CABLE

NOTES: 101B WD 101B WD 101B WS

QBA1 RELAYS MAY ALSO BE USED


ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:40 DRG No: CSTDW085 SHEET TITLE: POINTS EMERGENCY OPERATION - 'A' VALVE EDMS No: SG0602002 SHEET No: W085 CIRCUIT BOOK No: 00001

LOC 101A MASTER 'A' VALVE UNIT

LOC

NORMAL PUSH
101 101
N
PSU LOC EOLJR EOLJPR E5L E5R 101R
101N
B50
9B PBR PBR
f 4A A28 E14R 101 101
C1 C2 C1 C2
EOLJPR EOLJR PSU
N50
9W (LOC)
A29 R2 R4 A8 A7 t
N CALL
E13L E13R D1 D2 D1 D2
W

R2
E12L E12R

B T *1 MADE WHEN EOL SWITCH IS IN


2K2 2.5w
THE NORMAL POSITION
REVERSE PUSH 101N
E6R R PBR *2 MADE WHEN EOL SWITCH TURNED REVERSE

10B
A30

E7R C1 C2 101R 101N


PBR PBR
R E16R

10W
A31 R1 R3 D8 D7
R CALL
E15L E15R
W

R3
E11L E11R
NOTE: EOLR TO BE PROVED
ENERGISED IN THE
B T 101R
2K2 2.5w
DETECTION CCT
E8R PBR

11B
N A32
EOL
A1 A2
IN USE
E9L E9R
W

R1
E10L E10R

T B
2K2 2.5w
11W 101
A33
101
EOLR
EOL EOLJR
PSU LOC E1L E1R
B50 R R1 R2
6B 7B
f 4A A22 7 8 A24 D8 D7
A1
*2
B6

B7
60"
A8
RR 101
EOLJPR
101
101 101 EOLJR
*2
NWKR RWKR
R1 R2
EOL
PSU E3L E3R LOC RR RR LOC
C3 C4
N50 R # #
(LOC) 6W 7W
t A23 4 3 A25 D7 D8 D7 D8

Pt 12pr 101 101 101


CABLE EOLJR EOLJPR EOLR
101A WM *1
E2R
N
8B
5 6 A26 D8 D7 D8 D7 R1 R2

*1
E4R
N
8W
1 2 A27

Pt 12pr
# SEE NCR/RCR SHEET W075 FOR ALTERNATIVE
CABLE
ARRANGEMENT WHEN INSUFFICIENT CABLE CORES
101A WM

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:41 DRG No: CSTDW086 SHEET TITLE: POINTS AND DETECTION LAYOUT - SIEMENS: HMX, HM2, HM3 & HLM EDMS No: SG0602002 SHEET No: W086 CIRCUIT BOOK No: 00001

DETECTOR

LHCB RHCB

RHCB
8 7 2 1

LHCB
STANDARD WIRING BETWEEN CONTACT BLOCKS
N N-RI
RHSNC SHOWN

6 5 4 3

RHCB
R-NI R

LHCB
2 1 8 7

R-NI R

4 3 6 5

VIEW

N N-RI
RHCB

RHCB
LHCB - LEFT HAND CONTACT BLOCK

RHCB - RIGHT HAND CONTACT BLOCK

LHSNC - LEFT HAND SWITCH NORMALLY CLOSED


LHCB

LHCB
RHSNC - RIGHT HAND SWITCH NORMALLY CLOSED

DETECTOR

LHCB RHCB

8 7 2 1

STANDARD WIRING BETWEEN CONTACT BLOCKS


R R-NI
LHSNC SHOWN

6 5 4 3

N-RI N

2 1 8 7

N-RI N

4 3 6 5

R R-NI

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:41 DRG No: CSTDW087 SHEET TITLE: POINTS DETECTOR ARRANGEMENTS - EP HM STYLE EDMS No: SG0602002 SHEET No: W087 CIRCUIT BOOK No: 00001

RIGHT HAND CONTACT BLOCK LEFT HAND CONTACT BLOCK

LHSC (RHCB) RHSC (LHCB)


ACTIVATED IN NORMAL ACTIVATED IN NORMAL
POSITION POSITION

NOTE 1:
FOR CONSISTENCY INSTALL
THE CROSSING SIDE DETECTOR
ROD TO CLOSEST SWITCH
& TOE SIDE DETECTOR
ROD TO FURTHEST SWITCH

LH MOUNTED LH MOUNTED
DETECTOR DETECTOR

LHSC RHSC
NOTE 1 NOTE 1

"B" DETECTOR ROD ON CROSSING SIDE

RH MOUNTED RH MOUNTED
DETECTOR DETECTOR

LHSC RHSC
NOTE 1 NOTE 1

"A" DETECTOR ROD ON TOE SIDE

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:41 DRG No: CSTDW088 SHEET TITLE: POINTS OPERATION - EP CLAWLOCK - 'A' VALVE EDMS No: SG0602002 SHEET No: W088 CIRCUIT BOOK No: 00001

MASTER 'A' VALVE UNIT AND EOL

NW, RW
NW
LOC
PSU LOC NWR XXX PTS
BX120
1B
f 4A A8

C1 C2

PSU
NX120
(LOC) 1W
t A9

C4 C3

RW
RWR
2B
A10

A1 A2

2W
A11

A4 A3 Pt 12pr
CABLE
WM

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:41 DRG No: CSTDW089_1 SHEET TITLE: POINTS CONTROL - 'A' UNIT WITH ISOLATION MODULES - MICROLOK EDMS No: SG0602002 SHEET No: W089_1 CIRCUIT BOOK No: 00001

EF-RR EF-RR
SLAVE A1 SLAVE B1
N
PSU LOC PBR EOLJPR
B50(INT)
f 4A

C1 C2 A1 A2
ISOLATION MODULE (17)
1B RCR NCR EOLJPR
N17001102 (50V)

NCR + IR
IN 1 OUT 1 +
O/P1 E2 * A6 A5 B6 B5 R2 R4 B6 B5
#1
NCR + C1 C2

O/P1 E2 * N
IN4007
PSU PBR
1A
N50(INT)
(LOC) t

PSU LOC
D2 D1 D2 D1
B15 B12
f 4A
OUT 1 -

PSU
N15 N12
(LOC) t R
PSU LOC PBR EOLJPR
B50(INT)
f 4A

A1 A2 A3 A4

2B NCR RCR EOLJPR

RCR + IR
IN 2 OUT 2 +
O/P2 C2 * A8 A7 D6 D5 R1 R3 B8 B7
#1
RCR + D1 D2

O/P2 C2 * R
IN4007
2A PSU PBR
N50(INT)
(LOC) t

B2 B1 B4 B3

PSU
N12 N12 OUT 2 -
(LOC) t

LOCAL TRACKS

ISOLATION MODULE (18)


3B IR
N17001102 (50V) ES4.72BT ES4.72BT
IR + PR (2)
IN 1 OUT 1 +
O/P3 A2 * R2 R4
#1
B1 B2 B1 B2
IR +

O/P3 A2 * IR
IN4007
PSU LOC
3A B12
B15
f 4A C3 C4

OUT 1 -
PSU
N15 N12
4B (LOC) t

ZR +
IN 2 OUT 2 +
O/P4 E4 *
#1
ZR +

O/P4 E4 *

4A #1 WEIDMULLER PARTS * ETFE TEFLON COATED


STANDARD VITAL STANDARD VITAL IN4007 DIODES 1.23mm SQ, 19/29AWG
OUTPUT PCB (3) OUTPUT PCB (3) ZAP/TW2 PARTITIONS 600V GRADE
MKII SLOT 7 MKII SLOT 7 PSU ZTR2.5/D DIODE DISCONNECTORS
N12 N12 OUT 2 -
ZQV2.5/2 CROSS CONNECT
(LOC) t

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 14:41 DRG No: CSTDW089_2 SHEET TITLE: POINTS CONTROL - 'A' UNIT WITHOUT ISOLATION MODULES - MICROLOK EDMS No: SG0602002 SHEET No: W089_2 CIRCUIT BOOK No: 00001

EF-RR EF-RR
SLAVE A1 SLAVE B1
N
RR RR PBR EOLJPR
B12
f 4A

C1 C2 A1 A2

1B RCR NCR

NCR + IR RR
N12
O/P1 E2 * A6 A5 B6 B5 R2 R4 t (RR)
#1
NCR + C1 C2

O/P1 E2 *
IN4007
1A

R
RR RR PBR EOLJPR
B12
f 4A

A1 A2 A3 A4

2B NCR RCR

RCR + IR RR
N12
O/P2 C2 * A8 A7 D6 D5 R1 R3 t (RR)
#1
RCR + D1 D2

O/P2 C2 *
IN4007
2A

LOCAL TRACKS

3B IR
ES4.72BT ES4.72BT
IR + PR (2) RR
N12
O/P3 A2 * R2 R4 t (RR)
#1
B1 B2 B1 B2
IR +

O/P3 A2 * IR
IN4007
3A
C3 C4

4B

SPARE +

O/P4 E4 *
#1
SPARE +

O/P4 E4 *

4A #1 WEIDMULLER PARTS * ETFE TEFLON COATED


STANDARD VITAL STANDARD VITAL IN4007 DIODES 1.23mm SQ, 19/29AWG
OUTPUT PCB (3) OUTPUT PCB (3) ZAP/TW2 PARTITIONS 600V GRADE
MKII SLOT 7 MKII SLOT 7 ZTR2.5/D DIODE DISCONNECTORS
ZQV2.5/2 CROSS CONNECT

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW090 SHEET TITLE: POINTS DETECTION - EP CLAWLOCK - SINGLE END LH 'A' VALVE (M'LOK) EDMS No: SG0602002 SHEET No: W090 CIRCUIT BOOK No: 00001

MASTER 'A' VALVE MASTER 'A' VALVE


UNIT & EOL DETECTOR UNIT & EOL

PRESSURE
SWITCHES LHCB RHCB

3 8 7 2 1

ARR 1 B5 1B 3B B1 A1 4B

PSU LOC 1
B50(EXT) 3 2 R R-NI
B 3B
f 4A A16

2 6 5 4 3

B6 1W 4B B3 A3 5B

ELSAFE N
#2 N-RI N
ARRESTOR
MODULE SE

#4
3 2 1 8 7

B7 2B 4W B4 A4 5W

PSU 1
W
N50(EXT) 4 1 N-RI N
(LOC) 3W
t A19

2 4 3 6 5
Pt 12pr CABLE
(7/0.50mm)
B8 2W 3W B2 A2 4W

R Pt 8pr CABLE Pt 8pr CABLE Pt 12pr CABLE


R R-NI
(7/0.50mm) (7/0.50mm) (7/0.50mm)

LOC
LOC LOC INPUT PCB
B SIDE A SIDE IMM 1
A1+
3 2
I/P 1+ B B
E2 #3
ELSAFE
B1+
#2
IMMUNISATION
NKR
SE MODULE

A1-
W W #1
I/P 1- 4 1
E4 #3

B1-
I/P 1+ B
#1 ELSAFE IMMUNISATION MODULE E2
MODULE AND BASE PART Nos:
BASE- 216600A
NKR
MODULE- 216643 (YELLOW)

W
#2 ARRESTOR EARTHED MECHANICALLY I/P 1-
TO MOUNTING RAIL E4
MOUNTING RAIL ELECTRICALLY
IMM 2
CONNECTED TO MAIN EARTH
A2+
I/P 2+ 3 2
#3 WEIDMULLER PARTS: B B
C2 #3
TEST DISCONNECT TERM - ZTR 2.5
ELSAFE
CROSS CONNECTOR - ZQV 2.5/2 B2+
#2
IMMUNISATION
RKR
SE MODULE
#4 ELSAFE 290V ARRESTOR MODULE.
A2-
MODULE & BASE PART Nos: W W #1
BASE- 216600A
I/P 2- 4 1
C4 #3
MODULE- 216680 (GRAPHITE)
B2-
I/P 2+
B
ALL INTERNAL WIRING C2
ETFE TEFLON COATED
1.23mm SQ, 19/29AWG RKR
600V GRADE UNLESS
SHOWN OTHERWISE
W
I/P 2-
C4

VITAL VITAL
INPUT PCB __ INPUT PCB __
MKII SLOT __ MKII SLOT __

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW091 SHEET TITLE: POINTS DETECTION - EP CLAWLOCK - SINGLE END RH 'A' VALVE (M'LOK) EDMS No: SG0602002 SHEET No: W091 CIRCUIT BOOK No: 00001

MASTER 'A' VALVE MASTER 'A' VALVE


UNIT & EOL DETECTOR UNIT & EOL

PRESSURE
SWITCHES LHCB RHCB

3 8 7 2 1

ARR 1 B5
1B 3B
B1 A1
4B

PSU LOC 1
B50(EXT) 3 2 N N-RI
B 3B
f 4A A16
ELSAFE
2 6 5 4 3
ARRESTOR
MODULE 1W 4B 5B
B6 B3 A3

#4 N
#2 R-NI R

SE

3 2 1 8 7

2B 4W 5W
B7 B4 A4

PSU 1
W
N50(EXT) 4 1 R-NI R
(LOC) 3W
t A19

2 4 3 6 5
Pt 12pr CABLE
(7/0.50mm)
2W 3W 4W
B8 B2 A2

R Pt 8pr CABLE Pt 8pr CABLE Pt 12pr CABLE


N N-RI
(7/0.50mm) (7/0.50mm) (7/0.50mm)

LOC
LOC LOC INPUT PCB
B SIDE A SIDE IMM 1
A1+
I/P 1+ 3 2
E2 B #3 B

ELSAFE
B1+
#2
IMMUNISATION
101 NKR
SE MODULE

W
A1-
W
#1
I/P 1- 4 1
E4 #3

B1-
I/P 1+
E2 B

#1 ELSAFE IMMUNISATION MODULE


101 NKR
MODULE AND BASE PART Nos:
BASE- 216600A
MODULE- 216643 (YELLOW) W
I/P 1-
E4

#2 ARRESTOR EARTHED MECHANICALLY


IMM 2
TO MOUNTING RAIL
MOUNTING RAIL ELECTRICALLY A2+
CONNECTED TO MAIN EARTH. I/P 2+ 3 2
C2 B #3 B

ELSAFE
#3 WEIDMULLER PARTS: ZTR 2.5
B2+ #2
IMMUNISATION
101 RKR
SE MODULE
#4 ELSAFE 290V ARRESTOR MODULE.
W
A2-
W
#1
MODULE & BASE PART Nos:
I/P 2- 4 1
BASE- 216600A C4 #3
MODULE- 216680 (GRAPHITE)
B2-
I/P 2+
C2 B
ALL INTERNAL WIRING
ETFE TEFLON COATED
1.23mm SQ, 19/29AWG
101 RKR
600V GRADE UNLESS
SHOWN OTHERWISE
W
I/P 2-
C4

VITAL VITAL
INTPUT PCB __ INTPUT PCB __
MKII SLOT __ MKII SLOT __

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW093 SHEET TITLE: POINTS OPERATION - EP CLAWLOCK - 'A' VALVE EDMS No: SG0602002 SHEET No: W093 CIRCUIT BOOK No: 00001

101A
MASTER POINT 'A' VALVE
UNIT & EOL

101 NW, RW
NW
101
LOC NWR LOC
BX120
1B
f 4A 1 A8

C1 C2

LOC
NX120
1W
t 2 A9

C4 C3

RW
101
RWR

2B
3 A10

A1 A2

2W
4 A11

A4 A3 Pt 12pr
CABLE
101A WM

APPLIES TO MICROLOK POINTS ONLY

101 NWR 101 101 101


101B
NWR RWR RCR
101 SLAVE POINT 'A' VALVE
* LOC NCR UNIT
PSU PSU
B50(INT) N50(INT)
f 4A R2 R4 B8 B7 B8 B7 t (LOC)

C1 C2
NW

LOC
101
NWR 1
1B
A8

IN4007
D1 D2

1W
101 RWR 101 101 101 2 A9

RWR NWR NCR


101
* LOC RCR RW
PSU PSU
B50(INT) N50(INT)
f 4A R1 R3 D8 D7 D8 D7 t (LOC)

2B
A1 A2 3 A10

101
RWR

IN4007
2W
B1 B2 4 A11

Pt 8pr
CABLE
101B WS

ALL INTERNAL WIRING


ETFE TEFLON COATED
* MUST BE NO-BREAK SUPPLY NOTE: MASTER CAN BE ON "A" OR "B" END.
1.23mm SQ, 19/29AWG 12V RELAY & MICROLOK
600V GRADE UNLESS SUPPLY MAY BE USED TO 101C SLAVE

SHOWN OTHERWISE MICROLOK B50/N50(INT)


IS USUALLY BATTERY BACKUP

(ARRANGEMENT SHOWN FOR


THREE ENDED POINTS - WHERE INSTALLED)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW094 SHEET TITLE: POINTS EMERGENCY OPERATION - EP 'A' VALVE - MICROLOK EDMS No: SG0602002 SHEET No: W094 CIRCUIT BOOK No: 00001

101
MASTER 'A' VALVE
UNIT & EOL

NORMAL PUSH
101 101
N
PSU LOC EOLJR EOLJPR LOC
E5L E5R 101 R
101 N
B50(EXT) 4 1
B 9B PBR PBR
f 4A A28 E14R
ELSAFE
#2 C1 C2 C1 C2
LOC
ARRESTOR
MODULE SE 9W
A29 R2 R4 A8 A7
N CALL
PSU W #3 E13L E13R
N50(EXT) 3 2 W
(LOC) 11W
t
R2
D2 D1 D2 D1 Pt 12pr E12L E12R
CABLE
101 WM B T
2K2 2.5w

REVERSE PUSH 101 N


E6R
R PBR
#1
10B
A30

E7R C1 C2 101 R 101 N


PBR PBR
R E16R

10W
A31 R1 R3 D8 D7
R CALL
E15L E15R
W

R3
E11L E11R

B T
2K2 2.5w

101 R
E8R
PBR
#1
11B
N A32

Pt 12pr
A1 A2
CABLE
101 WM

EOL
IN USE
E9L E9R
W

R1
E10L E10R

T B
#1 RC SNUBBER 2K2 2.5w

REFER TO SHEET W095


A33

RS COMPONENTS: 206-7881

#2 ELSAFE MODULE EARTHED MECHANICALLY VIA THE


ATTACHMENT SCREW TO THE MOUNTING RAIL. THE MOUNTING
RAIL ELECTRICALLY CONNECTED TO THE MAIN EARTH.

#3 ELSAFE 290V ARRESTOR MODULE.


MODULE & BASE PART No's:
BASE- 216600A
MODULE- 216680 (GRAPHITE)

ALL INTERNAL WIRING


ETFE TEFLON COATED
1.23mm SQ, 19/29AWG
600V GRADE UNLESS
SHOWN OTHERWISE

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW095 SHEET TITLE: POINTS EMERGENCY OPERATION & DETECTION - EP - 'A' VALVE (MICROLOK) EDMS No: SG0602002 SHEET No: W095 CIRCUIT BOOK No: 00001

101 MASTER 'A' ALVE


USE POTENTIOMETER TO ADJUST
UNIT & EOL TIMER TO 60 SECONDS
101
EOL EOL JR
PSU LOC E1L E1R R1 R2
B50(EXT) 3 2 R 2 3
B 6B 7B
f 4A A22 7 8 A24
A1
ELSAFE *2 ELSAFE
#2 #2
ARRESTOR ARRESTOR
#1 B6
MODULE SE SE MODULE
EOL A8
PSU W #3 E3L E3R #3
N50(EXT) 4 1 R 1 4 B7 60"
6W 7W
t A23 4 3 A25

Pt 12pr *2
CABLE
QTD5
101
101 WM
*1 EOL
E2R JPR
N
8B
5 6 A26

*1 MADE WHEN EOL ROTARY SWITCH IS IN THE NORMAL POSITION R1 R2

*2 MADE WHEN EOL ROTARY SWITCH TURNED REVERSE


C3 C4
*1
E4R
N #1
8W
1 2 A27

Pt 12pr
CABLE
REFER TO SHEET W094
101 WM

RR RR
MASTER A MASTER B

101 101
EOL EOL
JR JPR

A9+
2 3
B B B 101 EOLR
D8 D7 A6 A5 #5 A12
ELSAFE
#2 B9+
IMMUNISATION
SE MODULE
I/P 9

A9-
#4 W W W
1 4
101 EOLR N
D5 D6 D5 D6 #5 A14

B9-

B 101 EOLR
A12

I/P 9

W
101 EOLR N
101 101 101 A14
NCR RCR IR

PSU LOC A10+


B50(INT)
B B B 101 IZR
f 4A A6 A5 A6 A5 A6 A5 #5 E16

B10+
I/P 10

PSU A10-
W W W
N50(INT)
101 IZR N
t D5 D6 D5 D6 D5 D6 #5 E18

B10-
#2 ELSAFE MODULE EARTHED MECHANICALLY VIA THE
#1 RC SNUBBER B 101 IZR
ATTACHMENT SCREW TO THE MOUNTING RAIL. THE MOUNTING E16
RAIL ELECTRICALLY CONNECTED TO THE MAIN EARTH.
I/P 10

RS COMPONENTS: 206-7881 #3 ELSAFE 290V ARRESTOR MODULE. #4 ELSAFE IMMUNISATION MODULE. ALL INTERNAL WIRING
MODULE & BASE PART Nos: MODULE & BASE PART Nos: ETFE TEFLON COATED W

BASE- 216600A BASE- 216600A 1.23mm SQ, 19/29AWG 101 IZR N


E18
MODULE- 216680 (GRAPHITE) MODULE- 216643 (YELLOW) 600V GRADE UNLESS
SHOWN OTHERWISE VITAL VITAL

#5 WEIDMULLER PARTS - ZTR 2.5 INPUT PCB (10) INPUT PCB (10)
MKII SLOT 10 MKII SLOT 10

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW097 SHEET TITLE: POINTS DETECTION - EP CATCHPOINT - RH 'A' VALVE (MICROLOK) EDMS No: SG0602002 SHEET No: W097 CIRCUIT BOOK No: 00001
101 101 101
MASTER 'A' VALVE 101 MASTER 'A' VALVE 101 MASTER 'A' VALVE
UNIT & EOL DETECTOR UNIT & EOL OPERATING BAR UNIT & EOL

PRESSURE
SWITCHES LHCB RHCB LHCB RHCB

3 8 7 2 1 8 7 2 1

ARR 1 B5
1B 3B
B1 C5
3B 1B
C1 A1
4B

PSU LOC 1
B50(EXT) 3 2 N N-RI N N-RI
B 3B
f 4A A16
ELSAFE
2 6 5 4 3 6 5 4 3
ARRESTOR
MODULE 1W 4B 4B 2B 5B
B6 B3 C7 C3 A3

#4 N
#2 R-NI R R-NI R

SE
3 2 1 8 7 2 1 8 7

2B 4W 4W 2W 5W
B7 B4 C8 C4 A4

PSU 1
W
N50(EXT) 4 1 R-NI R R-NI R
(LOC) 3W
t A19

2 4 3 6 5 4 3 6 5
Pt 12pr
CABLE
2W 3W 3W 1W 4W
101 WM B8 B2 C6 C2 A2

Pt 8pr Pt 8pr Pt 8pr Pt 8pr Pt 12pr


R
CABLE N N-RI CABLE CABLE N N-RI CABLE CABLE
101 WD 101 WD 101 WOB 101 WOB 101 WM

LOC
LOC LOC INPUT PCB
B SIDE A SIDE IMM 1
A1+
I/P 1+ 3 2
E2 B #3 B

ELSAFE
B1+
#2
IMMUNISATION
101 NKR
SE MODULE

W
A1-
W
#1
I/P 1- 4 1
E4 #3

B1-
#1 ELSAFE IMMUNISATION MODULE
I/P 1+
MODULE AND BASE PART Nos: E2 B
BASE- 216600A
MODULE- 216643 (YELLOW)
101 NKR

#2 ARRESTOR EARTHED MECHANICALLY


W
TO MOUNTING RAIL
I/P 1-
MOUNTING RAIL ELECTRICALLY E4
CONNECTED TO MAIN EARTH.
IMM 2
A2+
#3 WEIDMULLER PARTS:
TEST DISCONNECT TERM - ZTR 2.5
I/P 2+ 3 2
C2 B #3 B
CROSS CONNECTOR - ZQV 2.5/2
ELSAFE
B2+ #2
IMMUNISATION
101 RKR
#4 ELSAFE 290V ARRESTOR MODULE. SE MODULE
MODULE & BASE PART Nos:
W
A2-
W
#1
BASE- 216600A
I/P 2- 4 1
MODULE- 216680 (GRAPHITE) C4 #3
B2-
ALL INTERNAL WIRING I/P 2+
C2 B
ETFE TEFLON COATED
1.23mm SQ, 19/29AWG
600V GRADE UNLESS 101 RKR
SHOWN OTHERWISE

W
I/P 2-
C4

VITAL VITAL
INTPUT PCB __ INTPUT PCB __
MKII SLOT __ MKII SLOT __

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW098 SHEET TITLE: POINTS DETECTION - EP CATCHPOINTS - LH 'A' VALVE (MICROLOK) EDMS No: SG0602002 SHEET No: W098 CIRCUIT BOOK No: 00001

101 101 101


MASTER 'A' VALVE 101 MASTER 'A' VALVE 101 MASTER 'A' VALVE
UNIT & EOL DETECTOR UNIT & EOL OPERATING BAR UNIT & EOL

PRESSURE
SWITCHES LHCB RHCB LHCB RHCB

3 8 7 2 1 8 7 2 1

ARR 1 B5
1B 4B
B3 C7
4B 2B
C1 A1 4B

PSU LOC 1
B50(EXT) 3 2 R R-NI R R-NI
B 3B
f 4A A16

2 6 5 4 3 6 5 4 3

1W 3B 3B 1B 5B
B6 B1 C5 C3 A3

ELSAFE N
#2 N-RI N N-RI N
ARRESTOR
MODULE SE
3 2 1 8 7 2 1 8 7
#4
2B 3W 3W 1W 5W
B7 B2 C6 C4 A4

PSU 1
W
N50(EXT) 4 1 N-RI N N-RI N
(LOC) 3W
t A19

2 4 3 6 5 4 3 6 5
Pt 12pr
CABLE
2W 4W 4W 2W 4W
101 WM B8 B4 C8 C2 A2

R Pt 8pr Pt 8pr Pt 8pr Pt 8pr Pt 12pr


CABLE R R-NI CABLE CABLE R R-NI CABLE CABLE
101 WD 101 WD 101 WOB 101 WOB 101 WM

LOC
LOC LOC INPUT PCB
B SIDE A SIDE IMM 1
A1+
3 2
I/P 1+ B B
E2 #3
ELSAFE
B1+
#2
IMMUNISATION
101 NKR
SE MODULE

A1-
W W #1
I/P 1- 4 1
E4 #3

#1 ELSAFE IMMUNISATION MODULE B1-


MODULE AND BASE PART Nos: I/P 1+ B
E2
BASE- 216600A
MODULE- 216643 (YELLOW)
101 NKR

#2 ARRESTOR EARTHED MECHANICALLY


TO MOUNTING RAIL W
MOUNTING RAIL ELECTRICALLY I/P 1-
E4
CONNECTED TO MAIN EARTH.
IMM 2
#3 WEIDMULLER PARTS: A2+
TEST DISCONNECT TERM - ZTR 2.5 I/P 2+ 3 2
B B
CROSS CONNECTOR - ZQV 2.5/2 C2 #3
ELSAFE
B2+
#2
IMMUNISATION
#4 ELSAFE 290V ARRESTOR MODULE.
101 RKR
SE MODULE
MODULE & BASE PART Nos:
BASE- 216600A A2-
W W #1
MODULE- 216680 (GRAPHITE) I/P 2- 4 1
C4 #3

B2-
ALL INTERNAL WIRING
I/P 2+
ETFE TEFLON COATED B
C2
1.23mm SQ, 19/29AWG
600V GRADE UNLESS
101 RKR
SHOWN OTHERWISE

W
I/P 2-
C4

VITAL VITAL
INPUT PCB __ INPUT PCB __
MKII SLOT __ MKII SLOT __

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW099 SHEET TITLE: POINTS DETECTION - SIEMENS D84M MKIII - SINGLE END LH (MICROLOK) EDMS No: SG0602002 SHEET No: W099 CIRCUIT BOOK No: 00001

LHSNC
MOTOR
CONTACT NOTE: BLANKING PLATE REQUIRED ON RHSC SOCKET
ARR 1 R3 R5

PSU LOC 8.8 8.7 9.2 9.1 6.5 6.6


B50(EXT) 3 2
B 1B 13 17 2B
f 4A P1 L1 L5 P5

N N-RI N

ELSAFE
ARRESTOR R4 R8
MODULE
8.6 8.5 9.4 9.3 7.5 7.6
#2
#4 14 20 3B
P2 L2 L8 P8
SE

R-NI R R

R1 R7

PSU W 8.4 8.3 9.6 9.5 7.7 7.8


N50(EXT) 4 1
(LOC) 1W 15 19 2W
t P3 L3 L7 P7

Pt 4pr CABLE
N N-RI N
(7/0.50mm)

R2 R6

8.2 8.1 9.8 9.7 6.7 6.8

16 18 3W
P4 L4 L6 P6

Pt 4pr CABLE
R-NI R R
(7/0.50mm)

LOC
LOC LOC INPUT PCB
B SIDE A SIDE IMM 1
A1+
3 2
I/P 1+ B B
E2 #3
ELSAFE
B1+
#2
IMMUNISATION
NKR
SE MODULE

A1-
W W #1
I/P 1- 4 1
E4 #3

#1 ELSAFE IMMUNISATION MODULE B1-


MODULE AND BASE PART Nos: I/P 1+ B
E2
BASE- 216600A
MODULE- 216643 (YELLOW)
NKR

#2 ARRESTOR EARTHED MECHANICALLY


TO MOUNTING RAIL W
MOUNTING RAIL ELECTRICALLY I/P 1-
E4
CONNECTED TO MAIN EARTH.
IMM 2
#3 WEIDMULLER PARTS: A2+
TEST DISCONNECT TERM - ZTR 2.5 I/P 2+ 3 2
B B
CROSS CONNECTOR - ZQV 2.5/2 C2 #3
ELSAFE
B2+
#2
IMMUNISATION
#4 ELSAFE 290V ARRESTOR MODULE. RKR
SE MODULE
MODULE & BASE PART Nos:
BASE- 216600A A2-
W W #1
MODULE- 216680 (GRAPHITE) I/P 2- 4 1
C4 #3

ALL INTERNAL WIRING B2-


ETFE TEFLON COATED
I/P 2+
B
C2
1.23mm SQ, 19/29AWG
600V GRADE UNLESS
SHOWN OTHERWISE
RKR

W
I/P 2-
C4

VITAL VITAL
INPUT PCB __ INPUT PCB __
MKII SLOT __ MKII SLOT __

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW100 SHEET TITLE: POINTS DETECTION - SIEMENS D84M MKIII - SINGLE END RH (MICROLOK) EDMS No: SG0602002 SHEET No: W100 CIRCUIT BOOK No: 00001

RHSNC
MOTOR
NOTE: BLANKING PLATE REQUIRED ON LHSC SOCKET CONTACT

ARR 1 L4 6.7 6.8 L6

PSU LOC 8.6 8.5 9.4 9.3


B50(EXT) 3 2
B 1B 14 18 2B
f 4A P2 R2 R6 P6
N
ELSAFE
ARRESTOR
N-RI N
MODULE

L3 7.7 7.8 L7
#4
#2
8.8 8.7 9.2 9.1
SE
13 19 3B
P1 R1 R R7 P7

R R-NI

L2 7.5 7.6 L8

PSU W 8.2 8.1 9.8 9.7


N50(EXT) 4 1
(LOC) 1W 16 20 2W
t P4 R4 N R8 P8

Pt 4pr CABLE
N-RI N
(7/0.50mm)

L1 6.5 6.6 L5

8.4 8.3 9.6 9.5

15 17 3W
P3 R3 R R5 P5

Pt 4pr CABLE
R R-NI
(7/0.50mm)

LOC
LOC LOC INPUT PCB
B SIDE A SIDE IMM 1
A1+
I/P 1+ 3 2
E2 B #3 B

ELSAFE
B1+
#2
IMMUNISATION
101 NKR
SE MODULE

W
A1-
W
#1
I/P 1- 4 1
E4 #3

#1 ELSAFE IMMUNISATION MODULE B1-


MODULE AND BASE PART Nos:
I/P 1+
E2 B
BASE- 216600A
MODULE- 216643 (YELLOW)
101 NKR
#2 ARRESTOR EARTHED MECHANICALLY
TO MOUNTING RAIL W
MOUNTING RAIL ELECTRICALLY
I/P 1-
E4
CONNECTED TO MAIN EARTH.
IMM 2
#3 WEIDMULLER PARTS: A2+
TEST DISCONNECT TERM - ZTR 2.5 I/P 2+ 3 2
C2 B #3 B
CROSS CONNECTOR - ZQV 2.5/2
ELSAFE
B2+ #2
IMMUNISATION
#4 ELSAFE 290V ARRESTOR MODULE. 101 RKR
SE MODULE
MODULE & BASE PART Nos:
BASE- 216600A A2- #1
W W
MODULE- 216680 (GRAPHITE) I/P 2- 4 1
C4 #3
B2-
ALL INTERNAL WIRING
I/P 2+
ETFE TEFLON COATED B
C2
1.23mm SQ, 19/29AWG
600V GRADE UNLESS
SHOWN OTHERWISE 101 RKR

W
I/P 2-
C4

VITAL VITAL
INTPUT PCB __ INTPUT PCB __
MKII SLOT __ MKII SLOT __

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:49 DRG No: CSTDW101 SHEET TITLE: POINTS CONTROL, DETECTION & ISOLATION EDMS No: SG0602002 SHEET No: W101 CIRCUIT BOOK No: 00001

3 6
3AT 3BT

101A
FROM SYDNEY
101B

8BT 8AT
5 8

EOL BOX

@ @ 101 101 101


101A *
101A 101B NKR WTJR RKR
IR
3 8 EOL EOL 8 3
PSU RR ALSR USR RR LOC 3AT 8BT LOC LOC LOC RR USR ALSR PSU
B50(EXT) N N N50
1 2 (EXT)
f 4A 1 2 1 2 C8 C7 D3 A3 R1 R2 B8 B7 t
(RR)
C1 C2 C1 C2 C1 C2 C1 C2 C3 C4 C3 C4
ASSUMES EXTERNAL 101B *
DC MAINS IR
101A 101A 101B
PSU LOC IR IR IR PSU
B50(EXT) N50
f 4A C6 C5 D5 A5 R1 R2 B6 B5 t (EXT)
(LOC)
A1 A2 101 D1 D2 101 A1 A2
NKR WTJR
101
NWR
IR TO DOUBLE SWITCH
D8 D7 R1 R3 POINT MOTOR CIRCUIT
A3 A4 101 QCJ1 NOTE:
RKR NON-VITAL WTJR NOT PROVIDED IF
101 TIMER CUT-OUT TIMER
RWR 10-SECS IN POINT MACHINE

101 101 101 101 * A8 A7


RLR RWR RWR NWR
101 A3 A4 101 101 #1
RR NLR RR LOC
RKR NKR
PSU
101
B50(EXT)
f 4A A6 A5 A6 A5 D6 D5 R1 R2 PSU LOC LOC LOC NWR
B50(EXT)
B5 B6
f 4A A6 A5 R2 R4

101 101 A1 A2
101 *
NWR NWR RWR 101 101 #1
NKR RKR
A6 A5 DETECTION 101
CONTACTS RWR
B5 B6 A5 A6 D5 D6 R2 R1

D5 D6 R3 R1

PSU A2 A1
N50(EXT)
(RR) t A7 A8 PSU
N50(EXT)
B8 B7
EOL BOX
(LOC) t

@ @ 101A 101A 101B 101B 101 101 #


101A 101B IR IR IR IR RWKR NWKR
EOL EOL 101 101
A7 A8 PSU LOC LOC LOC NKR LOC RR NLR
B50(EXT) N N
3 4
B8 B7 f 4A 3 4 3 4 A6 A5 D6 D5 A6 A5 D6 D5 A8 A7 R1 R2

D1 D2 B1 B2

101 101 101 #


RKR NWKR RWKR
* IR, NWR & RWR ARE QBCA1 TYPE RELAYS 101
RLR
NWKR/RWKR ARE QBA1 TYPE RELAYS
#
A1 A2 A7 A8 R2 R1
#1 NKR/RKR USE QBBA1 RELAYS. QBA1 ALSO ACCEPTABLE
B2 B1
4 WIRE DETECTION
@ FOR D84M MACHINES EACH END IS PROVIDED WITH A SEPARATE EOL KEY
EOL BOX CIRCUITS ARE ALSO
ACCEPTABLE
@ @ A4 A3
101A 101B
EOL EOL 101
PSU LOC LOC NKR
N50(EXT) N N
(LOC) 5 6
t 7 8 7 8 A7 A8 D7 D8 A7 A8 D7 D8

D4 D3

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW102 SHEET TITLE: POINTS MAINTENANCE ISOLATION SWITCH - MICROLOK & RELAY EDMS No: SG0602002 SHEET No: W102 CIRCUIT BOOK No: 00001

POINTS
MAINTENANCE
LOC ISOLATION SWITCH

NV.OUT32(1)
I/F LOC
Y
1B
9 1 5
C8
MTCE *1
ISOLATION
IND
O/P 9 LOC
N12(EXT)
(LOC) 1W
t 2 6

NON VITAL
OUT32 (1)
LOC
MKII SLOT 7

LOC LOC
IN16(1)
LOC LOC I/F
B50
f 4A
B
3 2
2B
1
# 2
3B
2 3
B
1
B
E2 MTCE
MTCE #3 #3 MTCE
ISOLATION
ISOLATION ISOLATION
ARR IMM IND

LOC #1 SE SE #2 I/P 1
W W W
N50
(LOC) t 4 1
2W
4
# 3
3W
1 4 2
E4

VITAL
IN16 PCB (3)

POINTS
MAINTENANCE
(ALTERNATIVE WHERE ISOLATION SWITCH
RELAY DRIVEN)
POINTS
NORMAL
LOC LOC NKR
B50(EXT) Y
f 4A 5

A1 A2
*2

POINTS NORMAL
LOC
N50(EXT)
(LOC) t 6
Y
A4 A3 KEY
SWITCH ZIR

LOC LOC
B50(EXT)
f 4A 1
# 2 R1 R2 SIDING
NORMAL ISOLATED

LOC
N50(EXT)
(LOC) t 4
# 3

SANTON SWITCH NORMALLY CLOSED #1 ELSAFE BASE PART No. 21660


#
ELSAFE 290V ARRESTOR MODULE
PART No. 216680 (GRAPHITE)
NOTE:
420 OHMS
#2 ELSAFE BASE PART No. 216600 PERMISSION SHALL BE GRANTED FROM THE SIGNALLER
*1
ELSAFE IMMUNISATION MODULE PRIOR TO THE POINTS BEING ISOLATED
LED PART No. 216643 (YELLOW)
0.25W
KEY SWITCH 'NORMAL' INDICATIONS SHALL BE
12v - 20ma
#3 ELSAFE EARTHED MECHANICALLY PROVIDED TO THE LOGGER OR CONTROL SYSTEM
*2 LED TO THE MOUNTING RAIL
MOUNTING RAIL ELECTRICALLY
CONNECTED TO MAIN EARTH

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW103 SHEET TITLE: POINTS CONTROL (WITH MAINTENANCE ISOLATION SWITCH) - RELAY EDMS No: SG0602002 SHEET No: W103 CIRCUIT BOOK No: 00001

RLR RWR RWR NWR

PSU RR NLR RR LOC *


B50(EXT)
f 4A A6 A5 A6 A5 D6 D5 R1 R2

B5 B6

NWR NWR RWR

A6 A5
ZIR *

B5 B6 A5 A6 D5 D6 R2 R1

A2 A1

PSU
N50(EXT)
(RR) t A7 A8

B8 B7

A7 A8

B8 B7

* NWR & RWR ARE QBCA1 TYPE RELAYS

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW112 SHEET TITLE: POINTS MOTOR - SIEMENS 84M MKIII - RETROFIT DESIGN EDMS No: SG0602002 SHEET No: W112 CIRCUIT BOOK No: 00001

W LHSNC

INDUCTION MOTOR

7.3 7.4 2

4 CRANK
NOTE: 3.2 3.2
RETROFIT DESIGNS TO BE USED IN
CONTACT
CONJUNCTION WITH POINT OPERATING N-RI
CIRCUITS ON SHEET W113 FOR RIGHT
M
HAND MACHINES (RHSNC) AND SHEET
5.2 5.1
W114 FOR LEFT HAND MACHINES (LHSNC). 3.1 3.1

6.3 6.4

3 1
3.3 3.3

R-NI

2 3
BRAKE

1 5

RECTIFIER

1 2

W RHSNC

INDUCTION MOTOR

7.3 7.4 2

4 CRANK
3.2 3.2
CONTACT
R-NI

M
5.2 5.1
3.1 3.1

6.3 6.4

3 1
3.3 3.3

N-RI

2 3
BRAKE

1 5

RECTIFIER

1 2

ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW113 SHEET TITLE: POINTS OPERATION - SIEMENS 84M MKIII - DOUBLE RIGHT HAND EDMS No: SG0602002 SHEET No: W113 CIRCUIT BOOK No: 00001

* AW RHSNC

INDUCTION MOTOR

7/0.85 LOC 7.3 7.4 2


1 5

2 6 1 4 CRANK
3.2 3.2
C1 A C3 C1 C3 CONTACT
3 IR NWR 7 R-NI
4 8
C2 C4 C2 C4 M
5.2 5.1
3.1 3.1

85
7/0.
7/0.85 6.3 6.4
9

PSU LOC 7/0.85


10 2 3 1
3.3 3.3
WBX120
C1 C3
f 20A
RWR 11 N-RI
12
20A DP
C2 C4
2 3
BRAKE
PSU LOC 7/0.85
WBX120
1 5
f 20A
85

4
7/0.

RECTIFIER

PSU 7/0.85 7/0.85


17 13
WNX120
(LOC) t 18 14 3 1 2
C7 A C5

19 IR 15
20 16
C8 C6

* BW RHSNC

INDUCTION MOTOR

1 5 7/0.85 7.3 7.4 2

2 6 1 4 CRANK
3.2 3.2
C1 B C3 C5 C7 CONTACT
3 IR NWR 7 R-NI
4 8
C2 C4 C6 C8 M
5.2 5.1
3.1 3.1

7/0.85 6.3 6.4


9

10 2 3 1
3.3 3.3
C5 C7

RWR 11 N-RI

12
C6 C8
2 3
BRAKE

1 5

RECTIFIER

PSU 7/0.85 17 13 7/0.85


WNX120
(LOC) t 18 14 3 1 2
C7 B C5

19 IR 15
20 16
ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.
C8 C6

* WHERE 84M MKIII IS RETROFIT VERSION, REPLACE INTERNAL WIRING WITH CIRCUIT SHOWN ON SHEET W112

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW114 SHEET TITLE: POINTS OPERATION - SIEMENS 84M MKIII - DOUBLE LEFT HAND EDMS No: SG0602002 SHEET No: W114 CIRCUIT BOOK No: 00001

* AW LHSNC

INDUCTION MOTOR

7/0.85 LOC 7.3 7.4 2


1 5

2 6 1 4 CRANK
3.2 3.2
C1 A C3 C1 C3 CONTACT
3 IR NWR 7 N-RI
4 8
C2 C4 C2 C4 M
5.2 5.1
3.1 3.1

85
7/0.
7/0.85 6.3 6.4
9

PSU LOC 7/0.85


10 2 3 1
3.3 3.3
WBX120
C1 C3
f 20A
RWR 11 R-NI
12
20A DP
C2 C4
2 3
BRAKE
PSU LOC 7/0.85
WBX120
1 5
f 20A
85

4
7/0.

RECTIFIER

PSU 7/0.85 7/0.85


17 13
WNX120
(LOC) t 18 14 3 1 2
C7 A C5

19 IR 15
20 16
C8 C6

* BW LHSNC

INDUCTION MOTOR

1 5 7/0.85 7.3 7.4 2

2 6 1 4 CRANK
3.2 3.2
C1 B C3 C5 C7 CONTACT
3 IR NWR 7 N-RI
4 8
C2 C4 C6 C8 M
5.2 5.1
3.1 3.1

9 7/0.85 6.3 6.4

10 2 3 1
3.3 3.3
C5 C7

RWR 11 R-NI
12
C6 C8
2 3
BRAKE

1 5

RECTIFIER

PSU 7/0.85 17 13 7/0.85


WNX120
(LOC) t 18 14 3 1 2
C7 B C5

19 IR 15
20 16
ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.
C8 C6

* WHERE 84M MKIII IS RETROFIT VERSION, REPLACE INTERNAL WIRING WITH CIRCUIT SHOWN ON SHEET W112

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW119 SHEET TITLE: POINTS DETECTION - SIEMENS 84M - DOUBLE END LEFT HAND EDMS No: SG0602002 SHEET No: W119 CIRCUIT BOOK No: 00001

NOTE: BLANKING PLATE REQUIRED ON RHSC SOCKET

AW LHSNC BW LHSNC

MOTOR MOTOR
CONTACT CONTACT
R3 R5 R3 R5 RKR NKR

PSU LOC LOC 8.8 8.7 9.2 9.1 6.5 6.6 LOC LOC 8.8 8.7 9.2 9.1 6.5 6.6 LOC NWR
B50
13 17 13 17
f 4A P1 L1 L5 P5 P1 L1 L5 P5 A6 A5 R2 R4

A1 A2
N N-RI N N N-RI N

R4 R8 R4 R8 NKR RKR

8.6 8.5 9.4 9.3 7.5 7.6 8.6 8.5 9.4 9.3 7.5 7.6 RWR

14 20 14 20
P2 L2 L8 P8 P2 L2 L8 P8 D5 D6 R3 R1

A2 A1
R-NI R R R-NI R R

R1 R7 R1 R7

PSU 8.4 8.3 9.6 9.5 7.7 7.8 8.4 8.3 9.6 9.5 7.7 7.8
N50
(LOC) 15 19 15 19
t P3 L3 L7 P7 P3 L3 L7 P7

NOTE:
N N-RI N N N-RI N
QBA1 RELAYS MAY
ALSO BE USED
R2 R6 R2 R6

8.2 8.1 9.8 9.7 6.7 6.8 8.2 8.1 9.8 9.7 6.7 6.8

16 18 16 18
P4 L4 L6 P6 P4 L4 L6 P6

R-NI R R R-NI R R

EOL BOX

A A B B
A END B END IR IR IR IR RWKR NWKR
EOL EOL
PSU LOC LOC LOC NKR LOC RR NLR
B50 N N
3 4
f 4A 3 4 3 4 A6 A5 D6 D5 A6 A5 D6 D5 A8 A7 R1 R2

D1 D2 B1 B2

RKR
NWKR RWKR

A1 A2
RLR

A7 A8 R2 R1

EOL BOX B2 B1

A END B END
A4 A3
EOL EOL
PSU NKR
N50 N N
(LOC) 6
t 5 7 8 7 8 A7 A8 D7 D8 A7 A8 D7 D8

D4 D3

ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW120 SHEET TITLE: POINTS DETECTION - SIEMENS 84M DOUBLE RIGHT HAND EDMS No: SG0602002 SHEET No: W120 CIRCUIT BOOK No: 00001

NOTE: BLANKING PLATE REQUIRED ON LHSC SOCKET

AW RHSNC BW RHSNC

MOTOR MOTOR
CONTACT CONTACT
L4 6.7 6.8 L6 L4 6.7 6.8 L6 RKR NKR

PSU LOC LOC 8.6 8.5 9.4 9.3 LOC LOC 8.6 8.5 9.4 9.3 LOC NWR
B50
14 18 14 18
f 4A P2 R2 R6 P6 P2 R2 R6 P6 A6 A5 R2 R4
N N
A1 A2
N-RI N N-RI N

L3 7.7 7.8 L7 L3 7.7 7.8 L7 NKR RKR

8.8 8.7 9.2 9.1 8.8 8.7 9.2 9.1 RWR

13 19 13 19
P1 R1 R R7 P7 P1 R1 R R7 P7 D5 D6 R3 R1

A2 A1
R R-NI R R-NI

L2 7.5 7.6 L8 L2 7.5 7.6 L8

PSU 8.2 8.1 9.8 9.7 8.2 8.1 9.8 9.7


N50
(LOC) 16 20 16 20
t P4 R4 N R8 P8 P4 R4 N R8 P8
NOTE: QBA1 RELAYS MAY ALSO BE USED

N-RI N N-RI N

L1 6.5 6.6 L5 L1 6.5 6.6 L5

8.4 8.3 9.6 9.5 8.4 8.3 9.6 9.5

15 17 15 17
P3 R3 R R5 P5 P3 R3 R R5 P5

R R-NI R R-NI

EOL BOX

A A B B
A END B END IR IR IR IR RWKR NWKR
EOL EOL
PSU LOC LOC LOC NKR LOC RR NLR
B50 N N
3 4
f 4A 3 4 3 4 A6 A5 D6 D5 A6 A5 D6 D5 A8 A7 R1 R2

D1 D2 B1 B2

RKR
NWKR RWKR

A1 A2
RLR

A7 A8 R2 R1

EOL BOX B2 B1

A END B END
A4 A3
EOL EOL
PSU NKR
N50 N N
(LOC) 6
t 5 7 8 7 8 A7 A8 D7 D8 A7 A8 D7 D8

D4 D3

ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW121 SHEET TITLE: POINTS DETECTION - SIEMENS TD84M - DOUBLE END LEFT HAND EDMS No: SG0602002 SHEET No: W121 CIRCUIT BOOK No: 00001

NOTE: BLANKING PLATE REQUIRED ON RHSC SOCKET

AW LHSNC BW LHSNC

MOTOR MOTOR
CONTACT CONTACT
R3 R5 R3 R5 RKR NKR

PSU LOC LOC 8.8 8.7 9.2 9.1 6.5 6.6 LOC LOC 8.8 8.7 9.2 9.1 6.5 6.6 LOC NWR
B50
13 17 13 17
f 4A P1 L1 L5 P5 P1 L1 L5 P5 A6 A5 R2 R4

A1 A2
N N-RI N N N-RI N

R4 R8 R4 R8 NKR RKR

8.6 8.5 9.4 9.3 7.5 7.6 8.6 8.5 9.4 9.3 7.5 7.6 RWR

14 20 14 20
P2 L2 L8 P8 P2 L2 L8 P8 D5 D6 R3 R1

A2 A1
R-NI R R R-NI R R

R1 R7 R1 R7

PSU 8.4 8.3 9.6 9.5 7.7 7.8 8.4 8.3 9.6 9.5 7.7 7.8
N50
(LOC) 15 19 15 19
t P3 L3 L7 P7 P3 L3 L7 P7

N N-RI N N N-RI N NOTE: QBA1 RELAYS MAY ALSO BE USED

R2 R6 R2 R6

8.2 8.1 9.8 9.7 6.7 6.8 8.2 8.1 9.8 9.7 6.7 6.8

16 18 16 18
P4 L4 L6 P6 P4 L4 L6 P6

R-NI R R R-NI R R

A B
CRANK OP. CRANK OP.
MOTOR MOTOR A A B B
CUT-OFF CUT-OFF IR IR IR IR RWKR NWKR

PSU LOC LOC LOC LOC LOC NKR LOC RR NLR


B50
f 4A 7 5-5 5-6 8 7 5-5 5-6 8 A6 A5 D6 D5 A6 A5 D6 D5 A8 A7 R1 R2

D1 D2 B1 B2

RKR
NWKR RWKR

A1 A2
RLR

A7 A8 R2 R1

B2 B1

A4 A3

PSU NKR
N50
(LOC) t A7 A8 D7 D8 A7 A8 D7 D8

D4 D3

NOTE: THIS ARRANGEMENT IS SUITABLE ONLY


WHEN EOL IS NOT PROVIDED - Eg FREIGHT YARDS

ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW122 SHEET TITLE: POINTS DETECTION - SIEMENS TD84M - DOUBLE END RIGHT HAND EDMS No: SG0602002 SHEET No: W122 CIRCUIT BOOK No: 00001

NOTE: BLANKING PLATE REQUIRED ON LHSC SOCKET.

AW RHSNC BW RHSNC

MOTOR MOTOR
CONTACT CONTACT
L4 6.7 6.8 L6 L4 6.7 6.8 L6 RKR NKR

PSU LOC LOC 8.6 8.5 9.4 9.3 LOC LOC 8.6 8.5 9.4 9.3 LOC NWR
B50
14 18 14 18
f 4A P2 R2 R6 P6 P2 R2 R6 P6 A6 A5 R2 R4
N N
A1 A2
N-RI N N-RI N

L3 7.7 7.8 L7 L3 7.7 7.8 L7 NKR RKR

8.8 8.7 9.2 9.1 8.8 8.7 9.2 9.1 RWR

13 19 13 19
P1 R1 R R7 P7 P1 R1 R R7 P7 D5 D6 R3 R1

A2 A1
R R-NI R R-NI

L2 7.5 7.6 L8 L2 7.5 7.6 L8

PSU 8.2 8.1 9.8 9.7 8.2 8.1 9.8 9.7


N50
(LOC) 16 20 16 20
t P4 R4 N R8 P8 P4 R4 N R8 P8

N-RI N N-RI N NOTE: QBA1 RELAYS MAY ALSO BE USED

L1 6.5 6.6 L5 L1 6.5 6.6 L5

8.4 8.3 9.6 9.5 8.4 8.3 9.6 9.5

15 17 15 17
P3 R3 R R5 P5 P3 R3 R R5 P5

R R-NI R R-NI

A B
CRANK OP. CRANK OP.
MOTOR MOTOR A A B B
CUT-OFF CUT-OFF IR IR IR IR RWKR NWKR

PSU LOC LOC LOC LOC LOC NKR LOC RR NLR


B50
f 4A 7 5-5 5-6 8 7 5-5 5-6 8 A6 A5 D6 D5 A6 A5 D6 D5 A8 A7 R1 R2

D1 D2 B1 B2

RKR
NWKR RWKR

A1 A2
RLR

A7 A8 R2 R1

B2 B1

A4 A3

PSU NKR
N50
(LOC) t A7 A8 D7 D8 A7 A8 D7 D8

D4 D3

NOTE: THIS ARRANGEMENT IS SUITABLE ONLY


WHEN EOL IS NOT PROVIDED - Eg FREIGHT YARDS

ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:50 DRG No: CSTDW123 SHEET TITLE: POINTS DETECTION - SIEMENS D84M MKIII - SINGLE END LEFT HAND EDMS No: SG0602002 SHEET No: W123 CIRCUIT BOOK No: 00001

NOTE: BLANKING PLATE REQUIRED ON RHSC SOCKET

LHSNC

MOTOR
CONTACT
R3 R5 RKR NKR

PSU LOC LOC 8.8 8.7 9.2 9.1 6.5 6.6 LOC NWR
B50
13 17
f 4A P1 L1 L5 P5 A6 A5 R2 R4

A1 A2
N N-RI N

R4 R8 NKR RKR

8.6 8.5 9.4 9.3 7.5 7.6 RWR

14 20
P2 L2 L8 P8 D5 D6 R3 R1

A2 A1
R-NI R R

R1 R7

PSU 8.4 8.3 9.6 9.5 7.7 7.8


N50
(LOC) 15 19
t P3 L3 L7 P7

N N-RI N

R2 R6 NOTE: QBA1 RELAYS MAY ALSO BE USED

8.2 8.1 9.8 9.7 6.7 6.8

16 18
P4 L4 L6 P6

R-NI R R

CRANK OP.
MOTOR NOTE: REPLACE WHERE EOL
CUT-OFF NOT PROVIDED - Eg FREIGHT YARDS

LOC LOC

7 5-5 5-6 8

EOL BOX

IR IR RWKR NWKR
EOL
PSU LOC LOC LOC NKR LOC RR NLR
B50 N
3 4
f 4A 3 4 A6 A5 D6 D5 A8 A7 R1 R2

D1 D2 B1 B2

RKR
NWKR RWKR

A1 A2
RLR

A7 A8 R2 R1

EOL BOX B2 B1

A4 A3
EOL
PSU NKR
N50 N
(LOC) 5 6
t 7 8 A7 A8 D7 D8

D4 D3

ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDW124 SHEET TITLE: POINTS DETECTION - SIEMENS D84M MKIII - SINGLE END RIGHT HAND EDMS No: SG0602002 SHEET No: W124 CIRCUIT BOOK No: 00001

NOTE: BLANKING PLATE REQUIRED ON LHSC SOCKET

RHSNC

MOTOR
CONTACT
L4 6.7 6.8 L6 RKR NKR

PSU LOC LOC 8.6 8.5 9.4 9.3 LOC NWR


B50
14 18
f 4A P2 R2 R6 P6 A6 A5 R2 R4
N
A1 A2
N-RI N

L3 7.7 7.8 L7 NKR RKR

8.8 8.7 9.2 9.1 RWR

13 19
P1 R1 R R7 P7 D5 D6 R3 R1

A2 A1
R R-NI

L2 7.5 7.6 L8

PSU 8.2 8.1 9.8 9.7


N50
(LOC) 16 20
t P4 R4 N R8 P8

N-RI N

L1 6.5 6.6 L5 NOTE: QBA1 RELAYS MAY ALSO BE USED

8.4 8.3 9.6 9.5

15 17
P3 R3 R R5 P5

R R-NI

CRANK OP.
MOTOR NOTE: REPLACE WHERE EOL
CUT-OFF NOT PROVIDED - Eg FREIGHT YARDS

LOC LOC

7 5-5 5-6 8

EOL BOX

IR IR RWKR NWKR
EOL
PSU LOC LOC LOC NKR LOC RR NLR
B50 N
3 4
f 4A 3 4 A6 A5 D6 D5 A8 A7 R1 R2

D1 D2 B1 B2

RKR
NWKR RWKR

A1 A2
RLR

A7 A8 R2 R1

EOL BOX B2 B1

A4 A3
EOL
PSU NKR
N50 N
(LOC) 5 6
t 7 8 A7 A8 D7 D8

D4 D3

ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX001 SHEET TITLE: L.XING - APPROACH TRACK CCTS - SINGLE LINE AUTO SIGNALLING (OTS) EDMS No: SG0602002 SHEET No: X001 CIRCUIT BOOK No: 00001

B A

C D

DX XT UX

+ * R + R R * +

H G
* LENGTH TO PROVIDE MINIMUM 25 SEC.
WARNING AT MAXIMUM LINE SPEED
E F

TRACK PR'S DIRECTION STICK PROVING & TIMER

DX
PR DSJR DSJPR
DX
XING XING DX PR DX XING XING XING
B12 N12 B12 R1 R3
f 4A R1 R2 t (XING). f 10A R1 R2

B1 B2 B1 B2 B3 B4

XING
XT #1
N12 R2 R4
PR (XING) t

B1 B2
DDSR UDSR 300"

XT
D3 D5
PR A6 A5 A6 A5 A7 A8

XING XING XT XT XING


B12 N12 D4 D6
f 4A R1 R2 t (XING).

D1 D2 D3 D4
NOTE: A1 D2 NOTE:

OUTPUT RELAY
D3/D4 LOOP WIRING MUST
VOLTAGE STRAPPINGS
BE LESS THAN 2m
A2 D1
UX 12V - D1/D2
PR
UX 24V - D7/D2
A3 D7
XING XING UX PR UX XING
50V - D8/D2
B12 N12
f 4A R1 R2 t (XING).
A7 D8
D1 D2 B1 B2 D3 D4

XT #1
QTD4

PR

B3 B4

#1 TRACK STICK ARRANGEMENT ONLY REQUIRED


WHERE 12V CAPACITOR SLOW RELEASE DIRECTION
STICKS ARE USED AND WITH SHORT FAST TRAINS.
STICK PATH NOT REQUIRED WHERE DIRECTION STICKS
ARE 50V QSRA1 AND TRACK REPEATS ARE QSPA1.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX003 SHEET TITLE: L.XING - DIRECTION STICKS & CONTROL - SINGLE LINE AUTO SIG (OTS) EDMS No: SG0602002 SHEET No: X003 CIRCUIT BOOK No: 00001

B A

C D

DX XT UX

+ * R + R R * +

H G
* LENGTH TO PROVIDE MIMIMUM 25 SEC.
WARNING AT MAXIMUM LINE SPEED
E F

XT
PR
DX UX
PR PR

A6 A5

A3 A4 A4 A3

DDSR

A6 A5 B1 B2 A5 A6

UDSR

DIRECTION STICKS XT B1 B2
PR

XING XING DSJPR


B12
f 10A A8 A7

A1 A2 10000mF 10000mF
6R8W 6R8W
25V 10W 10W 25V

3 +2 1 1 +2 3

UDSR DDSR

XING
N12
R2 R1 R1 R2 t (XING)

C1 C2 C2 C1

C3 C4 C4 C3

C8 C7 C7 C8

CROSSING CONTROL MANUAL


XR OPERATION
XT SWITCH
XING XING DXPR PR UXPR XING
B12 N12
f 10A R1 R2 1 1 3 2 t (XING)

D1 D2 D1 D2 D1 D2

DSJPR UDSR DDSR DSJPR

D1 D2 D3 D4
D1 D2 D1 D2

EMR

A1 A2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX005 SHEET TITLE: L.XING - CONTROL - SHUNTER'S PUSHBUTTON SWITCHES EDMS No: SG0602002 SHEET No: X005 CIRCUIT BOOK No: 00001

UP TRACK UP TRACK
SHUNTERS SWITCHES
SYDNEY SIDE COUNTRY SIDE
SHUNTER'S PUSHBUTTON SHUNTER'S PUSHBUTTON

UP SS UP CS
UP (SH)R UP
START START (SH)R
UP
XING XING XING XING XING XING (SH)R XING
B15 N15
1 2 1 2 (XING)
f 4A R1 R2 t

UP SS UP CS A1 A2

CANCEL CANCEL
NOTE: A BATTERY SUPPLY MUST BE USED TRACK
WITH SHUNTERS PUSH BUTTONS
3

3
DN TRACK DN TRACK
SYDNEY SIDE COUNTRY SIDE
SHUNTER'S PUSHBUTTON SHUNTER'S PUSHBUTTON

DN SS DN CS
DN (SH)R DN
START START (SH)R
DN
XING XING XING XING XING XING (SH)R XING
B15 N15
1 2 1 2 (XING)
f 4A R1 R2 t

DN SS DN CS A1 A2

CANCEL CANCEL

TRACK

3
XRJR
XRJR
XING XING SSER CSER XING 3
B50 R1 R2 N50
f 4A t (XING)
A1
A1 A2 A1 A2
B7

B8
15"
A8

XR QTD5

FOR USE WHEN CROSSING HAS NO CANCELLING TRACK CIRCUIT

XING XING

XR

XING XING XING XING XING


B15 N15
f 4A R1 R2 t (XING)

SYDNEY SIDE COUNTRY SIDE


SHUNTER'S SWITCH SHUNTER'S SWITCH
NOTE: A BATTERY SUPPLY IS NOT ESSENTIAL

XR TRACK
XR
CONTROL CONTACTS UP DN
XING XING (SH)R (SH)R XING
B15 N15
f 4A R1 R2 t (XING)

A3 A4 A3 A4

XRJR

XR

D6 D5

C3 C4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX006 SHEET TITLE: L.XING - CONTROL & OPERATION - DOUBLE LINE (AUTOMATIC) EDMS No: SG0602002 SHEET No: X006 CIRCUIT BOOK No: 00001

SS GATE ZK
LXMON
B15 t14 3 1
SSER
VIO (12V)
XING XING XR XING
INPUT
4 2 N15 N15
OPTO 1 (XING) (XING)
t R1 R2 t
t22
SYDNEY SIDE GATE
BASE MECH C1 C2

LIGHT CONTROL (SSER)

SYDNEY SIDE LIGHT CONTROL 4C

GATES OPERATING XNR* CONTROL +


GATE 4B

DELAY XING 7/1.70mm


CONTROL + (MCRB)
1 MECH
* IF XNR PROVIDED
A1 A2 7/1.70mm
PROVE IN GATE CONTROL
CONTROL - REFER TO SHEET X039
2 7A

A4 A3 7/1.70mm

XING XING 7/.085 7/1.70mm


B15 MOTOR + (MCR2H) FOR DETAILS OF WESTERN CULLEN TYPE 3593
"EMERGENCY" MECH
f 20A 4 MECHANISM (LEVEL CROSSING BOOM GATE)
"SYDNEY SIDE BOOM"
XING 7/0.85 1 7/.085 7/1.70mm REFER TO SHEET X039
N15 MOTOR -
(XING) t 5 3 1 6 5 6A
4A

SS BOOM SW ZK CS GATE ZK
XING XING LXMON
B15 1 2 B15 t15 3 1
f 4A
CSER
VIO (12V) VIO (12V)
XING XING XR XING
LXMON INPUT INPUT
3 4 4 2 N15 N15
B15 t12 OPTO 1 t20 OPTO 1 (XING) (XING)
t R1 R2 t
t23
COUNTRY SIDE GATE
BASE MECH D1 D2

LIGHT CONTROL (CSER)


4C

COUNTRY SIDE LIGHT CONTROL CONTROL +


XNR*
GATE 4B
GATES OPERATING
DELAY XING 7/1.70mm
CONTROL + (MCRB)
1 MECH

D1 D2 7/1.70mm
CONTROL - REFER TO SHEET X039
2 7A

D4 D3 7/1.70mm

XING XING 7/.085 7/1.70mm


B15 MOTOR + (MCR2H)
"EMERGENCY" MECH
f 20A 4
"COUNTRY SIDE BOOM"
XING 7/0.85 1 7/.085 7/1.70mm
N15 MOTOR -
(XING) t 7 4 2 8 5 6A
4A

CS BOOM SW ZK
XING XING
B15 1 2
f 4A
VIO (12V)

LXMON INPUT
3 4
B15 t13 OPTO 1 t21

CS SS
GATE GATE GATE
XNR DELAY XNR
CS to CS SS to SS
XING XING XING BASE MECH MECH BASE XING XING BASE MECH MECH BASE XING XING
B15 N15
f 10A 3B 3C 3B 3C D6 D5 R1 R2 t (XING)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX007 SHEET TITLE: L.XING APPROACH & CONTROL - DOUBLE LINE AUTOMATIC EDMS No: SG0602002 SHEET No: X007 CIRCUIT BOOK No: 00001

XH 15S AT LINE SPEED XC 30S AT LINE SPEED B A


C D

DXH DX DD
+ R R + R

UD UX UXH
R + R R +

H G
XC XH
E F
30S AT LINE SPEED 15S AT LINE SPEED

CROSSING APPROACH
ARRANGEMENT FOR TRACK CIRCUIT APPROACH WITHOUT 2sec TIME DELAY PICK UP

DN UP
XAR XAR
DXH DX DN UXH UX UP
XING XING PR PR XAJR XING XING XING PR PR XAJR XING
B50 N50 B50 N50
f 4A R1 R2 t (XING) f 4A R1 R2 t (XING)

A1 A2 A1 A2 C1 C2 A1 A2 A1 A2 C1 C2

DN UP
XR XAJR XR XAJR

R1 R2 R1 R2
B1 B2 B3 B4
A1 A1

A7 A7

NOTE:
B7 B7
30" ALL LEVEL CROSSINGS WITH GATES INCLUDING 30"
B8 SINGLE LINE AND PEDESTRIAN ARE TO BE B8
FITTED WITH XAJR TIMERS TO PREVENT LOSS
C5 C6 OF SHUNT (NOT GCP). TYPICAL XAJR CIRCUIT C5 C6
SHOWN IS FOR DOUBLE LINE AUTOMATIC
QTD5 QTD5

DD WIRES TO BE KEPT SHORT UD WIRES TO BE KEPT SHORT


TOTAL WIRES TO C5/C6 TOTAL WIRES TO C5/C6
TO BE LESS THAN 5m TO BE LESS THAN 5m
CROSSING CONTROL
D6 D5 MANUAL D6 D5

XR OPERATION
UP UP DN DX SWITCH
XING XING XAR XAJR XAR XAJR XING
B15 N15
f 4A R1 R2 1 1 3 2 t (XING)

C1 C2 C1 C2 C1 C2 C1 C2

EMR

A1 A2

CROSSING CONTROL
ARRANGEMENT FOR TRACK CIRCUIT APPROACH WITH 3sec TIME DELAY PICK UP

EMR

MANUAL
XR OPERATION
A1 A2
SWITCH
XING XING UX DX UXH DXH XING
B15 N15
f 4A R1 R2 1 1 3 2 t (XING)

XR

A1 A2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX014 SHEET TITLE: L.XING - MONITORING - CIRCUIT CONNECTIONS EDMS No: SG0602002 SHEET No: X014 CIRCUIT BOOK No: 00001

LX MONITOR V4.0
ERICO
SURGE FILTER LXMON
DSF-6A-30 B15

RESET
XING XING
3 4 1
L1 E1 8 WAY OUTPUT OPTOISOLATOR LXMON B15 f8
B15 2 (+) 1
(USE PHOENIX CONNECTOR
f11 4A
2 DIGITAL INPUTS INPUT OPTO 1 t13
(USE PHOENIX 2 MSTB 2,5/2-ST OR EQUIVALENT)
DC SUPPLY 12VDC
CONNECTOR
INPUT 3 SSE PED ZK
MSTB 2,5/2-ST
XING 7 8
L2 E2 4 CSE PED ZK OR EQUIVALENT)
N15 1 (-)
(XING) t11 LXMON
5 BELL TIMER ZK
B15
5 t1
SIGNALLING 6 MODEM
EARTH
7 BATTERY
TEST R
8 TO RESET PUSHBUTTON B t1 TIMER
7/0.4
TEST R 7/0.4 LXMON
9 AC SUPPLY
O/P t1 N15
NOTE 4
OUTPUT
4 1 R1 R2 t1
10 LOW BATTERY
PORT 1
QBCA1
11 SPARE
12V
8-WAY
12 SS BOOM SW ZK
OUTPUT
13 CS BOOM SW ZK OPTOISOLATOR TIMER
TEST R
14 SS GATE ZK

7/0.4
15 CS GATE ZK
O/P t8
2 10
16 SAFE FLASH FLASHER FAIL

HH23PW-T
SAK-C10
DC 12V

LXMON
N15
SENSOR SUPPLY

1
BATTERY TEST R TO SSE ZK (0V) t2
1

2 INPUT OPTO 1 TO SSE (TIP) ZK (0V) t2


2

3 MODEM TO CSE ZK (0V) t2


(0V) 3

4 SSE PED ZK TO CSE (TIP) ZK (0V) t2


4

CSE PED ZK TO BATTERY ZK (0V) t1


5 5
(USE PHOENIX CONNECTOR
TO SSE ZK (12V) t1
6 6
MSTB 2,5/11-ST OR EQUIVALENT)
TO SSE (TIP) ZK (12V) t1
7
SAK-C10
TO CSE ZK (12V) t1
8
(+12V)
TO CSE (TIP) ZK (12V) t1
9

TO BATTERY ZK (12V) t2
10

INPUT TO TEST CUT OFF TIMER


TO LXMON INPUT OPTO 1 11
PORT 1 AND RELAY
O/P 1 * NOTE 3

NOTE 1: DISCONNECT LX MONITOR BEFORE INSULATION TESTING ANALOGUE INPUTS

NOTE 2:
# ALL WIRING TO LX MONITOR, VIO's AND CURRENT SENSORS 1
7/0.4mm UNLESS OTHERWISE SHOWN
INPUT SSE ZK t3
TO LXMON INPUT OPTO 1 2
NOTE 3: * CUSTOM MADE DB25 CABLE SUPPLIED WITH LX MONITOR O/P 2 * NOTE 3
PORT 2
3 SSE (TIP) ZK t3
NOTE 4: CUSTOM MADE DB15 CABLE SUPPLIED WITH LX MONITOR
4 CSE ZK t3

SPARE INPUT (USE PHOENIX CONNECTOR


5 CSE (TIP) ZK t3
PORT 3 MSTB 2,5/8-ST OR EQUIVALENT)
6 CSE (BOOM) ZK t3

7 SSE (BOOM) ZK t3

INPUT
8 BATTERY ZK t3
* NOTE 3 PORT 4

BLUE WIRE (Pin 1)


SSF ZK (VIO) t4

ORANGE OR YELLOW WIRE (Pin 2)


CSF ZK (VIO) t4

RED WIRE (Pin 22)


SSF ZK (VIO) t3

RED WIRE (Pin 23)


CSF ZK (VIO) t3

(CUT WIRES TO LENGTH BEFORE TERMINATING)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX015 SHEET TITLE: L.XING - MONITORING - CIRCUIT FUNCTION INPUTS (OPTO ISOLATOR) EDMS No: SG0602002 SHEET No: X015 CIRCUIT BOOK No: 00001

BATTERY BATTERY NOTE 1: ALL WIRING TO

TEST R TEST R PED US PED DS INPUT OPTOISOLATOR


LOCK LOCK 7/0.4mm UNLESS
OTHERWISE SHOWN
LXMON ZKR ZKR
B12 (B15) 1 17
t2 A8 A7 D8 D7 NOTE 2: WIRES CONNECT TO
INPUT INPUT INPUT OPTOISOLATOR
SEPARATE INPUTS WHERE POSSIBLE
THROUGH PHOENIX
DXT OPTO 1 OPTO 1 CONNECTORS MVSTBW
2 SSE PED ZK 18 2,5/8-ST-5,08 OR
EQUIVALENT

D1 D2
(INPUT OPTOISOLATOR NO. 1) (INPUT OPTOISOLATOR NO. 1)
NOTE 3: CUSTOM MADE DB25
XT #
CABLE SUPPLIED WITH
3 CSE PED ZK 19 LX MONITOR

D1 D2 NOTE 4: FOR SIGNALS OVER LEVEL


CROSSING AND ANY ADDITIONAL
UXT RELAY CONTACTS FOR SIGNALS,
4 SS BOOM SW ZK (VIO) 20 POINTS ETC WHICH ARE EASILY
AVAILABLE WITHOUT SIGNIFICANT
D1 D2 COST SHOULD BE CONNECTED
TO THE INPUT OPTO ON ANY
UDSR SPARE INPUTS.
5 CS BOOM SW ZK (VIO) 21

NOTE 5: AN ADDITIONAL INPUT


D1 D2 OPTOISOLATOR (INPUT OPTO 2)
DDSR CAN BE FITTED. ONLY THE FIRST

6 SS GATE ZK (VIO) 22 16 INPUTS ARE AVAILABLE.

NOTE 6: WHERE PROVIDED, DSPR & DSJPR


D1 D2 S-2000 D12/2.0 IIO S-2000 D12/2.0 IIO CONTACTS TO USE INPUTS
29 & 30
XR
7 CS GATE ZK (VIO) 23 NOTE 7: TRAFFIC LIGHT INTERFACING:
WHERE PROVIDED - INCLUDE THE
TDR & TLR AS MONITOR INPUTS
D1 D2

MANUAL DDT
OPERATION SWITCH
24
LOC LOC # NOTE 3
8 TO LXMON
3 2 4 4 # NOTE 3 D1 D2
DB25 INPUT PORT 2
UDT O/P 2
DB25 TO LXMON 25
XFR O/P 1 INPUT PORT 1
9
D1 D2
12 8

DXHT
PED GATE
26
ZKR
10
D1 D2
9 11
EMR UXHT
27

11
D1 D2
D6 D5 DN
XAR
28
BELL TIMER 12
D1 D2
UP
XAR
NOTE 6
29
PUSH BUTTON 13
D1 D2
RESET INPUT
XNR
NOTE 6
30
SPARE 14
D1 D2

SAFE FLASH
(FLASHER FAIL)
31
t2
NO CHARGE
15
WARNING KR

BATTERY TEST N12


32 LXMON

LOW BATTERY CUT-OFF N12 (N15)


16
t2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX023 SHEET TITLE: L.XING APPROACH & CONTROL - DOUBLE LINE (CONTROLLED SIGNALS) EDMS No: SG0602002 SHEET No: X023 CIRCUIT BOOK No: 00001

XH 15S AT LINE SPEED XC 30S AT LINE SPEED


1 3

R
DXH F R
DAT F R
1AT F R
1BT F R

101

R F R F R

UDT UAT UXH

XC XH

XR

XRJR XR MANUAL
UP UP DN DN OPERATION SWITCH
PSU LOC XAR XAJR XAR XAJR PSU
B50 N50
f 4A D6 D5 R1 R2 1 1 3 2 t (LOC)

C1 C2 C1 C2 C1 C2 C1 C2

EMR XR

A1 A2
A1 A2

NOTE:
ALL LEVEL CROSSINGS WITH GATES INCLUDING
XRJR SINGLE LINE AND PEDESTRIAN ARE TO BE
XRJR FITTED WITH XAJR TIMERS TO PREVENT LOSS
OF SHUNT (NOT GCP). TYPICAL XAJR CIRCUIT
PSU LOC SSER CSER PSU SHOWN IS FOR DOUBLE LINE WITH CONTROLLED SIGNALS
B50 R1 R2 N50
f 4A t (LOC)
A1
C1 C2 C1 C2
B7

B8
15"
A8

QTD5

DOWN XAR UP XAR


DN UP
XAR XAR
DXH DAT 1AT DN UXH UAT UP
PSU LOC PR PR PR XAJR PSU PSU LOC PR PR XAJR PSU
B50 N50 B50 N50
f 4A R1 R2 t (LOC) f 4A R1 R2 t (LOC)

A1 A2 A1 A2 A1 A2 C3 C4 A1 A2 A1 A2 C3 C4

DN UP
XR XAJR XR XAJR

R1 R2 R1 R2
B1 B2 1 B3 B4
A1 A1
LPR
1 2
A7 A7
ALSR ALSR
B7 B7
30" 30"
A6 A5
B8 B8
C1 C2 C1 C2
C5 C6 C5 C6

QTD5 QTD5

1BT WIRES TO BE KEPT SHORT WIRES TO BE KEPT SHORT UDT


TOTAL WIRES TO C5/C6 TOTAL WIRES TO C5/C6
TO BE LESS THAN 5m TO BE LESS THAN 5m

D6 D5 D6 D5

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX024 SHEET TITLE: L.XING - CONTROLLED SIGNALS EDMS No: SG0602002 SHEET No: X024 CIRCUIT BOOK No: 00001

1 LPR 1 1BT 1
TZR JR LPR
1 1 1AT 1BT 3AT 3BT 3XT DXH DAT
PSU LOC RUR SR PR PR PR PR PR PR PR PSU
B50 N50
f 4A A6 A5 A6 A5 R1 R2 t (LOC)

B1 B2 B1 B2 B1 B2 B1 B2 B1 B2 B1 B2 B1 B2 B1 B2
B1 B2

101 101
RWKR NWKR XRJR

B1 B2 C1 C2
B1 B2

XNR
THIS ARRANGEMENT IS WHERE A SIGNAL IS CLOSE TO THE
CROSSING, AND BOOMS NEED TO BE PROVED DOWN BEFORE SIGNAL
CLEARS.
B1 B2

1
LPR

A1 A2
1
1 UCR DAT
UCR

PR

R1 R2

B3 B4

XNR

B3 B4

1
UCR

A1 A2

2 UCR 2 2
TZR UCR
2 2 UAT UDT 31.0 UXH
PSU LOC RUR SR PR PR AT PR PSU
B50 N50
f 4A A6 A5 R1 R2 t (LOC)

B1 B2 B1 B2 B1 B2 B1 B2 B1 B2
B1 B2

XRJR

C3 C4
THIS ARRANGEMENT IS WHERE A SIGNAL IS WITHIN THE APPROACH,
BUT WHERE ADEQUATE WARNING IS STILL PROVIDED, AND THE SIGNAL
CLEARS WITH TRAIN APPROACHING.
XNR

C1 C2

2
UCR

A1 A2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:51 DRG No: CSTDX025 SHEET TITLE: L.XING - MONITORING - BATTERY CHARGER & TESTER CIRCUITS EDMS No: SG0602002 SHEET No: X025 CIRCUIT BOOK No: 00001

CUT OFF OMRON H3CR-A8 12VDC OR


TIMER NATIONAL PMH-10M 12VDC
BATTERY SOLID STATE TIMER
DELAY ON
TEST R (5 MINUTES) (8-PIN OCTAL BASE)
BATTERY
XING XING
SENSOR SUPPLY 7/0.4
TEST R 7 2
BX120
B12 t11
f 10A A6 A5 + -

BATTERY
12V (15V) DC A1 A2
CHARGER
XING
STORE NO.74

XING
NX120
(XING) t D1 D2

TIMER
SE TEST R
TEST
D6 D5 9 11 CUT OFF CUT OFF
R TIMER
TEST
CUT OFF 7/0.4 XING
N12
R
4 1 7 2 5 8 t (XING)

NATIONAL/MATSUSHITA
HG2-DC12V (20A)
5 8
(HG2-SFD Base)

BATTERY ZK
SENSOR GROUND (0V) t5
1
CURRENT SENSOR SUPPLY (+12V) t10
2
BATTERY SENSOR
ANALOGUE INPUT t8
TEST 4
TEST RESISTORS
XING XING
7/0.85
CUT OFF 7/0.85 7/0.4 7/0.4 7/0.4 XING
B12 BATT. BATT. N12
f 10A 3 1 1 3 C1 C3 C5 C7 t (XING)
3 OHM TEST TEST
7/0.4
R 7/0.4
R 7/0.4 XING
N12
2 4 C2 C4 C6 C8 t (XING)
3 OHM

7/0.4
I/P OPTO 1
t32

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX026 SHEET TITLE: L.XING - MONITORING - LOW BATTERY ALARM (STORE 74) EDMS No: SG0602002 SHEET No: X026 CIRCUIT BOOK No: 00001

TEST
CUT OFF
R

5 8

BATTERY
TEST R
STORE 74 CHARGER BUS No. OF CELLS
AMPERE CHARGING
HOURS VOLTAGE

D6 D5 B12 10 120 AH 14.5


NO CHARGE
+ 7/1.7 B15 12 140 AH 17.4
WARNING
XING XING 125V KR
V 0-20V
BX120
f 10A A6 A5 115V - 7/1.7

7/1.7 7/1.7
105V
RSA RSA

*SEE DETAILS BELOW


XING COM
7/1.7 7/1.7
NX120 N12/N15 B12/B15
(XING) t BUS BUS
t1 Ni/Cd CELLS
4A
7/0.4
* NO CHARGE
+
WARNING 7/0.4

KR -
BATTERY LOW ZK
XING XING
LXMON
B12 1 3
G B12 t10
f 4A
VIO (12V)
H
TO INPUT 16
T1 T2 2 4
9 ON INPUT OPTO 1

5
RESET NOT REQUIRED WHERE
8 ALARM ALARM CARD HAS
ADDITIONAL RELAY
LXMON TO INPUT 15 (AC SUPPLY) CONTACTS AVAILABLE
B12 t9 ON INPUT OPTO 1
T3 T4 E

* PLUG-IN 11-PIN RELAY


WITH BASE AND
RETAINING CLIPS
"FUJI" HH23PWT OR
"ORMRON" MK3P-1 #

TO INPUT 16
ON INPUT OPTO 1
1A
LXMON B12 t10
1F

# ALARM CARD
REFER TO DRAWING
M08-844/A FOR DETAILS

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX029 SHEET TITLE: PED.XING - GATE & LIGHT CONTROL (FLASHING) EDMS No: SG0602002 SHEET No: X029 CIRCUIT BOOK No: 00001

PEDESTRIAN GATE DELAY PEDESTRIAN LIGHT FLASHER

PED GATE
PED GATE
JR DELAY XR XFR
GATE
XING XING XING XING DELAY
B12 1 3 R1 R3 B12 10
f 4A R1 R2 f 4A B6 B5

12V A1 A2 OMRON
REGULATOR H3CR-A

XING XING
N12 2 4 R2 R4 N12 2
(XING) t (XING) t

T OFF = 500mS
T ON = 500mS

XR
D3 D5
D7 D8

D1 D2

D4 D6

A1 D1

NOTE: *
OUTPUT RELAY
VOLTAGE STRAPPING A2 D2
12V-D1/D2
24V-D7/D2
NOTE:
50V-D8/D2
A3 D7 TIME MAY VARY DEPENDING UPON WIDTH
18"
OF CROSSING- REFER TO DESIGN PRINCIPLES

* STRAPPING SHOWN FOR


12V GATE DELAY RELAY
A7 D8
D3/D4 LOOP WIRING
MUST BE LESS THAN 2m
QTD4

12V REGULATOR, 1A OUTPUT CURRENT


RIC STOCK CODE No: 1879485

NOTE: PROVE EMR DOWN IN SIGNALS OVER CROSSING

MASTER MASTER
EMR
EMERGENCY SW EMERGENCY SW
XING XING XING
B12 N12
1 3 2 (XING)
f 4A 1
# 2 R1 R2 3
#4 4 t

# CONTACTS NORMALLY OPEN

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX030 SHEET TITLE: PED.XING - LIGHTS OPERATING (FLASHING) EDMS No: SG0602002 SHEET No: X030 CIRCUIT BOOK No: 00001

SYDNEY SIDE "DON'T WALK" SYDNEY SIDE

PED LIGHT
SSE FLASH
XR DELAY APP. SIDE
PED ZK

XING XING XING BASE BASE XING XING


B15 5 4 N15
f 10A D6 D5 C6 C5 7/0.85mm 7/0.50mm 7/0.50mm 7/0.85mm t (XING)

LXMON
B15 3
t3 XFR
## LINE SIDE
1 3

OPTO
11 12 INPUT
t18 4 7/0.85mm 7/0.50mm 7/0.50mm

LXMON
N15 2
t4

# LAMPS: 12V LED TYPE

TRANSTECH PTS-VC 12VDC (0-3A DC)


#
ADJUST ALARM OUTPUT TO DETECT LOSS
OF ONE OR BOTH LIGHTS

##USE APPROPRIATE CONTROL RELAYS


AT LEAST TWO BACK CONTACTS
REQUIRED FOR REDUNDANCY

ALL WIRING 7/0.40mm UNLESS STATED

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX031 SHEET TITLE: PED.XING - EMERGENCY EXIT GATE OPERATION & CONTROL - MAGNETIC LATCH EDMS No: SG0602002 SHEET No: X031 CIRCUIT BOOK No: 00001

SS SS
UP SIDE DN SIDE
MAGNET MAGNET
SS SS
SS LOCK SS LOCK
UP SIDE UP PED P.BTN
DN SIDE DN PED P.BTN
XING LATCH DELAY XING BASE JB TERM STRIP
RED
* XING LATCH DELAY XING BASE JB TERM STRIP
RED
*
XING XING
B15 f 10A 5 9 B15 f 10A 5 9

SIOVS20K17 SIOVS20K17

XING XING
N15 N15
(XING) BLACK (XING) BLACK
t 10 6 t 10 6

LIMIT LIMIT
SWITCH SWITCH

COM GATE COM GATE


XING NC XING NC
CLOSED CLOSED
XING XING
B15 WHITE B15 WHITE
f 4A f 4A

NO NO
SS PED US SS PED DS
LOCK ZKR LOCK ZKR

XING XING
N15 N15
(XING) GREEN (XING) GREEN
t 10 2 t 10 2

PEDESTRIAN SS
LATCH DELAY UP SIDE
EMERG EMERG
REGULATOR SS PB 1 PB 2 SS LATCH DELAY
UP PED UP PED
XING XING BASE JB JB BASE XING
XING + + 14
B15 f 4A OMRON
INPUT OUTPUT 1 H3YN
4DC12 SET ON DELAY: 10 SEC
XING
N15 - - 13
(XING) t

SS
DN SIDE
EMERG EMERG
SS PB 1 PB 2 SS LATCH DELAY
DN PED DN PED
XING BASE JB JB BASE XING
+ 14

OMRON
OUTPUT 2 H3YN
4DC12 SET ON DELAY: 10 SEC

- 13

OUTPUT 3

OUTPUT 4

- 12V/1A REGULATOR
STOCK CODE 1879485
*MAGNET LOCK - SECURIRON MODEL SAMSC (12V)
ALL INTERNAL WIRING 7/0.40mm UNLESS OTHERWISE STATED.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX039 SHEET TITLE: L.XING - BOOM GATE MECHANISM - WESTERN CULLEN MODEL 3593 EDMS No: SG0602002 SHEET No: X039 CIRCUIT BOOK No: 00001

BASE

CONTROL-

CONTROL+

#1 LIGHT CONT.
(SS/CS ER)

XNR +
MANUAL TEST SWITCH TO BE
FIXED PERMANENTLY OPEN
XNR -
CIRCUIT OR REMOVED
1A 2A 3A 4A 5A
6A 7A

1B 2B 3B 4B 5B 6B 7B

#1 REFER TO SHEET X006 FOR


LEVEL CROSSING CONTROLS
AND OPERATION

1C 2C 3C 4C 5C 6C 7C

MCR
MOTOR +

#1
B N
MOTOR-

1F 1H

1B

PICK UP
COIL
2F 2H

2B
P
F S

PICK UP COIL
32 OHM
HOLD COIL
340 OHM

LRU1 SRU1
LIMIT
HOLD CLEAR SNUB
COIL RES.
RES
LRU2 SRU2
H
F S

CONTACT CLOSED FUNCTION

1 MOTOR ACTIVATED (POWER UP)

NOTE:
2 - SPARE A2 A1
CONFIRM CIRCUIT ARRANGEMENT
M
AGAINST SUPPLIED TYPE APPROVED
3 XNR (GATE DOWN)
SPECIFICATION OR CIRCUIT DIAGRAM
4 LIGHTS CONTROL (GATE CLEAR)

5 SPARE S2 S1

6 SNUB FIELD

7 MOTOR DE-ACTIVATED (POWER DOWN)

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX041 SHEET TITLE: L.XING / PED.XING - GATE TIMER CONTROL - QTD4 RELAYS EDMS No: SG0602002 SHEET No: X041 CIRCUIT BOOK No: 00001

GATE
GATE
JR DELAY

XING XING
B12 1 3 R1 R3
f 4A R1 R2

12V
REGULATOR

1 # 3
XING REGULATOR
N12 2 4 R2 R4
WITH HEATSINK
(XING) t FITTED
+ +

XR - -
1mF 0.1m F
D3 D5
50V 63V
D7 D8
(ELECTROLYTIC)
B3 B4 2 4

12V VOLTAGE REGULATOR


D4 D6

A1 D1
# 12V REGULATOR L78S12CV, 2A OUTPUT CURRENT:
* RS STOCK No: 633-032
HEATSINK: 8.6°C/W RS STOCK No: 268-076
A2 D2
TIMER SETTINGS NOTE:
10 SEC NO BRIDGING
OUTPUT RELAY
11-30 SEC A1-A7
A3 D7 VOLTAGE STRAPPING
10"-12"
12V-D1/D2
24V-D7/D2
50V-D8/D2
A7 D8

QTD4

* STRAPPING SHOWN FOR


12V GATE DELAY RELAY
D3/D4 LOOP WIRING
MUST BE LESS THAN 2m

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX042 SHEET TITLE: L.XING - CROSSING APPROACH & CONTROL SINGLE LINE EDMS No: SG0602002 SHEET No: X042 CIRCUIT BOOK No: 00001

NOTE:
XC 30S AT LINE SPEED
B A
ALL LEVEL CROSSINGS WITH GATES INCLUDING
SINGLE LINE AND PEDESTRIAN ARE TO BE
C D FITTED WITH XAJR TIMERS TO PREVENT LOSS
OF SHUNT (NOT GCP).
TYPICAL XAJR CIRCUIT SHOWN IS FOR SINGLE LINE
DX XT UX

+ + +
R R R

H G

E F
XC 30S AT LINE SPEED

XAR

XING XING DX UX XAJR XT XING


B15 N15
f 4A R1 R2 t (XING)

C3 C4

XAJR
UDSR DSJPR DDSR DSJPR
R1 R2

A1
C1 C2 C3 C4
C1 C2 C1 C2
A7

B7
30"
B8

C5 C6 C5 C6
GATE GATE IMPORTANT
QTD5
JR DELAY TOTAL WIRING LENGTH

XING
XT UX TO C5 AND C6 MUST NOT
XING
EXCEED 5m
B15 1 3 R1 R3
f 4A R1 R2
DDSR

12V
REGULATOR USE THIS ARRANGEMENT
C3 C4
WHERE THERE ARE NO
DIRECTION STICKS AND DX
XING
N15 2 4 R2 R4 TPR's NOT CUT BY XT
(XING) t
UDSR

C3 C4

XR USE THIS ARRANGEMENT WHERE


D3 D5
TPR's ARE QUALIFIED BY XT AND
D7 D8 DIRECTION STICKS ARE CAPACITOR
B3 B4 SLUGGED 12V QN1

D4 D6

MANUAL
NOTE: XR
OPERATION SWITCH
A1 D1
D3/D4 LOOP WIRING MUST XING XING XAR XAJR XING
BE LESS THAN 2m B15 N15
f 4A R1 R2 1 1 3 2 t (XING)
A2 D2
A1 A2 C1 C2
NOTE:

OUTPUT RELAY
A3 D7 * 12" VOLTAGE STRAPPING EMR
12V-D1/D2

A7 D8 24V-D7/D2
A1 A2
50V-D8/D2

QTD4

* STRAPPING SHOWN FOR


50V GATE DELAY RELAY

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX045 SHEET TITLE: L.XING - BELL OPERATION & TIMER WITH GATE PROTECTION - SINGLE LINE EDMS No: SG0602002 SHEET No: X045 CIRCUIT BOOK No: 00001

SS
BELL
BELLS
XR
BELL SS to SS SS
XING XING TIMER XING BASE BASE X-ARM X-ARM BASE XING XING
B15 N15
f 10A 6 7/0.85 * 7/0.85 7/0.85 7/0.85
7 t (XING)

CS
BELL

CS to CS CS
XING BASE BASE X-ARM X-ARM BASE XING

6 7/0.85 * 7/0.85 7/0.85 7/0.85


7

XNR
BELL TIMER # SUITABLE TYPE APPROVED ELECTRONIC AUDIBLE
WARNING DEVICE MAY BE USED
ZK *
LXMON
SUPPRESSION OF BELL
1 3
B15
t5
VIO (12V)
*BELL ON MORE DENSELY POPULATED
SIDE OF CROSSING MAY BE SUPPRESSED
XING WHEN THE GATES ARE NORMAL
N15 2 4 INPUT OPTO 1
XNR CAN BE USED IF PROVIDED IN
(XING) t t12 PLACE OF MECHANISM CONTACT

EMR
BELL TIMER SIGNAL PROVING
BELL
TIMER (WITH BOOMS)
A6 A5
HR

XING XING XING XING XING TRACK TRACK XNR


B15 N15 B15
+ - (XING)
f 10A t f 10A R1 R2

B1 B2

12V QUARTZ TIMER


MI: 09917055
STORE 570
OFF 2200Hrs
ON 0600Hrs
XR

SIGNAL PROVING
A6 A5
(LIGHTS ONLY)
EMR HR

XING XING TRACK


B15
f 10A A6 A5 R1 R2

NOTE:
REFER TO SPG724 APPENDIX D
FOR BELL VOLUME SETTINGS INFORMATION

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX051 SHEET TITLE: PED.XING - PED. GATE OPERATION WITHOUT GATE CONT. - THE MET STYLE M2 EDMS No: SG0602002 SHEET No: X051 CIRCUIT BOOK No: 00001

SYDNEY/COUNTRY SIDE GATES *1


LEFT HAND PEDESTRIAN GATE *1

PED
UP SIDE XNR
LIMIT SW
GATE
No 1 OPEN
DELAY 90°

A6 A5
MECH

B1 B2
*1
UP/DN PED 2R2
XING XING XING MECH 13 V
7/0.85mm 7/0.85mm 7/0.85mm BROWN
BX120
f 10A A8 A7 1 1 L1 10 20 19 11
25W
mF
20

2R2
B3 B4

25W
CLOSED
MOTOR

16 PEDESTRIAN TRAFFIC

50mF
2R2
XING XING
7/0.85mm 7/0.85mm 7/0.85mm BLACK
BX120
f 10A B6 B5 2 2 L2 17 21 22 18 15 14 W
25W
mF
25

EMERGENCY
PEDESTRIAN OPTIONAL
B8 B7
GATES
XING 7/0.85mm 7/0.85mm 7/0.85mm 24 BLUE
NX120
(XING) 3
t 10 3 1 9 3 L3 12 U

4
12 4 2 11

PED
GATE ZKR

XING XING
7/0.85mm
BX120
f 4A 2 10 5

RIGHT HAND PEDESTRIAN GATE *1

7/0.85mm

PED
XNR
GATE LIMIT SW
DELAY No 1
DOWN SIDE
B6 B5
MECH

C1 C2
*1
UP/DN PED 2R2
XING XING XING MECH 13 V
7/0.85mm 7/0.85mm 7/0.85mm BLACK
BX120
f 10A B8 B7 1 1 L1 10 20 19 11
25W
mF
20

2R2
C3 C4

25W
MOTOR

16

50mF
2R2
XING XING
7/0.85mm 7/0.85mm 7/0.85mm BROWN
BX120
f 10A C6 C5 2 2 L2 17 21 22 18 15 14 W
25W
mF
25
OPEN

90°

OPTIONAL
C8 C7

7/0.85mm 24 BLUE

3 3 L3 12 U


ARRANGEMENT WITHOUT GATE CONTROL RELAY
CLOSED

PEDESTRIAN TRAFFIC
*1 DELETE SIDE NOT RELEVANT. ENSURE MOTOR HAND MATCHES GATE SIDE.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX052 SHEET TITLE: PED.XING - PED. GATE OPERATION WITH GATE CONT. - THE MET STYLE M2 EDMS No: SG0602002 SHEET No: X052 CIRCUIT BOOK No: 00001

LEFT HAND PEDESTRIAN GATE *1


SYDNEY/COUNTRY SIDE GATES *1

LIMIT SW
No 1 OPEN
UP SIDE GATE
90°
CONTROL MECH

(SS/CS) PED 2R2


XING XING B1 B2 XING MECH 13 V
7/0.85mm 7/0.85mm 7/0.85mm BROWN
BX120
f 10A 1 1 L1 10 20 19 11
25W
mF
20

2R2
B3 B4

25W
CLOSED
MOTOR

16 PEDESTRIAN TRAFFIC

50mF
2R2
XING XING
7/0.85mm 7/0.85mm 7/0.85mm BLACK
BX120
f 10A B6 B5 2 2 L2 17 21 22 18 15 14 W
25W
mF
25

EMERGENCY
PEDESTRIAN OPTIONAL
B8 B7
GATES
XING 7/0.85mm 7/0.85mm 7/0.85mm 24 BLUE
NX120
(XING) 3
t 10 3 1 9 3 L3 12 U

4
12 4 2 11

PED
GATE ZKR

XING XING
7/0.85mm
BX120
f 4A 2 10 5
RIGHT HAND PEDESTRIAN GATE *1

7/0.85mm

LIMIT SW
DOWN SIDE
No 1
GATE
CONTROL MECH

(SS/CS) PED 2R2


XING XING C1 C2 XING MECH 13 V
7/0.85mm 7/0.85mm 7/0.85mm BLACK
BX120
f 10A 1 1 L1 10 20 19 11
25W
mF
20

2R2
C3 C4

25W
MOTOR

16

50mF
2R2
XING XING
7/0.85mm 7/0.85mm 7/0.85mm BROWN
BX120
f 10A C6 C5 2 2 L2 17 21 22 18 15 14 W
25W
mF
25

OPTIONAL
C8 C7

7/0.85mm 24 BLUE
OPEN
3 3 L3 12 U
90°

ARRANGEMENT WITH GATE CONTROL RELAY


(NOTE: XNR PROVED IN GATE CONTROL) 0°

CLOSED

*1 DELETE SIDE NOT RELEVANT. ENSURE MOTOR HAND MATCHES GARE SIDE.
PEDESTRIAN TRAFFIC

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:52 DRG No: CSTDX053 SHEET TITLE: PED.XING - PEDESTRIAN GATE MECHANISM - THE MET STYLE M2 EDMS No: SG0602002 SHEET No: X053 CIRCUIT BOOK No: 00001

R3

2R2 25W
R2

2R2 25W

LIMIT SW LIMIT SW
No.3 No.2 R1
120V DC
SONALERT
2R2 25W

EMERGENCY EMERGENCY
GATE GATE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

U V W
L1 L2 L3 L5 L6 L7 L8 L9 AUDIBLE
50uF 20uF 25uF
MOTOR INPUT
110V 50Hz DETECTION DETECTION
TERMINATION
LED PED LIGHTS
SUPPLY (JZA) LIMIT SW BLOCK
No.1

MAGNETIC MAGNETIC PED LOCK


LATCH LOCK ZKR
DELAY
NOTE:
SWITCHES SHOWN WITH GATE
IN CLOSED POSITION

LIMIT SWITCHES

OPEN OPEN

LEFT HAND RIGHT HAND No3


GATE GATE

POSITION OF CAMS
WITH GATE CLOSED
CLOSED CLOSED

No2

PEDESTRIAN PEDESTRIAN
TRAFFIC TRAFFIC

No1

ADJUSTABLE CAMS

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX054 SHEET TITLE: PED.XING - PEDESTRIAN GATE DETECTION - THE MET STYLE M2 EDMS No: SG0602002 SHEET No: X054 CIRCUIT BOOK No: 00001

PED. PED
GATE DELAY XNR

XING XING

D6 D5 R1 R2
NOTE: ARRANGEMENT WHEN VITAL XNR IS REQUIRED

PEDESTRIAN XNR/XRR

SW3 PED SW3


MADE XNR MADE
UP DOWN
0°-10° UP XING XING DN 0°-10°
GATE GATE

XING XING XING UP 5 5 DN XING XING


7 7 2 2 10 2 7 7
B15 N15
f 4A 1 5 5 1 t (XING)

6 6 6 6

MADE MADE
10°-90° 10°-90°
SW2 SW2
UP PED DOWN
GATE MADE XRR MADE GATE
UP 80°-90° UP DN 80°-90° DN

8 8 9 9 3 2 10 3 9 9 8 8

NOTE: NON-VITAL RELAY SHOWN FOR MONITOR INPUT ONLY.


IF VITAL XNR FUNCTION REQUIRED, USE Q TYPE RELAYS

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX055_1 SHEET TITLE: GRADE CROSSING PREDICTOR (GCP) - SAFETRAN 3000 ND EDMS No: SG0602002 SHEET No: X055_1 CIRCUIT BOOK No: 00001

CROSSING APPROACH XING CROSSING APPROACH


1215m TO T1, T2 LOC 1215m TO R1, R2
35sec @ 125Km/h B A 35sec @ 125Km/h
(INC 9sec PREEMPT WARNING TIME) EMERGENCY (INC 9sec PREEMPT WARNING TIME)
SWITCH
C D
348Hz NARROWBAND SHUNT 348Hz NARROWBAND SHUNT
P/No.62775-348 P/No.62775-348
16mm2 TRACK LEAD 16mm2 TRACK LEAD

1215m 20m 1215m

FROM TO
H G

T2)

R2)
T1)

R1)
NOTES
E F

(
(

(
1. ALL WIRING TO TRACK MUST BE 16mm2 AND TWISTED EVERY 150mm.

2. ALL WIRING BETWEEN THE SURGE PANEL AND THE SAFETRAN 3000
2 .
MUST BE 6mm

2 .
3. ALL JUMPER WIRES FOR LIGHT CIRCUITS TO BE NO LESS THAN 2.5mm
GCP
SEE NOTE 11 2 .
REGULATOR 4. TRACK LEAD WIRE MUST BE AT LEAST 16mm
XING XING
B15 5. MAXIMUM CABLE LENGTH FROM TRANSMITTER TERMINAL TO TRACK IS 30m.
# WIRES TYPE 2 # # 10A f 6. EACH TRANSMITTER AND RECEIVER PAIR ARE TO BE SEPARATED TO THE
TWISTED 6mm
B15 N15 MAXIMUM EXTENT. THE MAXIMUM TOTAL CABLE LENGTH FOR T1 + R1
RCV1 RCV2 Safetran XING
E 7 8 5 6 2 4 N15 SHALL BE APPROX 80m. THE MAXIMUM TOTAL CABLE LENGTH FOR
Surge Panel t (XING) T2 + R2 SHALL BE APPROX 80m.
XMT1 XMT2
1 3 Twisted
80026-01 7. ISLAND TRACK MAXIMUM LENGTH IS 90 METRES.
16mm 2 MANUAL
OPERATION 8. R1,T1 MUST BE CONNECTED TO THE SAME RAIL. R2,T2 MUST BE
# # # XR
SWITCH CONNECTED TO THE SAME RAIL.

9. TRACK MUST BE CONTINUOUSLY BONDED BETWEEN SHUNTS

R1 R2 1 1 3 2 10. NARROWBAND SHUNT SHOULD BE CONNECTED AS CLOSE AS POSSIBLE


TO THE RAILS AND HOUSED IN A PROTECTIVE ENCLOSURE.
QS2 (6F-6B)
PROGRAM 11. RS CATALOGUE NUMBER 2278823
35 Amp BRIDGE RECTIFIER MOUNTED ON ALUMINIUM PLATE
No. OF TRACKS : 1 MUST USE HEAT SINK COMPOUND BETWEEN RECTIFIER AND ALUMINIUM PLATE
FREQUENCY : 348 TRACK ISL RLY GCP POWER
F1 12. SURGE PANEL CONSISTS OF EQUALIZER, HD PART No. 022700 AND ARRESTOR
TRACK 1 : BIDIRECTIONAL XMT1 XMT2 RCV1 RCV2 MS/GCP ON
ENA B CONTROL N + - + - HD PART No. 022585.
TRANSMIT LEVEL : MAX TB1
1 2 3 4
APPROACH : 1215m 13. WHERE A SHUNTING ENHANCER IS USED, ONE BLOCK JOINT IS REQUIRED
UAX 8 ISL
5 6 7 9 10 11 12 3A/5B FOR EACH APPROACH.
UAX PICK UP DELAY : 35 TRANS OFF
ENA/UAX2 DELAY : 35 IND SLAVING + -
TB2 GCP RLY
SLAVING : MASTER
1 2 3 4
5 6
PASSWORD : ENTERED 7 8
CHK1 CHK2 RCV1 RCV2
RECORDER : INSTALLED
GCP - SINGLE TRACK - NO DAX J1 MODEL 3000 ND ISLAND
RS232C BAUD RATE : 1200 RECORDER P/N 80060-011 PR
Safetran Systems
RS232C DATA BITS : 8 ISLAND RELAY USED FOR
STOP BITS : 1 MONITORING PURPOSES ONLY
PARITY : NONE
DATE : ENTERED R1 R2

TIME : ENTERED
DAYLIGHT SAVING : OFF

DC SHUNTING
XING XING
ENHANCER PANEL. 80049 REQUIRED AT LOCATIONS WHERE
BX120
SHUNTING IS NOT RELIABLE DUE TO LOCAL CONDITIONS
f 4A

XING
NX120
MODULE PART
(XING) t MODULES
POSITION NUMBER

1 ISLAND MODULE 10.0KHz 80011

POS NEG
2 TRANCEIVER MODULE 80012
80058 REV-
SAFETRAN SYSTEM S

3 RELAY DRIVE 80013


BATTERY FUSE

4 PROCESSOR 80014
INPUT
NEG

POS

BX
CX
115AC
12DC

5 DATA RECORDER 80015

6 SPARE X

7 SPARE X
TB

8 SPARE X
OUTPUT

LINE FUSE

9 SPARE X
TN

10 KEY PAD PCB 80017


KEY PAD 80019
T4

T3

T2

T1

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX055_2 SHEET TITLE: GRADE CROSSING PREDICTOR (GCP) - 3000 - APPLICATION HISTORY CARD EDMS No: SG0602002 SHEET No: X055_2 CIRCUIT BOOK No: 00001

PROGRAMMING HISTORY EXPANDED PROGRAMMING HISTORY 3000GCP


INITIAL PROGRAMMED VALUE DATE INITIAL PROGRAMMED VALUE DATE APPLICATION HISTORY CARD
PRESS PROGRAM KEY PRESS FUNCTION KEY
(FILL OUT AND RETAIN WITH GCP)
NUMBER OF TRACKS (NUMBER OF
SWITCH TO MS (ENTER EZ VALUE) T1:
10 EZ (UNITS EQUIPPED WITH PROCESSOR MODULE 80014, 80044 OR 80214)
TRANSCEIVER MODULES, 1 OR 2) 1 X 2

FREQUENCY (MS/GCP)** T1:


348 HZ T2: EZ

T2: HZ TRANSFER DELAY MS TO GCP (0 = OFF) T1:


0 SEC EQUIPMENT 3000

UNIDIRECTIONAL/BIDIRECTIONAL T1: UNI BI X T2: SEC 3000D2

T2: UNI BI PRIME PREDICTION OFFSET (0 = OFF) T1:


0 FT 3000D2L

XMIT LEVEL T1: MAX MED X T2: FT 3000ND

T2: MAX MED PICKUP DELAY PRIME


15 SEC 3000ND2

PREDICTOR/MOTION SENSER T1: PRED X MS PICKUP DELAY DAX A


15 SEC

T2: PRED MS PICKUP DELAY DAX B


15 SEC

WARNING TIME SELECTED T1:


30 SEC PICKUP DELAY DAX C
15 SEC

T2: SEC PICKUP DELAY DAX D


15 SEC UNIT/SERIAL No:

APPROACH DISTANCE SELECTED T1:


3986 FT COMPENSATION VALUE T1:
COMPUTED CROSSING NAME:

T2: FT T2:
COMPUTED LINE:

COMPUTED T1: FT KILOMETRAGE:


ON X OFF
# ENHANCED DETECTION (ED) T1:
NEW SOUTH WALES
T2: FT STATE:
T2: ON OFF
UAX1 PICKUP DELAY (UAX) (0 = OFF)
5 SEC DATE INSTALLED:
NO X YES
0 # BACK TO BACK T1 AND T2
ENA/UAX2 DELAY (0 = ENA) SEC (WHEN ED IS ON) WEATHER CONDITIONS:

ISLAND DISTANCE (BETWEEN TRANSMIT T1:


66 FT ISLAND FREQUENCY: T1:
10.0 KHZ T2: KHZ
10
& RECEIVE TRACK WIRE CONNECTIONS) # STATION STOP TIMER T1: SEC
T2: FT (WHEN ED IS ON)
T2: SEC
NUMBER OF DAXS 0 1 2 3 4
X NUMBER OF TRACK WIRES T1: 4 X 6
(FOR 3000ND AND 3000ND2 UNITS,
SET THIS ITEM TO (0) 5 6 7 8
T2: 4 6

DAX A TRACK ASSIGNMENT T1: T2:


# LOW EX ADJUSTMENT T1:
FT
DAX A DISTANCE (0 = PREEMPT)
T2: NOTES:
SEC
DAX A WARNING TIME

LOW EZ DETECTION T1: ON OFF DETAILS ENTERED MAY VARY WITH SPECIFIC JOB & ARE
DAX B TRACK ASSIGNMENT T1: T2:

ON OFF AS INDICATIVE INFORMATION ONLY.


T2:
DAX B DISTANCE (0 = PREEMPT) FT

LOW EZ DETECTION TIMER T1: MIN BEFORE ENTERING INITIAL PROGRAM ALL VALUES MUST BE
DAX B WARNING TIME SEC
(WHEN LOW EZ DETECTION IS ON)
SET TO THE DEFAULT VALUE
T2: MIN
DAX C TRACK ASSIGNMENT T1: T2:
POSITIVE START (0 = OFF) T1:
0 EZ
DAX C DISTANCE (0 = PREEMPT) FT ** DUAL FREQUENCY OPERATION AVAILABLE ONLY IN
(ENTER EZ VALUE) DUAL-FREQUENCY 3000 GCP'S EQUIPPED WITH 80214 PROCESSORS
T2: EZ
DAX C WARNING TIME SEC

POSITIVE START TIMEOUT (0 = NONE) T1: MIN # APPLICABLE ONLY TO 3000 GCP'S EQUIPPED WITH 80044 OR
DAX D TRACK ASSIGNMENT T1: T2:
(WHEN POSITIVE START IS ON) 80214 PROCESSORS.
T2: MIN
DAX D DISTANCE (0 = PREEMPT) FT

SET AT OPERATION NORMAL X APPLICABLE ONLY TO 3000 GCP'S EQUIPPED WITH 80214
DAX D WARNING TIME SEC
PROCESSORS WITH A01C REVISION AND LATER.
DIAGNOSTIC
SLAVING MASTER/SLAVE MASTER X SLAVE
O ON OFF
C DIAGNOSTIC MESSAGES X APPLICABLE ONLY TO 3000 GCP'S EQUIPPED WITH 80214
PASSWORD ENABLED DISABLED
PROCESSORS WITH A01E REVISION AND LATER.
O ON OFF
C DAX MESSAGES X
ENABLED X
ADVANCE PREEMPT TIMER
0 SEC O APPLICABLE ONLY WHEN A SEA/R NODE HAS BEEN PROGRAMMED
C
RECORDER INSTALLED NOT INSTALLED
INTO THE GCP FROM A SEA/R.
INSTALLED X

EXTERNAL NODE # CALIBRATION HISTORY LINEARIZATION HISTORY


RS-232-C BAUD RATE
9600 BPS
EZ/EX VALUES HARDWIRE SHUNT AT HARDWIRE SHUNT AT 50
RS-232-C DATA BITS 7 8 X (TRACK UNOCCUPIED) TERMINATION SHUNT PERCENT POINT OF TRACK

RS-232-C STOP BITS 1 X 2


NO LINEARIZATION
.
RS-232-C PARITY NONE X ODD EVEN EZ . 2 LINEARIZATION COMPLETE
EZ EX EZ VALUE
VALUE
SPACE MARK
EZ VALUE STEP +/- EZ
DATE (E.G. THU 03 APR 1997)
(TO BE ENTERED)
EAST TRACK 1
TIME (E.G. 11:25:43 AM)
(TO BE ENTERED)
WEST TRACK 1
DAYLIGHT SAVINGS ON OFF X
EAST TRACK 2

WEST TRACK 2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX056 SHEET TITLE: L.XING - SURGE PROTECTION (FOR INFORMATION ONLY) EDMS No: SG0602002 SHEET No: X056 CIRCUIT BOOK No: 00001

NOTE: THIS DRAWING IS A GENERIC ARRANGEMENT.


THE SURGE PROTECTION FOR A PARTICULAR
INSTALLATION SHOULD BE SELECTED
TO SUIT THE CROSSING EQUIPMENT USED.

METER 240V
BOX SWITCHBOARD
FOR INFORMATION ONLY
DO NOT INCLUDE THIS SHEET IN CIRCUIT BOOKS

LX MONITOR
A A
3KVA

4A
240V XING XING LXMON
MAINS * * BX120 STORE B12 B12
240V VAP DSF
120V
SUPPLY 74
V

N N
XING XING LXMON
NX120 N12 N12 MODEM

E E
PHONE
PLP
LINE

C.E.
#

PREFERRED PEC
ARRANGEMENT
ALTERNATIVE
S.E. GRADE CROSSING PREDICTOR
ARRANGEMENT

G.C.P

SURGE PROTECTION COMPONENT LIST


MANUFACTURER/
LEGEND DESCRIPTION PART No.
SUPPLIER

PROPRIETARY G.C.P. SURGE


SPM
PROTECTION MODULES

TDS-MT-277 OR
* 240V MAINS SURGE DIVERTOR ERICO
DSD1160-8S

PEC 100C
PEC POTENTIAL EQUALISATION CLAMP ERICO
OR EQUIVALENT SPM

VAP 120V MAIN SURGE DIVERTOR RIC 1033893

DSF-6A-30A
DSF SURGE FILTER ERICO
OR EQUIVALENT

SIOVS20K30
V VARISTOR SIEMENS
OR EQUIVALENT

NOVARIS RJ11-PSTN

PLP PHONE LINE PROTECTOR ERICO UTB-S Tx Rx


TO TRACK TO TRACK
2 CABLE
TYPE # DIRECT BOND WITH 16mm
ELSAFE
216670 MODULE IF METAL SANDWICH PANEL BUILDING,

INSTALL POTENTIAL EQUALISATION CLAMP

IF CABLE DISTANCE IS LESS THAN 15m

OTHERWISE NO CONNECTION

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX060 SHEET TITLE: L.XING - ALARMS (RELAY TO SIGNAL BOX) EDMS No: SG0602002 SHEET No: X060 CIRCUIT BOOK No: 00001

LXING
ALARM
XING XING KR XING
B50(EXT)
f 4A 3 1 1

XING
N50(EXT)
(XING) t 2

LXING
TO
WARN
SIGNAL
KR BOX ALARMS

3 1 3

BATTERY
TEST R

XING
N50(EXT)
(XING) t 4

JOB NUMBER : C
DF 385*275
VERSION: 29/08/18 14:15 DRG No: CSTDX100 SHEET TITLE: L.XING - RMS INTERFACE EDMS No: SG0602002 SHEET No: X100 CIRCUIT BOOK No: 00001

SYDNEY TRAINS RMS

SYDNEY
RMS TRAINS
TDR I/F I/F

1B
TDNC
B2 B1

1W

TDR

2B
A5 A6
TDNO

2W

CSER SSER

3B
XENC
D2 D1 D2 D1

3W

CSER

4B
D5 D6 XENO

SSER

4W

D5 D6
CABLE
XING XING OLEX INSTROLEX WITH AN
B12/B15 OVERALL SCREEN, NYLON JACKET AND SACRIFICIAL
5B PVC SHEATH (ADDED TO THE STANDARD CABLE)
f 4A
RAILWAY SUPPLY
TWISTED PAIR (BLACK & WHITE), CONDUCTORS
XING
N12/N15
5W RATED CURRENT 12A.
(XING) t
SHEATH NOT TO BE EARTHED BY EITHER SYDNEY TRAINS OR RMS.
TLR

ASSUMES DISTANCE BETWEEN RMS AND SYDNEY TRAINS ENCLOSURES


6B TO BE LESS THAN 100m.
R2 R1
TLR

RELAYS:
6W
WB&S Q STYLE VITAL SIGNALLING RELAY
TO BRB SPEC 930.

TLR
REFER TO TMG A1620 FOR THE REQUIREMENTS OF THE
7B DESIGN INTERFACE BETWEEN RMS AND SYDNEY TRAINS
TLRNO
A2 A1

7W

SPARE SPARE
8B

SPARE SPARE
8W

TEST WIRE TEST WIRE


ORANGE

DO NOT EARTH DO NOT EARTH


SHEATH

8pr TWISTED

FIGURE 2: INTERFACE CABLE

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX101 SHEET TITLE: L.XING - CROSSING CONTROL WITH RMS INTERFACE (EXAMPLE 1) EDMS No: SG0602002 SHEET No: X101 CIRCUIT BOOK No: 00001

WITHOUT SIGNAL IN APPROACH

#3

X H /T D XC
1

AT BT CT XT

#2
XR
MANUAL
TLR XR OPERATION
TD TD SWITCH
XING XING JR SPR(2) AT BT CT XT XING
B #1 N
f 4A A6 A5 R1 R2 1 1 3 2 t (XING)

B3 B4 A1 A2

XR XR

A1 A2 A3 A4

EMR
NOTES: #1 TLR NOT PROVIDED WHERE ONLY A SINGLE
INPUT PROVIDED TO RMS.
TDR
A1 A2
#2 PROVIDED TO ENSURE TDR RECEIVED
TDR BY TRAFFIC CONTROLLER BEFORE
LEVEL CROSSING STOPS OPERATING.
XING XING AT BT CT XT TLR DE-ENERGISES WHEN
B TRAIN DEMAND (TD) REMOVED.
f 4A R1 R2

#3 SHOULD THE TRAIN DEMAND RESPONSE TIME


(TDRT) BE GREATER THAN THE REQUIRED
LEVEL CROSSING HOLDING TIME, THEN THE
LEVEL CROSSING HOLDING IS TO BE
EMR
EXTENDED TO ALIGN WITH THE TRAIN DEMAND.

A3 A4 RELAY TD SPR(2) AND TD JR SHOWN ON


SHEET X106

REFER TO TMG A1620 FOR THE REQUIREMENTS


OF THE DESIGN INTERFACE BETWEEN RMS AND
SYDNEY TRAINS
1
EMR UCR

A6 A5 R1 R2

XNR

B1 B2

1
HR
1
UCR

R1 R2

B1 B2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX102_1 SHEET TITLE: L.XING - CROSSING CONTROL WITH RMS INTERFACE (EXAMPLE 2) EDMS No: SG0602002 SHEET No: X102_1 CIRCUIT BOOK No: 00001

T
T
WITHT
T
SIGNAL IN APPROACH (SIGNAL POSITION 1)

#3
X H /TD XC
1

AT BT CT XT

#2
XR
MANUAL
TLR XRJR XR OPERATION
TD TD SWITCH
XING XING JR SPR(2) AT BT CT XT XING
B #1 N
f 4A A6 A5 D6 D5 R1 R2 1 1 3 2 t (XING)

B3 B4 A1 A2

XR XR XR

A1 A2 A3 A4 B1 B2
1
ALSR

B1 B2

EMR
NOTES: #1 TLR NOT PROVIDED WHERE ONLY A SINGLE

TDR INPUT PROVIDED TO RMS.

A1 A2
#2 PROVIDED TO ENSURE TDR RECEIVED
TDR BY TRAFFIC CONTROLLER BEFORE
LEVEL CROSSING STOPS OPERATING.
XING XING AT BT CT XT
TLR DE-ENERGISES WHEN
B
TRAIN DEMAND (TD) REMOVED.
f 4A R1 R2

#3 SHOULD THE TRAIN DEMAND RESPONSE TIME


(TDRT) BE GREATER THAN THE REQUIRED
1
LEVEL CROSSING HOLDING TIME, THEN THE
LPR LEVEL CROSSING HOLDING IS TO BE
1
EXTENDED TO ALIGN WITH THE TRAIN DEMAND.
ALSR

A6 A5
RELAY TD SPR(2) AND TD JR SHOWN ON
B3 B4 SHEET X106

REFER TO TMG A1620 FOR THE REQUIREMENTS


EMR OF THE DESIGN INTERFACE BETWEEN RMS AND
SYDNEY TRAINS

A3 A4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX102_2 SHEET TITLE: L.XING - LEVER & ROUTE CONTROLS WITH RMS INTERFACE (EXAMPLE 2) EDMS No: SG0602002 SHEET No: X102_2 CIRCUIT BOOK No: 00001

WITH SIGNAL IN APPROACH (SIGNAL POSITION 1)

1
EMR LPR

AT XING
N
A6 A5 R1 R2 t (XING)

XNR XRJR

C1 C2
B1 B2

XNR

B3 B4

1
UCR

AT XING
N
R1 R2 t (XING)

TLR
#1

B1 B2

#1 TLR NOT PROVIDED WHERE ONLY A SINGLE


TDJR
INPUT PROVIDED TO RMS.

A6 A5

XNR

C1 C2

1
HR
1
UCR

R1 R2

B1 B2

REFER TO TMG A1620 FOR THE REQUIREMENTS OF THE


DESIGN INTERFACE BETWEEN RMS AND SYDNEY TRAINS

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:53 DRG No: CSTDX103_1 SHEET TITLE: L.XING - CROSSING CONTROL WITH RMS INTERFACE (EXAMPLE 3) EDMS No: SG0602002 SHEET No: X103_1 CIRCUIT BOOK No: 00001

T
T
WITH T
T
SIGNAL IN APPROACH (SIGNAL POSITION 2)

ASSUMES SUFFICIENT WARNING TIME


TO LEVEL CROSSING WHEN SIGNAL
#3
X H /TD XC CLEARS AND BT OCCUPIED

AT BT CT XT

#2
XR
MANUAL
TLR XRJR XR OPERATION
TD TD SWITCH
XING XING JR SPR(2) AT BT CT XT XING
B #1 N
f 4A A6 A5 D6 D5 R1 R2 1 1 3 2 t (XING)

B3 B4 A1 A2

XR XR XR

A1 A2 A3 A4 B1 B2
1
ALSR

B1 B2

EMR
NOTES: #1 TLR NOT PROVIDED WHERE ONLY A SINGLE

TDR INPUT PROVIDED TO RMS.

A1 A2
#2 PROVIDED TO ENSURE TDR RECEIVED
TDR BY TRAFFIC CONTROLLER BEFORE
LEVEL CROSSING STOPS OPERATING.
XING XING AT BT CT XT
TLR DE-ENERGISES WHEN
B
TRAIN DEMAND (TD) REMOVED.
f 4A R1 R2

#3 SHOULD THE TRAIN DEMAND RESPONSE TIME


(TDRT) BE GREATER THAN THE REQUIRED
1
LEVEL CROSSING HOLDING TIME, THEN THE
LPR LEVEL CROSSING HOLDING IS TO BE
1
EXTENDED TO ALIGN WITH THE TRAIN DEMAND.
ALSR

A6 A5
RELAY TD SPR(2) AND TD JR SHOWN ON
B3 B4 SHEET X106

REFER TO TMG A1620 FOR THE REQUIREMENTS


EMR OF THE DESIGN INTERFACE BETWEEN RMS AND
SYDNEY TRAINS

A3 A4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX103_2 SHEET TITLE: L.XING - LEVER & ROUTE CONTROLS WITH RMS INTERFACE (EXAMPLE 3) EDMS No: SG0602002 SHEET No: X103_2 CIRCUIT BOOK No: 00001

WITH SIGNAL IN APPROACH (SIGNAL POSITION 2)

1
EMR LPR

AT BT XING
N
A6 A5 R1 R2 t (XING)

XNR XRJR

C1 C2
B1 B2

XNR

B3 B4

1
UCR

AT BT XING
N
R1 R2 t (XING)

TLR
#1

B1 B2

TDJR

A6 A5

XNR

C1 C2

1
HR
1
UCR

R1 R2

B1 B2

NOTE:
#1 TLR NOT PROVIDED WHERE ONLY A SINGLE REFER TO TMG A1620 FOR THE REQUIREMENTS OF THE
INPUT PROVIDED TO RMS. DESIGN INTERFACE BETWEEN RMS AND SYDNEY TRAINS

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX104_1 SHEET TITLE: L.XING - CROSSING CONTROL WITH RMS INTERFACE (EXAMPLE 4) EDMS No: SG0602002 SHEET No: X104_1 CIRCUIT BOOK No: 00001

T
T
WITH T
T
SIGNAL IN APPROACH (SIGNAL POSITION 3)

#3
X H/ TD XC

1
AT BT CT XT

#2 #5
XR
MANUAL
TLR TLR XRJR XR OPERATION
TD TD SWITCH
XING XING JR SPR(2) XR AT BT CT XT XING
B #1 N
f 4A A6 A5 A8 A7 D6 D5 R1 R2 1 1 3 2 t (XING)

B3 B4 A1 A2 B3 B4

XR TDR XR XR NOTES:
#1 TLR NOT PROVIDED WHERE ONLY A SINGLE
INPUT PROVIDED TO RMS.
A1 A2 B1 B2 A3 A4 B1 B2
1
#2 PROVIDED TO ENSURE TDR RECEIVED
ALSR BY TRAFFIC CONTROLLER BEFORE
#4
LEVEL CROSSING STOPS OPERATING.
TLR DE-ENERGISES WHEN
B1 B2 TRAIN DEMAND (TD) REMOVED.

BT CT
#3 SHOULD THE TRAIN DEMAND RESPONSE TIME
(TDRT) BE GREATER THAN THE REQUIRED
LEVEL CROSSING HOLDING TIME, THEN THE
EMR LEVEL CROSSING HOLDING IS TO BE
EXTENDED TO ALIGN WITH THE TRAIN DEMAND.

#4 IN THE EVENT THAT THE TRAIN HAS NOT YET PASSED


A1 A2
THE STRIKE POINT (Xc), THE APPROACH TRACKS CAN BE
USED TO QUALIFY AND PREVENT THE LEVEL CROSSING
OPERATING EARLIER THAN WOULD OTHERWISE
BE NECESSARY.

#5 PROVIDED TO INITIATE LEVEL CROSSING


OPERATION ON RECEIPT OF THE TLR (IE ENERGISED)
FROM THE TRAFFIC LIGHT CONTROLLER THUS AVOIDING
THE NEED TO WAIT FOR THE (TD)JR
TO TIME OUT. THIS REDUCES THE DELAYED CLEARING
ON A SIGNAL PROTECTING A LEVEL CROSSING THAT
REQUIRES THE BOOMS DOWN IN ORDER TO CLEAR
WITH AN APPROACHING TRAIN.

RELAY TD SPR(2) AND TD JR SHOWN ON


SHEET X106
TDR
TDR
REFER TO TMG A1620 FOR THE REQUIREMENTS OF THE
XING XING AT BT CT XT
DESIGN INTERFACE BETWEEN RMS AND SYDNEY TRAINS
B
f 4A R1 R2

1
LPR
1
ALSR

A6 A5

B3 B4

EMR

A3 A4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX104_2 SHEET TITLE: L.XING - LEVER & ROUTE CONTROLS WITH RMS INTERFACE (EXAMPLE 4) EDMS No: SG0602002 SHEET No: X104_2 CIRCUIT BOOK No: 00001

WITH SIGNAL IN APPROACH (SIGNAL POSITION 3)

1
EMR LPR

AT BT CT XING
N
A6 A5 R1 R2 t (XING)

XNR XRJR

C1 C2
B1 B2

XNR

B3 B4

1
UCR

AT BT CT XING
N
R1 R2 t (XING)

#1 TLR

B1 B2

TDJR

A6 A5

XNR

C1 C2

1
HR
1
UCR

R1 R2

B1 B2

NOTE: REFER TO TMG A1620 FOR THE REQUIREMENTS OF THE


#1 TLR NOT PROVIDED WHERE ONLY A SINGLE DESIGN INTERFACE BETWEEN RMS AND SYDNEY TRAINS
INPUT PROVIDED TO RMS.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX105 SHEET TITLE: L.XING - CROSSING CONTROL WITH RMS INTERFACE (EXAMPLE 5) EDMS No: SG0602002 SHEET No: X105 CIRCUIT BOOK No: 00001

T T
T
WITHOUT
T
SIGNAL IN APPROACH (WITH TD HOLDING #3)

#3 XH XC
1

A1T A2T BT CT XT

T T
T T

TDH TD

#2
XR
MANUAL
TLR XR OPERATION
TD TD SWITCH
XING XING JR SPR(2) A1T A2T BT CT XT XING
B #1 N
f 4A A6 A5 R1 R2 1 1 3 2 t (XING)

B3 B4 A1 A2

XR XR

A1 A2 A3 A4

EMR
NOTES; #1 TLR NOT PROVIDED WHERE ONLY A SINGLE

TDR INPUT PROVIDED TO RMS.

A1 A2
#2 PROVIDED TO ENSURE TDR RECEIVED
TDR BY TRAFFIC CONTROLLER BEFORE
LEVEL CROSSING STOPS OPERATING.
XING XING A1T A2T BT CT XT
TLR DE-ENERGISES WHEN
B
TRAIN DEMAND (TD) REMOVED.
f 4A R1 R2

#3 SHOULD THE TRAIN DEMAND RESPONSE TIME


(TDRT) BE LESS THAN THE REQUIRED
LEVEL CROSSING HOLDING TIME, THEN
TDR TRAIN DEMAND HOLDING WILL NEED
TO BE APPLIED TO ALIGN WITH THE LEVEL
CROSSING HOLDING

B1 B2

RELAY TD SPR(2) AND TD JR SHOWN ON


SHEET X106
EMR

REFER TO TMG A1620 FOR THE REQUIREMENTS


OF THE DESIGN INTERFACE BETWEEN RMS AND
A3 A4 SYDNEY TRAINS

1
EMR UCR

A6 A5 R1 R2

XNR

B1 B2

1
HR
1
UCR

R1 R2

B1 B2

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX106 SHEET TITLE: L.XING - CROSSING CONTROL WITH RMS INTERFACE EDMS No: SG0602002 SHEET No: X106 CIRCUIT BOOK No: 00001

TD SPR TD
#2 SPR(1)

LOC XING XING TDR


BX120 L1 E1 +
f 4A f 4A R1 R2 NOTES:
#1 LABEL 'MAXIMUM COIL VOLTAGE 48V'
A1 A2
#1 TO BE APPLIED TO RELAY.

TD
#2 SWITCHED MODE POWER SUPPLY
SPR(2)
MAINTAINS A CONSTANT COIL VOLTAGE ON
THE QSPA1 RELAYS PROVIDING A STABLE
AC DC
E SLOW TO ENERGISE TIME DELAY.
I/P O/P R1 R2

A1 A2
#1
REFER TO TMG A1620 FOR THE REQUIREMENTS
OF THE DESIGN INTERFACE BETWEEN RMS AND
1" SYDNEY TRAINS

#3
LOC
NX120 L2 E2 -
(XING) t t
#3 1 SEC DELAY PROVIDED TO ENSURE TDR
ERICO POWERBOX RECEIVED BY TRAFFIC CONTROLLER BEFORE
DSF-6A-150 PBB13C-48J-SNY L.XING STOPS OPERATING
(OUTPUT 48V, 1.1A)

TDJR TDR TD
J JR

XING XING
B15 1 3 R1 R3
f 4A R1 R2

12V
REGULATOR

XING
N15 2 4 R2 R4
(XING) t

TDR
D3 D5
D5 D6

A1 A2

D4 D6

A1 D1

A2 D2
TIMER SETTINGS NOTE:
10 SEC NO BRIDGING
11-30 SEC A1-A7 OUTPUT RELAY
A3 D7
TDRT" VOLTAGE STRAPPING

12V-D1/D2

A7 D8 24V-D7/D2

50V-D8/D2

QTD4

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX121_1 SHEET TITLE: L.XING - BOOM GATE LIGHTS OPERATING CIRCUITS - SAFE FLASH EDMS No: SG0602002 SHEET No: X121_1 CIRCUIT BOOK No: 00001

WESTINGHOUSE SAFE COUNTRY SIDE


FLASH UNIT 1 BASE CROSS ARM GATE & SIGNAL
XING
BANK 1 7/0.85
A
XING XING CSER SSER 8 4 5
B15 1 INHIBIT LAMP 1 12
SEE SHEET X122 FOR
f 4A B
WIRING DETAIL
D
A1 A2 A1 A2 XING XING #2 7/0.85
B15
XING f 10A 7 3 6
N15 2 INHIBIT LAMP 2 11
(XING) t N
CSE ZK 1
7/0.85
B
CSF ZK 1 1
2 SEE SHEET X122
FOR WIRING DETAIL
3 LAMP 3 10 C
7/0.85

TEST 9 2 2

7/0.85 XING
4 N12 9 N15
t (XING)

BOOM ARM
BOOM LIGHTS
XING XING XING XING #2 7/0.85
B15 5 SUPPLY 8 B15
f 4A B12 f 10A #1 10 9
1
#3
CSE (BOOM) ZK 7/0.85
BANK 2
2
11 6 FLASHING
6 LAMP 1 7
SEE SHEET X122 FOR
WIRING DETAIL 3
#3
7/0.85

XING CSER SSER SSER


XING 12 5
B15 7 INHIBIT LAMP 2 6
CSE (TIP) ZK 4

f 4A B XING XING #2 7/0.85


B15
D1 D2 D1 D2 #1
f 10A B6 B5 13 7
5
#3 TIP
XING XING 7/0.85
N15 8 INHIBIT LAMP 3 5 N15
t
CSER
(XING) N (XING) t 14 8
6 FOR DETAILS SEE SHT X123

SYDNEY SIDE
7/0.85 XING BASE CROSS ARM
B6 B5
9 N12 4 N15 GATE & SIGNAL
t (XING) 7/0.85
E
TEST 8 4 5

10 3 H
XING XING #2 7/0.85
B15
f 10A #1 7 3 6

XING XING INPUT SSE ZK 1


7/0.85
B15 11 SUPPLY 2 OPTO 1 F
f 4A B12 t31
SEE SHEET X122 FOR SSF ZK 1 1
WIRING DETAIL
FLASHER 2 SEE SHEET X122
FAIL FOR WIRING DETAIL
G
LXMON 7/0.85
12 1 B15
t16 9 2 2

BOOM ARM

XING XING #2 7/0.85 BOOM LIGHTS


B15
S.E.
f 10A #1 10 9
1
#3
SSE(BOOM) ZK 7/0.85

2
11 6 FLASHING
SEE SHEET X122 FOR
#1 WIND 7-10 TURNS THROUGH #3 WESTINGHOUSE BARRIER ARM WIRING DETAIL 3
LED LIGHT PART No
#3
CURRENT SENSOR FOR CURRENT
7/0.85
DETECTION. EXACT NUMBER TO 3250100301.
SSER
BE DETERMINED DURING CERBERUS STOCK CODE 001886662 12 5
SSE (TIP) ZK 4
SET UP AND RECORDED ON C.O.C.
NOTE: SAFE FLASH UNIT MUST BE XING XING #2 7/0.85
B15
DISCONNECTED DURING INSULATION TESTING.
f 10A B8 B7 #1 13 7
#2 ETFE TEFLON COATED 1.23mm SQ, 5
#3 TIP
19/29AWG 600V GRADE ALL INTERNAL WIRING 7/0.4mm
XING 7/0.85
UNLESS OTHERWISE SHOWN. N15
CSER
(XING) t 14 8
LAMPS LED TYPE 6 FOR DETAILS SEE SHEET
X123

B8 B7

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX121_2 SHEET TITLE: L.XING - BOOM GATE LIGHTS OPERATING CIRCUITS - SAFE FLASH EDMS No: SG0602002 SHEET No: X121_2 CIRCUIT BOOK No: 00001

BASE CROSS ARM COUNTRY SIDE


WITH ADDITIONAL WARNING LIGHTS GATE & SIGNAL
WESTINGHOUSE SAFE XING
7/0.85
FLASH UNIT 1 A
8 4 5
SEE SHEET X122 FOR
BANK 1 WIRING DETAIL
D
XING XING CSER SSER XING XING #2 7/0.85
B15 1 INHIBIT LAMP 1 12 B15
f 4A B f 10A 7 3 6

A1 A2 A1 A2 CSE ZK 1
7/0.85
B
XING CSF ZK 1 1
SEE SHEET X122
N15 2 INHIBIT LAMP 2 11
FOR WIRING DETAIL 2
(XING) t N
C
7/0.85

9 2 2
3 LAMP 3 10
BASE CROSS ARM
J
TEST
6 6

7/0.85 XING
4 N12 9 N15
5 5
t (XING)
K
2 2

XING XING
B15 5 SUPPLY 8 1 1
f 4A B12
BOOM LIGHTS
BASE BOOM ARM
XING XING #2 7/0.85
BANK 2 B15
f 10A #1 10 9
1
6 LAMP 1 7 #3
CSER CSE (BOOM) ZK 7/0.85

2
11 6 FLASHING
SEE SHEET X122 FOR
XING XING CSER SSER B6 B5
WIRING DETAIL 3
B15 7 INHIBIT LAMP 2 6 #3
f 4A B 7/0.85

D1 D2 D1 D2
SSER
12 5
CSE (TIP) ZK 4
XING XING XING #2 7/0.85
N15 8 INHIBIT LAMP 3 5 B15
(XING) t #1
N f 10A B6 B5 13 7
5
#3 TIP
XING 7/0.85
N15
7/0.85 XING (XING) t 14 8 FOR DETAILS SEE SHT X123
6
9 N12 4 N15
(XING) CROSS ARM
SYDNEY SIDE
t BASE
GATE & SIGNAL
TEST 7/0.85
E
8 4 5
10 3

H
XING XING #2 7/0.85
B15
XING XING INPUT f 10A #1 7 3 6
B15 11 SUPPLY 2 OPTO 1
f 4A B12 t31
SSE ZK 1
7/0.85
FLASHER F
SEE SHEET X122 FOR SSF ZK 1 1
FAIL
WIRING DETAIL
2 SEE SHEET X122
LXMON
FOR WIRING DETAIL
12 1 B15 G
t16 7/0.85

9 2 2

BOOM ARM
S.E.
XING XING #2 7/0.85 BOOM LIGHTS
B15
f 10A #1 10 9
1
CSER #3
#1 WIND 7-10 TURNS THROUGH #3 WESTINGHOUSE BARRIER ARM SSE(BOOM) ZK 7/0.85
CURRENT SENSOR FOR CURRENT LED LIGHT PART No
2
DETECTION. EXACT NUMBER TO 3250100301. 11 6 FLASHING

BE DETERMINED DURING CERBERUS STOCK CODE 001886662 SEE SHEET X122 FOR
B8 B7
SET UP AND RECORDED ON C.O.C. WIRING DETAIL 3
#3
NOTE: SAFE FLASH UNIT MUST BE 7/0.85
DISCONNECTED DURING INSULATION TESTING. SSER
#2 ETFE TEFLON COATED 1.23mm SQ, 12 5
SSE (TIP) ZK 4
19/29AWG 600V GRADE ALL INTERNAL WIRING 7/0.4mm
UNLESS OTHERWISE SHOWN. XING XING #2 7/0.85
B15
LAMPS LED TYPE f 10A B8 B7 #1 13 7
5
#3 TIP
XING 7/0.85
N15
(XING) t 14 8 FOR DETAILS SEE SHT X123
6

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX122 SHEET TITLE: L.XING - BOOM GATE LIGHT CURRENT SENSOR CONNECTIONS EDMS No: SG0602002 SHEET No: X122 CIRCUIT BOOK No: 00001

COUNTRY SIDE SYDNEY SIDE

CSE ZK SSE ZK

1 SENSOR SUPPLY (12V) t8 1 SENSOR SUPPLY (+12V) t6

CURRENT 2 SENSOR GND (0V) t3 CURRENT 2 SENSOR GND (0V) t1


CROSS ARM CROSS ARM
#1 OR #2 SENSOR #1 OR #2 SENSOR
LIGHTS 3 ANALOG INPUT 4 LIGHTS 3 ANALOG INPUT 2

4 4

1 1 1 1

#3 #3

CSF ZK SSF ZK
2 2 2 2

1 XING CSE GATE & SIGNAL t7 1 XING SSE GATE & SIGNAL t7

VIO 2 XING CSE GATE & SIGNAL t9 VIO 2 XING SSE GATE & SIGNAL t9
(12V) (12V)
3 INPUT PORT 4, PIN 23 RED WIRE 3 INPUT PORT 4, PIN 22 RED WIRE

4 INPUT PORT 4, PIN 2 ORANGE WIRE 4 INPUT PORT 4, PIN 1 BLUE WIRE

CSE(TIP) ZK SSE(TIP) ZK

1 SENSOR SUPPLY (+12V) t9 1 SENSOR SUPPLY (+12V) t7

CURRENT 2 SENSOR GROUND (0V) t4 CURRENT 2 SENSOR GROUND (0V) t2


BOOM TIP BOOM TIP
#1 OR #2 SENSOR #1 OR #2 SENSOR
LIGHTS 3 ANALOGUE INPUT 5 LIGHTS 3 ANALOGUE INPUT 3

4 4

CSE(BOOM) ZK SSE(BOOM) ZK

1 1

CURRENT 2 CURRENT 2
BOOM FLASHING BOOM FLASHING
#1 OR #2 SENSOR #1 OR #2 SENSOR
LIGHTS 3 ANALOGUE INPUT 6 LIGHTS 3 ANALOGUE INPUT 7

4 4

#1: FOR ALSTOM FL03 CROSS


ARM LIGHTS-
WIND SEVEN TURNS THROUGH
TIP OR BOOM CURRENT SENSOR
FOR CURRENT DETECTION.

#2: FOR WESTINGHOUSE RG4


CROSS ARM LIGHTS-WIND THREE
TURNS THROUGH TIP OR BOOM
CURRENT SENSOR FOR CURRENT
DETECTION.

#3: NOISE SUPPRESSION


RESISTORS 2K2W1W

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDX123 SHEET TITLE: L.XING - BOOM GATE LAYOUT (WITH FLASHING LED) EDMS No: SG0602002 SHEET No: X123 CIRCUIT BOOK No: 00001

BOOM TELESCOPIC BOOM ARM


MECHANISM

LED

FLASHER LIGHTS
7-PIN 7-PIN AT BOOM LED
AUTOMOTIVE AUTOMOTIVE MECHANISM END
SOCKET PLUG

LED
J-BOX

1 1
RED
MIDDLE
FLASHER LED
FLASHER
(MECHANISM END)
LIGHTS
2 2
YELLOW

LED
J-BOX

3 3
WHITE
TIP
FLASHER
MIDDLE
LIGHTS
4 4
BLACK

* J-BOX
LED

5 5
BROWN

TIP
LIGHT
6 6
BLUE

7 7
GREEN

GREEN SPARE WIRE


7-CORE AUTOMOTIVE INSULATED
TRAILER CABLE TO SUIT
AUTOMOTIVE PLUG

REFER NOTE 6
*
NOTES:

1. REFER TO ASSEMBLY DWG.


PROVIDED WITH LIGHT KIT.
FOR INSTALLATION DETAILS.

*2 CORE FLEX
2. USE BOOTLACE FERRULES
0.75mm 2
WHERE APPROPRIATE.

3. LED's ARE FLUSH MOUNTED TYPE

4. CABLES LINKING JUNCTION BOXES


TO BE RUN WITHIN HOLLOW BOOM.

5. ALL CABLE PENETRATIONS TO BE


DE-BURRED & BUSHED AS APPROPRIATE.

6. TERMINALS WITHIN PLUG & SOCKET ARE NOT PHYSICALLY ARRANGED


IN THE ORDER SHOWN ON THE CIRCUIT ABOVE. WIRES SHALL BE TERMINATED ON THE
TERMINAL NUMBER MOULDED ON THE PLUG AND SOCKET.

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDY001 SHEET TITLE: FILAMENT & LAMP FAILURE - ALARMS & INDICATIONS EDMS No: SG0602002 SHEET No: Y001 CIRCUIT BOOK No: 00001

FCKSR FILAMENT
FILAMENT FAILURE ALARMS FAIL
Y
1
SIGNAL BASE
PSU LOC TERMINALS

B24

N24
B50
f 4A
ECKSR LAMP
FAIL
3
R

5(M)
TOP LAMP SIG
TEST
CASE BASE TAPR
W
5

RER 5(S)
MOUNTED IN DIAGRAM
HR 7
7 8 6

6 8

HER

5(S)

6 8
FCKR

DER PSU
N50
2 10 t (LOC)
IN4004
6 8

500mS TO ALLOW
+
BOTTOM LAMP FOR 3 ASPECT SINGLE LIGHT
FOR CHANGEOVER
CASE SIGNAL, USE THE TOP LAMP
10R
CASE ARRANGEMENT AS PER mF
250
11
SPECIFICATION 571A/91
RER

7 8 12

6 8

HER

6 8 SLOW RELEASE RELAY


MODULE E9509/3
DER

6 8

WHERE GRN ECR

LAMP FAILURE ALARMS IS INSTALLED

(SINGLE LIGHT SIGNALLING ONLY)


ECKR
1 3 5 GRN 7
PSU LOC ECR ECR ECR ECR ECR
B50 N50
f 4A 2 10 t

DR

FCKR/ECKR - NORTH/SOUTH/EAST/WEST ARE OPTIONAL

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:54 DRG No: CSTDY002 SHEET TITLE: WARNINGS & ALARMS - CONTROL & OPERATION EDMS No: SG0602002 SHEET No: Y002 CIRCUIT BOOK No: 00001

ACR
NOTE: FOR FURTHER DETAILS ON

AUDIBLE ALARM ALARMS REFER TO STANDARD

SPECIFICATION No.713

WARNING 8 7 AXR
FAIL
PSU LOC PSKR PSR ECKSR FCKSR SCR PSU
B24 1 2 N24
UNIT
f 4A t (LOC)

AUDIBLE
ALARM
ALL ALARM CONDITIONS
PSU LOC PSU
B24 N24
f 4A t (LOC)

PSU LOC TAPR PSU


B24 W N24
f 4A t (LOC)
PULL TO
TEST
TAR

ACPR

TAPR

ACR

RESET/
CANCEL
ACPR (PUSH)

FCKSR

PSU LOC FCKR TAPR ACPR PSU


B24 N24
f 4A t (LOC)

ECKSR

ECKR

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:55 DRG No: CSTDY003 SHEET TITLE: EARTH LEAKAGE DETECTORS EDMS No: SG0602002 SHEET No: Y003 CIRCUIT BOOK No: 00001

GEC ALSTHOM ML/EB MRD


ELD
XG1902 STYLE D6 ELD AC/DC - AUTO-110
RESET
R

PSU LOC POJPR LOC PSU LOC


SE
BX120 R1 D1 DET E BUS 1 BX120 BX120 TEST E
#1 1 6
f 4A 1 5 4A f f 4A 110V AC
SUPPLY
PSU TE PSU #2
NX120 R2 D2 TEST E BUS 2 NX120 NX120 DET E
(LOC) #2 (LOC) (LOC) 3 5
t t t
#1
POJPR LOC LOC
PSU
110V BX120 B50 +B1
8
4A f f 4A SE TE
SE DC
R3 D3 3
#1 PSU BUSBAR
REMOTE TEST 0V NX120 N50 -B1
ELD (LOC) (LOC) 9
t t
TE
R4 D4 RESET
#2 LOC
R BX120
12
f 4A AC
4 1
BUSBAR

WARNING OUT A2 4 NX120


(LOC) 15
t

WARNING IN A1
F A

A3 WARNING OUT A
B

A6 WARNING IN F WARNING IN WARNING OUT


29
F A F A 30

A5 B
F A B

A7 SETTINGS:-
B TRIP DELAY - 4 SECONDS
TRIP POINT AC - 40k OHMS
MODE
TRIP POINT DC - 15k OHMS
23 24
NO LINK

#1 EARTH CONDUCTORS 7/0.67mm (2.5mm )2 GREEN/YELLOW

DESIGNER'S NOTES: #2 EARTH CONDUCTORS 7/0.67mm (2.5mm 2) VIOLET

1. BUS VOLTAGE: BX/NX 120

2. RESET AFTER POWER OFF: MOMENTARY BREAK DESIGNER'S NOTES:

3. CAUTION: RESETS MUST NOT BE WIRED IN PARALLEL 1. RESET AFTER POWER OFF: NOT REQUIRED

A
ELD
DIODE
RESET R
BLOCK
PSU LOC POJPR PSU
B50(INT) N50(INT)
f 4A 15 5 2 10 t (LOC)
1K5

25

mF
50
EARTHING OF EARTH LEAKAGE DETECTORS

SE THE MAIN EARTH ROD MUST BE OVER 2m FROM THE TEST EARTH RODS

TE THE TEST EARTH RODS MUST BE AT LEAST 0.5m APART

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:55 DRG No: CSTDZ001 SHEET TITLE: CIRCUIT NOMENCLATURE EDMS No: SG0602002 SHEET No: Z001 CIRCUIT BOOK No: 00001

# DENOTES TYPICAL CIRCUITS & LEGACY CIRCUITS, AS APPROPRIATE

RELAY SHEET RELAY SHEET


NAME MEANING FUNCTION LOCATED AT REF # NAME MEANING FUNCTION LOCATED AT REF #

ROUTE SETTING & OCS SYSTEMS


ROUTE SETTING INTERLOCKING
NWR NORMAL POINT OPERATES POINTS TO NORMAL POSITION LOCAL POINTS W01
CONTACTOR RELAY LOCATION

(F)R BUTTON PRESSED REPEATS PUSH BUTTON OPERATION INTERLOCKING


N01 RWR REVERSE FRONT OPERATES POINTS TO REVERSE POSITION LOCAL POINTS W01
CONTACTOR RELAY LOCATION
(T)R BUTTON PULLED
(CONTACTS MADE)
(FM)R PROVIDES FOR EMERGENCY USUALLY NON-VITAL
NWKR NORMAL POINTS INDICATES NORMAL POINT POSITION INTERLOCKING W029
REPLACEMENT OF SIGNAL RELAY
INDICATING RELAY
(FM)R BUTTON PULLED
(CONTACTS BROKEN)
RWKR REVERSE POINTS INDICATES REVERSE POINT POSITION INTERLOCKING W029
INDICATING RELAY
(R)PR BUTTON REVERSE USED IN RING CIRCUIT TO ENSURE ONLY 1 INTERLOCKING
NKR NORMAL INDICATING INDICATES POINTS NORMAL LOCAL POINTS W03
(PRESSED) (ONE) BUTTON PRESSED AT A TIME. N01
RELAY LOCATION
REPEAT RELAY OPERATES COMMENCE & FINISH RELAYS

RKR REVERSE INDICATING INDICATES POINTS REVERSE LOCAL POINTS W03


RELAY LOCATION
CeR COMMENCE RELAYS DEFINES & INITIATES ROUTE TO BE SET FROM. INTERLOCKING N01

NWAR NORMAL POINTS DETERMINES IF POINTS WOULD GO NORMAL INTERLOCKING N10


FnR FINISH RELAYS DEFINES END OF ROUTE IN CONJUNCTION INTERLOCKING N02
AVAILABLE RELAY IF OTHER CONDITIONAL LOCKING RELEASED
WITH CeR, SETS ROUTE

RWAR REVERSE POINTS DETERMINES IF POINTS WOULD GO REVERSE INTERLOCKING N11


MuR MACHINE IN USE RELAY OPERATES WHEN COMMENCED RELAY IS UP INTERLOCKING N02 AVAILABLE RELAY IF OTHER CONDITIONAL LOCKING RELEASED
TO MAKE NEXT BUTTON OPERATION A FINISH
WTJR POINTS TRANSIT CUTS POINTS SUPPLY IF MACHINE FAILS LOCAL POINTS
TIMER RELAY TO COMPLETE TRAVEL LOCATION
FnPR FINISH REPEAT RELAY INITIATES TIMING SEQUENCE TO REMOVE INTERLOCKING N02
ROUTE CALL

NOLR NORMAL OVERLAP RELAY SELECTS NORMAL OVERLAP IF CLEAR INTERLOCKING


FnJR FINISH TIMING RELAY
ROLR REVERSE OVERLAP RELAY SELECTS REVERSE OVERLAP IF CLEAR INTERLOCKING
FnJPR FINISH TIMING REPEAT PROVIDES TIMING SEQUENCE INITIATED BY INTERLOCKING N02
RELAY FINISH FUNCTION

FnJP2R FINISH TIMING REPEAT


SIGNAL CONTROLS
(No2) RELAY
SR LEVER STICK RELAY PREVENTS SIGNALS AUTOMATICALLY INTERLOCKING M01
RELEASING AFTER TRAINS N13
N02
(N)R NORMALISING RELAY NORMALISES ROUTE INTERLOCKING
N03 UCR ROUTE CHECKING RELAY CHECKS ALL TRACKS & POINTS DETECTION INTERLOCKING M01
FOR SIGNAL CONTROLS N06
P02
AUTO NORMALISING

LSpR LOW SPEED RELAY OPERATES LOW SPEED LIGHT SIGNAL LOCATION P02
TZR TRACK (SPECIAL) RELAY GUARANTEES INTEGRITY OF AUTOMATIC INTERLOCKING N03
HR SIGNAL CAUTION RELAY OPERATES SIGNAL LIGHTS TO CAUTION SIGNAL LOCATION A12
NORMALISING PATH

HDR SIGNAL MEDIUM RELAY OPERATES SIGNAL LIGHTS TO MEDIUM SIGNAL LOCATION A12
ROUTE SETTING & OCS SYSTEMS
DR SIGNAL CLEAR RELAY OPERATES SIGNAL LIGHTS TO CLEAR SIGNAL LOCATION A12

ECR LAMP CHECKING RELAY PROVES LAMPS ALIGHT SIGNAL LOCATION A12
NLR NORMAL LOCK RELAY MAIN INTERLOCKING RELAY. INDICATES INTERLOCKING N04
NGPR SIGNAL NORMAL REPEAT PROVES SIGNAL (& TRAINSTOP) IS NORMAL INTERLOCKING N06
WHEN ROUTE IS NORMAL.
SIGNALS
RELAY
RUR REVERSE ROUTE RELAY PICKS WHEN ROUTE IS SET. CALLS POINTS INTERLOCKING P01
RGKR SIGNAL REVERSE INDICATES SIGNAL CLEARED INTERLOCKING N06
TO CORRECT POSITION.
INDICATING RELAY

W01
IR ISOLATING RELAY CUTS POINT MOTOR CIRCUIT TO ENSURE NO POINT LOCATION
W02
MOVEMENT DUE TO LEAKAGE CURRENTS
TRAIN STOPS

NLR NORMAL LOCK RELAY MAIN INTERLOCKING RELAY FOR POINTS INTERLOCKING N05 VNR TRAIN STOP NORMAL TRAIN STOP NORMAL RELAY SIGNAL LOCATION V03
NORMAL POSITION RELAY
POINTS

RLR REVERSE LOCK RELAY MAIN INTERLOCKING RELAY FOR POINTS P03 VRR TRAIN STOP REVERSE TRAIN STOP REVERSE RELAY SIGNAL LOCATION V03
REVERSE POSITION RELAY

N05
WZR POINTS FREE RELAY INDICATES IT'S POINTS ARE FREE & WOULD INTERLOCKING VCSR TRAIN STOP CHECKING PROVES TRAIN STOP NORMALISING AFTER SIGNAL LOCATION A102
P03
RESPOND TO A CALL STICK RELAY TRAIN PASSAGE

A102
WJR POINTS TIMER RELAY PROVIDES ADDITIONAL TIME DELAY BEFORE INTERLOCKING VR TRAIN STOP RELAY OPERATES TRAIN STOP SIGNAL LOCATION
N05
POINTS BECOME FREE TO COVER BOBBING (FOR CONTACTOR)
TRACKS

NLKPR POINTS NORMAL & LOCKED CHECKS THAT POINTS ARE IN THE NORMAL INTERLOCKING N05
INDICATING RELAY POSITION & LOCKED P03 TRACK LOCKING
RLKPR POINTS REVERSE & N05
CHECKS THAT POINTS ARE IN THE REVERSE INTERLOCKING
LOCKED INDICATING RELAY P03 ALSR APPROACH LOCK STICK HOLDS LOCKING IF SIGNAL REPLACED IN INTERLOCKING N07
POSITION & LOCKED
RELAY IN FACE OF TRAIN

ALSJR APPROACH LOCK TIMER TIMES OUT APPROACH LOCKING INTERLOCKING N07
RELAY

JOB NUMBER : C
DF 385*275
VERSION: 31/08/18 13:55 DRG No: CSTDZ002 SHEET TITLE: CIRCUIT NOMENCLATURE EDMS No: SG0602002 SHEET No: Z002 CIRCUIT BOOK No: 00001

# DENOTES TYPICAL CIRCUITS & LEGACY CIRCUITS, AS APPROPRIATE

RELAY SHEET RELAY SHEET


NAME MEANING FUNCTION LOCATED AT NAME MEANING FUNCTION LOCATED AT
REF # REF #

TRACK LOCKING ROUTE SETTING


NON-VITAL DIAGRAM RELAYS
(M) AR MAIN APPROACH RELAY DROPS WHEN MAIN ASPECT AT SIGNAL IS INTERLOCKING P01
CLEARED & HELD BY APPROACH STICK FEKR BUTTON LIGHT CAUSES BUTTON LIGHT TO FLASH WHEN CONTROL PANEL N51
INDICATING (FLASHING) COMMENCE RELAY OPERATED LOCATION
USR ROUTE STICK RELAY HOLDS LOCKING AFTER TRAIN ENTERS ROUTE INTERLOCKING N07 RELAY

JR TIMING RELAY TRACK TIMING TO RELEASE ROUTE LOCKING INTERLOCKING N07 N51
FEK2R BUTTON LIGHT CAUSES BUTTON LIGHT TO BECOME STEADY
OR CONDITIONALLY CLEAR SIGNALS,
INDICATING No2 & INITIATES ROUTE LIGHTS WHEN ROUTE
DEPENDING ON APPLICATION
(STEADY) RELAY SETS

DPU DATA PICK UP UNIT DETECTS POSITION OF TRAIN ON TRACK SIGNAL LOCATION T20
CIRCUITS (PRINCIPALLY CSEE TYPE)
NWKKR NORMAL POINTS OPERATES NORMAL FLASHING LIGHTS IN CONTROL PANEL N52
INDICATION RELAY ROUTE OVER POINTS & LIGHT BEHIND POINT LOCATION
POJR POWER OFF TIMER DISCONNECTS QUICK RELEASE PATH IN INTERLOCKING U003
LEVER
RELAY APPROQACH STICKS & TZR TO RETAIN
LOCKING DURING POWER OUTAGES RWKKR REVERSE POINTS OPERATES REVERSE FLASHING LIGHTS IN N52
INDICATION RELAY ROUTE OVER POINTS & LIGHT BEHIND POINT
LEVER
RELEASING SWITCHES
WZKR POINTS FREE OPERATES GREEN FREE LIGHT BEHIND POINT N52
INDICATION RELAY LEVER
NR NORMAL RELAY DETECTS RELEASING SWITCH NORMAL INTERLOCKING N12

NKR NORMAL INDICATING DETECTS RELEASING SWITCH NORMAL INTERLOCKING N12


TUR TRACK ROUTE RELAY DROPS OUT IF POINTS TRACK OCCUPIED CONTROL PANEL
N53
RELAY (FOR DIAGRAM)
WITH NO ROUTE SET, TO ILLUMINATE ALL LOCATION
RED LIGHTS OVER POINTS

SINGLE LINE & BI-DIRECTIONAL


UR ROUTE RELAY WHEN ROUTE SET, ROUTE RELAY OPERATES CONTROL PANEL N51
YR DISENGAGING RELAY CALLS SECTION CONTROL WHEN SETTING INTERLOCKING C01
WHITE ROUTE LIGHTS LOCATION
ROUTE INTO SINGLE LINE SECTION
U2R No2 ROUTE RELAY USED IF MORE THAN 1 (ONE) TRACK CIRCUIT N51
DDSR DOWN DIRECTION STICK PROVES TRAIN TRAVELLING IN DOWN INTERLOCKING, C01
IN ROUTE
RELAY DIRECTION LEVEL CROSSING &
SIGNAL LOCATION C01 (IF ROUTE IS NORMALISED AFTER TRAIN
UDSR UP DIRECTION STICK PROVES TRAIN TRAVELLING IN UP
TAKES ROUTE, ROUTE RELAYS HOLD ROUTE
RELAY DIRECTION
LIGHTS IN FRONT OF TRAIN)
C01
DSCR DOWN SECTION CONTROL CHECKS SECTION CLEAR FOR DOWN TRAIN INTERLOCKING
RELAY
U2KR No2 ROUTE INDICATING FIRST REPEAT OF U2R CONTROL PANEL N51
RELAY LOCATION
USCR UP SECTION CONTROL CHECKS SECTION CLEAR FOR UP TRAIN INTERLOCKING C01
RELAY
UK2R ROUTE INDICATING SECOND REPEAT OF UR N51
RELAY No2
DSCJR DOWN SECTION CONTROL CHECKS SECTION CLEAR FOR REQUIRED TIME INTERLOCKING
C01
TIMER RELAY
TKR TRACK INDICATING TRACK CIRCUIT INDICATING RELAY FOR CONTROL PANEL N53
USCJR UP SECTION CONTROL CHECKS SECTION CLEAR FOR REQUIRED TIME INTERLOCKING
C01 RELAY DIAGRAM LOCATION
TIMER RELAY

JKR TIMER INDICATING TIME RELEASE LIGHT FOR DIAGRAM CONTROL PANEL
N54
SCR SECTION CONTROL CHECKS SECTION B01
RELAY LOCATION
RELAY

DGNR DOWN SIGNAL NORMAL PROVES DOWN DIRECTION SIGNALS NORMAL B02 NGKKR SIGNAL NORMAL N52
RELAY INDICATING RELAY
DIAGRAM INDICATION FOR SIGNAL REPEATER CONTROL PANEL
UGNR UP SIGNAL NORMAL PROVES UP DIRECTION SIGNALS NORMAL B01 RGKKR SIGNAL REVERSE LOCATION N52
RELAY INDICATING RELAY

LEVEL CROSSING
PROVIDES FLASHING RED SIGNAL REPEATER CONTROL PANEL
X01
XR CROSSING CONTROL OPERATES LEVEL CROSSING EQUIPMENT CROSSING LOCATION APPROACH LOCK STICK N52
ALSKR IF SIGNAL IS AT STOP BUT APPROACH LOCATION
X02
INDICATING RELAY
LOCKED
DSPR DIRECTION STICK
REPEAT RELAY ENSURES CROSSING FAILS SAFE IF OTS SECTION
DIRECTION STICKS FAIL TO DROP AWAY LEVEL CROSSING X03
GZKR SIGNAL SPECIAL FLASHES FIRST WHITE ROUTE LIGHT CONTROL PANEL
DSJR DIRECTION STICK AFTER TRAIN LOCATION
INDICATING RELAY IF LEVER STICK OR RUR IS DOWN LOCATION
TIMER RELAY

TDR TRAIN DEMAND RELAY RMS INTERFACE FOR ROAD TRAFFIC LIGHTS CROSSING LOCATION X100
CONTROL ROUTE SETTING - NON VITAL
CONTROL RELAYS
(N)R NORMAL RELAY
MECHANICAL INTERLOCKING
(R)R REVERSE RELAY REPEATS POINT LEVER POSITION INTERLOCKING N02
LNPR LEVER NORMAL INTERLOCKING M03
(C)R CENTRE RELAY
REPEAT RELAY
REPEATS LEVER POSITION
LRPR LEVER REVERSE INTERLOCKING M03
RSR ROUTE SETTING RELAY SETS ROUTE WHEN BUTTON PRESSED INTERLOCKING P01
REPEAT RELAY
UNR NORMAL ROUTE RELAY CANCELLS ROUTE WHEN BUTTON PRESSED INTERLOCKING P01
NLR NORMAL LOCK RELAY PROVES LEVER NORMAL & LOCKED INTERLOCKING M03
NZR NORMAL SETTING RELAY SETS POINTS NORMAL WHEN ROUTE P03
INTERLOCKING
RLR REVERSE LOCK RELAY PROVES LEVER REVERSE & LOCKED INTERLOCKING M03 CANCELLED

SETS POINTS REVERSE WHEN ROUTE INTERLOCKING


RZR REVERSE SETTING RELAY P03
CANCELLED