Manufacturer As above
This is to certify that representative samples of the Certified Product listed above have been investigated by Underwriters
Laboratories to the Standard(s) indicated on this Certificate, in accordance with the UL Global Services Agreement and the UL-EU
Mark Service Terms and Conditions (“Agreement”). The Certificate Holder is entitled to use the UL-EU Mark for the Certified Product
Authorized Certification Decision Maker listed on the certificate and manufactured at the production site(s) listed, in accordance with the terms of the Agreement. Only
those products bearing the UL-EU Mark for Europe should be considered as being covered by UL’s UL-EU Mark Service. This
Chris Miles Certificate shall remain valid through the Expiration date, unless a Standard identified on this Certificate is amended or withdrawn
prior to that date or there is a non-compliance with the Agreement.
This certificate relates to the use of Pyrocoustic® sealant for fire stopping where there are joints in or between walls & floors or
service penetrations through floors and walls. The detailed scope is given in pages 3 to 44 of this Certificate. This shows the
thickness and acceptable dimensions, substrates and orientations required to provide fire resistance periods of up to 240 minutes
for differing services and wall/floor constructions.
The movement capability of Pyrocoustic® joint seals is restricted to ≤ 7.5% unless specifically stated within the tables below
The durability class of Pyrocoustic® is Type X - Intended for use in conditions exposed to weathering and all lower classes
Pyrocoustic®
Sealant on source
room side of wall,
15mm deep x
60mm wide x
2000mm high, with
55mm deep
Stonewool
(60kg/m³)
Pyrocoustic®
Sealant on source
room side of wall,
25mm deep x
60mm wide x 51 (-1; -6) 63 (-1; -7) 61 (-1; -6)
2000mm high, with
55mm deep
Stonewool
(60kg/m³)
Key
2. Backing Material
3. Rigid Wall
E 120 – V – X – F – W 00 to W 50,
25
EI 60 – V – X – F – W 00 to W 50
PE backing rod, glass wool,
Concrete / masonry 2:1 ratio stone wool or ceramic wool E 120 – V – X – F – W 00 to W 50,
(width:depth) &
EI 45 – V – X – F – W 00 to W 50
Min. 10
Key
2. Backing Material
3. Rigid Wall
4. Steel
E 120 – V – X – F – W 00 to W 20,
10
EI 20 – V – X – F – W 00 to W 20
PE backing rod, glass wool,
Concrete or masonry / steel 2:1 ratio
stone wool or ceramic wool E 45 – V – X – F – W 00 to W 50,
(width:depth) &
EI 20 – V – X – F – W 00 to W 50
Min. 10
Key
2. Backing Material
3. Rigid Wall
4. Timber
2:1 ratio
E 30 – V – X – F – W 00 to W 50,
Concrete or masonry / (width:depth) & PE backing rod, glass wool,
EI 20 – V – X – F – W 00 to W 50
timber Min. 10 stone wool or ceramic wool
25 EI 45 – V – X – F – W 00 to W 50
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Wall
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Wall
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Wall
4. Steel
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Wall
4. Timber
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Wall
Key
3.
1. Pyrocoustic® Sealant Installed Either
Side of Wall
2.
2. Backing Material
3. Rigid Wall
1.
`
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
E 240 – H – X – F – W 00 to W 50,
25
EI 90 – H – X – F – W 00 to W 50
PE backing rod, glass wool,
Concrete / masonry
2:1 ratio stone wool or ceramic wool
E 240 – H – X – F – W 00 to W 50,
(width:depth) &
EI 45 – H – X – F – W 00 to W 50
Min. 10
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
E 240 – H – X – F – W 00 to W 50,
25
EI 90 – H – X – F – W 00 to W 50
PE backing rod, glass wool,
Concrete / masonry 2:1 ratio stone wool or ceramic wool E 240 – H – X – F – W 00 to W 50,
(width:depth) &
EI 45 – H – X – F – W 00 to W 50
Min. 10
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
4. Steel
E 240 – H – X – F – W 00 to W 50,
25
EI 90 – H – X – F – W 00 to W 50
PE backing rod, glass wool,
Concrete or masonry / steel 2:1 ratio
stone wool or ceramic wool E 120 – H – X – F – W 00 to W 50,
(width:depth) &
EI 30 – H – X – F – W 00 to W 50
Min. 10
Single sided linear joint in steel faced floor from top side
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
4. Steel
E 240 – H – X – F – W 00 to W 50,
25
EI 90 – H – X – F – W 00 to W 50
PE backing rod, glass wool,
Concrete or masonry / steel
2:1 ratio stone wool or ceramic wool
E 120 – H – X – F – W 00 to W 50,
(width:depth) &
EI 30 – H – X – F – W 00 to W 50
Min. 10
Single sided linear joint seal in timber faced floor from underside
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
4. Timber
25 EI 45 – H – X – F – W 00 to W 50
Concrete or masonry / 2:1 ratio PE backing rod, glass wool,
timber (width:depth) & stone wool or ceramic wool EI 30 – H – X – F – W 00 to W 50
Min. 10
Single sided linear joint seal in timber faced floor from top side
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
4. Timber
25 EI 45 – H – X – F – W 00 to W 50
Concrete or masonry / 2:1 ratio PE backing rod, glass wool,
timber (width:depth) & stone wool or ceramic wool EI 30 – H – X – F – W 00 to W 50
Min. 10
Single sided linear joint in floor from top side with movement
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
Key
2. Backing Material
3. Rigid Floor
E 240 – T – X – F – W 00 to W 50,
25
EI 90 – T – X – F – W 00 to W 50
PE backing rod, glass wool,
Concrete / masonry 2:1 ratio stone wool or ceramic wool E 240 – T – X – F – W 00 to W 50,
(width:depth) &
EI 45 – T – X – F – W 00 to W 50
Min. 10
Steel - Concrete or masonry walls & floors ≥150mm with a density of ≥650kg/m³
Key
2. Backing Material
3. Rigid Floor
4. Steel
E 240 – T – X – F – W 50,
25
EI 90 – T – X – F – W 50
PE backing rod, glass wool,
Concrete or masonry / steel 2:1 ratio stone wool or ceramic wool E 240 – T – X – F – W 00 to W 50,
(width:depth) &
EI 30 – T – X – F – W 00 to W 50
Min. 10
Timber - Concrete or masonry walls & floors ≥150mm with a density of ≥650kg/m³
Key
2. Backing Material
3. Rigid Floor
4. Timber
25 EI 45 – T – X – F – W 00 to W 50
Concrete or masonry / PE backing rod, glass wool,
2:1 ratio
timber stone wool or ceramic wool
(width:depth) & EI 30 – T – X – F – W 00 to W 50
Min. 10
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
Key
3.
1. Pyrocoustic® Sealant
2. Backing Material
3. Rigid Floor
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Flexible wall
Key
1. Pyrocoustic® Sealant
2. Backing Material
3. Flexible Wall
Key
1. Pyrocoustic® Sealant
2. Rigid Floor
3. Flexible Wall
Flexible / concrete
25 Steel head track EI 120 – T – X – F – W 00 to W 20
Masonry / concrete
Penetration Seals
Flexible or Rigid Walls Minimum Thickness 75mm
Metallic pipes
Key
1. Pyrocoustic® Sealant
2. Metallic Pipe
3. Flexible Wall
4. Backing Material
Single cables
Key
1. Pyrocoustic® Sealant
2. Single Cable
3. Flexible Wall
4. Backing Material
Maximum
Depth Backing
Penetration Service Aperture Size Classification
(mm) Material
(mm)
PE backing rod, glass
D1 cable* 10 100 Ø wool, stone wool or E 60, EI 45
ceramic wool
Stone wool or
B cable* 12 25 Ø ceramic wool (10mm E 90, EI 60
45kg/m³)
* As defined in EN 1366-3: 2009, Annex A
Cable trunking
Key
1. Pyrocoustic® Sealant
3. Flexible Wall
4. S-Line Pillows
5. Backing Material
Maximum Minimum
Depth Backing
Penetration Service Aperture Distance to Edge Classification
(mm) Material
Size (mm) of Aperture (mm)
PE backing rod,
Steel trunking up to glass wool,
10 170 x 170 0 E 60, EI 20
150mm x 150mm stone wool or
ceramic wool
PE backing rod,
Steel trunking up to glass wool,
10 70 x 70 0 E 60, EI 45
50mm x 50mm stone wool or
ceramic wool
Key
1. Pyrocoustic® Sealant
2. Metal Pipe
3. Flexible Wall
5. Backing Material
Maximum Minimum
Depth Backing
Penetration Service Annular Distance to Edge Classification
(mm) Material
(mm) of Aperture (mm)
Copper/Steel Pipe 159mm
PE backing rod,
Ø, 2-14.2mm wall
glass wool, E 60 C/U, C/C,
thickness insulated with 10 10 0
stone wool or EI 45 C/U, C/C
stone wool ≥50mm thick,
ceramic wool
≥90kg/m³ (C/S)
Cable trays
Key
1. Pyrocoustic® Sealant
2. Cable Tray
3. Flexible Wall
4. Backing Material
Maximum
Minimum
Depth Aperture Backing
Penetration Service Distance to Edge Classification
(mm) Size (mm) (h Material
of Aperture (mm)
x w)
Steel cable tray ≤450mm PE backing rod,
wide loaded with cables glass wool,
10 470 x 100 0 E 60, EI 20
≤21mm Ø + C1, C2, C3 stone wool or
cables* ceramic wool
Steel cable tray ≤450mm
wide loaded with cables
PE backing rod,
≤21mm Ø + C1, C2, C3
glass wool,
cables*with insulation 10 470 x 100 0 EI 45
stone wool or
≤40mm thick ≤45kg/m³,
ceramic wool
≤400mm either side of the
wall (L/I)
* As defined in EN 1366-3: 2009, Annex A
Cable bunches
Key
1. Pyrocoustic® Sealant
2. Single Bunch
3. Flexible Wall
4. Backing Material
Maximum Minimum
Depth Backing
Penetration Service Aperture Distance to Edge Classification
(mm) Material
Size (mm) of Aperture (mm)
PE backing rod,
Telecoms cables ≤21mm
glass wool,
Ø in cable bunch ≤100mm 10 120 Ø 0 E 60, EI 45
stone wool or
Ø
ceramic wool
Metallic pipes
Key
1. Pyrocoustic® Sealant
2. Metallic Pipe
3. Flexible Wall
4. Backing Material
Depth Annular
Penetration Service Backing Material Classification
(mm) (mm)
Steel pipe 42mm Ø, 2.8 – E 120 C/U, C/C,
14.2mm wall thickness PE backing rod, glass wool, EI 45 C/U, C/C
25 10
Steel pipe 42 – 114mm Ø, 3 – stone wool or ceramic wool E 120 C/U, C/C,
14.2mm wall thickness EI 20 C/U, C/C
Key
1. Pyrocoustic® Sealant
2. Cables
3. Flexible Wall
4. Backing Material
Maximum Minimum
Depth Backing
Penetration Service Aperture Distance to Edge Classification
(mm) Material
Size (mm) of Aperture (mm)
Cable bunch ≤100mm Ø EI 120
Metal pipes
Key
1. Pyrocoustic® Sealant
2. Metal Pipe
3. Flexible Wall
4. Backing Material
Annular
Depth Backing
Penetration Service Space Classification
(mm) Material
(mm)
Copper/Steel pipe 15-40mm Ø, 0.8 – 14.2mm E 120 C/U, C/C,
wall thickness EI 15 C/U, C/C
Copper/Steel pipe 40-159mm Ø, 1.8 –
E 120 C/U, C/C
14.2mm wall thickness
PE backing rod,
Copper/Steel pipe 40mm Ø, 0.8 – 14.2mm glass wool, stone
25 10 E 120 C/U, C/C,
wall thickness insulated with FSi TDW to wool or ceramic EI 90 C/U, C/C
both sides of the wall at 300mm (L/I) wool
Cable trays
Key
1. Pyrocoustic® Sealant
2. Cable Tray/Cables
3. Flexible Wall
4. Backing Material
Maximum
Minimum
Depth Aperture
Penetration Service Backing Material Distance to Edge Classification
(mm) Size (mm)
of Aperture (mm)
(w x h)
Stone wool or
Steel cable tray ≤450mm
ceramic wool
wide loaded with cables 25 490 x 100 20 E 120, EI 90
(≥35mm
≤21mm Ø
≥80kg/m³)
PE backing rod,
C1, C2, D1 and D2 glass wool, stone
25 200 x 100 20 E 90, EI 60
Cables* wool or ceramic
wool
* As defined in EN 1366-3: 2009, Annex A
Metal pipes
Key
1. Pyrocoustic® Sealant
2. Metal Pipe
3. Rigid Wall
4. Backing Material
Maximum Minimum
Depth
Penetration Service Aperture Backing Material Distance to Edge Classification
(mm)
Size of Aperture (mm)
Copper/Steel pipe 35 -
PE backing rod,
159mm Ø, 2 – 14.2mm Pipe Ø +
glass wool, stone
wall thickness insulated 5 55mm 0 EI 240 C/U, C/C
wool or ceramic
with stone wool 50mm
wool
thick 100kg/m³ (C/I)
Key
1. Pyrocoustic® Sealant
2. Metal Pipe
3. Rigid Wall
4. Backing Material
Maximum Minimum
Depth Backing
Penetration Service Aperture Distance to Edge Classification
(mm) Material
Size of Aperture (mm)
Steel pipe 40 -152mm Pipe Ø + Stone wool or
Ø, 2.5 – 14.2mm wall 6 50mm ceramic wool 0 E 240 C/C
thickness (≥144mm ≥80kg/m³)
Steel pipe 40mm Ø, 1.5 Pipe Ø + Stone wool or
E 240 C/C,
– 14.2mm wall 6 50mm ceramic wool 0
EI 120 C/C
thickness (≥144mm ≥80kg/m³)
27-CP-F0855 Issue: 3.1
Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-00500-CPR
Page 43/45
Date of Issue 2014-04-25
Metal pipes
Key
1. Pyrocoustic® Sealant
2. Metal Pipe
3. Rigid Floor
4. Backing Material
Maximum Minimum
Depth Backing
Penetration Service Aperture Size Distance to Edge Classification
(mm) Material
(mm) of Aperture (mm)
Copper/Steel pipe 42 –
159mm Ø, 1 – 14.2mm Stone wool or E 180 C/U, C/C
wall thickness ceramic wool
5 200 x 200 20
(≥145mm
Copper/Steel pipe 42mm Ø,
≥45kg/m³) E 240 C/U, C/C
1 – 14.2mm wall thickness
Cables
Key
1. Pyrocoustic® Sealant
2. Cables
3. Rigid Floor
4. Backing Material
Minimum
Maximum
Depth Backing Distance to Edge
Penetration Service Aperture Size Classification
(mm) Material of Aperture
(mm)
(mm)
Telecoms cables ≤21mm
Ø in cable bunch ≤100mm E 45, EI 15
Ø Stone wool
PVC conduits ≤16mm Ø or ceramic E 45, EI 15
Steel/Copper conduits 5 200 x 200 wool 0
E 45, EI 15
≤16mm Ø (≥145mm
Cables ≤80mm Ø ≥45kg/m³) E 90, EI 45
Cables ≤50mm Ø E 90, EI 45
Cables ≤21mm Ø E 240, EI 90
The minimum height of the registered trademark symbol ® shall be 1 mm. When the overall diameter of
the UL-EU Mark is less than 9.5 mm, the trademark symbol may be omitted if it is not legible to the naked
eye.
The UL-EU Mark may appear on a label, nameplate, or may be cast, stamped or molded into the product.
When appearing on a label or nameplate, the Manufacturer’s name or trademark along with a model
number are also required on that same label or nameplate. If cast, stamped or molded, the Manufacturer’s
name or trademark and model number shall also appear elsewhere on the product.
All content shall be in accordance with the details provided on this UL-EU Certificate.
PROCUREMENT
The Production site may reproduce the Mark or obtain it from a UL authorized supplier. The list of UL
authorized suppliers can be found on UL’s online directory at www.ul.com.