NMB(X)24-3(-T)

On/Off, Floating Point, Non-Spring Return, 24 V

Torque min. 90 in-lb for control of damper surfaces up to 22 sq ft.

Application
For on/off and floating point control of dampers in HVAC systems. Actuator sizing
should be done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft up to 1.05" in diameter by means
of its universal clamp, 1/2” self-centered default. A crank arm and several mounting
brackets are available for applications where the actuator cannot be direct coupled to
the damper shaft.

Operation
The actuator is not provided with and does not require any limit switches, but is
electronically protected against overload. The anti-rotation strap supplied with the
actuator will prevent lateral movement.
The NMB(X) series provides 95° of rotation and a visual indicator indicates position of
the actuator. When reaching the damper or actuator end position, the actuator
automatically stops. The gears can be manually disengaged with a button on the
actuator cover.
The NMB(X)24-3… actuators use a sensorless brushless DC motor, which is controlled
Technical Data NMB(X)24-3(-T) by an Application Specific Integrated Circuit (ASIC). The ASIC monitors and controls
Power supply 24 VAC ± 20% 50/60 Hz the actuator’s rotation and provides a digital rotation sensing (DRS) function to prevent
24 VDC ± 10% damage to the actuator in a stall condition. Power consumption is reduced in holding
Power consumption 2 W (0.2 W) mode.
Transformer sizing 4 VA (Class 2 power source) Add-on auxiliary switches or feedback potentiometers are easily fastened directly onto
Electrical connection 18 GA plenum rated cable the actuator body for signaling and switching functions.
1/2” conduit connector
protected NEMA 2 (IP54)
3 ft [1m] 10 ft [3m] 16 ft [5m] Dimensions (Inches [mm])
Overload protection electronic throughout 0 to 95° rotation

D121
Control on/off, floating point
1/2” to 1.05” [12.7 to 26.67]
Input impedance 600 Ω
Angle of rotation max. 95°, adjust. with mechanical stop 2/5” to 1.05” [10 to 26.67]

Torque 90 in-lb [10 Nm]

2.42” [61.4]
2.36” [60]

Direction of rotation reversible with switch


Position indication reflective visual indicator (snap-on)
Manual override external push button
Running time 95 seconds (default) 3.66” [93]
To center of

M40024 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.


constant independent of load mounting slot.
Humidity 5 to 95% RH non condensing (EN 60730-1) 4.88” [124]

Ambient temperature -22°F to 122°F [-30°C to 50°C]


Storage temperature -40°F to 176°F [-40°C to 80°C]
3.15” [80]

Housing NEMA 2, IP54, UL enclosure type 2


Housing material UL94-5VA
Agency listings† cULus acc. to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02,
CE acc. to 2004/108/EEC and 2006/95/EC
Noise level <45dB(A) 0.98”
[25] 3.9” [99] 2” [50.8]
Servicing maintenance free
Quality standard ISO 9001
Weight 1.7 lbs [0.75 Kg]

NMB(X)24-3-T
Electrical connection screw terminal (for 26 to 14 GA wire)
unprotected (NEMA 1/IP20)
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

245
NMB(X)24-3(-T)
On/Off, Floating Point, Non-Spring Return, 24 V

Accessories Wiring Diagrams


K-NA Reversible Clamp
ZG-100 Universal Mounting Bracket
ZG-101 Universal Mounting Bracket
1 Provide overload protection and disconnect as required.
ZG-103 Universal Mounting Bracket
ZG-104 Universal Mounting Bracket
3 Actuators may also be powered by 24 VDC.
ZG-NMA Crank arm Adaptor Kit
AV8-25 Universal Shaft Extension
ZG-NMSA-1 Shaft Adaptor
ZS-T Terminal Cover for NEMA 2
Meets cULus or UL and CSA Standard requirements without the
ZS-100 Weather Shield - Steel
need of an electrical ground connection.
ZS-150 Weather Shield - Polycarbonate
Tool-06 8 mm & 10 mm Wrench WARNING
G Live Electrical Components!
S1A, S2A Auxiliary Switch (es) During installation, testing, servicing and troubleshooting of this product, it may be
P370 Shaft Mount Auxiliary Switch necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
P…A Feedback Potentiometers tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-
NOTE: When using NMX24-3… actuators, only use accessories listed on this page.
nents could result in death or serious injury.

W263_08
Typical Specification
Floating point, on/off control damper actuators shall be electronic direct-coupled type,
which require no crank arm and linkage and be capable of direct mounting to a shaft
up to 1.05” diameter. Actuators shall have brushless DC motor technology and be
protected from overload at all angles of rotation. Actuators shall have reversing switch
and manual override on the cover. If required, actuators will be provided with a screw
terminal strip for electrical connections (NMX24-3-T). Run time shall be constant and
independent of torque. Actuators shall be cULus listed, have a 5-year warranty, and be
manufactured under ISO 9001 International Quality Control Standards. Actuators shall
be as manufactured by Belimo.

On/Off control

W264_08
M40024 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.

Floating Point or On/Off control

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA