Professional Documents
Culture Documents
42 Smoke Control
42 Smoke Control
42 Smoke Control
SMOKE CONTROL
Table of Contents
Scope and purpose........................................................................................................................ 42.1
Where required ............................................................................................................................ 42.2
Compliance ................................................................................................................................... 42.3
Definitions .................................................................................................................................... 42.4
Design team.................................................................................................................................. 42.5
Coordination letters .......................................................................................................................... 42.5.3
Special design considerations ....................................................................................................... 42.6
Tenant improvements....................................................................................................................... 42.6.1
Penthouses........................................................................................................................................ 42.6.3
Garage ventilation ............................................................................................................................ 42.6.5
Loading docks .................................................................................................................................... 42.6.6
Trash chutes ...................................................................................................................................... 42.6.7
Permit timing ................................................................................................................................ 42.7
Submittal requirements ................................................................................................................ 42.8
Conceptual smoke control submittal ................................................................................................ 42.8.1
Detailed smoke control submittal..................................................................................................... 42.8.2
Smoke control zones .................................................................................................................. 42.8.2.3
Fire-fighter’s Smoke Control Panel (FSCP) ...................................................................................... 42.9
Panel colors ....................................................................................................................................... 42.9.4
Panel indicators- equipment and status ........................................................................................... 42.9.5
Zone controls .................................................................................................................................... 42.9.6
Garage control .................................................................................................................................. 42.9.7
Shaft pressurization fans................................................................................................................... 42.9.8
Multiple fans operating in a single zone ........................................................................................... 42.9.9
Door unlocking switch..................................................................................................................... 42.9.10
System activation ....................................................................................................................... 42.10
Equipment .................................................................................................................................. 42.11
Design Approaches may include the Pressurization Method, Airflow Design Method,
Exhaust Method, Passive Smoke Control and Performance Based Designs. All of these
are defined in ICC standards. The objective of such designs is to accomplish the
following:
1. Contribute to the protection of life and to the reduction of property loss.
2. Provide conditions outside the event zone that enable emergency response personnel
to enter for rescue and fire-fighting operations.
3. Maintain a tenable environment in smoke refuge areas and exit enclosures, and
within the event zone when utilizing the exhaust method, for the required duration.
4. Inhibit smoke from entering stairwells, smoke refuge areas, elevator shafts, or
similar areas.
5. Inhibit the migration of smoke from the event zone.
42.2 Where required. The IBC requires the following smoke control systems:
1. High-rise Buildings (BCC 23.10.403.7 – IBC 403.7 amended)
2. When utilizing Washington Administrative Code 51-50-504.3 (5 story Type V over 1
story Type 1 Construction)
3. Pressurized Shafts/Smokeproof Enclosures (1022.10)
4. Underground Buildings (405.5)
5. Building Atriums (404.5)
6. Windowless Buildings (408.9)
7. Stages and Platforms (410.3.7.2)
8. Assembly Seating (1028.6.2.1)
42.3 Compliance. Smoke control and smoke management systems shall comply with
IBC/IFC Section 909 and generally accepted and well-established principles of
engineering as required by IBC Section 909.2. This shall include NFPA 92, A Guide to
Smoke Control in the 2006 IBC, Dr. John H. Klote, P.E., and Douglas H. Evans, P.E.,
2007, International Code Council, Principles of Smoke Management, Dr. John H. Klote,
P.E., and Dr. James A. Milke, P.E., 2002, Handbook of Smoke Control Engineering,
John H. Klote, James A Milke, Paul G Turnbull, Ahmed Kakhef, Michael J Ferreira,
(ASHRAE) 2012. American Society of Heating, Refrigerating, and Air-Conditioning
Engineers, Inc. (ASHRAE) Commissioning Process for Smoke Control Systems, 2012.
42.4 Definitions. The following words and terms shall, for the purposes of this chapter and
as used elsewhere, have the meanings shown herein.
ACTIVE ZONE. A smoke-control zone that utilizes mechanical ventilation for smoke-
control during smoke control mode to achieve design objectives.
Point of Information
Experience shows that the most successful projects utilize a Fire Protection Engineer
early in a project to develop the smoke control concept, detailed design and maintain an
active and integral role throughout the project. This individual is ideally the “Design
Professional in Responsible Charge”
42.5.3 Coordination letters. A signed statement must be provided from each of the
individual designers (Electrical, Mechanical, Fire Alarm, Fire Sprinkler and Building
Architectural) stating that the designer has read the Detailed Design Report and has
incorporated it into their design, unless the design professional is the author of the
report.
42.5.4 Commissioning. The owner must identify a special inspection agency and a
balancing agency acceptable to the Bellevue Fire Department who’s duties and
qualifications are further outlined in Section 42.13.7. These agencies must be separate
and distinct companies.
42.6.1 Tenant improvements. When the project work adds, modifies, or replaces
smoke control zones, barriers, or fan equipment, operational testing and performance
testing of the affected zones is required. Performance tests shall minimally demonstrate
satisfactory performance of the elements of the affected smoke-control zones.
Operational tests of selected areas outside of the work zone will be required to help
ensure that programming changes did not affect other zones. If variable frequency drive
(VFD) settings are modified, tests must be performed as required in the modified area
and in adjacent areas served by previous fan speed to confirm proper pressure
differentials.
Point of information
There are some smoke control systems in existence based on the codes and standards in
place at the time of original construction that would not be required under codes and
standards in place today. Owners of these buildings must either maintain these systems
in accordance with their original design or they must evaluate the entire building under
the codes and standards in place to determine if these systems could be
decommissioned. This will normally require an evaluation under the direction of a
licensed architect and fire protection engineer.
42.6.4 Generator and transfer switch. The emergency generator and transfer
switches shall be in a separate room from the normal power transformers and switch
gear. The rooms must feature 2-hour FRR construction in high-rise and underground
buildings, 1-hour FRR in all other buildings. (Ref. IBC 403.10, IBC 909.11, NFPA 110-
7.2.1.1).
42.6.6 Loading docks. Truck loading docks and similar facilities located interior of a
building that is provided with smoke control requires special consideration. In general,
smoke removal for the loading dock area within a building shall have a minimum
exhaust volume of 10 air changes per hour.
42.6.6.2 Fan control. Fan control and indication must be provided at the
FSCP in accordance with 42.9.4.
42.6.7 Trash chutes. Trash chutes equipped with continuously operating fans require
the fan to be on emergency power; however, control and status indication of the fan at
the FSCP is not required.
42.8.1 Conceptual smoke control submittal. The conceptual design is the initial
submittal of the Smoke Control Permit (type FH). The Conceptual Smoke Control Design
must be prepared by a Professional Engineer competent in the design of smoke control
systems. The Concept Design submittal contains the Life Safety Report, Summary Event
Matrix and Zone Drawings in accordance with number sheet 42A. Once the Concept has
been approved, then the Detailed Smoke Control Submittal is required to be submitted.
42.8.1.1. Life safety report. The life safety report must include a general
project description of the building, life safety systems and the smoke control
methods and objectives that will be applied. This report must include a
description of the various life safety features of the project (sprinklers, fire
pumps, reservoirs, standpipe systems, fire detection/alarm/communication
system, FCC requirements, firefighter smoke control panel features, emergency
power systems, in-building radio system, etc.) and how they will interface with
each other. The smoke control narrative must detail how the code requirements
of IBC 909 will be addressed, and describe the planned activation and operation
of the system. Calculations and computer modeling analysis are not required
until the detailed design stage.
42.8.2.3 Smoke control zones. The architect of record must prepare smoke
zone plans, with an appropriate legend showing the locations of all required
smoke barriers as outlined in the detailed design report and described in Sheet
42B-D. Zone drawings shall clearly identify (through the use of cross hatching or
color coding) all passive and active zones.
42.8.2.3.2 Floors. Floors define passive smoke zones. When floors are
open to each other, the interconnected levels may be viewed as a single
smoke zone.
42.8.2.5 Detailed event matrix. A detailed event matrix that includes every
fire System Input (alarm and smoke control initiating device) down one column,
and every fire alarm notification device (by zone), every smoke control device (i.e.
fans, dampers, etc.), and every other event that must occur in order for proper
operation of the smoke control system (i.e. HVAC shutdown, etc.) across the top.
See 2013 NFPA 72- Figure A14.6.2.4 for sample. With prior approval, some
devices may be combined.
42.8.2.6 Fire-fighter’s Smoke Control Panel. A full size (1:1) colored layout
of the proposed Fire-fighter's Smoke Control Panel (FSCP) must be included with
the Detailed Smoke Control Submittal.
42.9 Fire-fighter’s Smoke Control Panel (FSCP). The FSCP is a system that provides
visual status indication and manual overriding capability over smoke-control systems
and equipment. This is also referred to as the Fire Fighters’ Smoke-Control Station
(FSCS) in NFPA 92. The purpose of the FSCP is for fire department use during an
emergency. This panel shall be in accordance with IBC Sections 909.12 and 909.16, and
incorporate BFD standards listed in this section.
42.9.1 Priority and control. The FSCP shall have the highest priority control over all
smoke-control systems and equipment, whether or not the Automatic Fire Alarm System
has been activated. The panel shall be designed to enable Fire Department personnel
who may be unfamiliar with the specific system the ability to reconfigure the status of
each smoke zone as deemed necessary during an emergency.
42.9.2 Approval. The FSCP is not approved separately. Its features and functions are
integral to the smoke control system and fire alarm system. Therefore the panel layout
must be included in both permit submittals, in accordance with number sheet 42B. A
full-scale color representation of the FSCP must be submitted for final approval. Fire
alarm submittals that add, alter or replace an existing FSCP must also include a full-size
(1:1) color representation of the FSCP for review and approval.
42.9.4 Panel colors. The FSCP shall consist of a white background and generally
depict significant smoke barriers (i.e. floors, shaft walls, exterior walls) by single black
lines, appearing as a general section view of the building. The image shall sufficiently
illustrate all smoke zones in the building without providing the level of detail common to
architectural elevation or section views.
42.9.4.1 Air flow. The indication and direction of air movement shall be shown
with arrows of the following colors:
1. Stair/Elevator shaft pressurization supply air: BLUE
2. Building zoned smoke control exhaust shafts: RED
3. Building zoned smoke control supply air: GREEN
42.9.4.3 Text. All text shall be on contrasting background with a minimum size
and stroke equivalent to 12-point bold Sans Serif font (such as Helvetica).
Marking pens and self-adhesive labels are not acceptable for identification.
42.9.5 Panel indicators- equipment and status. The general location of each
smoke control system component, including fans, ducts and dampers, that is controlled
or annunciated by the panel shall be depicted on the panel.
42.9.5.10 Smoke and waterflow alarms. Each zone shall be provided with a
red smoke alarm indicator labeled AREA SMOKE, CORRIDOR SMOKE, LOBBY
SMOKE, etc. (initiated by smoke detection) and red waterflow alarm indicator
labeled WATERFLOW (initiated by automatic sprinkler protection waterflow).
The appropriate indicator shall be illuminated upon initiation of the respective
alarm in the zone. Where multiple zones exist on a floor, the zone of alarm shall
be clearly depicted on the panel. If required for clarity, such alarm zones shall be
shown in a plan view of the floor on the smoke control panel.
42.9.5.11 Duct detectors. When duct detectors for pressurization fans are
provided, they shall have a single indication lamp near the fan/damper depiction.
This shall be a yellow/amber lamp.
42.9.5.12 Additional alarms. The panel shall be provided with a list in the
upper right corner of the panel of all possible and potential initiating device
categories as appropriate, including: AREA SMOKE, CORRIDOR SMOKE,
LOBBY SMOKE, DUCT DETECTOR, WATERFLOW, SPECIAL SYSTEM, HEAT
DETECTOR, MANUAL STATION, POWER DISCONNECT. Each category shall
be provided with a red indicator. The respective indicator is to be illuminated
upon such an alarm event in the building.
42.9.5.14 LED’s. Where pilot type lamp indicators are required, Light Emitting
Diodes (LED’s) may be used.
42.9.6 Zone controls. Switches utilized for floor zone control shall be located on the
left side of the building image.
42.9.6.4 Auto. The AUTO position shall be configured in accordance with IBC
909.16.3 (2).
42.9.7 Garage control. A single 3 position switch shall be provided to operate the
garage supply and exhaust fans. Settings for this switch shall be in the following
sequence: GARAGE SUPPLY & EXHAUST FANS ON / AUTO /OFF. Monitoring of
garage system status shall be provided only if components are provided with emergency
power.
42.9.7.1 On. The GARAGE SUPPLY & EXHAUST FANS ON position shall serve
to automatically posture the components of both the supply and exhaust system
fans to on.
42.9.7.2 Auto. The AUTO position shall be the normal operating position of the
components. If the fire alarm system in the garage zone is in alarm the system
shall automatically posture the components of both the supply and exhaust
system fans to on.
42.9.7.3 Off. The OFF position shall serve to automatically posture the
components of both the supply and exhaust system fans to off.
42.9.8 Shaft pressurization fans. Shaft fan control switches shall be placed at the
top of the associated shaft. Where fans are not located at the top of shafts, leaders shall
be drawn from the switch to the fan(s) being controlled.
42.9.10 Door unlocking switch. A single switch shall be provided on the panel to
unlock all locking stairway doors in accordance with IBC 403.5.3, IFC 508.1.5, and IBC
1008.1.9.11, exception #3. The switch shall be provided in the lower right corner of the
panel and labeled AUTO/UNLOCKED.
42.10.3 Waterflow and manual pull stations. Waterflow detection devices serving
multiple smoke zones and manual pull stations may not be used to initiate smoke control
systems (exception: shaft pressurization only) since the smoke zone of origin is
unknown. Subsequent activation of an automatic fire alarm initiating device (i.e.
addressable smoke detector) within an active smoke control zone shall automatically
configure the smoke control system appropriately.
42.11 Equipment. All equipment must comply with IBC 909.10, the NEC and associated
NFPA documents.
42.11.1 Listed and labeled. All smoke control system equipment shall be listed and
labeled by Underwriters' Laboratories. Interconnecting equipment that has not been
listed for interconnection or the creation of components or system into a nonstandard
unit that is not normally available from the manufacturer is not acceptable.
42.11.3 Wiring. All wiring associated with the smoke control system shall be fully
enclosed within continuous raceways (IBC 909.12.1). This includes all fire alarm
component wiring utilized for activation and/or control. (Note: see raceway in
definitions)
Bellevue Fire would deem the following designs to comply with the above noted
integrity and survivability requirements.
1. Concrete cover: Wiring shall be located within concrete slabs and walls
when covered with a minimum of 2” of concrete.
2. Dedicated shaft/enclosure method: Wiring shall be located in a
dedicated 2-hour fire-resistance–rated (FRR) enclosure. Only wiring for
emergency systems, fire service access and occupant evacuation elevator,
fire alarm and pressurization systems may be located in this shaft. Panels,
cabinets, etc. are not allowed to be placed in the shaft, only conductors
installed in approved electrical raceway. All shaft penetrations must be
protected by UL listed methods.
Exception: Fire alarm panels and cabinets are allowed within the 2-hour
enclosure as long as all other circuits are in continues approved electrical
raceway without panels or splices.
3. 2-hour wiring systems: The use of 2-hour FRR wiring systems
protected by automatic sprinklers and against vandalism and other
adverse effects including falling equipment or debris. This can typically be
achieved by securing conduit tight to building structural elements.
4. Interior exit stairway: Wiring may be located within the 2-hour FRR
stairwell it is servicing, when routed such that it is adequately protected
against vandalism and other adverse effects including falling equipment
or debris and in accordance with IBC Chapter 7. This can typically be
achieved by securing raceway tight to building structural elements.
42.11.4 Auxiliary equipment. The requirements for the primary power supply shall
apply to all auxiliary panels and equipment. These shall include: A dedicated circuit,
marked at the electric panels location and the smoke control panel or auxiliary panels
locations. All primary power conductors shall be physically protected.
42.11.5 Data circuits. Signaling Line Circuits or other data control circuits shall be
arranged so that a short, ground or open fault within a smoke zone will not cause the loss
of initiating devices, monitoring devices or building control devices in any other smoke
zone of the protected premises.
42.11.6 Marking and identification. All portions of the control system must be
identified in the field in accordance with the National Electrical Code Article 700.9 as
amended by the City of Bellevue. This includes all applicable junction boxes, control
tubing, temperature control modules, relays, damper sensors, automatic door sensors
and air movement sensors. All junction boxes and covers for the smoke control system
(including all portions of the fire detection system which activate smoke control) shall be
externally identifiable.
42.11.6.1 Emergency systems. All boxes and enclosures larger than 6x6 in.
(including transfer switches, generators and power panels) for emergency circuits
shall be permanently marked with an identification plate that is orange in color
so they will be readily identified as a component of the emergency circuit or
system. All other device and junction boxes for emergency systems and circuits
shall be orange in color, both inside and outside.
42.11.6.2 Smoke control systems. All boxes and enclosures larger than 6x6
in. (including transfer switches, generators and power panels) for smoke control
power and circuits shall be permanently marked with an identification plate that
is orange in color with a yellow diagonal stripe so they will be readily identified as
a component of the smoke control circuit or system. All other device and junction
boxes for smoke control systems and circuits shall be orange in color both inside
and outside. Cover plates shall be orange in color with a yellow diagonal stripe.
Raceways for stair and elevator pressurization system wiring shall be identified
by labels or color coding and shall be visible at the time of inspection.
42.12 Testing and inspection. Smoke control systems shall be inspected and tested by
special inspector in accordance with IBC 909.18, 909.20 and this standard (ref.: IFC
909.3).
Point of Information
42.13.1 Coordination. The Special Inspection Agency must be provided with the
approved smoke control Detailed Design Report, the Special Inspection Test Procedures,
the control diagrams, and the approved smoke control permit plans.
42.13.2 Written test procedures. The testing shall follow the Special Inspector Test
Procedure approved as part of the detailed submittal.
42.13.3 Deficiencies. The SI/SIA shall give written notice to the owner of any deficient
or non-complying smoke control system feature that is discovered and is not corrected
prior to the end of the day. All deficient or non-complying aspects shall be corrected.
42.13.6 Special inspector qualifications. The City of Bellevue does not certify or
list special inspection agencies (SIA) or special inspectors (SI). The qualifications for
special inspector are described below.
42.13.6.4 Allowed to be SI. The P.E. who prepared the rational analysis and
Detailed Design Report may serve as the SI.
42.13.6.6 Air flow and pressure testing. All airflow and pressure testing
must be done by an approved Associated Air Balance Council (AABC), National
Environmental Balancing Bureau (NEBB), or Testing Adjusting, and Balancing
Bureau (TABB) agency. If this company is hired by the installing contractor or
responsible for the balancing of the system, the SI must witness all required
special inspection testing.
42.14.1 Prior testing required. The special inspector testing and final pre-test must
be completed prior to system commissioning testing by the Bellevue Fire Department.
42.14.2 Procedures. The SI/SIA will arrange for system commissioning by the
Bellevue Fire Department-Fire Prevention Division, to include witnessing contractor
executed operational and performance testing of the system. The SI Test Procedures
shall be referenced with regard to methodology for testing selected system components
and features. All testing shall be conducted in accordance with approved permit
documents.
42.14.5 Exhaust or airflow method (IFC 909.7 or 909.8): Atria or other spaces
utilizing the exhaust and/or airflow method. The testing must demonstrate proper
system operation and performance of 100% of the smoke control equipment. Smoke
control system features to be evaluated during system commissioning include:
1. Visual observation of elements described above.
2. Visual inspection of associated smoke barriers for absence of obvious
deficiencies.
3. Proper function of smoke control system, including a minimum of 1 of each
initiating device (i.e. smoke detector, waterflow switch, manual station) and
sequence of operation. It shall be demonstrated that airflow toward the fire does
not exceed 200 feet per minute, per IFC Sections 909.7.2 and 909.8.1.
4. Manual control of smoke control system equipment shall be demonstrated.
42.14.6 Other designs. For all other systems, conduct performance tests, observations
and measurements of all aspects of the smoke control system at a minimum number of
locations to demonstrate proper performance as approved by the BFD. Each test shall
attempt to involve as many different fan systems as practical. Other smoke control
systems or features shall be evaluated as requested by the Fire Prevention Officer based
on the approved design and installed condition to demonstrate proper operation of the
smoke control system and features.
42.14.8 Chemical smoke. Testing involving chemical smoke or a tracer gas can be
used for tracer test during acceptance testing to visually verify air movement.
42.14.9 System failures. If any smoke control system deficiency is discovered during
system commissioning, system commissioning may be ceased at the Fire Prevention
Officer’s discretion until such time as testing in accordance with Section 42.13.6 above
can be repeated as necessary to resolve the deficiency and a revised report is submitted
in accordance with this Section.
“I have reviewed the report and by personal knowledge and on-site observation
certify that the smoke-control system is in substantial compliance with the
design intent and to the best of my understanding complies with the
requirements of the code.”
42.15 Smoke control record documents. The following items must be maintained current
in the fire control room or other approved location for the life of the building: Items one
and two must be submitted to and approved by BFD prior to the start of special
inspections.
1. Approved control diagrams must be kept accessible in the Fire Control Room for
the life of the building and must be updated when changes are made to the
building.
2. Plans showing the devices and equipment which make up the smoke control
system. This will include control diagrams in accordance with IBC 909.15, all
smoke barriers, applicable initiating devices, controllers, fire alarm control panel,
fire-fighter’s smoke control panel, facility temperature controls, control wiring or
tubing, isolation valves, relays, doors, dampers, fans, all supervision devices.
3. Every device must have a distinct identifying address. For purposes of this
requirement, BFD will accept the detailed design drawings, provided all of the
devices listed above are shown, and no extraneous equipment other than fire
alarm devices.
4. A detailed event matrix (each device must be identified by individual address
exactly as it is shown on the control diagram plans above);
5. Documents describing the proper operation and maintenance requirements of
each component of the smoke control system, including fan curves for the smoke
control fans in the building.
6. Maintenance logs and quarterly testing logs.
7. The approved smoke control Detailed Design Report.
8. UUKL panel self-test printouts.
9. The final special inspection report.
42.16 Routine maintenance and testing. The system must be maintained in accordance
with the manufacturer’s instructions and IFC sections 909.12, and 909.20.1 - 909.20.5.
See Number sheet 42 E for additional information.